CONDITION M3/HR M
RATED 283.9 123.66 8x6x13A ES
150% 425.85 80.38
1000 GPM 118 to 198 psi, (273' to 457')
SECONDARY 300.02 122.5 1250 GPM 112 to 194 psi, (259' to 448')
1500 GPM 103 to 187 psi, (238' to 432')
PATTERSON PUMP COMPANY NOL (MAX) POWER IMPELLER D05-129793
A Gorman-Rupp Company Phone: (706) 886-2101 177 KW
Post Office Box 790 www.pattersonpumps.com CURVE No. EPCI-1117
Toccoa, Georgia 30577 U.S.A.
3000 RPM
180 600
UL LISTED / FM APPROVED

160
500
318 MM 55% 60% 65% 70% 75%
140
* 303 MM 80%
PUMP TOTAL HEAD (M)

81.6%
120 400
80%

PUMP TOTAL HEAD (FT)


100
75% 300
80 252 MM
70%
60 72.7% 200
65%

40
* ACTUAL IMPELLER DIAMETER 100
20 DETERMINED BY TESTING.

0 8 0
NPSHR (M)

NPSHR
4
PUMP INPUT POWER (KW)

PUMP INPUT POWER (HP)


300 0 400

300
200
200
318 MM
100
100
252 MM
0 0

M3/HR 0 80 160 240 320 400 480 560 640

0 400 800 1200 1600 2000 2400 2800


GPM