You are on page 1of 28

CDC APC 700 PAN

APC700PAN User’s
Manual

Code: 3AFE 58177580


Revision: B
Language: EN
APC700PAN User’s Manual 3AFE58177580

Issued by: FIIND/EIE


Date: 25.10.94
File: 58177580.DOC
Created with: Word for Windows 2.0
Designer 3.1

Table of revisions:

Date: Code: Rev.: Remark:


1994-10-25 3AFE58177580 A First issue
1996-09-20 3AFY58177580 B Second issue

Table of references:

For information on: See:

The technical data and specifications are valid at the time of printing.
We reserve the right to subsequent alterations.

2
3AFE58177580 APC700PAN User’s Manual

Contents Page
1. General information .......................................................................................... 5
1.1. Description ............................................................................................. 5
2. APC 700 PAN ................................................................................................... 6
2.1. Overview ................................................................................................ 6
2.2. Mechanical Description .......................................................................... 6
2.3. Technical specification........................................................................... 7
2.4. Connectors............................................................................................. 8
2.5. Cabling................................................................................................... 9
2.6. Communication ...................................................................................... 9
2.7. Operating modes ................................................................................... 10
2.7.1 Going to the internal mode ....................................................... 10
2.7.2 Automatic leaving from the internal mode .................................. 10
2.7.3 Selection of the researching alarms ........................................... 11
3. APC 700 PAN Test Instructions ( Version 2.00 )............................................... 12
3.1. Bush button order: ................................................................................. 12
3.2. Cold start (power on for the first time). ................................................... 12
3.3. Internal Test: .......................................................................................... 13
3.4. Normal operation ................................................................................... 13
4. Using the ACV 700 PANEL ............................................................................... 14
4.1. Push buttons .......................................................................................... 14
4.2. Signal display......................................................................................... 15
5. Using the DCV 700 PANEL............................................................................... 18
5.1. Push buttons .......................................................................................... 18
5.2. Signal display......................................................................................... 19
6. Using the Parameter Panel ............................................................................... 21
6.1. Function Description .............................................................................. 22
6.1.1. Upload &Save in APC............................................................... 22
6.1.2. Download to DDC ..................................................................... 22
6.1.3. Save in drive ............................................................................. 23
6.1.4. Save value ................................................................................ 23
6.1.5. Display messages:.................................................................... 25

3
APC700PAN User’s Manual 3AFE58177580

This paper is intentionally left blank!

4
3AFE58177580 APC700PAN User’s Manual

1. General information

1.1. Description

This unit gives technical information about the APC 700 PAN Control
Panel, and APC 700 PAN Control Panel test instructions.

5
APC700PAN User’s Manual 3AFE58177580

2. APC 700 PAN

2.1. Overview

The APC 700 PAN control panel is used as a basic interface for the
user to see:
status information (ready, run, fault, communication)
fault logger display with 100 events memory
reference values (speed, frequency, torque)
actual values (speed, frequency, torque)
It can be used to control from 1 to 4 DDCs one by one, depending on
the application program. Panel functions are freely programmable.

2.2. Mechanical Description

The APC 700 PAN can be mounted into the cabinet door, into the
control desk or on the wall (by using the assembling box).

DR 1 SPEED
DRIV E rpm 1000 #2
SPECurrent
ED A 1500RP
100 M

F1 F 2
Request Group Function

F3 F 4
*/ R Fast Parameter Enter

APC 700 PAN


Figure 1. APC 700 PAN.

