- This sheet can be used to calculate wire distances for any 24Vdc (or fwr) Notification Appliance Circuit

(NAC) as well
as audio circuits if you know the device loads and panel specs.
- Distances will be worst case (end loaded) based on lowest possible NAC starting voltage (low battery). Longer
distances may be achieved if you know the distances between each device (point to point wiring). See Detailed Dist.
Calc sheet for calculations.
- If using Edwards - Kidde signaling devices, you can use the Load NAC( ) sheets to calculate circuit loads, which can
then be entered below for NAC( ) operating currents.
- The Load SpkrStrb sheet is for speaker loading (used with audio panels). The strobe currents from that sheet will have
to be assigned to one or more of the 24V NACs.

Load factors: Source voltages*: Wire resistances (ohms/ft)*:


EBPS( )A = 0.59 EBPS( )A = 19.7 12AWG = 0.00198
FX-5 =0.40 FX Conv. = 20.4 14AWG = 0.00314
FX-10 = 0.20 FX Addr. = 20.4 16AWG = 0.00499
FX-64 = 0.20 *Under worst case, low 18AWG = 0.00795
FX-254 / FX-1000 = 0.24 battery condition. *Resistances are typical. Use wire
manufacturer's actual specs if known for
most accurate results.

Enter values in yellow boxes. Results in blue.


Refer to above load factors and source voltages for Edwards - Kidde panels.

Choose power source being used: NAC 3 & 4 not


Enter 1 for EBPS booster supply available on 5 zone
Enter 2 for FX conv. panel conventional or FX-
Enter 3 for FX addr. panel 64.
Enter 4 for Other

Wire Distances for 24V Notification Appliance Circuits


NAC1 NAC2 NAC3 NAC4
Enter total operating current (amps)
Enter load factor x 0 0 0 (Enter 0 if unknown)
Load voltage drop = 0 0 0 0
Enter source voltage 0 0 0
Load voltage drop
- 0 0 0 0
Minimum voltage
= 0 0 0 0
Enter min. device operating voltage
-
Voltage drop
= 0 0 0 0
Total operating current
/ 0 0 0 0
Maximum resistance=
Enter wire resistance (ohms/ft)
/
Maximum wire length (ft)
= (Single wire)
/ 2 2 2 2
Maximum cable length (ft) = (Pair of wires)
Below are two methods of determining speaker circuit wire distances (single pair, Class B). One method will
calculate the total dB loss based on the speaker circuit distance. The other method will calculate a distance based
on the dB loss not exceeding -1.0dB (some specs cannot exceed -0.5dB).

Typical fire alarm audio amplifier voltage is 25 or 70Vrms, but may be different depending on amplifier used (must
check amplifier's spec).

Audio Wiring Distance, dB Loss Audio Wiring Distance


Enter audio voltage (Vrms) Enter audio voltage (Vrms)
Enter wire guage Enter wire gauge
Enter wire resistance (ohms/ft) Enter wire resistance (ohms/ft)
Enter speaker load (in watts) Enter speaker load (in watts)
Enter cable length (in feet) Maximum cable length (ft) 0 Based on -1.0dB los
dB loss 0.0 Maximum cable length (ft) 0 Based on -0.5dB los
(See note 4) (See note 4)

dB Change vs Distance dB Change vs Wattage


Enter dB rating at starting distance Enter starting dB
Enter starting distance (10 ft typical) Enter starting wattage
Enter new distance (in feet) Enter new wattage
New dB 0.0 New dB 0.0
(See note 5) (See note 5)

dB Change vs Audio Voltage


Enter speaker voltage
Enter amplifier voltage
dB loss 0.0 (See note 6)

