Technical Offer
2.5” Melton Nozzle jet/spray/off
KENNEDY AWWA C509 RESILIENT WEDGE GATE VALVES (1993)
During the decade of the 1980’s, the waterworks industry was introduced to the Resilient Seated Gate Valve, a design
principal that now dominates in preference for use in distribution systems. Kennedy Valve Company was at the forefront in
this industry-wide movement by introducing the Style 8000, our version of the best European and domestic designs.
The combination of evolving technology and changing market influences presents the unique opportunity once again for
Kennedy Valve to be at the forefront as a leader in modern valve design.
The Style 8000 RS gate valve embodies all of the latest valve technology for simplicity, durability and superior performance;
It is available in size range 3” thru 12” and meets AWWA standards C-509. Additionally, 4” thru 12” are listed by
Underwriters Laboratories and are approved by Factory Mutual Association.
Designed to control. . . built to perform. . .here’s the valve that sets the standard. The Kennedy valve was engineered on the
belief that bottle-tight closure is the primary function of any valve. That’s why the totally encapsulated wedge was designed
to provide dual seating. A whistle-clean waterway provides maximum flow without the loss of head experienced in other
valves.
A durable fusion bonded epoxy coating both inside and out complying with ANSI / AWWA C550, providing unexcelled
abrasion and corrosion protection is standard. Absolutely no compromise in materials or workmanship and it carries a 10
year limited warranty. . . it’s the clear choice of those who demand the best.
EASE OF OPERATION
The Kennedy Valve RSGV has only two moving internal parts—the gate and the stem.
The gate is fully supported throughout travel by an integrally cast tongue and groove fit between it and the valve body. Lugs
on the gate fully engage the coated guides cast into the valve body so the gate closes smoothly, without “chatter”, every time.
This positive gate alignment, plus positioning and engagement of the stem nut, virtually eliminate stem binding, and provide
balanced loads and low operating torques. The Kennedy Valve RSGV is among the lowest in operating torques of all
available competitive type valves
POSITIVE SEALING
A dual rubber seal is formed between the rubber encapsulated resilient wedge and the valve body to guarantee drop-tight
shut-off every time. The combination of true compression and dynamic wedging of the gate is created without harmful
sliding, shearing or other wear-inducing action.
The massive vulcanized rubber seating edges on the gate self-absorb normal wear and tear, assuring a positive seal, even after
years of service. The Kennedy Valve RSGV will seal bubble-tight to 250 psi working pressure, with the flow in either
direction and the valve in any position.
PERFORMANCE INFORMATION
• 3”- 6” valves sizes have been hydrostatically shell tested at five (5) times UL rated pressure (1000 psi).
• 8”,10”, and 12” have been hydrostatically shell tested at four (4) times UL rated pressure (800 psi).
• Valve is capable of bubble-tight seal at pressures up to (400psi) for short periods of time.
• Valve has been subjected to torques 150 percent of the designated minimum required torques.
• Valve has been cycle tested 5,000 times without loss of bubble-tight seal.
• For complete data on the tests Underwriters Laboratories performed, reference UL File EX 783
Valves shall be rated for zero leakage at 250psi water working pressure and have a 500psi hydrostatic test
for structural soundness for 3” through 12”.
Materials: All cast iron shall conform to ASTM-A126 Class B. Castings shall be clean and sound without defects that
will impair their service. No plugging or welding of such defects will be allowed.
Stem and wedge nut shall be a copper alloy in accordance with section 4.4.5 of AWWA C509
Bolts for above ground valves shall be electro-zinc plated steel with hex heads and hex nuts in accordance
with ASTM A-307, and A-563 respectively.
Bolts for below ground valves shall be 304 stainless steel with hex heads and hex nuts.
____________________________________________________________________________________________________
Coating 5-8 mill inside and out.
Thickness
____________________________________________________________________________________________________
Wedge / Gate: The wedge shall be of cast iron and completely encapsulated with a resilient elastomer material
permanently bonded to the wedge and have a rubber tearing bond that meets ASTM D429.
____________________________________________________________________________________________________
Markings: Markings in accordance with AWWA standard. Includes approvals (AWWA, UL, FM), name of
manufacturer, the year of manufacture, maximum working pressure and size of valve.
In addition, country of origin to be clearly cast into body & cover castings.
____________________________________________________________________________________________________
End Mechanical joint end valves to match ANSI / AWWA C111/A21.11.
Connections: Flanged end valves to match ANSI / AWWA C110/A21.10(ASME B16.1, Class 125)
Tapping valves through 12” shall mate all sleeves through 12” outlet regardless of manufacturer. Valves
shall be furnished with tapping sleeve side to ACME B16.1 Class 125 flanged end with centering ring.
