Technical Offer
2.5” Melton Nozzle jet/spray/off
KENNEDY AWWA C509 RESILIENT WEDGE GATE VALVES (1993)
During the decade of the 1980’s, the waterworks industry was introduced to the Resilient Seated Gate Valve, a design
principal that now dominates in preference for use in distribution systems. Kennedy Valve Company was at the forefront in
this industry-wide movement by introducing the Style 8000, our version of the best European and domestic designs.

The combination of evolving technology and changing market influences presents the unique opportunity once again for
Kennedy Valve to be at the forefront as a leader in modern valve design.

The Style 8000 RS gate valve embodies all of the latest valve technology for simplicity, durability and superior performance;
It is available in size range 3” thru 12” and meets AWWA standards C-509. Additionally, 4” thru 12” are listed by
Underwriters Laboratories and are approved by Factory Mutual Association.

Designed to control. . . built to perform. . .here’s the valve that sets the standard. The Kennedy valve was engineered on the
belief that bottle-tight closure is the primary function of any valve. That’s why the totally encapsulated wedge was designed
to provide dual seating. A whistle-clean waterway provides maximum flow without the loss of head experienced in other
valves.

A durable fusion bonded epoxy coating both inside and out complying with ANSI / AWWA C550, providing unexcelled
abrasion and corrosion protection is standard. Absolutely no compromise in materials or workmanship and it carries a 10
year limited warranty. . . it’s the clear choice of those who demand the best.

EASE OF OPERATION
The Kennedy Valve RSGV has only two moving internal parts—the gate and the stem.

The gate is fully supported throughout travel by an integrally cast tongue and groove fit between it and the valve body. Lugs
on the gate fully engage the coated guides cast into the valve body so the gate closes smoothly, without “chatter”, every time.

This positive gate alignment, plus positioning and engagement of the stem nut, virtually eliminate stem binding, and provide
balanced loads and low operating torques. The Kennedy Valve RSGV is among the lowest in operating torques of all
available competitive type valves

POSITIVE SEALING
A dual rubber seal is formed between the rubber encapsulated resilient wedge and the valve body to guarantee drop-tight
shut-off every time. The combination of true compression and dynamic wedging of the gate is created without harmful
sliding, shearing or other wear-inducing action.

The massive vulcanized rubber seating edges on the gate self-absorb normal wear and tear, assuring a positive seal, even after
years of service. The Kennedy Valve RSGV will seal bubble-tight to 250 psi working pressure, with the flow in either
direction and the valve in any position.

FULL FLOW CAPACITY / DUAL SEATING


The Kennedy Valve RSGV features an unobstructed, thru-conduit flow path for full flow capacity. Closed, the RSGV
provides bottle-tight, zero leakage in either direction at full rated differential pressure with dual body gate seating.

July 2005 / C509 Gate Valves


PRODUCT ANALYSIS / FEATURES & BENEFITS / PERFORMANCE INFORMATION
KENNEDY AWWA C509 RESILIENT WEDGE GATE VALVES (1993)
FEATURES BENEFIT
Bubble Tight Closure at 250 psi (AWWA) • No Leakage – No loss of water
3” – 12” at 250 psi (AWWA)
Dual Rubber Seal • Assures drop-tight shut-off in either direction.
Smooth, unobstructed waterway to maximize flow. • High flow characteristics
• 100% smooth passage without turbulent flow
• No sediment build up
• Will not impede travel of line cleaning tools
Only Three Internal Parts • Virtually maintenance free
Only Two Moving Parts, the gate & the stem • Less friction, less torque, longer life.
Integral Cast Tongue and Groove between wedge • Positive gate alignment every time
and valve body.
No Seat Rings • Nothing to be damaged by scoring
Delrin* Anti-Friction Thrust Bearing • Operating torque to close and open held to
absolute minimum
Solid, Bronze Stem Nut and High Strength Bronze • No corrosion
Stem • Trouble free service
Stem Nut is Self Centering • Eliminates possible stress on stem and wedge
Two O-Ring Seals Above Stem Thrust Collar and • Two O-Rings can be replaced with valve in
One Below service
High Strength Iron Wedge Fully Encapsulated • Trouble free service with minimum maintenance
with rubber Permanently Bonded to Metal. • No leaks – no wear
No Lubrication Required • Trouble free service
American Cast and Assembled • American Jobs
• American backed product for more than 100
years
• American quality
10 year limited warranty against defective • Customer assurance that Kennedy Valve believes
materials or workmanship in the strong product they produce.
Body / Bonnet Epoxy Coating Inside & Out • Unprecedented Protection Against Corrosion and
abrasion
* DuPont Trademark

PERFORMANCE INFORMATION
• 3”- 6” valves sizes have been hydrostatically shell tested at five (5) times UL rated pressure (1000 psi).
• 8”,10”, and 12” have been hydrostatically shell tested at four (4) times UL rated pressure (800 psi).
• Valve is capable of bubble-tight seal at pressures up to (400psi) for short periods of time.
• Valve has been subjected to torques 150 percent of the designated minimum required torques.
• Valve has been cycle tested 5,000 times without loss of bubble-tight seal.
• For complete data on the tests Underwriters Laboratories performed, reference UL File EX 783

July 2005 / C509 Gate Valves


SUGGESTED SPECIFICATIONS (3”-12”) (Styles 8000 NRS: 4068 OS&Y)(1 of 2)
KENNEDY AWWA C509 RESILIENT WEDGE GATE VALVES (1993)
General: Gate valves shall be of the resilient seated wedge type, fusion bonded epoxy coated to ANSI / AWWA
C550, cast iron body design. They shall comply with the American Water Works Association Gate Valve
Standard C-509 as latest revised.
____________________________________________________________________________________________________
Approvals: Gate Valve to Meet or Exceed the Requirements of AWWA C509
Gate Valve to Meet or Exceed the Requirements of UL-262 (4”-12”)
Gate Valve to Meet or Exceed FM – 1120 / 1130 (4”-12”)
Gate Valve to Meet or Exceed ULC – Underwriters’ of Canada
Gate Valve to Meet NSF 61
Gate Valve Wedge to Meet or Exceed The Requirement of ASTM D429
____________________________________________________________________________________________________
Testing: Each valve shall be hydrostatically tested to the requirements of both AWWA and UL/FM and be rated for
250 psi AWWA service.

Valves shall be rated for zero leakage at 250psi water working pressure and have a 500psi hydrostatic test
for structural soundness for 3” through 12”.

All testing shall be conducted in accordance with AWWA C-509


____________________________________________________________________________________________________
Pressure Ratings: Size Range Water Working Pressure psi Bubble-tight Test psi Hydrostatic Shell Test psi
3”-12” AWWA 250psi 250psi 500psi
4”-12” ULFM 200psi 200psi 400psi

Materials: All cast iron shall conform to ASTM-A126 Class B. Castings shall be clean and sound without defects that
will impair their service. No plugging or welding of such defects will be allowed.

Stem and wedge nut shall be a copper alloy in accordance with section 4.4.5 of AWWA C509

Bolts for above ground valves shall be electro-zinc plated steel with hex heads and hex nuts in accordance
with ASTM A-307, and A-563 respectively.