Notes:
1) For public mode fire alarm applications you should be at least 15dB above ambient noise levels, or 5dB above the
maximum noise level having a duration of at least 60 seconds, whichever is greater, measured at 5 ft above the floor
(or 75dB minimum in sleeping rooms, measured at the pillow).
2) Speaker circuit cable must be a minimum of 18 gauge twisted pair. Shielded cable may be necessary in areas of
high electrical noise.
3) "T" tapping of NAC (Notification Appliance Circuit) wiring is NOT permitted.
4) Speaker circuit wiring should not exceed -1dB loss. In some cases, a spec may not allow more than a -0.5dB loss.
5) dB calculations are based on the distances being directly in front of the signaling device under ideal conditions.
Room acoustics and angles off center can affect actual dB readings.
6) If using a speaker with a higher voltage rating than the amplifier, you must de-rate speaker output by amount
shown. Example: If 70V speaker is rated at 90dB, then is connected to an amplifier that outputs 25V, speaker dB will
be less by the amount shown. You cannot connect a speaker to an amplifier with a higher voltage rating.
Distance Conversions
Miles Kilometers
Kilometers 0 Miles 0

Yards Meters
Meters 0 Yards 0

Feet Meters
Meters 0 Feet 0

Inches Centimeters
Centimeters 0 Inches 0

Area Conversion
Sound Circle Coverage (Diameter in feet)
Area in Square Miles 0.00
Area in Square Kilometers 0.00
Area in Acres 0.00

Temperature Conversions
Fahrenheit Celsius
Celsius Fahrenheit

Volume (Dry Capacity)


Cubic Feet Gallons
Gallons 0 Cubic Feet 0
- This sheet will give a more detailed voltage drop calculation for each device as they
are wired on the NAC (signal circuit). This often results in longer wire runs than if worst
case, end loaded voltage drop calcs were done.
- You will need to know the individual device current draws, and the wiring distances
between devices.
- Enter values in yellow boxes. If at any point the voltage drops below the device's
minimum operating voltage, a warning will appear. If a warning does appear, try
adjusting the number of devices, the wire guage (resistance) or the wire distances until
the warning goes away.

Source voltages*: Load factors: Wire resistances (ohms/ft)*:


EBPS( )A = 19.1 EBPS( )A = 0.59 12AWG = 0.00198
FX Conv. = 20.4 FX-5 =0.40 14AWG = 0.00314
FX Addr. = 20.4 FX-10 = 0.20 16AWG = 0.00499
*Under worst case, low FX-64 = 0.20 18AWG = 0.00795
battery condition. FX-254 / FX-1000 = 0.24 *Resistances are typical. Use wire
manufacturer's actual specs if known for
most accurate results.

Enter source voltage Volts


Enter load factor
Enter wire resistance Ohms
Enter distance from source to 1st device Feet
Enter device's minimum operating voltage Volts (for Regulated 24V devices, this will be 16V)
Starting Voltage = 0.00 Volts
Total circuit current = 0.000 Amps
Total wire distance = 0 Feet
Voltage at last device = 0.00 Volts

*You can refer to the Load NAC tabs or the


Enter current in amps (ie: 45mA device's installation sheet for currents. Be
= .045A) and distance in feet sure to use correct FWR or DC current values
depending on power supply type (EBPS
Device Device Distance From Voltage at booster use DC, FX panels use FWR).
Number Current* Previous Device Device
Device 1 0 Ok
Device 2 Ok
Device 3 Ok
Device 4 Ok
Device 5 Ok
Device 6 Ok
Device 7 Ok
Device 8 Ok
Device 9 Ok
Device 10 Ok
Device 11 Ok
Device 12 Ok
Device 13 Ok
Device 14 Ok
Device 15 Ok
Device 16 Ok
Device 17 Ok
Device 18 Ok
Device 19 Ok
Device 20 Ok
Device 21 Ok
Device 22 Ok
Device 23 Ok
Device 24 Ok
Device 25 Ok
Device 26 Ok
Device 27 Ok
Device 28 Ok
Device 29 Ok
Device 30 Ok
Device 31 Ok
Device 32 Ok
Device 33 Ok
Device 34 Ok
Device 35 Ok
Device 36 Ok
Device 37 Ok
Device 38 Ok
Device 39 Ok
Device 40 Ok
11/5/2019