Outlet side of valve shall be mechanical joint with (without) accessories to ANSI / AWWA C-111/A21.11.
Push-on ends suitable for stab joints with ductile or cast iron and C900 / SDR plastic pipe.
▪▪EFFICIENCY
High extinguishing performance rating due to its
multipurpose dry chemical powder “BAVARIA
Superlative Powder“ ABCDE, and easy use
RELIABILIT Y
Robust, functional and permanent reliable technology.
▪▪UNIVERSALIT Y
Suitable for solid and glowing incendiary substances,
liquid substances or substances becoming liquid and
gaseous substances
▪▪CREDENTIALS
BAVARIA Phoenix is approved and certified according to
EN3, TÜV, CE, GS and ES734
▪▪SPEED
Pull out safety pin for immediate readiness and press
down operating lever for fire fighting
▪▪EASY TO HANDLE
Optimized ergonomic grip, equipped with a hose and
nozzle with handle for high maneuverability
▪▪ECONOMY
Low maintenance due to identical components
throughout the series
▪▪QUALIT Y
BAVARIA is certified according to Quality, Environment
and OHSAS Management Systems ISO 9001, ISO 14001
and BS-OHSAS 18001
Portable Dry Chemical Powder Fire Extinguisher
Stored Pressure Operated
Features:
Technical Specifications:
Capacity 4 kg 6 kg
Extinguishing Rating Acc. to EN3 34A 144B C 43A 233B C
Operating Temperature Range* -30°C to +60°C -30°C to +60°C
Testing Pressure 35 bar 35 bar
Bursting Pressure Over 70 bar Over 70 bar
Valve Material Special engineered polymer valve
Discharge Material Hose with special engineered polymer nozzle
Shell Material DC 04 Steel according to DIN EN 10130
Extinguishing Agent MAP-based “BAVARIA Superlative Powder ABCDE“
Paint Finish Surface treatment and 100% polyester coating
Approx. Gross Weight 7.850 Kg 10.500 Kg
Approx. Unit Dimension (lxwxh) cm 23.0 x 18.0 x 47.0 25.5 x 17.5 x 56.5
Warranty:
Period of Warranty 2 Years
Coverage of the Warranty Against material failure and production defects
Limited to the replacement of the defected part or product after
Method of Warranty Coverage
verification that the failure is covered by the scope of the warranty
Failures due to misuse, mishandling, or inspection or repair by an
Warranty Exclusions
unauthorized dealer or entity
Carbon Steel Cabinets
Single Cabinet
Description
Melton Fire Cabinets are generally fabricated from Carbon steel material coated with RAL3000
Corrosion resistant coating.
Melton Cabinets are deigned to accommodate firefighting equipment. The cabinets are
designed in accordance with BSEN671-1 standard.
The quality of workmanship and finishes are carefully planned and executed from the initial
stages or preparing the material, fabrication, up to surface preparation and finishing.
Specifications
Dimension: 800*800*300 mm
Material: 1.5 mm Mild steel
Painting: Electrostatic Powder Coating, RAL3000
Two well-spaced bush and pin hinges or hidden hinges provide excellent support for
door and reduces door deflection during open position
Cup handle for ease access
Easy and fast installation with minimum labour required
Can be fixed on vertical legs on pallets using bolts
OSYSU-1, -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH
GENERAL INFORMATION
The OSYSU is used to monitor the open position of an OS screws and hex keys are available. See ordering informa-
& Y (outside screw and yoke) type gate valve. This device tion on page 4.
is available in two models; the OSYSU-1, containing one OPTIONAL COVER TAMPER SWITCH
set of SPDT (Form C) contacts and the OSYSU-2, con- A field installable cover tamper switch is available as an
taining two sets of SPDT (Form C) contacts. These option which may be used to indicate removal of the cover.
switches mount conveniently to most OS & Y valves See ordering information on page 4.
ranging in size from 2" to 12" (50mm to 300mm). They will
mount on some valves as small as 1/2" (12,5mm). TESTING
The OSYSU and its associated protective monitoring sys-
The cover is held in place by two tamper resistant screws tem should be inspected and tested in accordance with
that require a special tool to remove. The tool is furnished applicable NFPA codes and standards and/or the authority
with each device and should be left with the building owner having jurisdiction (manufacturer recommends quarterly or
or responsible party. Replacement or additional cover more frequently).
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
FIG. 1 SMALL VALVE INSTALLATION - 1/2" THRU 2 1/2" (12,5mm THRU 63,5mm) SIZES
THESE SWITCHES MOUNT CONVENIENTLY TO MOST 2" TO 12" OS & Y VALVES. THEY WILL MOUNT ON SOME
VALVES AS SMALL AS 1/2" (12,5MM). J-HOOKS MAY BE REQUIRED ON VALVES WITH LIMITED CLEARANCE.