Bolts for below ground valves shall be 304 stainless steel with hex heads and hex nuts.
____________________________________________________________________________________________________
Coating 5-8 mill inside and out.
Thickness
____________________________________________________________________________________________________
Wedge / Gate: The wedge shall be of cast iron and completely encapsulated with a resilient elastomer material
permanently bonded to the wedge and have a rubber tearing bond that meets ASTM D429.
____________________________________________________________________________________________________
Markings: Markings in accordance with AWWA standard. Includes approvals (AWWA, UL, FM), name of
manufacturer, the year of manufacture, maximum working pressure and size of valve.
In addition, country of origin to be clearly cast into body & cover castings.
____________________________________________________________________________________________________
End Mechanical joint end valves to match ANSI / AWWA C111/A21.11.
Connections: Flanged end valves to match ANSI / AWWA C110/A21.10(ASME B16.1, Class 125)
Tapping valves through 12” shall mate all sleeves through 12” outlet regardless of manufacturer. Valves
shall be furnished with tapping sleeve side to ACME B16.1 Class 125 flanged end with centering ring.
Outlet side of valve shall be mechanical joint with (without) accessories to ANSI / AWWA C-111/A21.11.
Push-on ends suitable for stab joints with ductile or cast iron and C900 / SDR plastic pipe.

July 2005 / C509 Gate Valves


Portable Dry Chemical Powder Fire Extinguisher
Stored Pressure Operated
▪▪APPLICATIONS
BAVARIA PHOENIX is designed for protecting medium
hazard areas, such as industrial and commercial
complexes, petroleum companies, warehouses,
residential buildings, vehicles and others

▪▪EFFICIENCY
High extinguishing performance rating due to its
multipurpose dry chemical powder “BAVARIA
Superlative Powder“ ABCDE, and easy use

RELIABILIT Y
Robust, functional and permanent reliable technology.

▪▪UNIVERSALIT Y
Suitable for solid and glowing incendiary substances,
liquid substances or substances becoming liquid and
gaseous substances

▪▪CREDENTIALS
BAVARIA Phoenix is approved and certified according to
EN3, TÜV, CE, GS and ES734

▪▪SPEED
Pull out safety pin for immediate readiness and press
down operating lever for fire fighting

▪▪EASY TO HANDLE
Optimized ergonomic grip, equipped with a hose and
nozzle with handle for high maneuverability

▪▪ECONOMY
Low maintenance due to identical components
throughout the series

▪▪OPERATION & IMPLEMENTATION


- Simple and easy-to-use release mechanism
- Perfect amount of extinguishing agent due to
ergonomically designed head valve & nozzle

▪▪QUALIT Y
BAVARIA is certified according to Quality, Environment
and OHSAS Management Systems ISO 9001, ISO 14001
and BS-OHSAS 18001
Portable Dry Chemical Powder Fire Extinguisher
Stored Pressure Operated
Features:

▪▪ High extinguishing rating


▪▪ Allows intermittent and repeated operation
▪▪ Special engineered polymer valve
▪▪ Equipped with a hose and polymer nozzle with handle
for high maneuverability
▪▪ Pressure gauge for instant pressure indication and
Pressure check valve.
▪▪ Electricity and corrosion-proof protective base
▪▪ Affords the highest extinguishing rating due to
its multipurpose dry chemical powder “BAVARIA
Superlative Powder ABCDE” that is also suitable for
Aluminum, Magnesium and their alloys, Calcium and
Zinc metals, which are classified as D class fires, by
applying the powder carefully and with gentle jet to
these metal fires
▪▪ Suitable for electrical equipment up to 1000 V, at
minimum distance 1 m
▪▪ High quality surface treatment and red polyester
coating

Technical Specifications:
Capacity 4 kg 6 kg
Extinguishing Rating Acc. to EN3 34A 144B C 43A 233B C
Operating Temperature Range* -30°C to +60°C -30°C to +60°C
Testing Pressure 35 bar 35 bar
Bursting Pressure Over 70 bar Over 70 bar
Valve Material Special engineered polymer valve
Discharge Material Hose with special engineered polymer nozzle
Shell Material DC 04 Steel according to DIN EN 10130
Extinguishing Agent MAP-based “BAVARIA Superlative Powder ABCDE“
Paint Finish Surface treatment and 100% polyester coating
Approx. Gross Weight 7.850 Kg 10.500 Kg
Approx. Unit Dimension (lxwxh) cm 23.0 x 18.0 x 47.0 25.5 x 17.5 x 56.5

Warranty:
Period of Warranty 2 Years
Coverage of the Warranty Against material failure and production defects
Limited to the replacement of the defected part or product after
Method of Warranty Coverage
verification that the failure is covered by the scope of the warranty
Failures due to misuse, mishandling, or inspection or repair by an
Warranty Exclusions
unauthorized dealer or entity
Carbon Steel Cabinets
Single Cabinet

Description
Melton Fire Cabinets are generally fabricated from Carbon steel material coated with RAL3000
Corrosion resistant coating.
Melton Cabinets are deigned to accommodate firefighting equipment. The cabinets are
designed in accordance with BSEN671-1 standard.
The quality of workmanship and finishes are carefully planned and executed from the initial
stages or preparing the material, fabrication, up to surface preparation and finishing.
Specifications
 Dimension: 800*800*300 mm
 Material: 1.5 mm Mild steel
 Painting: Electrostatic Powder Coating, RAL3000
 Two well-spaced bush and pin hinges or hidden hinges provide excellent support for
door and reduces door deflection during open position
 Cup handle for ease access
 Easy and fast installation with minimum labour required
 Can be fixed on vertical legs on pallets using bolts
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH

UL and CSFM Listed, FM Approved, NYMEA Accepted,


CE Marked
Dimensions: 6.19"L X 2.25"W X 5.88"H
15,7cm L X 5,7cm W X 14,6cm H
Weight: 2 lbs. (0,9 kg.)
Enclosure: Cover - Die-Cast
Finish - Red Spatter Enamel
Base - Die Cast Zinc
All parts have corrosion resistant finishes.
Cover Tamper: Tamper resistant screws,
Optional cover tamper kit available.
Contact Ratings:
OSYSU-1: One set of SPDT (Form C)
OSYSU-2: Two sets of SPDT (Form C)
15.00 Amps at 125/250VAC
2.50 Amps at 30VDC resistive
Environmental Limitations:
• NEMA 4 and NEMA 6P Enclosure (IP67) when
used with appropriate watertight conduit fittings.
• Indoor or Outdoor use (Not for use in hazardous
locations. See bulletin no. 5400705 OSYS-U-EX
for hazardous locations.)
• Temperature Range: -40°F to 140°F (-40°C to 60°C)
Conduit Entrances:
2 knockouts for 1/2" conduit provided
Service Use:
Automatic Sprinkler NFPA-13
OSYSU-1 Stock No. 1010106 One or two family dwelling NFPA-13D
OSYSU-2 Stock No. 1010206 Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72

GENERAL INFORMATION
The OSYSU is used to monitor the open position of an OS screws and hex keys are available. See ordering informa-
& Y (outside screw and yoke) type gate valve. This device tion on page 4.
is available in two models; the OSYSU-1, containing one OPTIONAL COVER TAMPER SWITCH
set of SPDT (Form C) contacts and the OSYSU-2, con- A field installable cover tamper switch is available as an
taining two sets of SPDT (Form C) contacts. These option which may be used to indicate removal of the cover.
switches mount conveniently to most OS & Y valves See ordering information on page 4.
ranging in size from 2" to 12" (50mm to 300mm). They will
mount on some valves as small as 1/2" (12,5mm). TESTING
The OSYSU and its associated protective monitoring sys-
The cover is held in place by two tamper resistant screws tem should be inspected and tested in accordance with
that require a special tool to remove. The tool is furnished applicable NFPA codes and standards and/or the authority
with each device and should be left with the building owner having jurisdiction (manufacturer recommends quarterly or
or responsible party. Replacement or additional cover more frequently).

Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com

PRINTED IN USA MKT. #8820004 - REV P PAGE 1 OF 4


12/01
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH

FIG. 1 SMALL VALVE INSTALLATION - 1/2" THRU 2 1/2" (12,5mm THRU 63,5mm) SIZES
THESE SWITCHES MOUNT CONVENIENTLY TO MOST 2" TO 12" OS & Y VALVES. THEY WILL MOUNT ON SOME
VALVES AS SMALL AS 1/2" (12,5MM). J-HOOKS MAY BE REQUIRED ON VALVES WITH LIMITED CLEARANCE.

SMALL VALVE INSTALLATION


6. Remove the OSYSU. File a 1/8" (3,2mm) deep groove
1. Remove and discard "C" washer and roller from the trip centered on the mark on the valve stem utilizing a 3/16"
rod. (4,8mm) round, non-tapered file. Round and smooth the
2. With the valve in the FULL OPEN position, locate the edges of the groove to prevent damage to the valve
OSYSU across the valve yoke as far as possible from the packing and to allow the trip rod to move easily in and out
valve gland, so that the trip rod lays against the non- of the groove as the valve is operated.
threaded portion of the valve stem. 7. Mount the OSYSU with the trip rod centered in groove.
3. Loosen the locking screw that holds the trip rod in place 8. Final adjustment is made by loosening 2 screws (see Fig.
and adjust the rod length (see Fig. 4). When adjusted 1) and sliding the OSYSU on the bracket. Adjustment is
properly, the rod should extend past the valve screw, but correct when switches are not activated with the trip rod
not so far that it contacts the clamp bar. Tighten the seated in the valve stem groove and that the switches
locking screw to hold the trip rod in place. activate when the trip rod moves out of the groove.
NOTE: If trip rod length is excessive, loosen the locking 9. Tighten the adjustment screws and all mounting hardware.
screw and remove the trip rod from the trip lever. Using Check to insure that the rod moves out of the groove easily
pliers, break off the 1" (25mm) long notched section (see and that the switches activate within one turn when the
Fig. 5). Reinstall trip rod and repeat Step 3 procedure. valve is operated from the FULL OPEN towards the
4. Mount the OSYSU loosely with the carriage bolts and CLOSED position.
clamp bar supplied. On valves with limited clearance use NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT
J-hooks supplied instead of the carriage bolts and clamp THE STEM THREADS DO NOT ACTIVATE THE SWITCH.
bar to mount the OSYSU. THE SWITCH BEING ACTIVATED BY THE STEM THREADS
5. Mark the valve stem at the center of the trip rod. COULD RESULT IN A FALSE VALVE OPEN INDICATION.

PRINTED IN USA MKT. #8820004 - REV P PAGE 2 OF 4


12/01
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH

FIG. 2 LARGE VALVE INSTALLATION - 3" THRU 12" (76mm THRU 300mm) SIZES

LARGE VALVE INSTALLATION (9,5mm) round, non-tapered file. Round and smooth the
edges of the groove to prevent damage to the valve
1. With the valve in the FULL OPEN position, locate the
packing and to allow the trip rod to move easily in and out
OSYSU across the valve yoke as far as possible from the
of the groove as the valve is operated.
valve gland, so that the trip rod lays against the non-
threaded portion of the valve stem. 6. Mount the OSYSU loosely with the trip rod centered in
groove.
2. Mount the OSYSU loosely with the carriage bolts and
clamp bar supplied. 7. Final adjustment is made by loosening 2 screws (see Fig.
2) and sliding the OSYSU on the bracket. Adjustment is
3. Loosen the locking screw that holds the trip rod in place
correct when switches are not activated with the trip rod
and adjust the rod length (see Fig. 4). When adjusted
seated in the valve stem groove and that the switches
properly, the rod should extend past the valve screw, but
activate within one turn when the valve is operated from the
not so far that it contacts the clamp bar. Tighten the
FULL OPEN towards the CLOSED position.
locking screw to hold the trip rod in place.
8. Tighten the adjustment screws and mounting hardware.
NOTE: If trip rod length is excessive, loosen the locking
Check to insure that the rod moves out of the groove
screw and remove the trip rod from the trip lever. Using
easily and that the switches activate within one turn when
pliers, break off the one 1" (25mm) long notched section
the valve is operated from the FULL OPEN towards the
(see Fig. 5). Reinstall trip rod and repeat Step 3 proce-
CLOSED position.
dure.
NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT
4. Mark the valve stem at the center of the trip rod.
THE STEM THREADS DO NOT ACTIVATE THE SWITCH.
5. Remove the OSYSU. File a 1/8" (3,2mm) deep groove THE SWITCH BEING ACTIVATED BY THE STEM THREADS
centered on the mark of the valve stem utilizing a 3/8" COULD RESULT IN A FALSE VALVE OPEN INDICATION.

PRINTED IN USA MKT. #8820004 - REV P PAGE 3 OF 4


12/01
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH

FIG. 3 DIMENSIONS FIG. 4 PARTS

BREAKING EXCESSIVE ROD SWITCH TERMINAL TYPICAL ELECTRICAL CONNECTIONS


LENGTH CONNECTIONS
CLAMPING PLATE
FIG. 5 TERMINAL

CAUTION:
An uninsulated section of a single conductor Contacts shown in normal (valve open) condition.
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervi- TYPICAL SWITCH ACTION
sion of the connection in the event that the wire
becomes dislodged from under the terminal.

ORDERING INFORMATION
MODEL DESCRIPTION STOCK NO.
OSYSU-1 Outside Screw & Yoke-Supervisory Switch (Single switch) 1010106
OSYSU-2 Outside Screw & Yoke-Supervisory Switch (Double switch) 1010206
-- Cover Screw 5490344
-- Hex Key for Cover Screws and Installation Adjustments 5250062
-- Optional Cover Tamper Switch Kit 0090131
For pressure reducer type valve installation kits (if required) contact valve manufacturer.

PRINTED IN USA MKT. #8820004 - REV P PAGE 4 OF 4


12/01
Test And Drain Valve

A61
• FEMALE x FEMALE
CERTIFICATIONS

Standard equipment:

b
Female NPT inlet and outlet, forged
brass body, chrome plated ball
with teflon seats.
<8>®
APPROVED LISTED 36Y7

FM APPROVAL ONLY FOR 1" and 1-1/4"


a Rated pressure: 300 psi

c
alb 1" 1" 1" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-114" 1-1/4"

Orifice 3/8" 7/16" 1/2" 17/32" 318" 7/16" 1/2" 17/32" 518" 3/4"

K factor 2.8 4.2 5.6 8.0 2.8 4.2 5.6 8.0 11.2 14.0
c

B~
H
B ~ alb 2"
o
idQ" Orifice

K factor
7/16"

4.2
1/2"

5.6
17/32"

8.0
5/8"

11.2
3/4"

14.0
15/16"

16.8
1-5/64"
22.4
1-9/64"

25.2
=
A
DIMENSION C (plug) PORT A B C D H

1" & 1-1/4" 1/4" 1-1/16" 5-1/32" 2-43/64" 5-11/32" 4-27164" 1-57/64

2" 1/4" 1-12/16" 6-6132" 4" 6-26/32" 6-21/64" 2-40/64"