NAC1
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC rating.
3) For FWR power supplies, such as with most Edwards - Kidde FA panels, use the FWR
currents. Total FWR Current Load = 0 amps
4) For DC power supplies, such as the EBPS6(10)A booster supplies, use the dc Total DC Current Load = 0 amps
currents.
5) Currents are worst case (U.L. nameplate) values.
6) This page does not list all the available fire alarm signals. Refer to catalog for
additional choices.

Device Total Device Total


Horns & Horn Strobes FWR mA FWR mA DC mA DC mA
Genesis wall mount horn only
EG1(*)-HD
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 51 0 26 0
low dBA 37 0 19 0

Genesis low current wall mount horn only


EG1A*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 29 0 23 0
low dBA 15 0 13 0

Genesis low freqency horn only (for sleeping areas)


G4LF(**)-H 215 0 166 0

Genesis wall mount horn strobes


EG1(*)-HDVM
Enter quantities for each candela & dB setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd, high dBA 176 0 129 0
30 cd, high dBA 230 0 167 0
75 cd, high dBA 397 0 281 0
110 cd, high dBA 443 0 337 0
15 cd, low dBA 162 0 122 0
30 cd, low dBA 216 0 160 0
75 cd, low dBA 383 0 274 0
110 cd, low dBA 429 0 330 0

Genesis low current LED wall mount horn strobes


EG1AV*
Enter quantities for each dBA setting
0 Temporal Horn / Strobe Count
0 Ok
high dBA 55 0 35 0
low dBA 43 0 45 0

Enter quantities for each dBA setting


0 Temporal Horn / Strobe Count
0 Ok
high dBA 60 0 50 0
low dBA 48 0 40 0

Genesis low freqency horn strobe (for sleeping areas)


G4LF(**)-HVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 308 0 219 0
30 cd 362 0 266 0
75 cd 510 0 381 0
110 cd 579 0 437 0

Genesis low current, ceiling mount horn only


EGCA*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 40 0 30 0
low dBA 25 0 20 0

Genesis ceiling low candela horn strobes


EGC(*)-HDVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 189 0 147 0
30 cd 253 0 190 0
75 cd 417 0 316 0
95 cd 451 0 372 0

Genesis ceiling high candela horn strobes


EGC(*)-HDVMH
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Genesis low current, ceiling mount horn strobe


EGCAV*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 75 0 60 0
low dBA 60 0 50 0

Strobes
Genesis wall strobes
EG1(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 125 0 103 0
30 cd 179 0 141 0
75 cd 346 0 255 0
110 cd 392 0 311 0

Genesis low current LED wall strobes


EG1V* 32 0 24 0

Genesis low candela ceiling strobes


EGC(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling strobes


EGC(*)-VMH
Enter quantities for each candela setting
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Genesis low current, LED ceiling strobes


EGCV* 45 0 35 0

Weatherproof Horn (Strobes)


Genesis low candela w.p. horn strobes
WG4**-HVMC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
15 cd 218 0 127 0
29 cd 239 0 168 0
70 cd 393 0 297 0
87 cd 422 0 351 0

Genesis high candela w.p. horn strobes


WG4**-HVMHC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
102 cd 447 0 342 0
123 cd 502 0 408 0
147 cd 614 0 517 0
161 cd 679 0 526 0