FIG. 2 LARGE VALVE INSTALLATION - 3" THRU 12" (76mm THRU 300mm) SIZES
LARGE VALVE INSTALLATION (9,5mm) round, non-tapered file. Round and smooth the
edges of the groove to prevent damage to the valve
1. With the valve in the FULL OPEN position, locate the
packing and to allow the trip rod to move easily in and out
OSYSU across the valve yoke as far as possible from the
of the groove as the valve is operated.
valve gland, so that the trip rod lays against the non-
threaded portion of the valve stem. 6. Mount the OSYSU loosely with the trip rod centered in
groove.
2. Mount the OSYSU loosely with the carriage bolts and
clamp bar supplied. 7. Final adjustment is made by loosening 2 screws (see Fig.
2) and sliding the OSYSU on the bracket. Adjustment is
3. Loosen the locking screw that holds the trip rod in place
correct when switches are not activated with the trip rod
and adjust the rod length (see Fig. 4). When adjusted
seated in the valve stem groove and that the switches
properly, the rod should extend past the valve screw, but
activate within one turn when the valve is operated from the
not so far that it contacts the clamp bar. Tighten the
FULL OPEN towards the CLOSED position.
locking screw to hold the trip rod in place.
8. Tighten the adjustment screws and mounting hardware.
NOTE: If trip rod length is excessive, loosen the locking
Check to insure that the rod moves out of the groove
screw and remove the trip rod from the trip lever. Using
easily and that the switches activate within one turn when
pliers, break off the one 1" (25mm) long notched section
the valve is operated from the FULL OPEN towards the
(see Fig. 5). Reinstall trip rod and repeat Step 3 proce-
CLOSED position.
dure.
NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT
4. Mark the valve stem at the center of the trip rod.
THE STEM THREADS DO NOT ACTIVATE THE SWITCH.
5. Remove the OSYSU. File a 1/8" (3,2mm) deep groove THE SWITCH BEING ACTIVATED BY THE STEM THREADS
centered on the mark of the valve stem utilizing a 3/8" COULD RESULT IN A FALSE VALVE OPEN INDICATION.
CAUTION:
An uninsulated section of a single conductor Contacts shown in normal (valve open) condition.
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervi- TYPICAL SWITCH ACTION
sion of the connection in the event that the wire
becomes dislodged from under the terminal.
ORDERING INFORMATION
MODEL DESCRIPTION STOCK NO.
OSYSU-1 Outside Screw & Yoke-Supervisory Switch (Single switch) 1010106
OSYSU-2 Outside Screw & Yoke-Supervisory Switch (Double switch) 1010206
-- Cover Screw 5490344
-- Hex Key for Cover Screws and Installation Adjustments 5250062
-- Optional Cover Tamper Switch Kit 0090131
For pressure reducer type valve installation kits (if required) contact valve manufacturer.
A61
• FEMALE x FEMALE
CERTIFICATIONS
Standard equipment:
b
Female NPT inlet and outlet, forged
brass body, chrome plated ball
with teflon seats.
<8>®
APPROVED LISTED 36Y7
c
alb 1" 1" 1" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-114" 1-1/4"
Orifice 3/8" 7/16" 1/2" 17/32" 318" 7/16" 1/2" 17/32" 518" 3/4"
K factor 2.8 4.2 5.6 8.0 2.8 4.2 5.6 8.0 11.2 14.0
c
B~
H
B ~ alb 2"
o
idQ" Orifice
K factor
7/16"
4.2
1/2"
5.6
17/32"
8.0
5/8"
11.2
3/4"
14.0
15/16"
16.8
1-5/64"
22.4
1-9/64"
25.2
=
A
DIMENSION C (plug) PORT A B C D H
1" & 1-1/4" 1/4" 1-1/16" 5-1/32" 2-43/64" 5-11/32" 4-27164" 1-57/64
A61
• GROOVE X GROOVE
CERTIFICATIONS
Standard equipment:
GROOVE inlet and outlet, forged
brass body, chrome plated ball
with teflon seats.
<8>®
APPROVED LISTED 36Y7
alb 1-1/4"
~~ --= K factor 4.2 5.6 8.0 11.2 14.0 16.8 22.4 25.2
42
4 3/4"
OUTLET
21
14
2
6
17
4
34 7
3
5 5 1/4"
13
12 1
10
11 Factory
Mutual
R
System
LISTED Approved
28WL
INLET
TEST PRESSURE
1.5 TIMES COLD WORKING PRESSURE-CWP
Revised 4-13-98
DATE
MATERIALS OF CONSTRUCTION 2/23/87
DRWG. NO.
