Professional Documents
Culture Documents
conditioning
MEng- 5212
Introduction
• Refrigeration: The process of removing heat, and
the practical application is to produce or maintain
temperatures below the ambient.
• Air-conditioning: A form of air treatment whereby
temperature, humidity, ventilation, and air
cleanliness are all controlled within limits
determined by the requirements of the air
conditioned enclosure.
• Ventilation is supply of fresh air or extraction of
used air without conditioning
Refrigeration systems
-Vapour cycle
- Gas cycle
Vapour cycle refrigeration system:
• where h2 and h1 are the specific enthalpies (kJ/kg) at the exit and
inlet to the compressor, respectively.
• (h 2 − h1 ) is known as specific work of compression or simply work of
compression, which is equal to the work input to the compressor per
kilogram of refrigerant.
• Condenser: Heat transfer rate at condenser, 𝑄𝑐 is given by:
• where h3 and h2 are the specific enthalpies (kJ/kg) at the exit and
inlet to the condenser, respectively.
• The condenser pressure Pc is the saturation pressure corresponding
to condenser temperature Tc , i.e.,
• Expansion device:
• The chlorine molecules are once again free to combine with ozone
and the process repeats up to 10 000 times The net result appears to
be a steady depletion of the ozone content of the atmosphere at high
altitudes.
• Since ozone is the agent in the upper atmosphere that prevents the
entry of excessive, dangerous, ultraviolet radiation the consequences
of ozone depletion are obvious and serious.
• If one of the chlorine atoms in the molecule of a CFC refrigerant is
replaced by a hydrogen atom the stability of the molecule is much
reduced and its ozone depleting effect becomes smaller. This has
encouraged the use of such refrigerants, which are termed
hydrochlorofluorocarbons (HCFC), such as R22.
• Refrigerants with no chlorine present have ODF (ozone depletion
factor) values of zero. Such refrigerants are termed
hydrofluorocarbons (HFC).
• Of the refrigerants listed, R134a offers promise, being similar in many
respects to R12 but with no ozone depletion effect.
Safety
• Whichever refrigerant is used it must be safe. This is dealt with
in BS 4434: 1989, covering the design, construction and
installation of refrigeration plant and systems.
• Refrigerants are classified in three groups:
1. These are non-inflammable in vapour form at any concentration
in air at standard atmospheric pressure and 20C. They have a low
toxicity although when in contact with a flame or a hot surface
toxic products of decomposition may form. Examples are: R11,
R12, R13, R22, R113.
2. Toxicity is the dominant feature with these refrigerants and it is
almost impossible to avoid a toxic concentration if an escape of
refrigerant occurs. An example is: R717 (ammonia).
3. These are inflammable and are an explosive hazard, although
with a low order of toxicity. Examples are: R170 (ethane), R290
(propane), R600 (butane).
Group 3 refrigerants should not be used for institutional or
residential buildings, or those buildings used for public assembly.
Chapter-2: Vapor absorption refrigeration system
42
The COP of actual absorption refrigeration
systems is usually less than 1.
Air-conditioning systems based on absorption
refrigeration, called absorption chillers,
perform best when the heat source can supply
heat at a high temperature with little
temperature drop.
43
• SINGLE EFFECT VAPOUR ABSORPTION SYSTEM
• The single effect vapour absorption cycle using lithium bromide –water as working
fluid is shown in the figure below . Evaporator (E), Absorber (A), Generator (G),
Condenser(C), Precooler (PC), Preheater (PH) and Pump are the main components
of this system. An evaporator and absorber work at low pressure while the
generator and condenser work at high pressure.
• Process 3-4: High pressure gas from the heat exchanger flows
through a turbine, undergoes isentropic expansion and delivers net
work output.
• Process 4-1: Cold and low pressure gas from turbine flows through
the low temperature heat exchanger and extracts heat sensibly and
isobarically from a heat source, providing a useful refrigeration effect.
• From the above expression for COP, the following observations can be
made:
• a) For fixed heat rejection temperature (T3) and fixed refrigeration
temperature (T1), the COP of reverse Brayton cycle is always lower
than the COP of reverse Carnot cycle
• Fig. Comparison of reverse Carnot and reverse Brayton cycle in
T-s plane
• b) COP of Brayton cycle approaches COP of Carnot cycle as T1
approaches T4 (thin cycle), however, the specific refrigeration
effect [cp(T1-T4)] also reduces simultaneously.