6
3AFE58177580 APC700PAN User’s Manual

Dimensions:

Door and desk assembling:


width 196 mm
height 196 mm
depth 52 mm
Wall assembling (box):
width 200 mm
height 200 mm
depth 64 mm

2.3. Technical specification

APC 700 PAN:


2 lines (20 characters) LCD display
10 pushbuttons
9 VDC power supply by the external power supply board
(APC 700 PPW)

Pushbuttons:

arrows (left right, PB1) up arrow (PB2)


F1 F2
Request Group
F1 (PB3) F2 (PB4)
I */ R
Function
start (PB5) */R (PB6)
F3
Fast
down arrow (PB7) F3 (PB8)
F4
Parameter
F4 (PB9) stop (PB10)

APC 700 PPW:


used to create the 9VDC supply voltage for the APC 700 PAN
24 VDC (max. 200 mA) power supply connected directly to the
APC 700 PAN’s phone jack type connector

7
APC700PAN User’s Manual 3AFE58177580

2.4. Connectors

The connection is done to the APC 700 PPW power supply board,
connector X1 as follows:

X1:1 24 VDC
X1:2 0V GND
X1:3 RS signal A
X1:4 RS signal B
X1:5 floating frame
X1:6 fixed frame

Connector X3 is a female 6 pole phone type jack, and it snaps directly


to panel’s similiar connector with male/male jack.

X3:1 RS signal A
X3:2 9 VDC
X3:3 9 VDC
X3:4 0 V GND
X3:5 0 V GND
X3:6 RS signal B
X2 is connected to the frame, by the jumper S1, the GND can be
connected to the frame.

X2
X1 X3
S1 5
6
1 2 3 4 5 6 3

2
4

Figure 2. APC 700 PPW connectors.

8
3AFE58177580 APC700PAN User’s Manual

2.5. Cabling
APC
(YPP 110A)
APC 700 PAN APC 700 PPW X2:1

+9V X01:02 X3:2 + X1:1


+ X2:2
LED_9V X01:03 X3:3
9V 24V 24V Power
LED_0V X01:04 X3:4 - X1:2
- X2:3
X01:05 X3:5
GND
X01:01 X3:1 Data X1:3 X2:4
A

X01:06 X3:6 Data-N X1:4 X2:5


B

S1 X2:6

Floating X1:5
Frame X2:7
Frame
X1:6
X2:8
Frame
X2

APC 700 PAN APC 700 PPW


+9V X01:02 X3 :2 + X1:1
LED_9V X01:03 X3 :3
9V 24V
LED_0V X01:04 X3 :4 - X1:2
X01:05 X3 :5
GND
X01:01 X3 :1 Data X1:3
A

X01:06 X3 :6 Data-N X1:4


B

S1
Floating X1:5
Frame
Frame
X1:6
X2

Figure 3. APC 700 PAN on the Panel Bus.

Cable recommentation screened cable with min. 0.8 mm 2 twisted


cores.

2.6. Communication

Panel are connected to and APC board trough multidrop


communication bus. Panel communicate with the APC by Panel
protocol. The protocol is of master -follower type where the APC is
always the master. All communication is initiated by the APC which
cyclically polls the panels. 1-4 panel can be connected to one APC.

Communication bus data:


Communication standard RS 485, differential two wire, half duplex,
multidrop
Baud rate 19200 baud
max lenght 300 m
max nodes 8
updating interval 100ms/2 nodes

9
APC700PAN User’s Manual 3AFE58177580

2.7. Operating modes

The panel has three operation modes:


− internal mode, to choose a node number and
communication time-out value
− normal mode, includes signal and events displays
(automatically after power up)
− test mode, press buttons PB1, PB5 and connect
power up.

2.7.1 Going to the internal mode

There is a new selection in the internal mode to defining either is it


possible to go to the internal mode as a normal function or should it be
more safety.
The selection will be done with up and down buttons ↑ up arrow (S2),
↓ down arrow (S7). Pressing the button will change the selection.
With the button */R (S6) will be the selection taken to use.
If the access is allowed then the panel will working like in versions 1.00
and 1.01.
If the access is prevent, then it is possible to go to the internal mode
only with the following way:
Switch the panel power off. Press the display exchange button (S1)
while the power will be switched on.

Text of the internal mode:


INT.MODE SELECT Upper line of the display. The valid
selection is on the lower line.
ACCEPTED Lower line of the display, when the
internal mode is allowed
FORBIDDEN Lower line of the display, when the
internal mode prevent.

On the second line will be shown *(asterisk), if the selection on the


screen is also valid.