®
VALVE AND MANUFACTURING CORP. VM-15A-M
September 17, 2013 Miscellaneous 906a
3. TECHNICAL DATA
Connection: 1/4” NPT
Working Pressure:
• Water Gauge: 300 psi (20.7 bar)
• Air Gauge: 80 PSI (5.5 bar)
Maximum Pressure: Water Pressure Gauge Air Pressure Gauge
• Water Gauge: 300 PSI (20.7 bar)
• Water Gauge: 600 PSI (41.4 bar)
• Air Gauge: 250 PSI (17.2 bar) (Air gauge includes a “Retard Zone” between 80 and 250 PSI)
Material Standards
Case: ABS (Acrylonitrile Butadiene Styrene)
Window: Polycarbonate
Viking Technical Data may be found on
Dial: Black Figures on White Background
The Viking Corporation’s Web site at
Pointer: Black, Aluminum http://www.vikinggroupinc.com.
Movement: Suspended Spring with Polyester Segment The Web site may include a more recent
Bourdon Tube: Bronze edition of this Technical Data Page.
Socket: Brass, Soft Soldered
Ordering Information
Available since 1977.
300 PSI (20.7 bar) Water Pressure Gauge - VWATERSF
600 PSI (41.4 bar) Water Pressure Gauge - VWATERSF600
250 PSI (17.2 bar) Air Pressure Gauge - VAIRSF
4. INSTALLATION
1. Gauges are to be installed in accordance with the latest published standards of the National Fire Protection Association or other
similar organizations, and also with the provisions of governmental codes, ordinances, and standards whenever applicable.
2. Gauges must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install
gauges that have been dropped or damaged in any way. Such gauges should be destroyed immediately.
3. Adequate heat must be provided where gauges are installed.
4. The gauges must be protected from mechanical damage. Install the gauges according to the following steps:
a. Apply a small amount of pipe-joint compound or tape to the external threads of the gauge only. Take care that no joint com-
pound is allowed into the orifice of the gauge.
b. Turn the unit clockwise to thread the gauge into the 1/4” (6.4 mm) NPT connection of the fitting. DO NOT over-tighten the
gauge.
5. AVAILABILITY
The water and air gauges �������������������������������������������������������������������������������������������������������
are available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
6. GUARANTEES
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Form No. F_052197 Revised page replaces page 906a-b dated May 11, 2012.
(Added 600 PSI Water Gauge and Updated Figure 1 Dimensions.)
Miscellaneous 906b September 17, 2013
Form No. F_052197 Revised page replaces page 906a-b dated May 11, 2012.
(Added 600 PSI Water Gauge and Updated Figure 1 Dimensions.)
Page 1 of 6
MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1. DESCRIPTION
The Viking Micromatic® Standard Response Upright VK100 Sprinkler is a small, ther-
mosensitive, glass-bulb spray sprinkler available in several different finishes and tem-
perature ratings to meet design requirements. The special Polyester and Electroless
Nickel PTFE (ENT) coatings can be used in decorative applications where colors are
desired. In addition, these coatings have been investigated for installation in corrosive
atmospheres and are listed/approved as corrosion resistant as indicated in the Approval
Charts.
Viking standard response sprinklers may be ordered and/or used as open sprinklers (glass
bulb and pip cap assembly removed) on deluge systems. Refer to Ordering Instructions.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)†
Maximum Working Pressure: 175 psi (12 bar) wwp
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2” NPT, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-3/8” (60 mm)
† cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
** Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Brass UNS-C23000 or Copper UNS-C19500
Bulb: Glass, nominal 5 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT coated Sprinklers: Belleville Spring - Exposed, Screw and Pipcap - ENT plated.
††Not for FM Approval.
Ordering Information: (Also refer to the current Viking price list.)
Order Micromatic® Standard Response Upright VK100 by first adding the appropriate suffix for the sprinkler finish and then the
appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, Wax Coated = C, Wax Over Polyester = V-/W,
ENT = JN
Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 212 °F (100 °C) = M, 286 °F
(141 °C) = G, 360 °F (182 °C) = H, 500 °F (260 °C) = L.
For example, sprinkler VK100 with a 1/2” thread, Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12986AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Form No. F_052014 19.10.14 Rev 19.1 Replaces Form No. F_052014 Rev 17.1.P65
(Added ENT; updated FM language.)
