You are on page 1of 12

FieldIT

PROFIBUS Redundancy Link Module RLM01

Release Notes
FieldIT
PROFIBUS Redundancy Link Module RLM01

Release Notes
NOTICE
This document contains information about one or more ABB products and may include a
description of or a reference to one or more standards that may be generally relevant to
the ABB products. The presence of any such description of a standard or reference to a
standard is not a representation that all of the ABB products referenced in this document
support all of the features of the described or referenced standard. In order to determine
the specific features supported by a particular ABB product, the reader should consult the
product specifications for the particular ABB product.

The information in this document is subject to change without notice and should not be
construed as a commitment by ABB. ABB assumes no responsibility for any errors that
may appear in this document.

In no event shall ABB be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB be
liable for incidental or consequential damages arising from use of any software or hard-
ware described in this document.

This document and parts thereof must not be reproduced or copied without written per-
mission from ABB, and the contents thereof must not be imparted to a third party nor used
for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.

This product meets the requirements specified in EMC Directive 89/336/EEC and in Low
Voltage Directive 72/23/EEC.

TRADEMARKS
All rights to copyrights, registered trademarks, and trademarks reside with their respec-
tive owners.

Copyright © 1999 - 2007 by ABB.


All rights reserved.

Release: June 2007


Document number: 2PAA102758R0101
Table of Contents

Section 1 - Release Notes


Introduction .......................................................................................................................7
How to Use This Document ..............................................................................................7
Version Designation...........................................................................................................8
Compatibility / Restrictions...............................................................................................9
Related Documentation ...................................................................................................10
Known Problems and Work Arounds .............................................................................10
Product Support ...............................................................................................................10

2PAA102758R0101 5
Table of Contents

6 2PAA102758R0101
Section 1 Release Notes

Introduction
This document represents the release notes for the PROFIBUS Redundancy Link
Module RLM01 and the belonging documentation.

How to Use This Document


This document provides information not contained in the ordinary manuals, sales
information, or other types of product information.
The document describes known software or documentation problems and errors that
were discovered at too late a date to be included in the current user instructions.

2PAA102758R0101 7
Version Designation Section 1 Release Notes

Version Designation
PROFIBUS Redundancy Link Module RLM01 hardware and firmware in the
current release as listed in Table 1:

Table 1. Version Designation

Released Hardware Version Changes


HW 01.00 First release
HW 01.01 New Firmware released.
• Support of short line lenght
HW 02.00 Change in internal hardware components.
• PCB adapted for GL certification
HW 02.01 Change in internal hardware components.
• Resistor adaption on PCB
HW 02.02 New Firmware released.
• Improved redundancy swith-over function
HW 02.03 Change in internal hardware components.
• Plug adaption on PCB
HW 02.04 Change in internal hardware components.
• Resistor adaption on PCB
HW 02.05 New Firmware released.
• Improved short circuit detection

8 2PAA102758R0101
Section 1 Release Notes Compatibility / Restrictions

Compatibility / Restrictions
In accordance with the UL/CSA requirements an external protection (e.g. fuse) is
prescribed. The fuse rating can amounted to 1.6A to 10A (characteristic: medium
slow-acting or slow-acting). Protection of groups of several devices with a common
fuse is admissible (several RLM01 or RLM01 together with other devices).
When selecting a mounting location, make certain that the limit values for ambient
conditions specified in the technical data are observed and the module can discharge
heat without any obstruction.
In accordance with the PROFIBUS installation guideline the shielding of the bus
cables are preferably connected at the start and at the end with earth potential. Place
the module on a low-resistance and low-inductance earthed DIN mounting rail.
RLM01 is certified for applications on ships and maritime systems by the
Germanischer Lloyd (GL). To meet the increased requirements regarding EMC and
overvoltage, RLM01 must have one or two "24 VDC power supply filters (surge)"
depending on the supply (single / redundant). The supply of several RLM01 behind
one filter is not admissible. The max. length of the lines between filter and RLM01
must not exceed 1 m.
The PROFIBUS line lenght between the RLM01 and the device next to the RLM01
(PROFIBUS master or slave) must not exceed the following distance:

Table 2. Line Lenght Restrictions

Connection Line Lenght


PROFIBUS Master <-> Plug M (RLM01) < 50 m
Plug M (RLM01) <-> PROFIBUS Slave < 50 m
Plug A/B (RLM01) <-> Plug A/B (RLM01) according PROFIBUS specification

2PAA102758R0101 9
Related Documentation Section 1 Release Notes

Related Documentation
Table 3 contains a list of relevant documentation. The placeholder “xx” in the
document number describes the current documentation revision available for
download from ABB Solutionsbank (http://solutionsbank.abb.com)

Table 3. User Documentation

Title Document Number


User Instructions RLM01 (English, German) 3BDD011600Rxx01
Product Guide RLM01 (English) 3BDD011777Rxx01
Data Sheet (English) 3BDD011641Rxx01
Data Sheet (German) 3BDD011641Rxx03

Known Problems and Work Arounds


not applicable

Product Support
Contact ABB technical support for assistance in problem reporting.

10 2PAA102758R0101
BackCover.fm Page 19 Wednesday, October 20, 2004 10:27 AM
2PAA102758R0101. Printed in Sweden June 2007
Copyright © 1999 - 2007 by ABB. All Rights Reserved
® Registered Trademark of ABB.
™ Trademark of ABB.

http://www.abb.com

Automation Technology Products Automation Technology Products Automation Technology Products


Wickliffe, Ohio, USA Västerås, Sweden Mannheim, Germany
www.abb.com/controlsystems www.abb.com/controlsystems www.abb.de/controlsystems

You might also like