You are on page 1of 42

Secure Power Always

90-NET from 60 to 800 kVA

UPS Catalogue
Uninterruptible Power
Supply Systems

UPS Catalogue • 2007 90-NET


from 60 to 800 kVA
Scope 2

System description 2

Device description 3

General requirements 5

AC/DC converter 5

Control unit, IGBT inverter 8

Electronic static switch 9

Monitoring and control, interfaces 10

Mechanical data 16

Environmental conditions 16

Technical data (60 to 200 kVA) 17

Technical data (250 to 800 kVA) 21

Options 25

Parallel configurations 27

Appendix: Planning and Installation 33

01 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

1 Scope
This specification describes a and without interruption, upon failure UPS, are driven by vector control
continuous duty three-phase, solid or degradation of the commercial AC algorithms (covered by patents 95
state, insulated gate bipolar transistor source. The continuity of conditioned P3875, 95 P3879 and 96 P3198)
(IGBT) uninterruptible power supply electric power shall be delivered for running on dedicated digital signal
(UPS) system. The UPS shall the time period defined by the battery processor (DSP) systems.
automatically provide continuity of system. The inverter, and other
electrical power, within defined limits mission critical converters within the

2 System description
This specification describes a static to ensure the complete protection of The UPS shall automatically provide
UPS in intelligent double conversion the loads. continuity of electrical power, within
configuration, as shown in Figure 1. defined limits and without interruption,
The systems shall operate on a 2.1 The system upon failure or degradation of the
microprocessor-based IGBT inverter. commercial AC source. The duration of
The vector control technology will The UPS shall provide high quality AC autonomy (i.e. back up power time) in
enhance the performance of the power for electronic equipment loads the event of network failure shall be
inverter. In order to increase system and shall offer the following features: determined by the battery capacity.
redundancy, an independent electronic • Increased power quality
static bypass shall be integrated into
the UPS. By adding system • Full noise rejection
components, such as parallel kits,
central output cubicles, CROSS • Full compatibility with all types of
switches, safety and disconnecting loads
devices, system bypass switches, in
• Power blackout protection
addition to software and
communications solutions, it shall be • Full battery care
possible to set up elaborate systems

Maintenance Bypass
(only for 60 to 500kVA)

Fuse
Reserve
Mains
Reserve switch

Regular Load
Mains
Switch Fuse Output switch
Rectifier Inverter Electronic
Bypass switch
Electronic
Battery switch

Battery Fuse

Battery switch

LIFE.net Battery Fuse Optional remote


Connectivity Connectivity
bundled. (IP; SNMP; J-BUS;
Basic signalling PROFIBUS;Etc.)

Battery System

Figure 1. 90-NET single block system

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 02
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

2 System description
2.2 Models Available MODEL Rating (kVA) MODEL Rating (kVA)
The 90-NET range shall include the 90-NET/60 60 90-NET/250 250
following three-phase input/output 90-NET/80 80 90-NET/300 300
models: 90-NET/100 100 90-NET/400 400
90-NET/120 120 90-NET/500 500
90-NET/160 160 90-NET/600 600
90-NET/200 200 90-NET/800 800