Integrity weatherproof horn


2447TH-* 82 0 35 0

Integrity 4 wire weatherproof worn wtrobe


2452THS-15/75-* 210 0 150 0
2452THS-110-* 420 0 329 0

Weatherproof strobe
CS405-7A-T* 210 0 150 0
CS405-8A-T* 420 0 329 0

Explosionproof
Horn
889D-AW 160 0 160 0
Strobe
116DEGEX-FJ 683 0 505 0

fwr mA dc mA
Other (not included above) fwr mA Total dc mA Total

Qty Part Number


0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0

Totals = 0 0
11/5/2019

NAC2
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC rating.
3) For FWR power supplies, such as with most Edwards - Kidde FA panels, use the FWR
currents. Total FWR Current Load = 0 amps
4) For DC power supplies, such as the EBPS6(10)A booster supplies, use the dc Total DC Current Load = 0 amps
currents.
5) Currents are worst case (U.L. nameplate) values.
6) This page does not list all the available fire alarm signals. Refer to catalog for
additional choices.

Device Total Device Total


Horns & Horn Strobes FWR mA FWR mA DC mA DC mA
Genesis wall mount horn only
EG1(*)-HD
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 51 0 26 0
low dBA 37 0 19 0

Genesis low current wall mount horn only


EG1A*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 29 0 23 0
low dBA 15 0 13 0

Genesis low freqency horn only (for sleeping areas)


G4LF(**)-H 215 0 166 0

Genesis wall mount horn strobes


EG1(*)-HDVM
Enter quantities for each candela & dB setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd, high dBA 176 0 129 0
30 cd, high dBA 230 0 167 0
75 cd, high dBA 397 0 281 0
110 cd, high dBA 443 0 337 0
15 cd, low dBA 162 0 122 0
30 cd, low dBA 216 0 160 0
75 cd, low dBA 383 0 274 0
110 cd, low dBA 429 0 330 0

Genesis low current LED wall mount horn strobes


EG1AV*
Enter quantities for each dBA setting
0 Temporal Horn / Strobe Count
0 Ok
high dBA 55 0 35 0
low dBA 43 0 45 0

Enter quantities for each dBA setting


0 Temporal Horn / Strobe Count
0 Ok
high dBA 60 0 50 0
low dBA 48 0 40 0

Genesis low freqency horn strobe (for sleeping areas)


G4LF(**)-HVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 308 0 219 0
30 cd 362 0 266 0
75 cd 510 0 381 0
110 cd 579 0 437 0

Genesis low current, ceiling mount horn only


EGCA*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 40 0 30 0
low dBA 25 0 20 0

Genesis ceiling low candela horn strobes


EGC(*)-HDVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 189 0 147 0
30 cd 253 0 190 0
75 cd 417 0 316 0
95 cd 451 0 372 0

Genesis ceiling high candela horn strobes


EGC(*)-HDVMH
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Genesis low current, ceiling mount horn strobe


EGCAV*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 75 0 60 0
low dBA 60 0 50 0

Strobes
Genesis wall strobes
EG1(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 125 0 103 0
30 cd 179 0 141 0
75 cd 346 0 255 0
110 cd 392 0 311 0

Genesis low current LED wall strobes


EG1V* 32 0 24 0

Genesis low candela ceiling strobes


EGC(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling strobes


EGC(*)-VMH
Enter quantities for each candela setting
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Genesis low current, LED ceiling strobes


EGCV* 45 0 35 0

Weatherproof Horn (Strobes)


Genesis low candela w.p. horn strobes
WG4**-HVMC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
15 cd 218 0 127 0
29 cd 239 0 168 0
70 cd 393 0 297 0
87 cd 422 0 351 0

Genesis high candela w.p. horn strobes


WG4**-HVMHC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
102 cd 447 0 342 0
123 cd 502 0 408 0
147 cd 614 0 517 0
161 cd 679 0 526 0