• c) COP of reverse Brayton cycle decreases as the pressure ratio
rp increases
• Actual reverse Brayton cycle:
• The actual reverse Brayton cycle differs from the ideal cycle due to:
i. Non-isentropic compression and expansion processes
ii. Pressure drops in cold and hot heat exchangers
Fig. 9.4. Comparison of ideal and actual Brayton cycles T-s plane
• Ti = cabin temperature
simple vapour aircraft
refrigeration cycle
• where
– p = pt = total barometric pressure
– pa = partial pressure of dry air
– pv = partial pressure of water vapor.
Important psychrometric properties:
• Dry bulb temperature (DBT) is the temperature of
the moist air as measured by a standard
thermometer or other temperature measuring
instruments.
• Saturated vapour pressure (psat) is the saturated
partial pressure of water vapour at the dry bulb
temperature.
• Wet Bulb Temperature (TWB; °C or °F)
• The temperature at which water, by evaporating
into air, can bring the air to saturation at the same
temperature.
• In other words, TWB is the minimum temperature
that the moist air could achieve if enough water
was added to achieve saturation (RH = 100%).TWB
is often used to indicate how much water can be
added to the air through evaporation.
• Sling Psychrometer
• One device that uses the wet/dry bulb method is
the sling psychrometer, where the thermometers
are attached to a handle or length of rope and spun
around in the air for a few minutes
• What does the reading tell you?
• A. If the wet bulb temperature is lower than the dry
bulb the air-vapor mixture is unsaturated.
• B. If the wet bulb temperature is the same as the
dry bulb, the air-vapor is saturated.
• Relative humidity (Φ) is defined as the ratio of the mass of
water vapour in moist air to mass of water vapour in
saturated air at the same temperature and pressure.
𝑃𝑣
Φ=
𝑃𝑣𝑠
• When Φ is 100 percent, the air is saturated.
• Humidity ratio (W): The humidity ratio (or specific
humidity) W is the mass of water associated with each
kilogram of dry air.
• Dew-point temperature: If unsaturated moist air is cooled at constant
pressure, then the temperature at which the moisture in the air
begins to condense is known as dew-point temperature (DPT) of air.
• DPT is the temperature at which water will begin to condense out of
moist air.
• Enthalpy: The enthalpy of moist air is:
• Where
– cp = specific heat of dry air at constant pressure, kJ/kg.K
– cpw = specific heat of water vapor, kJ/kg.K
– t = Dry-bulb temperature of air-vapor mixture, oC
– W = Humidity ratio, kg of water vapor/kg of dry air
– ha = enthalpy of dry air at temperature t, kJ/kg
– hg = enthalpy of water vapor at temperature t, kJ/kg
– hfg = latent heat of vaporization at 0oC, kJ/kg
• Humid specific heat: From the equation for enthalpy of
moist air, the humid specific heat of moist air can be
written as:
cpm = cp + W.cpw
• where cpm = humid specific heat, kJ/kg.K
• cp = specific heat of dry air, kJ/kg.K
• cpw = specific heat of water vapor, kJ/kg
• W = humidity ratio, kg of water vapor/kg of dry air
• Substituting the approximate values of cp and hg, we obtain:
Psychrometric chart
• A Psychrometric chart graphically represents the thermodynamic
properties of moist air.
• the total, latent and sensible heat transfer rates (Qt, Ql and
Qs) can be written as:
• SHF is defined as the ratio of sensible to total heat transfer
rate, i.e.,
Energy balance:
• if hi > ha; then the total heat transfer is from water to air and water
gets cooled
• if hi < ha; then the total heat transfer is from air to water and water
gets heated
• if hi = ha; then the net heat transfer is zero, i.e., the sensible heat
transfer rate is equal to but in the opposite direction of latent heat
transfer. Temperature of water remains at its wet bulb temperature
value
Inside And Outside Design Conditions
• Introduction:
• Design and analysis of air conditioning systems involves selection of
suitable inside and outside design conditions, estimation of the
required capacity of cooling or heating equipment, selection of
suitable cooling/heating system, selecting supply conditions, design
of air transmission and distribution systems etc.