3 Device description
90-NET is the result of an innovative 3.3.1 Double Conversion Mode 3.3.1.4 Recharge
research and development programme
Upon restoration of the commercial
designed to offer users the most 3.3.1.1 Normal
AC source, even where batteries are
reliable power supply at a minimum
The UPS inverter continuously completely discharged, the rectifier/
cost.
supplies the critical AC load. The charger shall restart automatically,
rectifier/charger derives power from 'walk in' and gradually take over both
3.1 Components
the commercial AC source and the inverter and battery recharge
The UPS shall consist of the following converts it into DC power for the loads. This function shall be fully
major components: inverter whilst simultaneously automatic and shall cause no
maintaining the battery in a fully interruption to the critical load.
• Rectifier/battery charger/electronic charged and optimum operational
battery switch condition (for more details see section 3.3.2 Digital interactive mode
5.11 “Battery Management”). The
• IGBT inverter If priority has been set to digital
inverter converts the DC power into
interactive mode, intelligent double
• Digital signal processor (DSP) clean and regulated AC power which is
conversion technology shall allow
supplied to the critical load through the
90-NET to continuously monitor the
• Electronic static switch and reserve static transfer switch. The static switch
condition of the input supply including
supply monitors and ensures that the inverter
its failure rate to ensure maximum
tracks the reserve supply frequency.
• Manual maintenance bypass switch reliability for critical users. On the
This ensures that any automatic
basis of the analysis performed, it shall
transfer to the reserve supply (due to
• Matching battery cubicles decide whether to supply the load
an overload etc.) is frequency
through the direct line or the
synchronised and does not cause
3.2 Microprocessor control and conditioned line.
interruption to the critical load.
diagnostics This operational mode, which allows
significant energy savings by
Operation and control of the UPS shall 3.3.1.2 Overload
increasing the overall AC/AC efficiency
be provided through the use of of the UPS (see section 11.6), is
In the event of an inverter overload,
microprocessor-controlled logic. primarily intended for general purpose
manual stop or failure the static switch
Indications, measurements and ICT applications. However, it does not
shall automatically transfer the critical
alarms, together with battery provide the same output power quality
load to the reserve supply without
autonomy, shall be shown on an as when the UPS operates in double
interruption.
illuminated, forty character liquid conversion mode. Therefore it will be
crystal display (LCD). The procedures necessary to verify whether this mode
3.3.1.3 Emergency
for start up, shutdown and manual is appropriate for special applications.
transfer of the load to and from bypass Upon failure or reduction of the Digital interactive mode is not available
shall be explained in clear step-by-step commercial AC source (see tables 11 for parallel systems.
sequences on the LCD display. and 12 for tolerances), without
switching, the inverter shall supply the 3.3.2.1 Normal
3.3 Intelligent double conversion critical load, drawing power from the
operating modes associated battery. There shall be no The operating mode will depend on
interruption to the critical load upon the quality of the mains supply in the
90-NET shall adopt intelligent double short-term past. If the line quality has
failure, reduction or restoration of the
conversion technology which allows remained within permitted tolerance
commercial AC source. While the UPS
the UPS to operate in double parameters in this timeframe, the
is powered by the batteries,
conversion or digital interactive mode direct line will provide continuous
indications shall be provided of actual
according to the selected priority. supply to the critical AC load through
autonomy time remaining as well the
The UPS will operate as follows: the static switch. The IGBT inverter will
duration of the mains failure.
remain in constant operation and
synchronisation with the direct line.

03 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

3 Device description
This ensures that the load can be 3.3.2.4 Return to normal conditions 3.4.1 Vector control
transferred to the conditioned line
without a break in the supply where When the mains supply returns to with- To ensure the quick and flexible pro-
there is a deviation from the selected in tolerance limits, 90-NET will continue cessing of measuring data, special
input power tolerance levels. If the to supply the load via the conditioned arithmetic algorithms shall be imple-
direct line failure rate has been outside line for a period of time dependant on mented in DSP, rapidly generating con-
permitted parameters, 90-NET shall the direct line failure rate (the condi- trolled variables as a result. This will
supply the load from the conditioned tioned line draws power from the mains thus render possible the real-time con-
line. The battery charger supplies the not the battery). When the direct line trol of the inverter electronics, result-
energy necessary for maintaining has stabilised, 90-NET returns to nor- ing in obvious advantages concerning
maximum charge to the battery. mal operation. The battery charger auto- the performance of the power compo-
matically begins to recharge the battery, nents. These advantages will be:
3.3.2.2 Inverter stop or overload so that maximum autonomy is guaran-
teed in the shortest possible time. • Improvement of short circuit
If the inverter is stopped either by the behaviour, as individual phases can
operator or as a result of an overload, 3.3.3 Maintenance bypass be more quickly controlled
there is no transfer to the conditioned • Synchronism or phase angle
line and the load continues to be If, for any reason, it is necessary to take
the UPS out of service for maintenance precision between UPS output and
supplied by the direct line. The mains reserve supply even in the case of
voltage and frequency values must be or repair, the UPS shall be fitted with an
internal maintenance bypass switch a distorted mains voltage.
within the tolerance limits specified.
In the event of an overload with a (60 to 500kVA only) which enables a • High flexibility in parallel operation:
duration in excess of the maximum load transfer to a bypass supply with no parallel blocks may be housed in
capacity specified, the load is interruption to power to the critical load separate rooms.
transferred to the conditioned line, (for 600 and 800kVA models the manu-
which will supply it for a specific time al bypass switch is not present, there- Several algorithms included in the
depending on the level of overload. fore it shall be provided externally in Vector Control firmware are covered
In the event of an overload and an the distribution. This external bypass by patents owned by Chloride (95
unsuitable mains supply, 90-NET shall shall be equipped with an auxiliary con- P3875, 95 P3879 and 96 P3198).
transfer the load from the direct line to tact, which shall be remoted to the
the conditioned line (assuming 90-NET UPS using the appropriate signal input). 3.4.2 Redundancy, preventive monitoring
was operating from the direct line) and Bypass isolation shall be complete, all
serviceable components such as In order to maximise the reliability of
the inverter shall continue to supply
fuses, power modules etc. shall be iso- the system, the control unit shall
the critical load for a period dependant
lated. monitor a wide number of operating
on the degree of the overload and the
parameters for the rectifier, inverter
UPS features. Visual and audio alarms
3.3.4 Operation Without Battery and battery. All vital operating
alert the user to the problem.
parameters, such as temperatures,
If the battery is taken out of service for frequency and voltage stability at the
3.3.2.3 Emergency (due to mains maintenance, it is to be disconnected system output, load parameters and
supply failure or variance beyond from the rectifier/charger by means of internal system values shall be
tolerance limits) a switch situated in the UPS cabinet. constantly monitored and controlled
If 90-NET is supplying the load via the The UPS will continue to operate and for irregularities at all times. The
direct line and the mains supply varies meet the performance criteria specified system shall react automatically
beyond tolerance levels (adjustable with the exception of the stand-by peri- before a critical situation arises either
using the software from ± 2% to od. In such a case, the overload perfor- for the UPS or the load, in order to
+10% -8%), the load will be mance from the conditioned line may ensure the supply of the load even in
transferred from the direct line to the also be affected, depending on the actual these difficult conditions.
conditioned line. The load is powered input voltage level.
from the mains via the rectifier and 3.4.3 Telediagnosis and telemonitoring
inverter, (provided the input mains 3.4 Control and diagnostics
In all the above modes of operation,
remains within the tolerances stated in Control of the power electronics modules the UPS may be monitored and con-
tables 11 and 12). Should the input shall be optimised in order to provide: trolled from a remote location such as
mains fall below the lower limit the
a service centre, in order to maintain
batteries shall be used to power the • optimum three-phase supply of the the reliability of the system at nominal
load via the inverter. The user is alerted load levels. Even during complete shut-
to the battery discharge by visual and
• controlled battery charging down of the UPS, information relating
audio alarms and the remaining
to the operating parameters shall not
autonomy is displayed on the LCD.
• minimum phase effects upon the be lost thanks to non volatile RAMs,
During this process, it is possible to
supply network. which will store the information for up
extend the remaining autonomy by
to 10 years.
switching off non-essential loads. By using digital signal processors
(DSP) 90-NET shall implement the
most advanced digital control.