2.7.2 Automatic leaving from the internal mode

Panel will go automatically from the internal mode to the normal mode if
no buttons will be pressed during 2 minutes. If any of buttons will be
pressed then the new delay counting will be started.

10
3AFE58177580 APC700PAN User’s Manual

2.7.3 Selection of the researching alarms

There is a new selection in the internal mode (this function reguires


APC system software 1.1./0 or later). With it will be selected either to
investigate all or only unacknowledged alarms (functions are same,
which will be chosen in the APC application program with the PANCON
function block with the negative/positive logger number.)
If mode, where all events can be investigated, is selected by panel, it is
not permanent. (With the selected panel mode will be investigated all
alarms, which will show only unacknowledged alarms if no buttons will
be pressed. If any buttons will be pressed then the delay counting starts
from begin. Delay counting will be not done in internal mode.
Selections will be done with up and down buttons. Pressing of the
button will change the selection. Selection will be taken to use with the
button */R (S6).

(The negative logger number has been set in the PANCON function
block. With it will be selected the investigation of all alarms. This will
compensate settings of the panel.)
If the negative logger number has been set in the PANCON function
block, it wins setting of the panel and the investigation of all events is
select.

Texts of the internal mode:


EVENT DISPLAY The upper line of the display. The valid selection
is on the lower liner.
NORMAL When only unacknowledged events will be
shown.
ALL EVENTS When all events will be shown.

On the second line will be shown also *(asterisk), if this selection is


valid.

If the display of all alarms has been selected with the PANCON function
block, ↑ up-, ↓ down and */R buttons has no function and on the display
is permanent text * ALL EVENTS.

11
APC700PAN User’s Manual 3AFE58177580

3. APC 700 PAN Test Instructions ( Version 2.00 )

3.1. Bush button order:

S1 S2 S3 S4 S5
S6 S7 S8 S9 S10

3.2. Cold start (power on for the first time).

 Push S10 button and hold it while connecting the power.


Panel will display the text: "Cold Start, Started / Wait "
and after a short delay "Cold Start, Done / Take power off"

ô Remove power.

(Internal state)
í Connect power again.
Panel will display the text: "New Eprom / Wait..."
After a short delay panel goes to internal mode and displays:
"Time out select: *10"
S1 button will select the display: "ID number: *1";
User can change the number value on the display with buttons
S2
(increase) and S7 (decrease).
New value must be stored to EEprom with button S6 (reset)
even
if the values are not changed.
The "*" sign will indicate that the new value is stored
successfully.

÷ Push and hold S4 button more than 4 seconds to return panel


to normal operation mode. (Hold S4 button 4 more seconds for
internal state again).

12
3AFE58177580 APC700PAN User’s Manual

3.3. Internal Test:

 Push S5 button and hold it while connecting power.


Panel will display the text:"Start of test / Press any key"
Panel will test Ram and then EEprom memories.

ô Panel goes to the "Keys" test.


Push all buttons down starting from S10. At the display O will
change to the
*depending what button is pushed, last push button S1.

í Panel will test all display segments.

÷ Panel will go through contrast test.

û The last test is serial communication test. This requires APC


board and application software. If communication does not
exist, panel will give an error message.

3.4. Normal operation

 Connect the power.


Panel will display the text:"CDC door panel"
After delay, panel will go to normal operation mode if serial
communication is OK.
If serial communication is not OK. Panel will display the text:
"Serial time out / Waiting....’

13
APC700PAN User’s Manual 3AFE58177580

4. Using the ACV 700 PANEL


This application is made by using type circuit AC_PANEL

4.1. Push buttons

↔ − Display change push button


− the panel have two modes, internal mode and
normal mode
− the internal mode is used for panel address and
communication time-out settings
− the normal mode includes event and signa l displays
− mode change happens by pressing the push button
longer time than 4 seconds.

*/R − Event display, event acknowledge push button


in signal display and local control external acknowledge
− (the first character on the second line is blinking when
there are unacknowledged events)
− in internal mode updating the changed parameter
− shift push button which is used together with ↑, ↓ and
F push buttons different kind of selections.