Integrity weatherproof horn


2447TH-* 82 0 35 0

Integrity 4 wire weatherproof worn wtrobe


2452THS-15/75-* 210 0 150 0
2452THS-110-* 420 0 329 0

Weatherproof strobe
CS405-7A-T* 210 0 150 0
CS405-8A-T* 420 0 329 0

Explosionproof
Horn
889D-AW 160 0 160 0
Strobe
116DEGEX-FJ 683 0 505 0

fwr mA dc mA
Other (not included above) fwr mA Total dc mA Total

Qty Part Number


0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0

Totals = 0 0
11/5/2019

NAC3
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC rating.
3) For FWR power supplies, such as with most Edwards - Kidde FA panels, use the FWR
currents. Total FWR Current Load = 0 amps
4) For DC power supplies, such as the EBPS6(10)A booster supplies, use the dc Total DC Current Load = 0 amps
currents.
5) Currents are worst case (U.L. nameplate) values.
6) This page does not list all the available fire alarm signals. Refer to catalog for
additional choices.

Device Total Device Total


Horns & Horn Strobes FWR mA FWR mA DC mA DC mA
Genesis wall mount horn only
EG1(*)-HD
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 51 0 26 0
low dBA 37 0 19 0

Genesis low current wall mount horn only


EG1A*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 29 0 23 0
low dBA 15 0 13 0

Genesis low freqency horn only (for sleeping areas)


G4LF(**)-H 215 0 166 0

Genesis wall mount horn strobes


EG1(*)-HDVM
Enter quantities for each candela & dB setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd, high dBA 176 0 129 0
30 cd, high dBA 230 0 167 0
75 cd, high dBA 397 0 281 0
110 cd, high dBA 443 0 337 0
15 cd, low dBA 162 0 122 0
30 cd, low dBA 216 0 160 0
75 cd, low dBA 383 0 274 0
110 cd, low dBA 429 0 330 0

Genesis low current LED wall mount horn strobes


EG1AV*
Enter quantities for each dBA setting
0 Temporal Horn / Strobe Count
0 Ok
high dBA 55 0 35 0
low dBA 43 0 45 0

Enter quantities for each dBA setting


0 Temporal Horn / Strobe Count
0 Ok
high dBA 60 0 50 0
low dBA 48 0 40 0

Genesis low freqency horn strobe (for sleeping areas)


G4LF(**)-HVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 308 0 219 0
30 cd 362 0 266 0
75 cd 510 0 381 0
110 cd 579 0 437 0

Genesis low current, ceiling mount horn only


EGCA*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 40 0 30 0
low dBA 25 0 20 0

Genesis ceiling low candela horn strobes


EGC(*)-HDVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 189 0 147 0
30 cd 253 0 190 0
75 cd 417 0 316 0
95 cd 451 0 372 0

Genesis ceiling high candela horn strobes


EGC(*)-HDVMH
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Genesis low current, ceiling mount horn strobe


EGCAV*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 75 0 60 0
low dBA 60 0 50 0

Strobes
Genesis wall strobes
EG1(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 125 0 103 0
30 cd 179 0 141 0
75 cd 346 0 255 0
110 cd 392 0 311 0

Genesis low current LED wall strobes


EG1V* 32 0 24 0

Genesis low candela ceiling strobes


EGC(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling strobes


EGC(*)-VMH
Enter quantities for each candela setting
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Genesis low current, LED ceiling strobes


EGCV* 45 0 35 0

Weatherproof Horn (Strobes)


Genesis low candela w.p. horn strobes
WG4**-HVMC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
15 cd 218 0 127 0
29 cd 239 0 168 0
70 cd 393 0 297 0
87 cd 422 0 351 0

Genesis high candela w.p. horn strobes


WG4**-HVMHC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
102 cd 447 0 342 0
123 cd 502 0 408 0
147 cd 614 0 517 0
161 cd 679 0 526 0

