Profibus - Manual
AERtronic AS 300 V1.07 and later
The Profibus EM5 Module works with 64 word input and 8 word output data.

Data from client to AERtronic:

1. Byte Acknowledge status


Place this byte to hex value „ 5A“ and the most recent status will be acknowledged. It
is recommended to only enter this value in the register for 1-2 seconds and then to
overwrite it with hex value „ 00“.

2. Byte: Remote on / off


Bit 0: compressor on
Bit 1 – Bit 6: 0
Bit 7: release or enable compressor on / off
The remote on / off control will only be active if the controller parameters have been
set to active and the release Bit 7 has been set. When properly activated the local on /
off screen buttons show a lock symbol and the machine may be started with Bit 0 = 1
and stopped with Bit 0 = 0. The parameter “remote on/off” must set to
“Modbus/Profibus”. (main menu  control  misc.  remote on/off)

3. Byte Remote pressure control


Bit 0: remote pressure control on
Bit 1 – Bit 6: 0
Bit 7: release or enable remote pressure control
The remote pressure control will only be active if the controller parameters have been
set to active and the release Bit 7 has been set.
In this case the pressure control may be activated with Bit 0. Bit 0 = 1 will put the
compressor into load mode or it starts from standby mode in case the shut-down-
operation (main menu  control system misc.  operation mode) has been set. Set
Bit 0 = 0 then the machine will go into unload and idle mode and will place it into
standby mode (main motor off) upon elapsing the “minimum run-on time” (main menu
 machine parameter). The shut-down-operation must be set to active also.
 

4. Byte Remote pressure set value


Bit 0 – Bit 5: 0
Bit 6: release or enable remote RPM set value
Bit 7: release or enable remote pressure set value
The pressure set value is only active if Bit 7 is set. Within this value the set value may
 be provided in Byte 5 and 6.
The RPM set value is only active if Bit 6 is set. Within this value the RPM may be
controlled with Byte 7 and 8. The RPM will only be visible/ displayed once the main
motor has reached at least min speed. This is also for the HMI display; at standstill the
value would be e.g. 0%.

5. Byte: \ Actual pressure set value [mbar] / word (16bit) integer


6. Byte: /

7. Byte: \ Actual RPM set value [0,1 %] / word (16bit) integer


8. Byte: / The information [0,1 %] refers to the decimal point. Example: At a speed
demand of 45,8% the value 458 must be transmitted

9. Byte –
16. Byte Free
 

Data from AERtronic to client:

Shutdown status message: 

With an active shut down the corresponding Bit is set =1. In the attached list all possible shut downs
or trips are detailed. Which ones are selected depends on the type of machine (i.e. Blower,
Compressor single stage, or two stage) and the chosen configuration.
Principle:
- Trip signals must lead to the shutdown of the drive motor
- The designation 2 indicates a 2 stage machine
- All configured analog inputs have an alarm sensor (signal failure)
- All configured analog inputs with limit values have an alarm or shut down signal

1. Byte: Bit 0: Shutdown voltage breakdown


Bit 1: Shutdown Emergency OFF Digital Input
Bit 2: Shutdown main motor over load Digital Input
Bit 3: Shutdown main motor over temperature Digital Input
Bit 4: Shutdown fan (electric) over load Digital Input
Bit 5: Shutdown electric oil demister over load Digital Input
Bit 6: Shutdown electric oil demister 2 over load Digital Input
Bit 7: Shutdown oil pump over load

2. Byte: Bit 0: Shutdown vibration Digital Input


Bit 1: Shutdown condition monitoring Digital Input
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Free

3. Byte: Bit 0: Shutdown suction pressure Limit exceeded


Bit 1: Shutdown compression ratio Limit exceeded
Bit 2: Shutdown discharge pressure Limit exceeded
Bit 3: Shutdown discharge temperature Limit exceeded
Bit 4: Shutdown system (header) temperature Limit exceeded
Bit 5: Shutdown oil pressure Limit exceeded
Bit 6: Shutdown oil temperature Limit exceeded
Bit 7: Shutdown intake temperature 2 Limit exceeded

4. Byte: Bit 0: Shutdown discharge pressure 2 Limit exceeded


Bit 1: Shutdown discharge temperature 2 Limit exceeded
Bit 2: Shutdown oil pressure 2 Limit exceeded
Bit 3: Shutdown oil temperature 2 Limit exceeded
Bit 4: Free
Bit 5: Shutdown RPM (revolutions per minute) Limit exceeded
Bit 6: Shutdown oil level Limit exceeded
Bit 7: Free
 