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 04
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

4 General Requirements
4.1 Applied standards 4.2 Safety Therefore the UPS shall not modify the
state of the upstream neutral, in any
Chloride operates a Quality Management In terms of general and safety operating mode, and the neutral state
System which complies with BS EN ISO requirements, the UPS conforms to of the distribution downstream from
9001-2000 for the design, manufacture, standard IEC EN 62040-1-2 governing the UPS is imposed by the mains one.
sales, installation, maintenance and ser- use in restricted access locations. 90-NET should be used in installations
vice of uninterruptible power supply sys- with grounded neutral; for further
tems. The Chloride Environmental Policy 4.3 EMC and surge suppression details please contact Chloride
and Management Systems comply with Technical Support.
EN ISO 14001 and Chloride is committed Electromagnetic effects (of internal or
to implementing a policy of continuous external origin) shall be minimised in
order to ensure that computer 4.5 Materials
improvement to production processes
and pollution reduction. systems and other similar electronic All materials and components
loads shall neither be adversely comprising the UPS shall be new and
90-NET shall carry the CE mark in accor- affected by nor affect the UPS. The of current manufacture.
dance with the Safety and EMC UPS shall be designed to meet the
Directives 2006/95 (superseding the 73/23 requirements of EN 50091-2. The
and successive amendments), 89/336, manufacturer and customer in
92/31 and 93/68. 90-NET is designed and partnership agree to ensure the
manufactured in accordance with the fol- essential EMC protection requirements
lowing international standards: for the specific resulting installation
(with particular emphasis on surge
• IEC EN 62040-1-2 general and suppression).
safety requirements
• EN50091-2 EMC requirements 4.4 Neutral connection and grounding

• IEC EN62040-3 operating requirements. The 90-NET output neutral shall be


electrically isolated, except for RFI
• Surge withstandability EN61000-4-5, filters, from the UPS chassis. The input
level 3. and output neutral connections are the
same, i.e. they are solidly tied together.