↑ − Event display scroll up


− signal display scroll up
− internal mode, increase value

↓ − Event display scroll down


− signal display scroll down
− internal mode, decrease value

I − Local control, start the drive

0 − Local control, stop the drive

F1...F4 − Function push buttons

14
3AFE58177580 APC700PAN User’s Manual

4.2. Signal display

When starting the panel program (TC AC_PANEL), coming to the


signal display or changing the drive the selected drive basic display
appeares in the panel’s display:

− vector control:

R 1 S P E E D ( r p m ) 0
C U R R E N T ( A ) 0

− scalar control:

R 1 F R E Q . ( H z ) 0 . 0
C U R R E N T ( A ) 0

Other displays in vector control:

R 1 S P E E D ( r p m ) 0
R E F E R E N C E 0

R 1 T O R Q U E ( % ) 0
R E F E R E N C E 0

R 1 F R E Q . ( H z ) 0 . 0
R E F E R E N C E 0 . 0

R 1 S T A T U S
C O M M . E R R O R

F A U L T
C

R E A D Y F O R R U N
R U N N I N G

In this display it is possible to change the language of the display if that


other languages TC ( for instance TC AC_FIN2) is properly connected
in the application program. This changeover is done by pressing
buttons F1 and F2 simultaneously.

15
APC700PAN User’s Manual 3AFE58177580

Next display level is

R 1 R U N T I M E
I N H O U R S 0

If there is a TC RUNTIMER in the application program.This counter is


reseted by pressing buttons F1, F2, F3 and F4 simultaneously for more
than 2 seconds.

Other displays in scalar control:

R 1 F R E Q . ( H z ) 0 . 0
R E F E R E N C E 0 . 0

R 1 S T A T U S
C O M M . E R R O R
F A U L T
R E A D Y F O R R U N
R U N N I N G

In this display it is possible to change the language of the display if that


other languages TC is properly connected in the application program.
This changeover is done by pressing buttons F1 and F2
simultaneously.

Next display level is

R 1 R U N T I M E
I N H O U R S 0

If there is a TC RUNTIMER in the application program.This counter is


reseted by pressing buttons F1, F2, F3 and F4 simultaneously for more
than 2 seconds.

Further more these displays both controls have a fault/alarm display,


where are the selected drive’s unacknowledged and acknowledged
faults and alarms. It is possible to select (scrolling signal display) and to
scroll the display only then, when the drive have faults or alarms. The
display can be scrolled by pressing F1 push button. Fault/alarm display
comes to the display automatically when the first fault or alarm
appeares.

16
3AFE58177580 APC700PAN User’s Manual

The first character on the first line is blinking if there are


unacknowledged or acknowledged faults or alarms.

1 to 4 drives can be controlled by the panel. The drive is selected by


pressing together */R and ↑ or ↓ push buttons.

The drives have two control modes, remote control and local control.
Control mode can be changed by pressing together */R and F4 push
buttons.
In remote control the basic ident of the drive (drives) is DR1 (DR1 to
DR4), but it can be named freely (max. 3 character). In local control the
ident of the drive (drives) is L1 (L1 to L4).
In remote control the display of the panel can be scrolled, but control is
not available.
When the local control is selected it is possible to scroll the display,
start and stop the drive, change the speed reference (vector control) or
frequency reference (scalar control) and give the external
acknowledge.
Speed reference and frequency reference changes can be made only
on the display in question.
Changing the reference value:

- F3 + ↑ or ↓ slow (+5 or -5)


- F4 + ↑ or ↓ normal (+20/200 or -20/200)
- F3 + F4 + ↑ or ↓ fast (+500 or -500)

Nominal maximum value +20000 and minimum value -20000.


If the application program start/stop-logic not stop the drive, when
control mode is changed then the reference value which is given in the
remote control remains in the local control otherwise the reference
value goes to zero. The reference value which is given in the local
control is changed to the same which is given in the remote control.

17
APC700PAN User’s Manual 3AFE58177580

5. Using the DCV 700 PANEL


This application is made by using type circuit DC_PANEL.