• Assuming no heat transfer due to the ducts and fans, the sensible and
latent heat transfer rates at the cooling coil are exactly equal to the
sensible and latent heat transfer rates to the conditioned space; i.e.,
• Fig.: A simple, 100% re-circulation type air conditioning system
• If the by-pass factor (X) of the cooling coil is known, then, from room
conditions, coil ADP and by-pass factor, the supply air temperature ts
is obtained using the definition of by-pass factor as:
• when the by-pass factor is zero, the minimum amount of
supply air flow rate required is:
• Fig.: A summer air conditioning system with reheat coil for high
latent cooling load applications
Cooling And Heating Load Calculations
-Solar Radiation Through Fenestration Ventilation And
Infiltration
Solar radiation through fenestration:
• Fenestration refers to any glazed (transparent) apertures in
a building, such as glass doors, windows, skylights etc.
• Because of their transparency, fenestrations transmit solar
radiation into the building.
• Thus the fenestration or glazed surfaces contribute a major
part of cooling load of a building.
Estimation of solar radiation through fenestration:
• The figure below shows an unshaded window made of
clear plastic glass. As shown in the figure, the
properties of this glass for solar radiation are:
• transmittivity (τ) = 0.80, reflectivity (ρ) = 0.08 and
absorptivity (α) = 0.12.
• As shown below, out of 100% radiation, 84% is
transmitted to the interiors of the building. Of course,
these figures are for a clear plate glass only.
• For other types of glass, the values will be different.
• the amount of solar radiation passing through a transparent surface
can be written as:
• where:
• A = Area of the surface exposed to radiation
• It = Total radiation incident on the surface
• τ = Transmittivity of glass for direct, diffuse and reflected
radiations
• α = Absorptivity of glass for direct, diffuse and reflected
radiations
• N = Fraction of absorbed radiation transferred to the indoors
by conduction and convection
• Fig.: Radiation properties of clear plate glass
• Under steady state conditions it can be shown that the fraction of
absorbed radiation transferred to the indoors, i.e., N is equal to:
• where U is the overall heat transfer coefficient, which takes into
account the external heat transfer coefficient, the conduction
resistance offered by the glass and the internal heat transfer
coefficient, and ho is the external heat transfer coefficient.
• From the above two equations, we can write:
• The term in square brackets for a single sheet, clear window glass
(reference) is called as Solar Heat Gain Factor (SHGF), i.e.,
• Thus SHGF is the heat flux due to solar radiation through the
reference glass (SS). The maximum SHGF values for different
latitudes, months and orientations have been obtained and are
available in the form of Tables in ASHRAE handbooks.
• Table: Maximum SHGF factor for sunlit glass located at 32°N (W/m2)
• Similar tables are available for other latitudes also in ASHRAE
Handbooks.
• For fenestrations other than the reference SS glass, a Shading Coefficient
(SC) is defined such that the heat transfer due to solar radiation is given by:
• The shading coefficient depends upon the type of the glass and the type of
internal shading devices.
• Table : Shading coefficients for different types of glass and internal shading
Effect of external shading:
• A very common method of providing external shading is to
use overhangs.
• The solar radiation transmitted into the building with
overhang is :
Infiltration:
• Infiltration may be defined as the uncontrolled entry of untreated,
outdoor air directly into the conditioned space.
• Infiltration of outdoor air into the indoors takes place due to wind
and stack effects.
• The wind effect refers to the entry of outdoor air due to
the pressure difference developed across the building due
to winds blowing outside the building.
• The stack effect refers to the entry of outdoor air due to
buoyancy effects caused by temperature difference
between the indoor and outdoors.
• infiltration is specified in terms of number of air changes
per hour (ACH). One ACH is equal to the airflow rate equal
to the internal volume of the occupied space per hour.
Heating and cooling loads due to ventilation and infiltration:
• The sensible and latent heat transfer rates due to ventilation and
infiltration, Qs,vi and Ql,vi are given by:
• 𝒎𝒐 and 𝒗𝒐 are the mass flow rate and volumetric flow rates of
outdoor air due to ventilation and infiltration
Cooling And Heating Load Calculations
-Heat Transfer Through Buildings - Fabric Heat
Gain/Loss
Introduction:
• Whenever there is a temperature difference between the
conditioned indoor space of a building and outdoor
ambient, heat transfer takes place through the building
structure (walls, roof, floor etc.).