Page 2 of 6
MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
7. AVAILABILITY
The Viking Micromatic® Standard Response Upright Sprinkler VK100 is available through a network of domestic and international
distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Wrench Flat
Figure 1:
Standard Sprinkler Wrenches
MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black PTFE in all temperature ratings. ENT in all temperature
ratings except 135 °F (57 °C). Wax-Coated Brass and Wax over Polyester5 for sprinklers with the following temperature ratings:
155 °F (68 °C) Lt. Brown Wax 175 °F (79 °C) Brown Wax 200 °F (93 °C) Brown Wax 286 °F (141 °C) Dk. Brown Wax5
Footnotes
1
The sprinkler temperature rating is stamped on the deflector.
2
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),
response time may be severely retarded.
4
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
5
Wax melting point is 170 °F (76 °C) for 286 °F (141 °C) temperature rated sprinklers.
MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1.)
cULus Listing Requirements:
The Viking Micromatic® Standard Response Upright Sprinkler VK100 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with
the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light, Ordinary, and Extra Hazard occupancies.
• The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Bulletin
Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Standard Orifice
12986 VK100 1/2” 15 mm 5.6 80.6 2-1/4” 57 A1, B2, C3, D1, E4, F6
12993 VK100 -- 15 mm 5.6 80.6 2-1/4” 57 A1, D1, E4, F6, G5
NOTICE - Product Below - Limited Availability (Contact Local Viking Office)
10138 VK100 1/2” 15 mm 5.6 80.6 2-1/4” 57 A1, B2, C3, D1, E4, F6
10193 VK100 -- 15 mm 5.6 80.6 2-1/4” 57 A1, G5, D1, E4, F6
Approved Temperature Ratings
A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 Approved Finishes
°F (93 °C), 212 °F (100 °C), 286 °F (141 °C), and 360 °F
(182 °C) 1 - Brass, Chrome, White Polyester4
, and Black Polyester4
B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F 2 - Wax-Coated Brass (corrosion resistant)
(93 °C) and 212 °F (100 °C)
3 - High Temperature 200 °F (93 °C) Wax Coating (corrosion resistant); maximum ambient
C - 286 °F (141 °C)
temperature allowed at ceiling = 150 °F (65 °C)
D - 500 °F (260 °C)5
E - 155 °F (68 °C) 4 - Wax-Coated Brass and Wax Over Polyester5
F - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F 5 - White Polyester and Wax-Coated Brass (corrosion resistant)
(141 °C), 360 °F (182 °C), and 500 °F (260 °C)5
6- ENT6
G - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and
200 °F (93 °C)
Footnotes
1
Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4
Other colors are available on request with the same Approvals as the standard colors.
5
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),
the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
6
FM approved as corrosion resistant.
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2.)
FM Approval Requirements:
The Viking Micromatic® Standard Response Upright Sprinkler VK100 is is FM Approved as standard response Non-Storage upright sprinkler as
indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data
Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply
requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Bulletin
Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
MICROMATIC® STANDARD
TECHNICAL DATA RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Wax Coated
Upright Sprinkler
Form No. F_052014 19.10.14 Rev 19.1 Replaces Form No. F_052014 Rev 17.1.P65
(Added ENT; updated FM language.)
Page 1 of 6
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
1. DESCRIPTION
The Viking Microfast® Standard/Quick Response Extended Coverage Horizontal
Sidewall Sprinkler VK605 is thermosensitive spray sprinklers available in several dif-
ferent finishes and temperature ratings to meet varying design requirements. The ori-
fice design allows efficient use of available water supplies for hydraulically designed
fire-protection systems. The glass bulb operating element and special deflector
characteristics meet the challenges of quick response extended coverage standards.
The special Polyester and Electroless Nickel PTFE (ENT) coatings can be used in
decorative applications where colors are desired. In addition, the Electroless Nickel
PTFE (ENT) coating has been investigated for installation in corrosive environments
and is listed/approved as indicated in the Approval Chart(s).
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the bulb to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance require-
ments.
7. AVAILABILITY
Viking Model VK605 is available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking
Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Wrench Flat
Figure 1:
Standard Sprinkler Wrench 21475M/B
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
Approval Chart
Microfast® EC/QREC Horizontal Sidewall Sprinkler VK605
For Light Hazard Occupancies Only
Sprinkler Base NPT Thread Size Nominal K-Factor Maximum Water Overall Length
SIN
Part Number1 Inches mm U.S. metric2 Working Pressure Inches mm
12120 VK605 1/2 15 5.6 80.6 175 psi (12 Bar) 2-11/16 68
Sprinkler Base Listings and Approvals3
SIN Maximum Areas of Coverage6 Minimum Water Supply Requirements6
Part Number cULus4
Standard Response - Maximum 175 PSI WWP
5
For Installation with the deflector located 6” to 12” (152 mm to 305 mm) below smooth, flat, horizontal ceilings only.
