Professional Documents
Culture Documents
• Low pressure Refrigerant vapours (from the evaporator) enter the Abrsorber
where these are absorbed by the liquid solution present in the absorber thus
forming a rich solution
(The solution in the absorber is called a strong solution because it is rich in
refrigerant)
• The absorption process causes the increase in solution temperature. To resist
the tendency, a cooling coil removes this heat of solution
ME - 437 : Refrigeration & Air Conditioning 5
• The pump draws the strong solution from the absorber, elevates the pressure
of the solution, and forces it into the generator
• In the generator the addition of heat raises the temperature, which drives off
some of the refrigerant as a vapour at high pressure and temperature
• The heat can added from Solar energy, waste heat from the process
industry, exhaust gases from automobile, power plants, steel plants, gas
power plants, etc.
• As the refrigerant vapour leaves the solution (to condenser) in the generator,
the solution becomes weak or have a low concentration of refrigerant
• The weak solution flows back to the absorber through a throttling valve
whose purpose is to expand it to lower pressure
• From the generator the refrigerant proceeds through the condenser,
expansion valve and evaporator, thus completing the cycle
• If two vessels were connected as shown in the figure, one vessel containing LiBr-
water solution and the other pure water, each liquid would exert a water-vapour
pressure that is a function of the solution temperature and the concentration of the
solution.
• At equilibrium the water-vapour pressure exerted by the two liquids would be equal ,
reaching a T-P-C point state having Tw = 40 C, Tsolution = 80 C and concentration of
solution 59%LiBr
• Many such combinations Tw = f ( Tsoluiton , LiBr %, Pvapor) are possible for a given
solution and can be plotted on graphs; like Fig 17.5 let see it
ME - 437 : Refrigeration & Air Conditioning 12
Temperature-Pressure-Concentration Properties
X1 = 0.5 or 50%
X2 = 0.664 or 66.4%
18
ME - 437 : Refrigeration & Air Conditioning
Calculation of Mass Flow Rates
• Knowing m1 0.6kg / s and applying mass balance across generator give us
following two equations
• Total mass flow balance : m2 m3 m1 0.6
• LiBr Solution Mass flow : m1 x1 m2 x2
0.6 0.50 m2 0.664
• Solving these
two equations, we get
the values of mass flow rates
m 2 0.452kg / s m 3 0.148 Kg / s
19
ME - 437 : Refrigeration & Air Conditioning
Enthalpy of LiBr Solutions
• For thermal calculations on the absorption cycle, enthalpy data must be available for the
working substances at all crucial positions in the cycle
• Water in liquid and vapour forms flows in and out of the condenser & evaporator, so
enthalpies at these points can be determined from a table of properties of water
• In the generator and absorber, LiBr-water solutions exist for which enthalpy is a function
of both - solution temperature and concentration
Ex. 17.3 : For absorption system of previous example, compute qg, qc, qa, qe & COP
Data from Previous Exam ple
m1 = 0.6 Kg/s, m2 = 0.452 Kg/s, m3 = m4 = m5 = 0.148 Kg/s, X1 =0.5 and X2 =0.664
Enthalpy of Solution from Fig. 17.8
• at 30 °C and x1 of 50% h1 = -168 kJ/kg
• At 100 °C and x2 of 66.4% h2 = -52 kJ/kg
Enthalpy of water are fond from Table A.1 as:
• h3 = hvapor @ 100 C = 2676 KJ/Kg
• h4 = hliquid @ 40 C = 167.5 KJ/Kg
• h5 = hvapor @ 10 C = 2520 KJ/Kg
Now from Energy Balance, heat transfer rates are established as:
Qg m3 h3 m2 h2 m1 h1 473.3KW Qa m2 h2 m5 h5 m1 h1 450.3KW
Qe m5 h5 m4 h4 384.2 KW Qc m3 h3 m4 h4 371.2 KW
Qe 348.2
COP 0.736
Q g 476.6
The solution of Ex. Show that Qa reduces while Qg reduces slightly and increases
COP to 0.783 (from 0.736)
Cooling effect
COPabs
Work input
QL QL
Qgen W p ,in Qgen