A61
• GROOVE X GROOVE
CERTIFICATIONS

Standard equipment:
GROOVE inlet and outlet, forged
brass body, chrome plated ball
with teflon seats.
<8>®
APPROVED LISTED 36Y7

FM APPROVAL ONLY FOR 1" and 1-1/4"


Rated pressure: 300 psi

alb 1-1/4"

Orifice 3/8" 7/16" 1/2" 17/32" 518" 3/4"

___ C_~ K factor 2.8 4.2 5.6 8.0 11.0 14.0


~~-
H --r=IL
H
alb 2"
DB~_~,,~
r- ~~ ir-' .r<- ~
Orifice 7/16" 1/2" 17/32" 518" 3/4" 15/16" 1-5/64" 1-9/64"

~~ --= K factor 4.2 5.6 8.0 11.2 14.0 16.8 22.4 25.2

DIMENSION C (plug) PORT A B C D H

1-1/4" 1/4" 1-1/16" 6-13/32" 2-43/64" 5-11/32" 4-27164" 1-1/4" GROOVE"

2" 1/4" 1-12/16" 7-17/32" 4" 6-26/32" 6-21/64" 2" GROOVE"

42
4 3/4"

OUTLET

21
14
2
6
17
4
34 7
3
5 5 1/4"
13
12 1

10
11 Factory
Mutual
R
System
LISTED Approved
28WL
INLET
TEST PRESSURE
1.5 TIMES COLD WORKING PRESSURE-CWP

SEE DRAWING NO. VM-15A-M FOR STANDARD MATERIAL OF CONSTRUCTION.


VALVE MODEL INLET OUTLET CWP ORIFICE
SIZE NO. SIZE SIZE P.S.I. SIZE
1/2" 1 / 2 " -15A 1 / 2 " N.P.T. 1 / 2 " N.P.T. 175 1 / 16 "
3/4" 3 / 4 " -15A.2 3 / 4 " N.P.T. 1 / 2 " N.P.T. 175 1 / 16 "

1" 1 " -15A.3 1 " N.P.T. 1 / 2 " N.P.T. 175 1 / 16 "

1 BODY 11 ORIFICE BUTTON


2 COVER 12 PIVOT PIN
3 LEVER FRAME 13 PIN RETAINER (NOT SHOWN)
4 SEAT 14 PIPE PLUG
5 FLOAT 17 FLOAT RETAINER
6 GASKET 21 LOCATOR
7 COVER BOLT 34 LOCK WASHER
10 FLOAT ARM
Revision 4-13-98
DATE
AIR RELEASE VALVE 2-23-87
DRWG. NO.
®
VALVE AND MANUFACTURING CORP. VM-15A
AIR RELEASE VALVE
SERIES NO. 15A
STANDARD MATERIALS OF CONSTRUCTION

PART NO. PART NAME MATERIAL


1 BODY CAST IRON ASTM A126, CLASS B
2 COVER CAST IRON ASTM A126, CLASS B
3 LEVER FRAME STAINLESS STEEL T304, ASTM A240
4 SEAT STAINLESS STEEL T303, ASTM A582
5 FLOAT STAINLESS STEEL T304, ASTM A240
6 GASKET COMPRESSED NON-ASBESTOS FIBER
7 COVER BOLT ALLOY STEEL SAE, GRADE 5
10 FLOAT ARM STAINLESS STEEL T304, ASTM A240
11 ORIFICE BUTTON VITON
12 PIVOT PIN STAINLESS STEEL T303, ASTM A582
13 PIN RETAINER STAINLESS STEEL PH 15-7 MO
14 PIPE PLUG STEEL
17 FLOAT RETAINER STAINLESS STEEL T304, ASTM F879
21 LOCATOR STAINLESS STEEL T304, ASTM F593
34 LOCK WASHER STAINLESS STEEL T304, ASTM A240

NOTE: ALL SPECIFICATIONS AS


LAST REVISED.

Revised 4-13-98
DATE
MATERIALS OF CONSTRUCTION 2/23/87
DRWG. NO.
®
VALVE AND MANUFACTURING CORP. VM-15A-M
September 17, 2013 Miscellaneous 906a

Water and air


TECHNICAL DATA Pressure Gauges

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Pressure Gauges give visual indication of the
water or air pressure available to the fire protection sys-
tem.

2. LISTINGS AND APPROVALS


UL Listed - VEVX
ULc Listed - VEVXC
FM Approved - Pressure Gauges

3. TECHNICAL DATA
Connection: 1/4” NPT
Working Pressure:
• Water Gauge: 300 psi (20.7 bar)
• Air Gauge: 80 PSI (5.5 bar)
Maximum Pressure: Water Pressure Gauge Air Pressure Gauge
• Water Gauge: 300 PSI (20.7 bar)
• Water Gauge: 600 PSI (41.4 bar)
• Air Gauge: 250 PSI (17.2 bar) (Air gauge includes a “Retard Zone” between 80 and 250 PSI)

Material Standards
Case: ABS (Acrylonitrile Butadiene Styrene)
Window: Polycarbonate
Viking Technical Data may be found on
Dial: Black Figures on White Background
The Viking Corporation’s Web site at
Pointer: Black, Aluminum http://www.vikinggroupinc.com.
Movement: Suspended Spring with Polyester Segment The Web site may include a more recent
Bourdon Tube: Bronze edition of this Technical Data Page.
Socket: Brass, Soft Soldered
Ordering Information
Available since 1977.
300 PSI (20.7 bar) Water Pressure Gauge - VWATERSF
600 PSI (41.4 bar) Water Pressure Gauge - VWATERSF600
250 PSI (17.2 bar) Air Pressure Gauge - VAIRSF

4. INSTALLATION
1. Gauges are to be installed in accordance with the latest published standards of the National Fire Protection Association or other
similar organizations, and also with the provisions of governmental codes, ordinances, and standards whenever applicable.
2. Gauges must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install
gauges that have been dropped or damaged in any way. Such gauges should be destroyed immediately.
3. Adequate heat must be provided where gauges are installed.
4. The gauges must be protected from mechanical damage. Install the gauges according to the following steps:
a. Apply a small amount of pipe-joint compound or tape to the external threads of the gauge only. Take care that no joint com-
pound is allowed into the orifice of the gauge.
b. Turn the unit clockwise to thread the gauge into the 1/4” (6.4 mm) NPT connection of the fitting. DO NOT over-tighten the
gauge.

5. AVAILABILITY
The water and air gauges �������������������������������������������������������������������������������������������������������
are available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.

6. GUARANTEES
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Form No. F_052197 Revised page replaces page 906a-b dated May 11, 2012.
(Added 600 PSI Water Gauge and Updated Figure 1 Dimensions.)
Miscellaneous 906b September 17, 2013

Water and air


TECHNICAL DATA Pressure Gauges

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com

Figure 1 - Gauge Dimensions


(Dimensions Apply to Air and Water Gauges)

Form No. F_052197 Revised page replaces page 906a-b dated May 11, 2012.
(Added 600 PSI Water Gauge and Updated Figure 1 Dimensions.)
Page 1 of 6

MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

1. DESCRIPTION
The Viking Micromatic® Standard Response Upright VK100 Sprinkler is a small, ther-
mosensitive, glass-bulb spray sprinkler available in several different finishes and tem-
perature ratings to meet design requirements. The special Polyester and Electroless
Nickel PTFE (ENT) coatings can be used in decorative applications where colors are
desired. In addition, these coatings have been investigated for installation in corrosive
atmospheres and are listed/approved as corrosion resistant as indicated in the Approval
Charts.
Viking standard response sprinklers may be ordered and/or used as open sprinklers (glass
bulb and pip cap assembly removed) on deluge systems. Refer to Ordering Instructions.