5.1. Push buttons

↔ − Display change push button


− the panel has two modes, internal mode and normal
mode
− the internal mode is used for panel address and
communication time-out settings
− the normal mode includes event and signal displays
− mode change happens by pressing the push button
longer time than 4 seconds.

*/R − Event display, event acknowledge push button


− in signal display and local control external
acknowledge
− (the first character on the second line is blinking when
there are unacknowledged events)
− in internal mode updating the changed parameter
− shift push button which is used together with ↑, ↓ and
F push buttons for different kind of selections.

↑ − Event display scroll up


− signal display scroll up
− internal mode, increase value

↓ − Event display scroll down


− signal display scroll down
− internal mode, decrease value

I − Local control, start the drive

0 − Local control, stop the drive

F1...F4 − Function push buttons

18
3AFE58177580 APC700PAN User’s Manual

5.2. Signal display

When starting the panel program (TC DC_PANEL), coming to the


signal display or changing the drive, the selected drive’s basic display
appeares into the panel’s display:

R 1 S P . A C T . ( r p m ) 0
C U R R . A C T ( A ) 0

Other displays are:

R 1 S P . R E F . ( % ) 0
S P . A C T . ( % ) 0

R 1 F I . A C T . ( A ) 0
A R M . A C T . ( V ) 0

R 1 T O R Q . R E F ( %) 0 . 0
T O R Q . A C T ( %) 0 . 0

R 1 S T A T U S
C O M M . E R R O R

F A U L T
E L E C T . D I S C O N .
M A I N C O N T . O P E N
R E A D Y F O R R U N
R U N N I N G
D D C T O O L I N L O C A L

Next display level is

R 1 R U N T I M E
I N H O U R S 0

If there is a TC RUNTIMER in the application program.This counter is


reseted by pressing buttons F1, F2, F3 and F4 simultaneously for more
than 2 seconds.

19
APC700PAN User’s Manual 3AFE58177580

Further more these displays both controls have a fault/alarm display,


where are the selected drive’s unacknowledged and acknowledged
faults and alarms. It is possible to select (scrolling signal display) and to
scroll the display only then, when the drive have faults or alarms. The
display can be scrolled by pressing F1 push button. Fault/alarm display
comes to the display automatically when the first fault or alarm
appeares.
The first character on the first line is blinking if there are
unacknowledged or acknowledged faults or alarms.

1 to 4 drives can be controlled by the panel. The drive is selected by


pressing together */R and ↑ or ↓ push buttons.

The drives have two control modes, remote control and local control.
Control mode can be changed by pressing together */R and F4 push
buttons.
In remote control the basic ident of the drive (drives) is R1 (R1 to R4).
In local control the ident of the drive (drives) is L1 (L1 to L4).
In remote control the display of the panel can be scrolled, but control is
not available.
When the local control is selected it is possible to scroll the display,
start and stop the drive, change the speed reference and give the
external acknowledge.
Speed reference changes can be made only on the display in question.

Changing the reference value:


− F3 + ↑ or ↓ slow (+20 or -20)
− F4 + ↑ or ↓ normal (+50/200 or -50/200)
− F3 + F4 + ↑ or ↓ fast (+500 or -500)

Nominal maximum value +20000 and minimum value -20000.


If the application program start/stop-logic doesn’t stop the drive, when
control mode is changed then the reference value which is given in the
remote control remains in the local control otherwise the reference
value goes to zero. The reference value which is given in the local
control is changed to the same which is given in the remote control.

20
3AFE58177580 APC700PAN User’s Manual

6. Using the Parameter Panel

This panel software (made by using type circuits APCPAR, DRPANEL,


DRUSD) is used for setting of APC or drive parameters by the ACV 700
PAN panel. This can, in certain cases, replace the DDCTool and the
FCE during the commissioning. For example a pump drive with a PI-
level control on the APC board can be tuned over the ACV 700 PAN.