5 AC/DC Converter
5.1 General/Input 5.2 Voltage regulation, temperature The rectifier shall be capable of
compensation supplying the inverter with DC voltage
The three-phase current taken from at rated power, even if the input
the commercial AC source shall be The rectifier output voltage shall voltage is below the nominal voltage
converted to a regulated DC voltage by operate within narrow parameters. In tolerance specified. This will not
a rectifier available in both 6-pulse and order to ensure optimum battery require the discharging of the batteries.
12-pulse versions. Above 200kVA charging, regulation shall be This connection is illustrated in Figure 2.
90-NET will be available with a 12 automatically adjusted to the ambient
pulse rectifier (consisting of two 6- temperature.
pulse thyristor rectifiers operating at a
phase shift of 30°) and harmonic filters
as standard. In order to protect the Input AC (Nominal Voltage)
Voltage
power components within the system 100%
each phase of the rectifier input shall
be individually fitted with a fast-acting 85%
fuse.
75%
The rectifier battery charger shall be
operable with the following types of
batteries: Time

• Sealed Lead Acid


Battery DC
Voltage (Float Charge Voltage)
• Lead Acid

• NiCd
2.27 Vpc
The selection of the optimum charging
2.0 Vpc
method shall be completely managed
by the microprocessor.
T1 T2 Time

Figure 2. Rectifier behaviour during reduction of the commercial AC source.

05 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

5 AC/DC Converter
5.3 Soft start

After applying the input voltage the


rectifier starts a programmable current
soft start (1-90 seconds). This
procedure results in a gradual and soft AC Hold-off Current
walk-in of the current taken from the Input Delay soft
Current (5-180 s) start
input voltage supply network. This (1-90 s)
ensures that any standby generator is
gradually introduced into the UPS
input, as shown in Figure 5. To avoid
the simultaneous start-up of different
rectifiers, it is possible to programme a
hold-off dedicated start delay (5-180
seconds) for each unit.
In addition, the UPS includes an ‘on Mains Failure Mains OK Time
generator’ function which, when
activated via floating contact, provides
the possibility, of inhibiting either
battery charging, synchronisation of
the inverter to the direct line supply or
transfer to the direct line. Figure 3. Rectifier soft start

5.4 Power Factor Correction Mode utility or generator) shall be 15% 5.8.2 Sealed, low-maintenance lead
(normal operation is guaranteed up to acid accumulators or NiCd
The rectifier/battery charger control 8%). The maximum current THD accumulators:
provides an algorithm for input power injected into the mains shall be 30%
factor optimisation. but will be reduced to 5% for the units Charging at increased charging voltage
When batteries are fully charged, the above 200kVA which shall have 12 and constant charging current. If the
battery care algorithm puts them on pulse rectifiers and filters provided as charging current falls short of a lower
stand-by (see section 5.11 “Battery standard. threshold value the rectifier shall
Management”). It is in this condition automatically return to load voltage
that the rectifier enters its PFC mode 5.7 Operation with diesel generator level (two-step charging method).
(Power-Factor Control). In this mode it
is able to perform a dynamic real-time In order to obtain the required THD on 5.9 Overvoltage protection
maximisation of the input power input voltage, the coordination
factor, compensating mains utility between diesel generator and UPS The rectifier/battery charger shall
fluctuations. The PFC makes it shall be based on the generator’s sub- automatically switch off if the DC
possible to reach PF > 0.92 (>0.9 for transient reactance, as opposed to its voltage exceeds the maximum value
twelve-phase configurations) under short-circuit reactance. associated with its operational status.
normal operating conditions. This
means time-average PF > 0.9 for most 5.8 Capacity and charging 5.10 Shared battery operation
typical applications. characteristics UPS in parallel configuration can
Example: assuming a typical utility The rectifier shall be capable of operate with common batteries (a
MTBF of 200h and a 10h period for full supporting the inverter at nominal maximum of two UPS can share a
battery recharge results shall be: power and supplying the batteries with common battery bank). In this case the
charging current. After discharge of the batteries are recharged in parallel by
PF = 0.75 10 hours battery the rectifier will power the the rectifiers of the two UPS. The total
PF = 0.92 190 hours inverter and recharge the batteries. The current supplied by the rectifiers is
PFAVG = (0.75*10+0.92*190)/200 = 0.91 200 hours following charging methods for the divided equally, with a maximum
different types of accumulators are unbalance equal to the programmed
5.5 Residual ripple filtering available: level of battery current limits.
Although this configuration leads to
The rectifier output shall have a optimisation of the initial economic
residual voltage ripple of < 2% RMS, 5.8.1 Sealed, maintenance-free lead
acid accumulators: investment, it reduces reliability
while in PFC mode. advantages, which are usually offered
Charging at constant current up to the by parallel UPS systems (see chapter
5.6 Total harmonic distortion (THD) maximum load voltage level. 14 for details).
of input voltage Thereafter the loading voltage shall be
The maximum voltage THD permitted kept at a constant level within narrow
on the rectifier input (either from the limits (single-step charging method).

