Decide CT ratios , plug settings and the TMS at all locations A B C D E Load 183A 80A 100 A 77 A 70 A Min
Fault 915A 1000 A 780 A 585 A 390 A Current Max fault 6000A 5000 A 3000 A 2000 A 1000 A Current
Comments (1) 쇱
Step-by-step explanation
Assuming 1A relay to be used, CT ratio can be selected to be 90:1, then plug setting can be done at 100%. Hence, ps=1.0A
Assuming 1A relay to be used, CT ratio can be selected to be 200:1, the plug setting can be done at 100%. Hence, ps=1.0A
If 1A relay to be used, CT ratio can be 310:1, then plug setting can be done at 100%. Hence, ps= 1.0A
If 1A relay to be used, CT ratio can be 410:1, then plug setting can be done at 100%. Hence, ps=1.0A