Question 숤 Answered step-by-step

Please provide solution asap to get a upvote

Image transcription text


D B C D G1 m IDMT A2 X . For the system shown , design a complete OC protection scheme using IDMT Relays.

Decide CT ratios , plug settings and the TMS at all locations A B C D E Load 183A 80A 100 A 77 A 70 A Min

Fault 915A 1000 A 780 A 585 A 390 A Current Max fault 6000A 5000 A 3000 A 2000 A 1000 A Current

Engineering & Technology Electrical Engineering 섈 쉋

Comments (1) 쇱

Answer & Explanation Solved by verified expert 숨 Rated


싙 Helpful

The solution of the question is as follows:

Step-by-step explanation

Designing of CT ratio and plug setting: 


 At relay D, assuming 25% overload is 70A+ (0.25×70) = 87.5A

Assuming 1A relay to be used, CT ratio can be selected to be 90:1, then plug setting can be done at 100%. Hence, ps=1.0A

At relay C, assuming 25 % overload is (70A+77A) + (0.25x 147)= 183.75A

Assuming 1A relay to be used, CT ratio can be selected to be 200:1, the plug setting can be done at 100%. Hence, ps=1.0A

 At relay B, assuming 25 % overload is (70+77 +100 ) + (0.25x247)= 308.75A

If 1A relay to be used, CT ratio can be 310:1, then plug setting can be done at 100%. Hence, ps= 1.0A

 At relay A, the max current = (70+77 +100+80) + (0·25x327)= 408.75A

If 1A relay to be used, CT ratio can be 410:1, then plug setting can be done at 100%. Hence, ps=1.0A

The operating time of RD for maximum fault is TR,D= 0.14 (TMS)/PSM0.02-1


for max fault at D,
fault current = 8000 A primary 
Primary side, becomes 2000/90 = 22.22A Secondary
Since, plug setting = 1.0A 

https://www.coursehero.com/tutors-problems/Electrical-Engineering/31656119-Please-provide-solution-asap-to-get-a-upvote/?justUnlocked=1 1/3
5/8/22, 10:18 PM [Solved] D B C D G1 m IDMT A2 X . For the system shown , design a complete OC protection scheme using IDMT Relays. | Course Hero

PSM relay = Irelay/ps =22.22 /1 =22.22


Find study resources 숿
TR,D=(0.14×0.1)/22.220.02-1 = 0.218 sec.
Let TCB,D= 0.5sec 
then, TR,D +TCB, = 0.21+ 0.5=0.71 sec .
This 0.71 sec is desired operating RC time Assuming 10% of overshoot time of Rc, we get,
TR,C = 0.21+0.5+0.071 = 0.781sec.
TMS of RC can be determined by
0.781 = 0.14 (TMS)/PSM0.02-1
Since, PSM= Irelay /ps = (2000/200)/1 =10
Therefore, TSM = 0.781(100.02-1)/0.14 = 0.262
For max fault at B, fault current = 5000 A.
Primary side becomes 5000 /310 = 16.18A secondary. 
Since, ps=1.0A, PSM = 16.12/1 =16.12.
TMS is set for 0.3 sec
TR,B= 0.14 (0.3)/16.120.02-1 =0.735 sec TCB,D= 0.5 sec 
then,
TR,B+TCB,D= 0.735 +0.5= 1.235 sec.
1.235 sec is desired operating time of RA. Assuming 10% overshoot time of RA
We get,
TR,A max fault current at B =0.735+0.5+1.235
= 1.3585 sec.
TMS of RA can be found by
1.3585= 0.14(TMS)/ PSM0.02 - 1
Since, PSM= 5000/ 410= 12.19
Now, TSM= 1.3585 (12.190.02-1)/0.14
Therefore, TSM= 0.4976 sec.

Student reviews 싙 100% (2 ratings)

Is this answer helpful? Helpful 싙 Unhelpful 싗


Report this answer

Add to library

Related Answered Questions

숵 Q: Consider a single-phase 11 kV/11 숵 Q: If algae grows at a rate that can be


kV, 1.1 MVA transformer protected by modeled by the exponential function A(t) =
percentage differential protection. CTs wi… ae rt , what is the surface area of alga

Answered over 90d ago Answered over 90d ago 싙 93%

숵 Q: Design the differential protection for 숵 Q: If f(x) = log(x), what is the


a three-phase, 50 Hz transformer with the transformation that occurs if g(x) =
following nameplate ratings: MVA 250, 1 3log(x)?

Answered over 90d ago Answered over 90d ago

솩 솩 솩

Related Course Resources

https://www.coursehero.com/tutors-problems/Electrical-Engineering/31656119-Please-provide-solution-asap-to-get-a-upvote/?justUnlocked=1 2/3
5/8/22, 10:18 PM [Solved] D B C D G1 m IDMT A2 X . For the system shown , design a complete OC protection scheme using IDMT Relays. | Course Hero

Find study resources 숿


ELECTRICAL 101 ELECTRICAL 304 E

NED University of Engineerin… NED University of Engineerin… NED Univ



섵 188 Documents 섵 101 Documents 섵 58 Do

❓ 3 Question & Answers

솩 솩

Company Get Course Hero Careers

About Us iOS Leadership


Scholarships Android Careers
Sitemap Chrome Extension Campus Rep Program
Q&A Archive Educators
Standardized Tests Tutors
Education Summit

Help Legal Connect with Us

Contact Us Copyright Policy College Life


FAQ Academic Integrity Facebook
Feedback Our Honor Code Twitter
Privacy Policy LinkedIn
Terms of Use YouTube
Attributions Instagram

Copyright © 2022. Course Hero, Inc.

Course Hero is not sponsored or endorsed by any college or university.

https://www.coursehero.com/tutors-problems/Electrical-Engineering/31656119-Please-provide-solution-asap-to-get-a-upvote/?justUnlocked=1 3/3

You might also like