5. Byte: Bit 0: Shutdown sensor suction pressure Signal fault


Bit 1: Shutdown sensor ambient temperature Signal fault
Bit 2: Shutdown sensor discharge pressure Signal fault
Bit 3: Shutdown sensor discharge temperature Signal fault
Bit 4: Shutdown sensor system (header) pressure Signal fault
Bit 5: Shutdown sensor system (header) temperature Signal fault
Bit 6: Shutdown sensor oil pressure Signal fault
Bit 7: Shutdown sensor oil temperature Signal fault

6. Byte: Bit 0: Shutdown sensor intake temperature 2 Signal fault


Bit 1: Shutdown sensor discharge pressure 2 Signal fault
Bit 2: Shutdown sensor discharge temperature 2 Signal fault
Bit 3: Shutdown sensor oil pressure 2 Signal fault
Bit 4: Shutdown sensor oil temperature 2 Signal fault
Bit 5: Shutdown sensor RPM (revolutions per minute) Signal fault
Bit 6: Free
Bit 7: Shutdown sensor external set value Signal fault

7. Byte: Bit 0: Shutdown sensor oil level Signal fault


Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Shutdown vibration 1S1 Limit exceeded
Bit 5: Shutdown vibration G1 Limit exceeded
Bit 6: Shutdown vibration 3S1 Limit exceeded
Bit 7: Shutdown vibration 1S2 Limit exceeded

8. Byte: Bit 0: Shutdown vibration G2 Limit exceeded


Bit 1: Shutdown vibration 3S2 Limit exceeded
Bit 2: Shutdown sensor vibration 1S1 Signal fault
Bit 3: Shutdown sensor vibration G1 Signal fault
Bit 4: Shutdown sensor vibration 3S1 Signal fault
Bit 5: Shutdown sensor vibration 1S2 Signal fault
Bit 6: Shutdown sensor vibration G2 Signal fault
Bit 7: Shutdown sensor vibration 3S2 Signal fault

9. Byte: Bit 0: Free


Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Free

10. Byte: Bit 0: Free


Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Free
 

11. Byte: Bit 0: Shutdown communication module address 1 internal


Bit 1: Shutdown communication module address 2 internal
Bit 2: Shutdown communication module address 3 internal
Bit 3: Shutdown communication module address 4 internal
Bit 4: Shutdown communication module address 5 internal
Bit 5: Shutdown communication module address 6 internal
Bit 6: Shutdown communication module address 7 internal
Bit 7: Shutdown communication module address 8 internal

12. Byte: Bit 0: Shutdown communication module address 9 internal


Bit 1: Shutdown communication module address 10 internal
Bit 2: Shutdown communication module address 11 internal
Bit 3: Shutdown communication module address 12 internal
Bit 4: Shutdown communication module address 13 internal
Bit 5: Shutdown communication module address 14 internal
Bit 6: Shutdown communication module address 15 internal
Bit 7: Shutdown parameter invalid internal

Warning / alarm:

With an active alarm the corresponding Bit is set =1. In the attached list all possible alarms are
detailed. Which ones are selected depends on the type of machine (i.e. Blower, Compressor single
stage, or two stage) and the chosen configuration.
Principle:
- Alarm and warning signals don’t lead to a shutdown of the drive motor
- The designation 2 indicates a 2 stage machine
- All configured analog inputs have an alarm sensor (signal failure)
- All configured analog inputs with limit values have an alarm or warning signal

13. Byte: Bit 0: Free


Bit 1: Warning / alarm suction pressure Limit exceeded
Bit 2: Warning / alarm ambient temperature low Limit exceeded
Bit 3: Warning / alarm ambient temperature high Limit exceeded
Bit 4: Warning / alarm discharge pressure Limit exceeded
Bit 5: Warning / alarm discharge temperature Limit exceeded
Bit 6: Warning / alarm system (header) temperature Limit exceeded
Bit 7: Warning / alarm oil pressure Limit exceeded

