Professional Documents
Culture Documents
Release Notes
IndustrialIT
800xA - Control and I/O
800xA for TRIO/Genius
System Version 5.0 SP1
Release Notes
NOTICE
This document contains information about one or more ABB products and may include a
description of or a reference to one or more standards that may be generally relevant to
the ABB products. The presence of any such description of a standard or reference to a
standard is not a representation that all of the ABB products referenced in this document
support all of the features of the described or referenced standard. In order to determine
the specific features supported by a particular ABB product, the reader should consult the
product specifications for the particular ABB product.
The information in this document is subject to change without notice and should not be
construed as a commitment by ABB. ABB assumes no responsibility for any errors that
may appear in this document.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB be
liable for incidental or consequential damages arising from use of any software or hard-
ware described in this document.
This document and parts thereof must not be reproduced or copied without written per-
mission from ABB, and the contents thereof must not be imparted to a third party nor used
for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
This product meets the requirements specified in EMC Directive 89/336/EEC and in Low
Voltage Directive 72/23/EEC.
TRADEMARKS
All rights to copyrights, registered trademarks, and trademarks reside with their respec-
tive owners.
3BUR002461R5011 5
Table of Contents
6 3BUR002461R5011
Section 1 Release Notes
Introduction
This document represents the release notes for Industrial IT ™ 800xA - Control I/O
800xA for TRIO/Genius System Version 5.0 SP1 software. This instruction
includes:
• A brief overview of new and modified functionality since the last release.
• A listing of problems fixed since the last release (SV 5.0) that are fixed by this
release (SV5.0 SP1).
• A listing of known problems that exist after final testing with workarounds that
help overcome the problem.
The document contains additional notes that may be valuable to customers and
service personnel working with the product. It replaces release notes for prior
releases and is included on the product media.
Requirements
800xA for TRIO/Genius requires the following:
• 800xA System with Control Builder M professional.
• CI862 at firmware level 3.0.0 or higher.
• CI862 FPGA version 1.2 or higher.
800xA for TRIO/Genius can consist of:
• Up to four CI862 Interface modules to a AC800M controller.
• Up to 30 TRIO blocks to a CI862 field bus.
• The maximum I/O with TRIO in an AC800M is 1000 I/O points.
3BUR002461R5011 7
Functionality Changes Section 1 Release Notes
Functionality Changes
CI862 redundant configurations are not supported and are not to be used with
this release.
Product Support
Contact ABB technical support for assistance in problem reporting.
Fixed Problems
Configuration
Table 1 lists the major system or product configuration issues that have been
corrected since the previous version or service pack. A brief description of the
correction has also been given.
800xATRI-CN-4000-0003
8 3BUR002461R5011
Section 1 Release Notes Known Problems
Known Problems
Installation
Table 2 lists issues that may exist and affect the installation and upgrade of the
system or product at time of release. Workarounds, clarifications, or helpful hints
have been provided for each issue wherever possible.
800xATRI-IN-5010-001
Configuration
Table 3 lists the issues that may exist and affect configuration of the system or
product at time of release. Workarounds, clarifications, or helpful hints have been
provided for each issue wherever possible.
3BUR002461R5011 9
Configuration Section 1 Release Notes
800xATRI-CN-4000-0002
10 3BUR002461R5011
Section 1 Release Notes Operational
Operational
Table 4 lists the issues that may exist and affect operations of the system or product
at time of release. Workarounds, clarifications, or helpful hints have been provided
for each issue wherever possible.
800xATRI-OL-5010-003
INVERT functionality after initial download for the After initial download, make a DUMMY
TRIO blocks does not work. configuration change for the block along with
changing INVERT to TRUE/FALSE for any of
800xATRI-OL-5010-004 the channels. By doing this, INVERT
functionality will work accordingly.
Miscellaneous
Table 5 list the problems or issues known to exist with the current release that do not
fit into one of the other categories. A workaround, when possible, has been
identified for each problem or issue.
800xATRI-MS-5010-005