• This is known as fabric heat gain or loss, depending upon
whether heat transfer is to the building or from the
building, respectively.
• Semi-empirical methods:
• The semi-empirical methods use the form suggested by the
analytical method along with experimental observations on
standard walls.
• These semi-empirical methods based on Equivalent
Temperature Difference (ETD) or Cooling Load Temperature
Difference (CLTD), are widely used by air conditioning
industry due to their simplicity.
• However, the empirical data covers only standard walls and
is suitable for specific location, orientation and day.
• Decrement factor and Time Lag:
• the heat transfer rate to the conditioned space at any time
θ can be written as:
• Where Tsol-air,m is the time averaged sol-air
temperature,Tsol-air,θ-φ is the sol-air temperature φ hours
before θ, U and A are the overall heat transfer coefficient
and area of the wall, λ is the decrement factor and φ is the
time lag.
• The time lag, φ is the difference between the time at which
the outer surface receives heat and the time at which the
inner surface senses it.
• Similar data are available for other types of walls and roofs
and for different latitudes. Adjustments are also suggested
for walls and roofs with insulation, wetted roofs etc.
Cooling And Heating Load Calculations
• Introduction
• heating and cooling load calculations are carried out to estimate the
required capacity of heating and cooling systems, which can maintain
the required conditions in the conditioned space.
• To estimate the required cooling or heating capacities, one has to
have information regarding the design indoor and outdoor
conditions, specifications of the building, specifications of the
conditioned space (such as the occupancy, activity level, various
appliances and equipment used etc.) and any special requirements of
the particular application.
• For comfort applications, the required indoor conditions are fixed by
the criterion of thermal comfort, while for industrial or commercial
applications the required indoor conditions are fixed by the particular
processes being performed or the products being stored.
• heating load calculations are carried out to estimate the heat loss
from the building in winter so as to arrive at required heating
capacities.
• cooling loads
• For any building there exists a balance point at which the solar
radiation (Qsolar) and internal heat generation rate (Qint) exactly
balance the heat losses from the building. Thus from sensible heat
balance equation, at balanced condition:
( a)
(b)
• when Tout > Tout,bal, then there is a need for cooling the building.
On the other hand, when Tout < Tout,bal, then there is a need for
heating the building. When Tout = Tout,bal, then there is no need for
either cooling or heating the building.
• For residential buildings (with fewer internal heat sources), the
balanced outdoor temperature may vary from 10 to 18 ℃ . As
discussed before, this means that if the balanced outdoor
temperature is 18℃, then a cooling system is required when the
outdoor temperature exceeds 18℃.
Methods of estimating cooling and heating loads:
• In practice, a variety of methods ranging from simple rules-of-thumb
to complex Transfer Function Methods are used in practice to arrive
at the building loads. For example, typical rules-of-thumb methods
for cooling loads specify the required cooling capacity based on the
floor area or occupancy.
• Rules-of-thumb are useful in preliminary estimation of the
equipment size and cost. The main conceptual drawback of rulesof-
thumb methods is the presumption that the building design will not
make any difference. Thus the rules for a badly designed building are
typically the same as for a good design.
• Table 35.1: Required cooling capacities for various applications based on rules-of
thumb(Croome and Roberts, 1981)
• More accurate load estimation methods involve a combination of analytical
methods and empirical results obtained from actual data, for example the
use of Cooling Load Temperature Difference (CLTD) for estimating fabric
heat gain and the use of Solar Heat Gain Factor (SHGF) for estimating heat
transfer through fenestration.
• These methods are very widely used by air conditioning engineers as they
yield reasonably accurate results and estimations can be carried out
manually in a relatively short time. Over the years, more accurate methods
that require the use of computers have been developed for estimating
cooling loads, e.g. the Transfer Function Method (TFM). Since these
methods are expensive and time consuming they are generally used for
estimating cooling loads of large commercial or institutional buildings.
ASHRAE suggests different methods for estimating cooling and heating
loads based on applications, such as for residences, for commercial
buildings etc.