2. LISTINGS AND APPROVALS


cULus Listed: Category VNIV
FM Approved: Classes 2001, 2002, 2015, 2017, 2043 

NOTE: Other International approval certificates are available upon request.


Refer to Approval Charts and Design Criteria for listing and approval requirements that must be followed.

3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)†
Maximum Working Pressure: 175 psi (12 bar) wwp
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2” NPT, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-3/8” (60 mm)
† cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
** Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Brass UNS-C23000 or Copper UNS-C19500
Bulb: Glass, nominal 5 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT coated Sprinklers: Belleville Spring - Exposed, Screw and Pipcap - ENT plated.
††Not for FM Approval.
Ordering Information: (Also refer to the current Viking price list.)
Order Micromatic® Standard Response Upright VK100 by first adding the appropriate suffix for the sprinkler finish and then the
appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, Wax Coated = C, Wax Over Polyester = V-/W,
ENT = JN
Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 212 °F (100 °C) = M, 286 °F
(141 °C) = G, 360 °F (182 °C) = H, 500 °F (260 °C) = L.
For example, sprinkler VK100 with a 1/2” thread, Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12986AB
Available Finishes And Temperature Ratings: Refer to Table 1.

Form No. F_052014 19.10.14 Rev 19.1 Replaces Form No. F_052014 Rev 17.1.P65
(Added ENT; updated FM language.)
Page 2 of 6

MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Accessories: (Also refer to the Viking website.)


Sprinkler Wrenches:
A. Standard Wrench: Part No. 21475M/B (available since 2017).
B. Standard Wrench for Wax Coated Sprinklers: Part No. 10896W/B (available since 2000)
C. Socket Wrench for Wax Coated Sprinklers: Part No. 13577W/B* (available since 2006)
*A ½” ratchet is required (not available from Viking).
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)

4. INSTALLATION
Refer to appropriate NFPA Installation Standards.

5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.

6. INSPECTIONS, TESTS AND MAINTENANCE


Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.

7. AVAILABILITY
The Viking Micromatic® Standard Response Upright Sprinkler VK100 is available through a network of domestic and international
distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.

8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

Protective Sprinkler Cap

Wrench Flat

Standard Sprinkler Standard Sprinkler Wrench for Wax


Wrench 21475M/B Coated Sprinklers 10896W/B

Figure 1:
Standard Sprinkler Wrenches

Form No. F_052014 19.10.14 Rev 19.1


Page 3 of 6

MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES


Sprinkler Temperature Sprinkler Nominal Maximum Ambient
Bulb Color
Classification Temperature Rating1 Ceiling Temperature2
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Extra High 360 °F (182 °C) 300 °F (149 °C) Mauve
Ultra High3 500 °F (260 °C) 465 °F (240 °C) Black

Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black PTFE in all temperature ratings. ENT in all temperature
ratings except 135 °F (57 °C). Wax-Coated Brass and Wax over Polyester5 for sprinklers with the following temperature ratings:
155 °F (68 °C) Lt. Brown Wax 175 °F (79 °C) Brown Wax 200 °F (93 °C) Brown Wax 286 °F (141 °C) Dk. Brown Wax5

Footnotes
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),
response time may be severely retarded.
4
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
5
Wax melting point is 170 °F (76 °C) for 286 °F (141 °C) temperature rated sprinklers.

Form No. F_052014 19.10.14 Rev 19.1


Page 4 of 6

MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Approval Chart 1 (UL)


Micromatic Standard Response Upright Sprinkler VK100
®

Maximum 175 PSI (12 bar) WWP


Sprinkler Listings and Approvals3
Thread Size Nominal K-Factor Overall Length
Base Part SIN (Refer also to UL Design Criteria.)
Number1 NPT BSP U.S. metric2 Inches mm cULus4 VdS LPCB
Standard Orifice
12986 VK100 1/2” 15 mm 5.6 80.6 2-1/4” 57 A1, B3, C4, D2, E5 -- -- --
12993 VK100 -- 15 mm 5.6 80.6 2-1/4” 57 A1, B3, C4, D2, E5 -- -- --
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
10138 VK100 1/2” 15 mm 5.6 80.6 2-1/4” 57 A1, B3, C4, D2, E5 -- -- --
10193 VK100 -- 15 mm 5.6 80.6 2-1/4” 57 A1, B3, C4, D2, E5 -- -- --
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C),
200 °F (93 °C), 286 °F (141 °C), and 360 °F (182 Approved Finishes
°C) 1 - Brass, Chrome, White Polyester5,6, and Black Polyester5,6
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 2 - Brass and Chrome
and 200 °F (93 °C) 3 - Wax-Coated Brass and Wax Over Polyester5
C - 286 °F (141 °C) 4 - High Temperature 200 °F (93 °C) Wax Coating (corrosion resistant); maximum ambient tem-
D - 500 °F (260 °C)7 perature allowed at ceiling = 150 °F (65 °C)
E - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 5 - ENT5
°C), 286 °F (141 °C), 360 °F (182 °C), and 500 °F
(260 °C)7
Footnotes
1
Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
5
cULus Listed as corrosion resistant.
6
Other colors are available on request with the same Listings and Approvals as the standard colors.
7
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),
the response time of the Ultra-High temperature rated sprinkler may be severely retarded.

DESIGN CRITERIA - UL
(Also refer to Approval Chart 1.)
cULus Listing Requirements:
The Viking Micromatic® Standard Response Upright Sprinkler VK100 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with
the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light, Ordinary, and Extra Hazard occupancies.
• The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Bulletin
Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.

Form No. F_052014 19.10.14 Rev 19.1


Page 5 of 6

MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Approval Chart 2 (FM)


Micromatic® Standard Response Upright Sprinkler VK100
Maximum 175 PSI (12 bar) WWP

Sprinkler Base Thread Size Nominal K-Factor Overall Length FM Approvals3


SIN
Part Number1 NPT BSP U.S. metric 2
Inches mm (Refer also to Design Criteria below.)

Standard Orifice
12986 VK100 1/2” 15 mm 5.6 80.6 2-1/4” 57 A1, B2, C3, D1, E4, F6
12993 VK100 -- 15 mm 5.6 80.6 2-1/4” 57 A1, D1, E4, F6, G5
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
10138 VK100 1/2” 15 mm 5.6 80.6 2-1/4” 57 A1, B2, C3, D1, E4, F6
10193 VK100 -- 15 mm 5.6 80.6 2-1/4” 57 A1, G5, D1, E4, F6
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 Approved Finishes
°F (93 °C), 212 °F (100 °C), 286 °F (141 °C), and 360 °F
(182 °C) 1 - Brass, Chrome, White Polyester4
, and Black Polyester4
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F 2 - Wax-Coated Brass (corrosion resistant)
(93 °C) and 212 °F (100 °C)
3 - High Temperature 200 °F (93 °C) Wax Coating (corrosion resistant); maximum ambient
C - 286 °F (141 °C)
temperature allowed at ceiling = 150 °F (65 °C)
D - 500 °F (260 °C)5
E - 155 °F (68 °C) 4 - Wax-Coated Brass and Wax Over Polyester5
F - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F 5 - White Polyester and Wax-Coated Brass (corrosion resistant)
(141 °C), 360 °F (182 °C), and 500 °F (260 °C)5
6- ENT6
G - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and
200 °F (93 °C)
Footnotes
1
Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4
Other colors are available on request with the same Approvals as the standard colors.
5
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),
the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
6
FM approved as corrosion resistant.