14. Byte: Bit 0: Warning / alarm oil temperature Limit exceeded


Bit 1: Warning / alarm intake temperature 2 Limit exceeded
Bit 2: Warning / alarm discharge pressure 2 Limit exceeded
Bit 3: Warning / alarm discharge temperature 2 Limit exceeded
Bit 4: Warning / alarm oil pressure 2 Limit exceeded
Bit 5: Warning / alarm oil temperature 2 Limit exceeded
Bit 6: Free
Bit 7: Warning / alarm RPM (revolutions per minute) Limit exceeded
 

15. Byte: Bit 0: Warning / alarm oil level Limit exceeded


Bit 1: Warning / alarm compression ratio Limit exceeded
Bit 2: Warning / alarm cooling water flow Digital input
Bit 3: Warning / alarm condensate drain 1 Digital input
Bit 4: Warning / alarm condensate drain 2 Digital input
Bit 5: Warning / alarm after cooler 1 Digital input
Bit 6: Warning / alarm after cooler 2 Digital input
Bit 7: Free

16. Byte: Bit 0: Warning / alarm vibration 1S1 Limit exceeded


Bit 1: Warning / alarm vibration G1 Limit exceeded
Bit 2: Warning / alarm vibration 3S1 Limit exceeded
Bit 3: Warning / alarm vibration 1S2 Limit exceeded
Bit 4: Warning / alarm vibration G2 Limit exceeded
Bit 5: Warning / alarm vibration 3S2 Limit exceeded
Bit 6: Free
Bit 7: Free

17. Byte: Bit 0: Free


Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Free

18. Byte: Bit 0: Free


Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Free
Bit 7: Warning / alarm BLC-Module internal
 

Maintenance:

If a maintenance required or necessary the corresponding Bit is set = 1. The maintenance message is
so long active until the reset in the menu “acknowledge maintenance”

19. Byte: Bit 0: Maintenance intake filter service needed


Bit 1: Maintenance pressure filter service needed
Bit 2: Maintenance cooling air in / out service needed
Bit 3: Maintenance drive V-belts service needed
Bit 4: Maintenance coupling service needed
Bit 5: Maintenance pressure relief valve service needed
Bit 6: Maintenance lube oil service needed
Bit 7: Maintenance oil filter service needed

20. Byte: Bit 0: Maintenance check valve service needed


Bit 1: Maintenance oil demister service needed
Bit 2: Maintenance water cooling service needed
Bit 3: Maintenance water condensate drain service needed
Bit 4: Maintenance main motor service needed
Bit 5: Maintenance 1.inspection service needed
Bit 6: Maintenance main inspection service needed
Bit 7: Maintenance battery service needed
 

Status display:

21. Byte: Bit 0: Start temperature too low Limit exceeded = 1


 No start possible
Bit 1: Start / stops exceeded Number of motor starts
 per hour exceeded = 1
  No start possible
Bit 2: Re-start-delay active Active = 1
 No start possible
Bit 3: Waiting for timer Waiting = 1
Bit 4: Automatic re-starts After voltage breakdown
Automatic start = 1
Bit 5: Free
Bit 6: Free
Bit 7: Free

22. Byte: Free

Status:

23. Byte: Bit 0: System ready Machine ready to


start = 1. After the start
up and during operation
  the Bit is set to 1. Also
during shut-down
operation and standby
mode the Bit is set to 1

Bit 1: System waiting (Timer, Automatic restart delay) Timer or automatic


restart delay active = 1
Bit 2: System standby Machine is in standby
mode = 1
(main motor off)
Bit 3: System Motor Starting / ramp up Only during start up of
the motor is the Bit = 1
Bit 4: System in idle / unload (cont. operation) Bit is set = 1, when the
machine is running and
in unload. Only active
 by continuously
operation mode
Bit 5: System in load Bit is set = 1, when the
machine is running and
in load
 

 
Bit 6: System in ramp down (shut down operation) Bit is set = 1, when the
shut-down operation is
active and the machine
is in unload. The
machine switches into
standby mode when the
“Min. run-on time” is
expired (main motor off)
Bit 7: System in soft ramp down Bit is set = 1, when the
machine is within the
“switch off time”. The
machine stop is
activated but it remains
running in idle mode for
a present time before the
main motor is stopped.