• Cooling load calculations:
• The cooling load experienced by a building varies in magnitude from
zero (no cooling required) to a maximum value. The design cooling
load is a load near the maximum magnitude, but is not normally the
maximum. Design cooling load takes into account all the loads
experienced by a building under a specific set of assumed conditions.
• The assumptions behind design cooling load are as follows:
1. Design outside conditions are selected from a long-term
statistical database.
2. The load on the building due to solar radiation is estimated for
clear sky conditions.
3. The building occupancy is assumed to be at full design
capacity.
4. All building equipment and appliances are considered to be
operating at a reasonably representative capacity.
• The total building cooling load consists of heat transferred through
the building envelope (walls, roof, floor, windows, doors etc.) and
heat generated by occupants, equipment, and lights. The load due to
heat transfer through the envelope is called as external load, while
all other loads are called as internal loads.
• The percentage of external versus internal load varies with building
type, site climate, and building design. The total cooling load on any
building consists of both sensible as well as latent load components.
The sensible load affects dry bulb temperature, while the latent load
affects the moisture content of the conditioned space.
• Buildings may be classified as externally loaded and internally
loaded. In externally loaded buildings the cooling load on the
building is mainly due to heat transfer between the surroundings and
the internal conditioned space. Since the surrounding conditions are
highly variable in any given day, the cooling load of an externally
loaded building varies widely.
• In internally loaded buildings the cooling load is mainly due to
internal heat generating sources such as occupants or appliances or
processes. In general the heat generation due to internal heat
sources may remain fairly constant, and since the heat transfer from
the variable surroundings is much less compared to the internal heat
sources, the cooling load of an internally loaded building remains
fairly constant.
(g)
• where ACH is the number of air changes per hour and V is the
gross volume of the conditioned space in m3. Normally the
ACH value varies from 0.5 ACH for tight and well-sealed
buildings to about 2.0 for loose and poorly sealed buildings. For
modern buildings the ACH value may be as low as 0.2 ACH. Thus
depending upon the age and condition of the building an
appropriate ACH value has to be chosen, using which the
infiltration rate can be calculated.
• Representative values of infiltration rate for different types of windows,
doors walls etc. have been measured and are available in tabular form in air
conditioning design handbooks.
d) Miscellaneous external loads: In addition to the above loads, if the cooling
coil has a positive by-pass factor (BPF > 0), then some amount of ventilation air
directly enters the conditioned space, in which case it becomes a part of the
building cooling load. The sensible and latent heat transfer rates due to the by-
passed ventilation air can be calculated using equations (e) and (f) by replacing
Vo withVvent .BPF, where Vvent is the ventilation rate and BPF is the by-pass
factor of the cooling coil.
• In addition to this, sensible and latent heat transfer to the building also
occurs due to heat transfer and air leakage in the supply ducts. A safety
factor is usually provided to account for this depending upon the specific
details of the supply air ducts.
• If the supply duct consists of supply air fan with motor, then power
input to the fan becomes a part of the external sensible load on the
building. If the duct consists of the electric motor, which drives the
fan, then the efficiency of the fan motor also must be taken into
account while calculating the cooling load.
• Most of the times, the power input to the fan is not known as the
amount of supply air required is not known at this stage. To take this
factor into account, initially it is assumed that the supply fan adds
about 5% of the room sensible cooling load and cooling loads are
then estimated.
• Then this value is corrected in the end when the actual fan selection
is done.
• Estimation of internal loads:
• The internal loads consist of load due to occupants, due to
lighting, due to equipment and appliances and due to
products stored or processes being in the conditioned
space.
a) Load due to occupants: The internal cooling load due to
occupants consists of both sensible and latent heat
components.
(h)
• Table : Total heat gain, sensible heat gain fraction from occupants
• Values of CLF have been obtained for different types of buildings and
have been tabulated in ASHRAE handbooks.
• Since the latent heat gain from the occupants is instantaneous the CLF for
latent heat gain is 1.0, thus the latent heat gain due to occupants is given
by:
(i)
b) Load due to lighting: Lighting adds sensible heat to the conditioned space.