DESIGN CRITERIA - FM
(Also refer to Approval Chart 2.)

FM Approval Requirements:
The Viking Micromatic® Standard Response Upright Sprinkler VK100 is is FM Approved as standard response Non-Storage upright sprinkler as
indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data
Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply
requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Bulletin
Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.

Form No. F_052014 19.10.14 Rev 19.1


Page 6 of 6

MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Sprinkler wrench 13577W/B**


must be used for installing
wax coated sprinklers.

Step 1: Carefully slide the


wrench sideways around the
deflector, ensuring engage-
ment with the sprinklger
wrench flats.

Wax Coated
Upright Sprinkler

** A 1/2” ratchet is required Step 2: Carefully press the wrench downward


(not available from Viking) and ensure engagement with the sprinkler
wrench flats.
Figure 2: Socket Wrench 13577W/B for Wax Coated Sprinklers

Form No. F_052014 19.10.14 Rev 19.1 Replaces Form No. F_052014 Rev 17.1.P65
(Added ENT; updated FM language.)
Page 1 of 6

MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

1. DESCRIPTION
The Viking Microfast® Standard/Quick Response Extended Coverage Horizontal
Sidewall Sprinkler VK605 is thermosensitive spray sprinklers available in several dif-
ferent finishes and temperature ratings to meet varying design requirements. The ori-
fice design allows efficient use of available water supplies for hydraulically designed
fire-protection systems. The glass bulb operating element and special deflector
characteristics meet the challenges of quick response extended coverage standards.
The special Polyester and Electroless Nickel PTFE (ENT) coatings can be used in
decorative applications where colors are desired. In addition, the Electroless Nickel
PTFE (ENT) coating has been investigated for installation in corrosive environments
and is listed/approved as indicated in the Approval Chart(s).

2. LISTINGS AND APPROVALS


cULus Listed: Category VNIV
For Light Hazard Occupancies Only
Refer to the Approval Chart and Design Criteria for cULus Listing requirements that
must be followed. 
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: Refer to the Approval Chart.
Maximum Working Pressure: 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 1/2” (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metric*)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-11/16” (68 mm)
Material Standards:
Sprinkler Frame: Brass UNS-C84400
Deflector: Copper UNS-C19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Compression Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pip Cap-ENT Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Sprinkler VK605 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the tempera-
ture rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D
For example, sprinkler VK605 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12120AB.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 21475M/B (available since 2017)
B. Wrench for coated and/or recessed sprinklers: Part No. 13655W/B** (available since 2006)
**A ½” ratchet is required (not available from Viking).
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
Form No. F_072414 20.06.04 Rev 20.1 Replaces Form No. F_072414 Rev 19.2
(Remove Black PTFE)
Page 2 of 6

MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the bulb to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance require-
ments.
7. AVAILABILITY
Viking Model VK605 is available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking
Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature Sprinkler Nominal Maximum Ambient


Bulb Color
Classification Temperature Rating1 Ceiling Temperature2
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Available Sprinkler Finishes: Brass, Chrome, White Polyester5, Black Polyester5, and ENT3,4
Corrosion Resistant Sprinkler Coating: ENT3,4
Footnotes
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3
The corrosion-resistant coatings have passed the standard corrosion tests required by the approving agencies as indicated in the Approval Chart.
These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are
compatible with or suitable for the proposed environment. For ENT automatic sprinklers, the waterway is coated. Note that the spring is exposed on
sprinklers with ENT coatings.
4
cULus Listed as corrosion resistant.
5
For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester coatings.

Wrench Flat

Figure 1:
Standard Sprinkler Wrench 21475M/B

Form No. F_072414 20.06.04 Rev 20.1


Page 3 of 6

MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Approval Chart
Microfast® EC/QREC Horizontal Sidewall Sprinkler VK605
For Light Hazard Occupancies Only
Sprinkler Base NPT Thread Size Nominal K-Factor Maximum Water Overall Length
SIN
Part Number1 Inches mm U.S. metric2 Working Pressure Inches mm
12120 VK605 1/2 15 5.6 80.6 175 psi (12 Bar) 2-11/16 68
Sprinkler Base Listings and Approvals3
SIN Maximum Areas of Coverage6 Minimum Water Supply Requirements6
Part Number cULus4
Standard Response - Maximum 175 PSI WWP
5

For Installation with the deflector located 6” to 12” (152 mm to 305 mm) below smooth, flat, horizontal ceilings only.
12120 VK605 16’ Wide x 16’ Throw (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) B1W, B2Y
12120 VK605 16’ Wide x 18’ Throw (4.9 m x 5.5 m) 29 gpm @ 26.8 psi (109.8 L/min @ 1.85 Bar) B1W, B2Y
12120 VK605 16’ Wide x 20’ Throw (4.9 m x 6.1 m) 32 gpm @ 32.7 psi (121.1 L/min @ 2.25 Bar) B1X, B2X
Quick Response - Maximum 175 PSI WWP
For Installation with the deflector located 6” to 12” (152 mm to 305 mm) below smooth, flat, horizontal ceilings only.
12120 VK605 16’ Wide x 16’ Throw (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) B1W, B2Y
12120 VK605 16’ Wide x 18’ Throw (4.9 m x 5.5 m) 29 gpm @ 26.8 psi (109.8 L/min @ 1.85 Bar) B1W, B2Y
12120 VK605 16’ Wide x 20’ Throw (4.9 m x 6.1 m) 32 gpm @ 32.7 psi (121.1 L/min @ 2.25 Bar) A1W, C2Y
Quick Response - QREC Specific Application - Maximum 175 PSI WWP
For Installation with the deflector located 4” to 6” (102 mm to 152 mm) below sloped7 ceilings
with slopes from 2/12 through 4/12 (9.5° to 18.4°) pitch. Sprinkler must be located at the high-point intersection
of the wall and the ceiling with spray directed down the slope. Refer to Figure 6.
12120 VK605 16’ Wide x 16’ Throw (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) B1W, B2Y
12120 VK605 16’ Wide x 18’ Throw (4.9 m x 5.5 m) 29 gpm @ 26.8 psi (109.8 L/min @ 1.85 Bar) B1W, B2Y
12120 VK605 16’ Wide x 20’ Throw (4.9 m x 6.1 m) 32 gpm @ 32.7 psi (121.1 L/min @ 2.25 Bar) A1W, C2Y
Approved Escutcheons
Approved Temperature Ratings Approved Finishes W - Standard surface-mounted escutcheons or recessed with the
A - 135 °F (57 °C) and 175 °F (79 °C) 1 - Brass, Chrome, White Polyester, and Micromatic® Model E-1, E-2, or G-1 Recessed Escutcheon
B - 155 °F (68 °C) Black Polyester X - Recessed with the Micromatic® Model E-1 Recessed Escutcheon only
C - 155 °F (68 °C) 2 - ENT8 Y - Standard surface-mounted esctucheons or recessed with the
Micromatic Model E-1 Recessed Escutcheon.
Footnotes
1
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This chart shows listings and approvals available at time of printing. Check with the manufacturer for any additional approvals.
4
cULus Listed for use in the U.S. and Canada for Light-Hazard occupancies only.
5
Listings are limited to Light Hazard Occupancies where allowed by the installation standards being applied.
6
For areas of coverage smaller than shown, use the “Minimum Water Supply Requirement” for the next larger area listed. Flows and pressures listed
are per sprinkler.
7
Listed area of coverage measured along ceiling slope. Consult Figure 6 for installation notes.
8
cULus Listed as corrosion resistant.