Integrity weatherproof horn


2447TH-* 82 0 35 0

Integrity 4 wire weatherproof worn wtrobe


2452THS-15/75-* 210 0 150 0
2452THS-110-* 420 0 329 0

Weatherproof strobe
CS405-7A-T* 210 0 150 0
CS405-8A-T* 420 0 329 0

Explosionproof
Horn
889D-AW 160 0 160 0
Strobe
116DEGEX-FJ 683 0 505 0

fwr mA dc mA
Other (not included above) fwr mA Total dc mA Total

Qty Part Number


0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0

Totals = 0 0
11/5/2019

NAC4
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC rating.
3) For FWR power supplies, such as with most Edwards - Kidde FA panels, use the FWR
currents. Total FWR Current Load = 0 amps
4) For DC power supplies, such as the EBPS6(10)A booster supplies, use the dc Total DC Current Load = 0 amps
currents.
5) Currents are worst case (U.L. nameplate) values.
6) This page does not list all the available fire alarm signals. Refer to catalog for
additional choices.

Device Total Device Total


Horns & Horn Strobes FWR mA FWR mA DC mA DC mA
Genesis wall mount horn only
EG1(*)-HD
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 51 0 26 0
low dBA 37 0 19 0

Genesis low current wall mount horn only


EG1A*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 29 0 23 0
low dBA 15 0 13 0

Genesis low freqency horn only (for sleeping areas)


G4LF(**)-H 215 0 166 0

Genesis wall mount horn strobes


EG1(*)-HDVM
Enter quantities for each candela & dB setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd, high dBA 176 0 129 0
30 cd, high dBA 230 0 167 0
75 cd, high dBA 397 0 281 0
110 cd, high dBA 443 0 337 0
15 cd, low dBA 162 0 122 0
30 cd, low dBA 216 0 160 0
75 cd, low dBA 383 0 274 0
110 cd, low dBA 429 0 330 0

Genesis low current LED wall mount horn strobes


EG1AV*
Enter quantities for each dBA setting
0 Temporal Horn / Strobe Count
0 Ok
high dBA 55 0 35 0
low dBA 43 0 45 0

Enter quantities for each dBA setting


0 Temporal Horn / Strobe Count
0 Ok
high dBA 60 0 50 0
low dBA 48 0 40 0

Genesis low freqency horn strobe (for sleeping areas)


G4LF(**)-HVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 308 0 219 0
30 cd 362 0 266 0
75 cd 510 0 381 0
110 cd 579 0 437 0

Genesis low current, ceiling mount horn only


EGCA*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 40 0 30 0
low dBA 25 0 20 0

Genesis ceiling low candela horn strobes


EGC(*)-HDVM
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
15 cd 189 0 147 0
30 cd 253 0 190 0
75 cd 417 0 316 0
95 cd 451 0 372 0

Genesis ceiling high candela horn strobes


EGC(*)-HDVMH
Enter quantities for each candela setting
0 Temporal Horn / Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Genesis low current, ceiling mount horn strobe


EGCAV*
Enter quantities for each dBA setting
0 Temporal Horn Count
0 Ok
high dBA 75 0 60 0
low dBA 60 0 50 0

Strobes
Genesis wall strobes
EG1(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 125 0 103 0
30 cd 179 0 141 0
75 cd 346 0 255 0
110 cd 392 0 311 0

Genesis low current LED wall strobes


EG1V* 32 0 24 0

Genesis low candela ceiling strobes


EGC(*)-VM
Enter quantities for each candela setting
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling strobes


EGC(*)-VMH
Enter quantities for each candela setting
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Genesis low current, LED ceiling strobes


EGCV* 45 0 35 0

Weatherproof Horn (Strobes)


Genesis low candela w.p. horn strobes
WG4**-HVMC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
15 cd 218 0 127 0
29 cd 239 0 168 0
70 cd 393 0 297 0
87 cd 422 0 351 0

Genesis high candela w.p. horn strobes


WG4**-HVMHC
Enter quantities for each candela setting
0 Horn Strobe Count
0 Ok
102 cd 447 0 342 0
123 cd 502 0 408 0
147 cd 614 0 517 0
161 cd 679 0 526 0