12120 VK605 16’ Wide x 16’ Throw (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) B1W, B2Y
12120 VK605 16’ Wide x 18’ Throw (4.9 m x 5.5 m) 29 gpm @ 26.8 psi (109.8 L/min @ 1.85 Bar) B1W, B2Y
12120 VK605 16’ Wide x 20’ Throw (4.9 m x 6.1 m) 32 gpm @ 32.7 psi (121.1 L/min @ 2.25 Bar) B1X, B2X
Quick Response - Maximum 175 PSI WWP
For Installation with the deflector located 6” to 12” (152 mm to 305 mm) below smooth, flat, horizontal ceilings only.
12120 VK605 16’ Wide x 16’ Throw (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) B1W, B2Y
12120 VK605 16’ Wide x 18’ Throw (4.9 m x 5.5 m) 29 gpm @ 26.8 psi (109.8 L/min @ 1.85 Bar) B1W, B2Y
12120 VK605 16’ Wide x 20’ Throw (4.9 m x 6.1 m) 32 gpm @ 32.7 psi (121.1 L/min @ 2.25 Bar) A1W, C2Y
Quick Response - QREC Specific Application - Maximum 175 PSI WWP
For Installation with the deflector located 4” to 6” (102 mm to 152 mm) below sloped7 ceilings
with slopes from 2/12 through 4/12 (9.5° to 18.4°) pitch. Sprinkler must be located at the high-point intersection
of the wall and the ceiling with spray directed down the slope. Refer to Figure 6.
12120 VK605 16’ Wide x 16’ Throw (4.9 m x 4.9 m) 26 gpm @ 21.6 psi (98.4 L/min @ 1.49 Bar) B1W, B2Y
12120 VK605 16’ Wide x 18’ Throw (4.9 m x 5.5 m) 29 gpm @ 26.8 psi (109.8 L/min @ 1.85 Bar) B1W, B2Y
12120 VK605 16’ Wide x 20’ Throw (4.9 m x 6.1 m) 32 gpm @ 32.7 psi (121.1 L/min @ 2.25 Bar) A1W, C2Y
Approved Escutcheons
Approved Temperature Ratings Approved Finishes W - Standard surface-mounted escutcheons or recessed with the
A - 135 °F (57 °C) and 175 °F (79 °C) 1 - Brass, Chrome, White Polyester, and Micromatic® Model E-1, E-2, or G-1 Recessed Escutcheon
B - 155 °F (68 °C) Black Polyester X - Recessed with the Micromatic® Model E-1 Recessed Escutcheon only
C - 155 °F (68 °C) 2 - ENT8 Y - Standard surface-mounted esctucheons or recessed with the
Micromatic Model E-1 Recessed Escutcheon.
Footnotes
1
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This chart shows listings and approvals available at time of printing. Check with the manufacturer for any additional approvals.
4
cULus Listed for use in the U.S. and Canada for Light-Hazard occupancies only.
5
Listings are limited to Light Hazard Occupancies where allowed by the installation standards being applied.
6
For areas of coverage smaller than shown, use the “Minimum Water Supply Requirement” for the next larger area listed. Flows and pressures listed
are per sprinkler.
7
Listed area of coverage measured along ceiling slope. Consult Figure 6 for installation notes.
8
cULus Listed as corrosion resistant.
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
DESIGN CRITERIA
(Also refer to the Approval Chart.)
cULus Listing Requirements: Microfast® EC/QREC Horizontal Sidewall Sprinkler VK605 is cULus Listed as indicated in the Approval Chart for instal-
lation in accordance with the latest edition of NFPA 13 for extended coverage sidewall spray sprinklers:
• Sprinkler VK605 is cULus Listed for Light Hazard occupancies with smooth, flat, horizontal ceilings. Sprinkler VK605 is also listed for ceilings with
slopes to 4/12 (18.4°), as a QREC “Specific Application Sprinkler”.
• For sprinkler VK605 in sloped ceiling applications, Sections 11.2.3.2.3 and 11.2.3.2.4 of the 2007 Edition of NFPA-13 do not apply regarding System
Area of Operation. Sprinkler VK605 should be installed according to the areas of coverage, and flows and pressures listed in the Approval Chart.
• In sloped ceiling installations, sprinkler VK605 is listed for installation at the high-point intersection of the wall and the ceiling. In sloped ceiling
installations, the spray must be directed down the slope. Spray may NOT be directed across the slope. Refer to Figure 6.
• Listed area of coverage for sloped ceilings corresponds to ceiling slope. (For sloped ceiling applications, actual floor coverage will be less than
the listed area.)
• Refer to the Approval Chart for required deflector distance below the ceiling. Install with the leading edge of the deflector oriented parallel to the
ceiling (see Figure 4).
• Minimum distance from end walls is 4 in. (102 mm).