24. Byte: Bit 0: Control ON/OFF enabled over Profibus Bit is set = 1. when the
 parameter “remote
on/off” is set to
“Profibus” and the
release Bit 7 from
Byte 2 is set to 1
Bit 1: Control Load enabled over Profibus Bit is set = 1, when the
 parameter
“remote load/idle” is set
to “Profibus” and the
release Bit 7 from
Byte 3 is set to 1
Bit 2: System is initiate (start command) Bit is set = 1, when the
machine is initiate. In
this case the machine
can be running or is in
standby mode
Bit 3: System main motor running Bit is set = 1, when the
main motor is running
Bit 4: System re-start block active Bit is set = 1, when the
re-start is blocked (max
starts, start-up temp.,
etc.)
Bit 5: System maintenance active Bit is set = 1, when a
maintenance is needed
Bit 6: System warning / alarm active Bit is set = 1, when a
warning or an alarm is
active
Bit 7: System shut down active Bit is set = 1, when a
shut down is active
 

Digital Inputs:

25. Byte: Bit 0: Input Emergency Stop fixed dedicated


Bit 1: Input 2 on Address 1
Bit 2: Input 3 on Address 1
Bit 3: Input main motor temperature too high fixed dedicated
Bit 4: Input 1 on Address 2
Bit 5: Input 2 on Address 2
Bit 6: Input 3 on Address 2
Bit 7: Free

26. Byte: Bit 0: Input 1 on Address 3


Bit 1: Input 2 on Address 3
Bit 2: Input 3 on Address 3
Bit 3: Input 4 on Address 3
Bit 4: Input 1 on Address 4
Bit 5: Input 2 on Address 4
Bit 6: Input 3 on Address 4
Bit 7: Input 4 on Address 4

27. Byte: Bit 0: Input 1 on Address 5


Bit 1: Input 2 on Address 5
Bit 2: Input 3 on Address 5
Bit 3: Input 4 on Address 5
Bit 4: Input 1 on Address 6
Bit 5: Input 2 on Address 6
Bit 6: Input 3 on Address 6
Bit 7: Input 4 on Address 6

28. Byte: Bit 0: Input 1 on Address 7


Bit 1: Input 2 on Address 7
Bit 2: Input 3 on Address 7
Bit 3: Input 4 on Address 7
Bit 4: Input 1 on Address 8
Bit 5: Input 2 on Address 8
Bit 6: Input 3 on Address 8
Bit 7: Input 4 on Address 8

29. Byte: Bit 0: Input 1 on Address 9


Bit 1: Input 2 on Address 9
Bit 2: Input 3 on Address 9
Bit 3: Input 4 on Address 9
Bit 4: Input 1 on Address 10
Bit 5: Input 2 on Address 10
Bit 6: Input 3 on Address 10
Bit 7: Input 4 on Address 10

30. Byte: Free


 

Digital outputs:

31. Byte: Bit 0: Output 1 on Address 1


Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Output 1 on Address 2
Bit 5: Output 2 on Address 2
Bit 6: Output 3 on Address 2
Bit 7: Free

32. Byte: Bit 0: Output 1 on Address 3


Bit 1: Output 2 on Address 3
Bit 2: Output 3 on Address 3
Bit 3: Output 4 on Address 3
Bit 4: Output 1 on Address 4
Bit 5: Output 2 on Address 4
Bit 6: Output 3 on Address 4
Bit 7: Output 4 on Address 4

33. Byte: Bit 0: Output 1 on Address 5


Bit 1: Output 2 on Address 5
Bit 2: Output 3 on Address 5
Bit 3: Output 4 on Address 5
Bit 4: Output 1 on Address 6
Bit 5: Output 2 on Address 6
Bit 6: Output 3 on Address 6
Bit 7: Output 4 on Address 6

34. Byte: Bit 0: Output 1 on Address 7


Bit 1: Output 2 on Address 7
Bit 2: Output 3 on Address 7
Bit 3: Output 4 on Address 7
Bit 4: Output 1 on Address 8
Bit 5: Output 2 on Address 8
Bit 6: Output 3 on Address 8
Bit 7: Output 4 on Address 8

35. Byte: Bit 0: Output 1 on Address 9


Bit 1: Output 2 on Address 9
Bit 2: Output 3 on Address 9
Bit 3: Output 4 on Address 9
Bit 4: Output 1 on Address 10
Bit 5: Output 2 on Address 10
Bit 6: Output 3 on Address 10
Bit 7: Output 4 on Address 10

36. Byte: Free


 