Form No. F_072414 20.06.04 Rev 20.1


Page 4 of 6

MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

DESIGN CRITERIA
(Also refer to the Approval Chart.)

cULus Listing Requirements: Microfast® EC/QREC Horizontal Sidewall Sprinkler VK605 is cULus Listed as indicated in the Approval Chart for instal-
lation in accordance with the latest edition of NFPA 13 for extended coverage sidewall spray sprinklers:
• Sprinkler VK605 is cULus Listed for Light Hazard occupancies with smooth, flat, horizontal ceilings. Sprinkler VK605 is also listed for ceilings with
slopes to 4/12 (18.4°), as a QREC “Specific Application Sprinkler”.
• For sprinkler VK605 in sloped ceiling applications, Sections 11.2.3.2.3 and 11.2.3.2.4 of the 2007 Edition of NFPA-13 do not apply regarding System
Area of Operation. Sprinkler VK605 should be installed according to the areas of coverage, and flows and pressures listed in the Approval Chart.
• In sloped ceiling installations, sprinkler VK605 is listed for installation at the high-point intersection of the wall and the ceiling. In sloped ceiling
installations, the spray must be directed down the slope. Spray may NOT be directed across the slope. Refer to Figure 6.
• Listed area of coverage for sloped ceilings corresponds to ceiling slope. (For sloped ceiling applications, actual floor coverage will be less than
the listed area.)
• Refer to the Approval Chart for required deflector distance below the ceiling. Install with the leading edge of the deflector oriented parallel to the
ceiling (see Figure 4).
• Minimum distance from end walls is 4 in. (102 mm).
• Maximum distance from the end wall shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler installation and obstruction rules contained in NFPA 13 for extended coverage sidewall spray sprinklers must be followed.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Step 1: Carefully slide the


wrench sideways around
the deflector, ensuring en-
gagement with the sprinkler
wrench flats.

Sprinkler wrench 13655W/B**


must be used for installing
wax coated sprinklers.

** A 1/2” ratchet is required Step 2: Carefully press the wrench onto the
(not available from Viking) sprinkler wrench flats.
Figure 2: Wrench 13655W/B for Recessed Sprinklers

Form No. F_072414 20.06.04 Rev 20.1


Page 5 of 6

MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

2-11/16”
(68 mm) 2-7/16”
(62 mm)

Wall Opening Size: Installed with a Standard


2-5/16” (59 mm) minimum 1/8” Surface-Mounted
2-1/2” (64 mm) maximum Escutcheon

Figure 3: Sidewall Sprinkler Dimensions with a Standard Escutcheon

Minimum Minimum

1-5/8” 1-3/4”

(41 mm) (45 mm)

2-1/8” 2-1/8”
(54 mm) (54 mm)

2-1/4” 2-5/8”

(57 mm) (67 mm)


Maximum Maximum

Wall Opening Size: Installed with the Installed with the


2-5/16” (59 mm) minimum Micromatic Model E-1 Threaded Model E-2
Recessed Escutcheon Recessed Escutcheon
2-1/2” (64 mm) maximum

Figure 4: Sidewall Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons

Form No. F_072414 20.06.04 Rev 20.1


Page 6 of 6

MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Adjustable 1/8” Wall opening size with the


Adjustable (3 mm) Model G-1 Escutcheon:
Outer
Adapter 2-5/8” (66 mm) minimum
Cup
Ring 3-3/4” (95 mm) maximum

2-5/8” 4”
(66 mm) (102 mm)

Depth
1-1/16” 1-1/16”
(27 mm) (27 mm) Maximum Recess:
1/2” (13 mm)
** A 1/2” ratchet is required Step 2: Carefully press the wrench onto the
(not available from Viking) sprinkler wrench flats.
Figure 5: Sidewall Sprinkler Dimensions with the Model G-1 Escutcheon

NOTES:
1. In sloped ceiling installations, sprinkler VK605 is listed for instal-
lation at the high-point intersection of the wall and the ceiling.
In sloped ceiling installations, the spray must be directed
down the slope. Spray may NOT be directed across the slope.
2. Listed area of coverage for sloped ceilings corresponds to
ceiling slope. (For sloped ceiling applications, actual floor
coverage will be less than the listed area.)

Figure 6: Sprinkler VK605-Sloped Ceiling Installation with a Model E-1 or E-2 Recessed Escutcheon

Form No. F_072414 20.06.04 Rev 20.1 Replaces Form No. F_072414 Rev 19.2
(Remove Black PTFE)
VSR
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
UL, CUL and CSFM Listed, FM Approved, LPCB Approved, For
CE Marked (EN12259-5) / VdS Approved model use VSR-EU
Service Pressure: 450 PSI (31 BAR) - UL
Flow Sensitivity Range for Signal:
4-10 GPM (15-38 LPM) - UL
Maximum Surge: 18 FPS (5.5 m/s)
Contact Ratings: Two sets of SPDT (Form C)
10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
10 mAmps min. at 24VDC
Conduit Entrances: Two knockouts provided for 1/2" conduit.
Individual switch compartments suitable
for dissimilar voltages.
Environmental Specifications:
• NEMA 4/IP54 Rated Enclosure suitable for indoor or
outdoor use with factory installed gasket and die-cast housing
when used with appropriate conduit fitting.
• Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL
• Non-corrosive sleeve factory installed in saddle.
Service Use:
Automatic Sprinkler NFPA-13
Specifications subject to change without notice. One or two family dwelling NFPA-13D
Ordering Information Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Nominal Pipe Size Model Part Number
2" DN50 VSR-2 1144402
2 1/2" DN65 VSR-2 1/2 1144425
• Installation must be performed by qualified personnel and in
3" DN80 VSR-3 1144403 accordance with all national and local codes and ordinances.
3 1/2" - VSR-3 1/2 1144435 • Shock hazard. Disconnect power source before servicing. Serious
4" DN100 VSR-4 1144404 injury or death could result.
• Risk of explosion. Not for use in hazardous locations. Serious
5" - VSR-5 1144405 injury or death could result.
6" DN150 VSR-6 1144406
8" DN200 VSR-8 1144408

Optional: Cover Tamper Switch Kit, stock no. 0090148 Waterflow switches that are monitoring wet pipe sprinkler systems shall
Replaceable Components: Retard/Switch Assembly, stock no. 1029030 not be used as the sole initiating device to discharge AFFF, deluge,
or chemical suppression systems. Waterflow switches used for this
application may result in unintended discharges caused by surges,
trapped air, or short retard times.

Important: This document contains important information on the installation and operation of the VSR waterflow switches. Please read all
instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
General Information Enclosure
The Model VSR is a vane type waterflow switch for use on wet sprinkler The VSR switches and retard device are enclosed in a general purpose,
systems. It is UL Listed for use on a steel pipe; schedules 5 through 40, die-cast housing. The cover is held in place with two tamper resistant
sizes 2" - 6" and is UL Listed and FM Approved for use on steel pipe; screws which require a special key for removal. A field installable
schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). LPC cover tamper switch is available as an option which may be used
approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering to indicate unauthorized removal of the cover. See bulletin number
Information chart. 5401103 for installation instructions of this switch.
The VSR may also be used as a sectional waterflow detector on large
systems. The VSR contains two single pole, double throw, snap action
switches and an adjustable, instantly recycling pneumatic retard. The
switches are actuated when a flow of 10 GPM (38 LPM) or more occurs
downstream of the device. The flow condition must exist for a period
of time necessary to overcome the selected retard period.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com
PRINTED IN USA MFG. #5401146 - REV M PAGE 1 OF 4
11/15
VSR
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
Installation (see Fig. 1)
These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they
will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24"
(60 cm) of a valve or drain.
NOTE: Do not leave cover off for an extended period of time.
Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other
material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend
or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive
bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque
(see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way.

Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise prevent
the trip stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm. If an alarm is not desired, a qualified
technician should disable the alarm system.
Fig. 1 Retard Adjustment
DO NOT LEAVE COVER OFF FOR
AN EXTENDED PERIOD OF TIME The delay can be adjusted by rotating the retard adjustment knob from
0 to the max setting (60-90 seconds). The time delay should be set at
the minimum required to prevent false alarms

TIGHTEN NUTS
ALTERNATELY

Hole must be drilled perpendicular to the pipe and vertically centered.


Refer to the Compatible Pipe/Installation Requirements chart for size.
Correct Incorrect
MOUNT ON PIPE SO
ARROW ON SADDLE
POINTS IN DIRECTION
OF WATERFLOW

50mm
ROLL PADDLE IN
OPPOSITE DIRECTION ADAPTER ADAPTER
DIRECTION OF OF WATERFLOW
WATERFLOW
20mm ±2mm MAX.
(Flowing water activates
device in one direction only.) DN50 ONLY
USE (2) 5180162 ADAPTERS AS SHOWN ABOVE
DWG# 1146-1F

Compatible Pipe/ Installation Requirements


Model Nominal Pipe Nominal Pipe Pipe Wall Thickness Hole Size U-Bolt Nuts
Size O.D.
Lightwall Schedule 10 (UL) Schedule 40 (UL) BS-1387 (LPC) DN (VDS) Torque

inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm ft-lb n-m
VSR-2 2 DN50 2.375 60.3 .065 1.651 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3
1.25 + .125/-
VSR-2 1/2 2.5 - 2.875 73.0 .084 2.134 0.120 3.05 0.203 5.16 - - - - 33.0 ± 2.0
.062
VSR-2 1/2 - DN65 3.000 76.1 - - - - - - 0.142 3.6 0.102 2.6
VSR-3 3 DN80 3.500 88.9 .083 2.108 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9
VSR-3 1/2 3.5 - 4.000 101.6 - - 0.120 3.05 0.226 5.74 - - - - 20 27
VSR-4 4 DN100 4.500 114.3 .084 2.134 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2
2.00 ± .125 50.8 ± 2.0
VSR-5 5 - 5.563 141.3 - - 0.134 3.40 0.258 6.55 - - - -
VSR-6 6 DN150 6.625 168.3 .115 2.921 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0
VSR-8 8 DN200 8.625 219.1 - - 0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5
NOTE: For copper or plastic pipe use Model VSR-CF.
PRINTED IN USA MFG. #5401146 - REV M PAGE 2 OF 4
11/15
VSR
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
Fig. 2 Fig. 3 Fig. 4 Switch Terminal Connections Clamping
To remove knockouts: Place screwdriver at Break out thin section of cover when Plate Terminal
inside edge of knockouts, not in the center. wiring both switches from one conduit
entrance.

An uninsulated section of a single conductor should not be looped


around the terminal and serve as two separate connections. The
DWG 1146-4
wire must be severed, thereby providing supervision of the
connection in the event that the wire become dislodged from under
the terminal. Failure to sever the wire may render the device
Do not drill into the base as this creates inoperable risking severe property damage and loss of life.
metal shavings which can create Do not strip wire beyond 3/8" of length or expose an uninsulated
electrical hazards and damage the conductor beyond the edge of the terminal block. When using
device. Drilling voids the warranty. stranded wire, capture all strands under the clamping plate.
CONNECTOR

Fig. 5 Typical Electrical Connections NEUTRAL FROM


BREAKER NEUTRAL FROM BELL
BELL

LOAD TO BELL
BREAKER

Notes: LINE FROM BREAKER


EOL (End Of Line Resistor)
1. The Model VSR has two switches, one can be used to operate a central
station, proprietary or remote signaling unit, while the other contact
is used to operate a local audible or visual annunciator.
2. For supervised circuits, see “Switch Terminal Connections”
drawing and warning note (Fig. 4).     NOTE:
When connecting to a UL Listed
control panel, use the panel’s
resistor value for circuit supervision.

Testing
The frequency of inspection and testing for the Model VSR and  its associated protective monitoring system shall be in accordance with applicable
NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
If provided, the inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection
device on the system, application of the VSR is not recommended or advisable.
A minimum flow of 10 GPM (38 LPM) is required to activate this device.
Advise the person responsible for testing of the fire protection system that this system must be tested in accordance
with the testing instructions.
Fig. 6 Mounting Dimensions 5.56 in Fig. 7
3.50 in (141.2 mm)
2.00 in
(89.0 mm) (50.8 mm) GREEN GROUND
SCREWS
2.34 in
(59.4 mm)

PIPE DIA.
U-BOLT NUT + 5.25 in
(+ 133.4 mm)
U-BOLT WASHER

PIPE SADDLE

PIPE
PLASTIC PADDLE DWG. 1146-14

U-BOLT NOMINAL PIPE DIA. +1.75 in (+44.5 MM) FOR DN 50 – DN 65 2–2.5 in


NOMINAL PIPE DIA. +2.125 in (+54.0 MM) FOR DN 80 – DN 200 3–8 in DWG 1146-15

PRINTED IN USA MFG. #5401146 - REV M PAGE 3 OF 4


11/15
VSR
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
Maintenance
Inspect detectors monthly. If leaks are found, replace the detector. The VSR waterflow switch should provide years of trouble-free service.
The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order
replacement retard switch assembly stock #1029030 (see Fig. 8). There is no maintenance required, only periodic testing and inspection.

Retard/Switch Assembly Replacement (See Fig. 8)


The Retard/Switch Assembly is field-replaceable without draining the system or removing the waterflow switch from the
pipe

1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.
2. Disconnect the power source for local bell (if applicable).
3. Identify and remove all wires from the waterflow switch.
4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
5. Remove the retard assembly by lifting it straight up over the tripstem.
6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base.
7. Re-install the (2) original mounting screws.
8. Reconnect all wires. Perform a flow test and place the system back in service.

REMOVE (2) ORIGINAL MOUNTING


Fig. 8 SCREWS HOLDING RETARD/SWITCH
ASSEMBLY TO BASE

BREAK OUT THIN SECTION OF COVER


WHEN WIRING BOTH SWITCHES
FROM ONE CONDUIT ENTRANCE. (2) ORIGINAL MOUNTING
SCREWS
RETARD/SWITCH ASSEMBLY

(2) LOCATING PINS

(2) LOCATING PIN


DO NOT REMOVE BOSSES IN BASE
(2) RETARD HOUSING
SCREWS

BASE

DWG# 1146-10

Removal of Waterflow Switch


• To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are
removed or replaced.
• Turn off electrical power to the detector, then disconnect wiring.
• Loosen nuts and remove U-bolts.
• Gently lift the saddle far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing
to lift the waterflow detector saddle.
• Lift detector clear of pipe.

PRINTED IN USA MFG. #5401146 - REV M PAGE 4 OF 4