• Maximum distance from the end wall shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
• The sprinkler installation and obstruction rules contained in NFPA 13 for extended coverage sidewall spray sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
** A 1/2” ratchet is required Step 2: Carefully press the wrench onto the
(not available from Viking) sprinkler wrench flats.
Figure 2: Wrench 13655W/B for Recessed Sprinklers
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
2-11/16”
(68 mm) 2-7/16”
(62 mm)
Minimum Minimum
1-5/8” 1-3/4”
2-1/8” 2-1/8”
(54 mm) (54 mm)
2-1/4” 2-5/8”
Figure 4: Sidewall Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons
MICROFAST® SR/QR
EXTENDED COVERAGE
TECHNICAL DATA
HSW SPRINKLER
VK605 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.
2-5/8” 4”
(66 mm) (102 mm)
Depth
1-1/16” 1-1/16”
(27 mm) (27 mm) Maximum Recess:
1/2” (13 mm)
** A 1/2” ratchet is required Step 2: Carefully press the wrench onto the
(not available from Viking) sprinkler wrench flats.
Figure 5: Sidewall Sprinkler Dimensions with the Model G-1 Escutcheon
NOTES:
1. In sloped ceiling installations, sprinkler VK605 is listed for instal-
lation at the high-point intersection of the wall and the ceiling.
In sloped ceiling installations, the spray must be directed
down the slope. Spray may NOT be directed across the slope.
2. Listed area of coverage for sloped ceilings corresponds to
ceiling slope. (For sloped ceiling applications, actual floor
coverage will be less than the listed area.)
Figure 6: Sprinkler VK605-Sloped Ceiling Installation with a Model E-1 or E-2 Recessed Escutcheon
Form No. F_072414 20.06.04 Rev 20.1 Replaces Form No. F_072414 Rev 19.2
(Remove Black PTFE)
VSR
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
UL, CUL and CSFM Listed, FM Approved, LPCB Approved, For
CE Marked (EN12259-5) / VdS Approved model use VSR-EU
Service Pressure: 450 PSI (31 BAR) - UL
Flow Sensitivity Range for Signal:
4-10 GPM (15-38 LPM) - UL
Maximum Surge: 18 FPS (5.5 m/s)
Contact Ratings: Two sets of SPDT (Form C)
10.0 Amps at 125/250VAC
2.0 Amps at 30VDC Resistive
10 mAmps min. at 24VDC
Conduit Entrances: Two knockouts provided for 1/2" conduit.
Individual switch compartments suitable
for dissimilar voltages.
Environmental Specifications:
• NEMA 4/IP54 Rated Enclosure suitable for indoor or
outdoor use with factory installed gasket and die-cast housing
when used with appropriate conduit fitting.
• Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL
• Non-corrosive sleeve factory installed in saddle.
Service Use:
Automatic Sprinkler NFPA-13
Specifications subject to change without notice. One or two family dwelling NFPA-13D
Ordering Information Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Nominal Pipe Size Model Part Number
2" DN50 VSR-2 1144402
2 1/2" DN65 VSR-2 1/2 1144425
• Installation must be performed by qualified personnel and in
3" DN80 VSR-3 1144403 accordance with all national and local codes and ordinances.
3 1/2" - VSR-3 1/2 1144435 • Shock hazard. Disconnect power source before servicing. Serious
4" DN100 VSR-4 1144404 injury or death could result.
• Risk of explosion. Not for use in hazardous locations. Serious
5" - VSR-5 1144405 injury or death could result.
6" DN150 VSR-6 1144406
8" DN200 VSR-8 1144408
Optional: Cover Tamper Switch Kit, stock no. 0090148 Waterflow switches that are monitoring wet pipe sprinkler systems shall
Replaceable Components: Retard/Switch Assembly, stock no. 1029030 not be used as the sole initiating device to discharge AFFF, deluge,
or chemical suppression systems. Waterflow switches used for this
application may result in unintended discharges caused by surges,
trapped air, or short retard times.
Important: This document contains important information on the installation and operation of the VSR waterflow switches. Please read all
instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
General Information Enclosure
The Model VSR is a vane type waterflow switch for use on wet sprinkler The VSR switches and retard device are enclosed in a general purpose,
systems. It is UL Listed for use on a steel pipe; schedules 5 through 40, die-cast housing. The cover is held in place with two tamper resistant
sizes 2" - 6" and is UL Listed and FM Approved for use on steel pipe; screws which require a special key for removal. A field installable
schedules 10 through 40, sizes 2" thru 8" (50 mm thru 200 mm). LPC cover tamper switch is available as an option which may be used
approved sizes are 2" thru 8" (50 mm thru 200 mm). See Ordering to indicate unauthorized removal of the cover. See bulletin number
Information chart. 5401103 for installation instructions of this switch.
