You are on page 1of 2

Declaration

Parameter Settings
Order information
Customer ERC Technik GmbH
DE-21244 Buchholz
Customer purchase order A8512147310S35300 Duro Dakovic -
Sales order number / Item 3023958027
Internal order number / Item DE-3006893280-10

Device information
Description Promag H 200 DN04 / 5/32"
TAG
Serial number SC32A219000
Order code 5H2B04-2U03/0
Extended order code 5H2B04-AABCCAAD5S0A+AAJA

Device
Device software 01.01.05
Communication type HART
Device revision Dev.Rev.: 2
Bus address 0

Expert → Sensor → System units


Volume flow unit dm³/min
Volume unit dm³
Mass flow unit kg/min
Mass unit kg
Density unit kg/l
Temperature unit °C

Expert → Sensor → Process param. → Low flow cut off


On value 0.05 dm³/min

Expert → Sensor → Sensor adjustm.


Install. direct. In arrow direct.

Expert → System → Display


Language English
Format display 1 value, max.
Value 1 display Volume flow
Value 2 display None
Value 3 display None
Value 4 display None
Display damping 0s

Operator
Cernay, 2022-01-25, Christophe Ansel

This document was generated electronically and is valid without signature.

Endress+Hauser Flowtec AG
35, Rue de l'Europe
F-68700 Cernay
France
www.endress.com Document ID: 22080078 Page 1/2
Declaration

Parameter Settings
Device information
Description Promag H 200 DN04 / 5/32"
TAG
Serial number SC32A219000

Expert → Application → Totalizer 1


Assign variable Volume flow
Unit totalizer dm³
Operation mode Net flow total
Failure mode Actual value

Expert → Application → Totalizer 2


Assign variable Volume flow
Unit totalizer dm³
Operation mode Net flow total
Failure mode Actual value

Expert → Application → Totalizer 3


Assign variable Volume flow
Unit totalizer dm³
Operation mode Net flow total
Failure mode Actual value

Expert → Output → Curr.output 1


Assign curr. Volume flow
Current span 4...20 mA NAMUR
4 mA value 0 dm³/min
20 mA value 2 dm³/min
Failure mode Max.
Damping out. 3s

Expert → Output → PFS output


Assign pulse Volume flow
Value per pulse 0.03 dm³
Pulse width 100 ms
Invert outp.sig. No
Failure mode No pulses

Endress+Hauser Flowtec AG
35, Rue de l'Europe
F-68700 Cernay
France
www.endress.com Document ID: 22080078 Page 2/2