Integrity weatherproof horn


2447TH-* 82 0 35 0

Integrity 4 wire weatherproof worn wtrobe


2452THS-15/75-* 210 0 150 0
2452THS-110-* 420 0 329 0

Weatherproof strobe
CS405-7A-T* 210 0 150 0
CS405-8A-T* 420 0 329 0

Explosionproof
Horn
889D-AW 160 0 160 0
Strobe
116DEGEX-FJ 683 0 505 0

fwr mA dc mA
Other (not included above) fwr mA Total dc mA Total

Qty Part Number


0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0

Totals = 0 0
8/29/2016

Speaker Strobes
Notes:
1) Enter quantities below per circuit in yellow boxes. Totals will appear to the right.
2) Be sure total does not exceed panel's NAC (or amplifer) rating.
3) For FWR power supplies, such as with most Edwards - Kidde panels, use the FWR
currents. Total FWR Current Load = 0 amps
4) For DC power supplies, such as the EBPS6(10)A, use the dc currents. Total DC Current Load = 0 amps
5) Currents are worst case (U.L. nameplate) values.
6) This page does not list all the available fire alarm signals. Refer to catalog for additional Total Wattage = 0 watts
choices.

Device Total Device Total Speaker


Indoor Speakers & Speaker Strobes FWR mA FWR mA DC mA DC mA Wattage

Genesis high fidelity wall mount speakers


G4HF*-S*
Enter quantities for each wattage setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0

Genesis high fidelity wall mount speaker strobes


G4HF*-S*VMC
Enter quantities for each wattage and candela setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
15 cd 120 0 96 0
30 cd 169 0 130 0
75 cd 329 0 239 0
110 cd 375 0 294 0

Genesis wall mount speakers


(E)G4*-S*
Enter quantities for each wattage setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0

Genesis wall mount speaker strobes


(E)G4*-S*VM
Enter quantities for each wattage and candela setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
15 cd 120 0 96 0
30 cd 169 0 130 0
75 cd 329 0 239 0
110 cd 375 0 294 0

Genesis ceiling speakers


(E)GC*-S*
Enter quantities for each wattage setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0

Genesis low candela ceiling speaker strobes


(E)GC*-S*VM
Enter quantities for each wattage and candela setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
15 cd 131 0 109 0
30 cd 194 0 151 0
75 cd 379 0 281 0
95 cd 437 0 318 0

Genesis high candela ceiling speaker strobes


(E)GC*-S*VMH
Enter quantities for each wattage and candela setting
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
95 cd 432 0 330 0
115 cd 518 0 392 0
150 cd 643 0 502 0
177 cd 693 0 565 0

Weatherproof Speaker(Strobes)

Genesis weatherproof speaker only


WG4**-S
Enter quantities for each wattage
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0

Genesis low candela weatherproof speaker strobe


WG4**-SVMC
Enter quantities for each wattage and candela
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
15 cd 120 0 106 0
29 cd 178 0 144 0
70 cd 347 0 167 0
87 cd 386 0 319 0

Genesis high candela weatherproof speaker strobe


Enter quantities for each wattage and candela setting
WG4**-SVMHC
0 Speaker Count
0 Ok
1/4 watt 0
1/2 watt 0
1 watt 0
2 watt 0
0 Strobe Count
0 Ok
102 cd 412 0 324 0
123 cd 487 0 390 0
147 cd 607 0 494 0
161 cd 646 0 495 0

Double reentrant (projection) speaker


5552-15-R(W)
0 Speaker Count
0 Ok
1 watt 0
2 watt 0
4 watt 0
8 watt 0
15 watt 0

Hazardous Location
Hazardous location (Division 2) speaker
5553-25/70-R(G)
0 Speaker Count
0 Ok
1 watt 0
2 watt 0
4 watt 0
8 watt 0
15 watt 0

Others (not included above)


Strobe Currents
Speaker fwr mA dc mA Speaker
Qty Part Number Wattage fwr mA Total dc mA Total Wattage
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0
0 0 0

Totals = 0 0 0

You might also like