The VSR may also be used as a sectional waterflow detector on large
systems. The VSR contains two single pole, double throw, snap action
switches and an adjustable, instantly recycling pneumatic retard. The
switches are actuated when a flow of 10 GPM (38 LPM) or more occurs
downstream of the device. The flow condition must exist for a period
of time necessary to overcome the selected retard period.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833 • www.pottersignal.com
PRINTED IN USA MFG. #5401146 - REV M PAGE 1 OF 4
11/15
VSR
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
Installation (see Fig. 1)
These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they shall be installed on the top side of the pipe where they
will be accessible. The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24"
(60 cm) of a valve or drain.
NOTE: Do not leave cover off for an extended period of time.
Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other
material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend
or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive
bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque
(see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way.
Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise prevent
the trip stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm. If an alarm is not desired, a qualified
technician should disable the alarm system.
Fig. 1 Retard Adjustment
DO NOT LEAVE COVER OFF FOR
AN EXTENDED PERIOD OF TIME The delay can be adjusted by rotating the retard adjustment knob from
0 to the max setting (60-90 seconds). The time delay should be set at
the minimum required to prevent false alarms
TIGHTEN NUTS
ALTERNATELY
50mm
ROLL PADDLE IN
OPPOSITE DIRECTION ADAPTER ADAPTER
DIRECTION OF OF WATERFLOW
WATERFLOW
20mm ±2mm MAX.
(Flowing water activates
device in one direction only.) DN50 ONLY
USE (2) 5180162 ADAPTERS AS SHOWN ABOVE
DWG# 1146-1F
inch mm inch mm inch mm inch mm inch mm inch mm inch mm inch mm ft-lb n-m
VSR-2 2 DN50 2.375 60.3 .065 1.651 0.109 2.77 0.154 3.91 0.142 3.6 0.091 2.3
1.25 + .125/-
VSR-2 1/2 2.5 - 2.875 73.0 .084 2.134 0.120 3.05 0.203 5.16 - - - - 33.0 ± 2.0
.062
VSR-2 1/2 - DN65 3.000 76.1 - - - - - - 0.142 3.6 0.102 2.6
VSR-3 3 DN80 3.500 88.9 .083 2.108 0.120 3.05 0.216 5.49 0.157 4.0 0.114 2.9
VSR-3 1/2 3.5 - 4.000 101.6 - - 0.120 3.05 0.226 5.74 - - - - 20 27
VSR-4 4 DN100 4.500 114.3 .084 2.134 0.120 3.05 0.237 6.02 0.177 4.5 0.126 3.2
2.00 ± .125 50.8 ± 2.0
VSR-5 5 - 5.563 141.3 - - 0.134 3.40 0.258 6.55 - - - -
VSR-6 6 DN150 6.625 168.3 .115 2.921 0.134 3.40 0.280 7.11 0.197 5.0 0.157 4.0
VSR-8 8 DN200 8.625 219.1 - - 0.148 3.76 0.322 8.18 0.248 6.3 0.177 4.5
NOTE: For copper or plastic pipe use Model VSR-CF.
PRINTED IN USA MFG. #5401146 - REV M PAGE 2 OF 4
11/15
VSR
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
Fig. 2 Fig. 3 Fig. 4 Switch Terminal Connections Clamping
To remove knockouts: Place screwdriver at Break out thin section of cover when Plate Terminal
inside edge of knockouts, not in the center. wiring both switches from one conduit
entrance.
LOAD TO BELL
BREAKER
Testing
The frequency of inspection and testing for the Model VSR and its associated protective monitoring system shall be in accordance with applicable
NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
If provided, the inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection
device on the system, application of the VSR is not recommended or advisable.
A minimum flow of 10 GPM (38 LPM) is required to activate this device.
Advise the person responsible for testing of the fire protection system that this system must be tested in accordance
with the testing instructions.
Fig. 6 Mounting Dimensions 5.56 in Fig. 7
3.50 in (141.2 mm)
2.00 in
(89.0 mm) (50.8 mm) GREEN GROUND
SCREWS
2.34 in
(59.4 mm)
PIPE DIA.
U-BOLT NUT + 5.25 in
(+ 133.4 mm)
U-BOLT WASHER
PIPE SADDLE
PIPE
PLASTIC PADDLE DWG. 1146-14
1. Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.
2. Disconnect the power source for local bell (if applicable).
3. Identify and remove all wires from the waterflow switch.
4. Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
5. Remove the retard assembly by lifting it straight up over the tripstem.
6. Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base.
7. Re-install the (2) original mounting screws.
8. Reconnect all wires. Perform a flow test and place the system back in service.
BASE
DWG# 1146-10