(j)
• The usage factor accounts for any lamps that are installed but are not
switched on at the time at which load calculations are performed. The
ballast factor takes into account the load imposed by ballasts used in
fluorescent lights. A typical ballast factor value of 1.25 is taken for
fluorescent lights, while it is equal to 1.0 for incandescent lamps. The values
of CLF as a function of the number of hours after the lights are turned on,
type of lighting fixtures and the hours of operation of the lights are
available in the form of tables in ASHRAE handbooks.
• c) Internal loads due to equipment and appliances: The
equipment and appliances used in the conditioned space
may add both sensible as well as latent loads to the
conditioned space.
(k)
• The installed wattage and usage factor depend on the type
of the appliance or equipment. The CLF values are available
in the form of tables in ASHARE handbooks.
• The latent load due to appliances is given by:
(l)
Table: Typical appliance load (C.P. Arora)
• where 𝑚𝑣𝑒𝑛𝑡 and 𝑉𝑣𝑒𝑛𝑡 are the mass and volumetric flow rates of the
ventilated air and X is the by-pass factor of the coil.
• The latent heat load on the coil due to ventilation is given by:
(b)
Fig. Single duct, constant volume system with multiple zones and
reheat coils
• Advantages of single duct, multiple zone, constant
volume systems with reheat coils:
a) Relatively small space requirement
b) Excellent temperature and humidity control over a wide range of
zone loads
c) Proper ventilation and air quality in each zone is maintained as the
supply air amount is kept constant under all conditions
• Disadvantages of single duct, multiple zone, constant
volume systems with reheat coils:
a) High energy consumption for cooling, as the air is first cooled to a
very low temperature and is then heated in the reheat coils.
b) b) Simultaneous cooling and heating is not possible.
• Single duct, variable air volume (VAV) systems:
(b)
Estimation of pressure loss in ducts:
• As air flows through a duct its total pressure drops
in the direction of flow. The pressure drop is due to:
1. Fluid friction
2. Momentum change due to change of direction and/or
velocity
• pressure drop or dynamic loss, Δpd. Thus the total
pressure drop Δpt is :
(c)
(f)
(a) (b)
• where V2 is the velocity in the downstream, and A1’ and A2 are the
areas at vena contracta and after contraction, respectively.
Table : Values of contraction coefficient Cc for different area ratios
• f) Miscellaneous fittings, openings etc.: The dynamic pressure loss
coefficients for other types of fittings, such as suction and discharge
openings are also available in the form of tables.
• Filters, cooling and heating coils, dampers etc.: The pressure drop
across air handling unit equipment, such as, air filters, dampers,
cooling and heating coils depend on several factors. Hence, normally
these values have to be obtained from the manufacturer’s data.
Static regain:
• Whenever there is an enlargement in the cross-sectional area of the
duct, the velocity of air decreases, and the velocity pressure is
converted into static pressure.
• The increase in static pressure due to a decrease in velocity pressure
is known as static regain.
• In an ideal case, when there are no pressure losses, the increase in
static pressure (Δps ) is exactly equal to the decrease in velocity
pressure (Δpv ) and the total presure (Pt) remains constant. In an
ideal case, when there are no pressure losses:
• Thus for ideal enlargement the Static Regain Factor R is equal to 1.0,
whereas it is less than 1.0 for non-ideal enlargement.
• Fig.(a): Ideal enlargement Fig.(b): Sudden enlargement
Design Of Air Conditioning Ducts
• Introduction:
• The chief requirements of an air conditioning duct
system are:
1. It should convey specified rates of air flow to prescribed locations
2. It should be economical in combined initial cost, fan operating cost
and cost of building space
3. It should not transmit or generate objectionable noise
• Generally at the time of designing an air conditioning duct
system, the required airflow rates are known from load
calculations. The location of fans and air outlets are fixed
initially. The duct layout is then made taking into account
the space available and ease of construction. In principle,
required amount of air can be conveyed through the air
conditioning ducts by a number of combinations.
• However, for a given system, only one set results in the
optimum design.
• General rules for duct design:
1. Air should be conveyed as directly as possible to save
space, power and material
2. Sudden changes in directions should be avoided. When
not possible to avoid sudden changes, turning vanes
should be used to reduce pressure loss
3. Diverging sections should be gradual. Angle of
divergence ≤ 20°.