Analog input:

The configured and connected analog inputs will be transmitted as (16Bit) integer. The information
[0,1 %] refers to the decimal point. In that case the value must divide by 10.
(Example 457% / 10 = 45,7%)

37. Byte: \ Actual set value for variable speed drive [0,1 %] Value divide by 10
38. Byte: /

39. Byte: \ External set value (pressure) [0,1 %] Value divide by 10


40. Byte: /

41. Byte: \ Actual RPM (revolutions per minute) [UpM]


42. Byte: /

43. Byte: \ Suction pressure [mbar]


44. Byte: /

45. Byte: \ Ambient temperature [°C]


46. Byte: /

47. Byte: \ Discharge pressure [mbar]


48. Byte: /

49. Byte: \ Discharge temperature [°C]


50. Byte: /

51. Byte: \ Oil pressure [mbar]


52. Byte: /

53. Byte: \ Oil temperature [°C]


54. Byte: /

55. Byte: \ System (header) pressure [mbar]


56. Byte: /

57. Byte: \ System (header) temperature [°C]


58. Byte: /

59. Byte: \ Intake temperature 2 [°C]


60. Byte: /

61. Byte: \ Discharge pressure 2 [mbar]


62. Byte: /

63. Byte: \ Discharge temperature 2 [°C]


64. Byte: /

65. Byte: \ Oil pressure 2 [mbar]


66. Byte: /

67. Byte: \ Oil temperature 2 [°C]


68. Byte: /
 

69. Byte: \ Free


70. Byte: /

71. Byte: \ Oil level [%]


72. Byte: /

73. Byte: \ Vibration 1S1 / 3S1 [%] Only the highest value
74. Byte: / will transmitted

75. Byte: \ Vibration G1 [%]


76. Byte: /

77. Byte: \ Vibration 1S2 / 3S2 [%] Only the highest value
78. Byte: / will transmitted

79. Byte: \ Reserve


80. Byte: /

Hours:

The following hours will transmitted as (32Bit) double integer

81. Byte: \
82. Byte: \ Operating hours [h]
83. Byte: /
84. Byte: /

85. Byte: \
86. Byte: \ Loaded hours [h]
87. Byte: /
88. Byte: /

89. Byte: \
90. Byte: \ Idle / no load hours [h]
91. Byte: /
92. Byte: /

93. Byte: \
94. Byte: \ Rented hours [h]
95. Byte: /
96. Byte: /
 

Maintenance interval:

The following remaining times will transmitted (16Bit) integer

97. Byte: \ Maintenance interval intake filter remaining time [h]


98. Byte: /

99. Byte: \ Maintenance interval pressure filter remaining time [h]


100. Byte: /

101. Byte: \ Maintenance interval cooling air in / out remaining time [h]
102. Byte: /

103. Byte: \ Maintenance interval drive V-belts remaining time [h]


104. Byte: /

105. Byte: \ Maintenance interval coupling remaining time [h]


106. Byte: /

107. Byte: \ Maintenance interval pressure relief valve remaining time [h]
108. Byte: /

109. Byte: \ Maintenance interval lube oil remaining time [h]


110. Byte: /

111. Byte: \ Maintenance interval oil filter remaining time [h]


112. Byte: /

113. Byte: \ Maintenance interval check valve remaining time [h]


114. Byte: /

115. Byte: \ Maintenance interval oil demister remaining time [h]


116. Byte: /

117. Byte: \ Maintenance interval water cooling remaining time [h]


118. Byte: /

119. Byte: \ Maintenance interval water condensate drain remaining time [h]
120. Byte: /

121. Byte: \ Maintenance interval 1.inspection remaining time [h]


122. Byte: /

123. Byte: \ Maintenance interval main inspection remaining time [10h] Value must be
124. Byte: / multiplied by 10

125. Byte: \ Maintenance interval main motor remaining time [h]


126. Byte: /
 

Communication status:

127. Byte: Free

128. Byte: Bit 0: Free


Bit 1: Free
Bit 2: Free
Bit 3: Free
Bit 4: Free
Bit 5: Free
Bit 6: Live Bit / control bit sent every second The Bit changed each
second the status.
Therefore it is very easy
to monitoring the
communication
Bit 7: Communication with main controller ok Bit is set = 1, when the
communication between
the Profibus module
EM5 and the AS300
internal is established