The software includes the following functions:

− Read and change values of APC parameters


− Read and change values of pre-programmed drive parameters
− Save the pre-programmed drive parameters on APC flash
− PROM
− Save parameters on DDC EEPROM

The drive types, numbers and the parameter indexes must be defined
in the APC software.

If there is just one panel connected to the APC, the PAR mode is
entered by changing the ID number in the internal mode of the ACV
700 PAN. The ID number of the parameter panel program is a pre-
programmed value in the APC application program (this is normally 10
to 15, since these node numbers do not have a link supervision).

DR 1 SPEED
DRIV E rpm 1000 #2
SPECurrent
ED A 1500RP
100 M

F1 F 2
Request Group Function

F3 F 4
*/ R Fast Parameter Enter

APC 700 PAN

21
APC700PAN User’s Manual 3AFE58177580

6.1. Function Description

F & Push FUNCTION & ARROW to select


the function.

6.1.1. Upload &Save in APC

DRIVE NUMBER 1
Upload&Save in APC

Use ARROW buttons to change the drive.

F &
E FUNCTION & ENTER uploads the
parameters from the selected drive and
saves them on the flash PROM of the APC.

6.1.2. Download to DDC

DRIVE NUMBER: 1
Download to DDC

Use ARROW buttons to change the drive.

F &
E FUNCTION & ENTER downloads the
parameters to the selected drive.

22
3AFE58177580 APC700PAN User’s Manual

6.1.3. Save in drive

DRIVE NUMBER: 1
Save in DDC

Use ARROW buttons to change the drive.

F &
E FUNCTION & ENTER stores the parameters
on the EEPROM of the selected drive.

6.1.4. Save value

PARAMETER NR: 1.4


change value: 0
This function is used to view and modify the parameter values.

G &
= Displays the type and identity number
of the drive.

ACV 700 drive nr: 4


change value: 0

P &
= Displays the index of the parameter in
the drive.

23
APC700PAN User’s Manual 3AFE58177580

PARAMETER NR: 1.1


index in DDC: 404

= Displays the parameter value on the APC.

PARAMETER NR: 1.1


APC value- = 5

APC value - = XXX value is not stored on flash PROM.


APC value + = XXX value is stored on flash PROM.

++/--
&
= FAST & EQUAL Sets the old
parameter value to the counter output.

PARAMETER NR: 1.1


APC value+ = 520

Changes the value of the counter output.


You can also use the ++/-- button to get
faster change Continuous pressing of button
will speed up the change of values.

F &
E FUNCTION & ENTER Reads the counter
output to parameter and saves the
parameter value on the flash PROM of the
APC.

24
3AFE58177580 APC700PAN User’s Manual

6.1.5. Display messages:

DRIVE NUMBER: 1
Upload&Save in APC

F&E
DRIVE NUMBER: 1
uploading...

DRIVE NUMBER: 1
Saving in APC...

DRIVE NUMBER: 1
...done

R DRIVE NUMBER: 1
timeout ERROR! (R)

R DRIVE NUMBER: 1
ERROR! (R)
Panel displays of the upload & store function.

25
APC700PAN User’s Manual 3AFE58177580

DRIVE NUMBER: 1
Download to DDC

F&E
DRIVE NUMBER: 1
Downloading...

DRIVE NUMBER: 1
...done

R DRIVE NUMBER: 1
timeout ERROR! (R)

R DRIVE NUMBER: 1
ERROR! (R)
Panel displays of the download functions.

26
3AFE58177580 APC700PAN User’s Manual

DRIVE NUMBER: 1
Save in DDC

F&E

DRIVE NUMBER: 1
Saving in DDC...

DRIVE NUMBER: 1
...done

R DRIVE NUMBER: 1
timeout ERROR! (R)

R DRIVE NUMBER: 1
ERROR! (R)
Display of the store in drive function.

27
APC700PAN User’s Manual 3AFE58177580

PARAMETER NR: 1.1


change value 123

F&E

PARAMETER NR: 1.1


saving in APC...

PARAMETER NR: 1.1


...done

R PARAMETER NR: 1.1


timeout ERROR! (R)

R PARAMETER NR: 1.1


ERROR! (R)

28