4. Aspect ratio should be as close to 1.0 as possible.
Normally, it should not exceed 4
5. Air velocities should be within permissible limits to
reduce noise and vibration
6. Duct material should be as smooth as possible to
reduce frictional losses
• Classification of duct systems:
– Low pressure systems: Velocity ≤ 10 m/s, static pressure
≤ 5 cm H2O (g)
– Medium pressure systems: Velocity ≤ 10 m/s, static
pressure ≤ 15 cm H2O (g)
– High pressure systems: Velocity > 10 m/s, static pressure
15<ps ≤ 25 cm H2O (g)
• High velocities in the ducts results in:
1. Smaller ducts and hence, lower initial cost and lower
space requirement
2. Higher pressure drop and hence larger fan power
consumption
3. Increased noise and hence a need for noise attenuation
• Typical recommended velocities are:
– Residences: 3 m/s to 5 m/s
– Theatres: 4 to 6.5 m/s
– Restaurants: 7.5 m/s to 10 m/s
• If nothing is specified, then a velocity of 5 to 8 m/s is used
for main ducts and a velocity of 4 to 6 m/s is used for the
branches.
• The allowable air velocities can be as high as 30 m/s in
ships and aircrafts to reduce the space requirement.
• Commonly used duct design methods:
• A-B is the duct running from the supply air fan to zone 1, A-
B-C is the duct running from supply fan to conditioned zone
and so on.
• These are known as duct runs. The run with the highest
pressure drop is called as the index run.
• Due to the several issues involved, the design of an air
conditioning duct system in large buildings could be a
sophisticated operation requiring the use of Computer
Aided Design (CAD) software. However, the following
methods are most commonly used for simpler lay-outs
such as the one shown in Fig. below:
1. Velocity method
2. Equal Friction Method
3. Static Regain method
Fig.: Typical air conditioning duct lay-out
Velocity method:
• The various steps involved in this method are:
i. Select suitable velocities in the main and branch ducts
ii. Find the diameters of main and branch ducts from airflow rates and
velocities for circular ducts. For rectangular ducts, find the cross-
sectional area from flow rate and velocity, and then by fixing the aspect
ratio, find the two sides of the rectangular duct
iii. From the velocities and duct dimensions obtained in the previous
step, find the frictional pressure drop for main and branch ducts using
friction chart or equation.
iv. From the duct layout, dimensions and airflow rates, find the dynamic
pressure losses for all the bends and fittings
v. Select a fan that can provide sufficient FTP for the index run
vi. Balancing dampers have to be installed in each run. The damper in
the index run is left completely open, while the other dampers are
throttled to reduce the flow rate to the required design values.
• Equal friction method:
• In this method the frictional pressure drop per unit
length in the main and branch ducts (Δpf/L) are kept
same, i.e.,
• iii. Since the frictional pressure drop per unit length is same for
all the duct runs, the equivalent diameters of the other duct
runs, B to I are obtained from the equation:
• iv. If the ducts are rectangular, then the two sides of the rectangular
duct of each run are obtained from the equivalent diameter of that
run and by fixing aspect ratio as explained earlier.
• v. Next from the dimensions of the ducts in each run, the total
frictional pressure drop of that run is obtained by multiplying the
frictional pressure drop per unit length and the length, i.e.,
• vi. Next the dynamic pressure losses in each duct run are
obtained based on the type of bends or fittings used in that run.
• vii. Next the total pressure drop in each duct run is obtained by
summing up the frictional and dynamic losses of that run, i.e.,
• viii. Next the fan is selected to suit the index run with the highest
pressure loss.
• Dampers are installed in all the duct runs to balance the total
pressure loss.
• Equal friction method is simple and is most widely used conventional
method.
• Static Regain Method:
• This method is commonly used for high velocity systems with long
duct runs, especially in large systems. In this method the static
pressure is maintained same before each terminal or branch. The
procedure followed is as given below:
• i. Velocity in the main duct leaving the fan is selected first.
• ii. Velocities in each successive runs are reduced such that the gain
in static pressure due to reduction in velocity pressure equals the
frictional pressure drop in the next duct section. Thus the static
pressure before each terminal or branch is maintained constant.
Fig.: Principle of static regain method