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 06
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

5 AC/DC Converter
5.11 Battery Management 5.11.2 Automatic Battery Test 5.11.4 Time Compensated End Of
Discharge Voltage
Using advanced battery care (ABC) The operating condition of the
90-NET series shall increase battery batteries shall be automatically tested When the discharge time exceeds one
life by up to 50%. The main battery by the control unit at selectable hour, the shutdown voltage shall be
care features are described below. intervals, e.g. weekly, fortnightly or automatically increased, as shown in
monthly. A short-time discharge of the Figure 4 for VRLA, to avoid heavy battery
5.11.1 Operating Parameters battery will be made to confirm that all discharge as a result of a light load.
the battery blocks and connecting
When operating with a maintenance elements are in good working order. In 5.11.5 Battery Ripple Current
free, valve regulated lead acid battery order to preclude a faulty diagnosis the
(VRLA), the parameters per cell shall test will be launched 24 hours after the When batteries are fully charged the
be as follows: latest battery discharge at the earliest. battery care algorithm places them in
The battery test shall be performed stand-by mode, disconnecting them
• End of discharge voltage (V) 1.65 without any risk to the user, even if the from the rectifier. This status prevents
battery is completely defective. Users charging current ripple and enhance
• Shutdown imminent alarm (V) 1.75 shall be alerted to a detected battery battery operating life.

• Minimum battery test voltage (V) 1.9 fault. The battery test shall not cause
any degradation in terms of the battery 5.11.6 Remaining Battery Life
• Nominal voltage (V) 2.0 system life expectancy. 90-NET uses sophisticated algorithms
• Battery discharging alarm (V) 2.20 to determine the battery life remaining
5.11.3 Ambient Temperature Com- based on real operating conditions
@ 20°C pensated Battery Charger such as temperature, discharge and
• Float voltage (V) 2.27 @ 20°C The float voltage and battery discharge charging cycles, and discharge depth.
alarm shall be automatically adjusted
• High voltage alarm (V) 2.4
as a function of the temperature in the
battery compartment (-0.11% per °C ) in
order to maximise battery operating life.

Voltage per cell

1.80

1.75

1.70

1.65

0 1 2 3 4 5 6 7 8 9 10 Time (hours)

Figure 4. End-of-discharge voltage in relation to discharge time

07 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

6 Control Unit, IGBT Inverter


6.1 AC voltage generation 6.4 Total Harmonic Distortion load from the reserve supply without
interruption, if it is within permissible
From the DC voltage of the intermediate The inverter shall provide harmonic limits.
circuit the inverter shall generate neutralisation and filtering to limit the
sinusoidal AC voltage for the user load THD on the voltage to less than 3% 6.9 Output voltage symmetry
on the basis of pulse-width modulation. with a linear load. For reference non-
By means of the digital signal processor linear load (as defined by EN62040-3) The inverter shall guarantee the
of the control unit the inverter IGBTs the THD shall be limited to less than 5%. symmetry of the output voltages at
shall be controlled so that DC voltage is ±1% for balanced loads and ±3% for
divided up into pulsed voltage packets. 6.5 Neutral sizing 100% unbalanced loads.
A transformer shall be provided at the
output of the inverter. Through this The sizing of the inverter neutral shall 6.10 Phase displacement
transformer and a low-pass filter the be oversized on all ratings in order to
pulse-width modulated signal shall be cope with the combination of The phase angle displacement
converted into sinusoidal AC voltage. harmonics on the neutral wire when between the three-phase voltages
driving single-phase reference non- shall be:
6.2 Voltage regulation linear loads. From 60 to 200kVA the
inverter neutral is sized x 1.7 in relation • 120° ± 1° for balanced loads
The inverter output voltage on the to the phase, while from 250 to
three phases shall be individually 500kVA it is x 1.4 in relation to the • 120° ± 2° for unbalanced loads
controlled to achieve the following phase. Further oversizing could be (0, 0, 100%)
performances: provided on demand.

6.2.1 Steady state 6.11 Short Circuit


6.6 Output power transformer
The inverter steady state output The inverter short circuit capacity of
A dry type isolation transformer shall 90-NET for the first 10ms shall be
voltage shall not deviate by more than be provided for the inverter AC output.
±1% in a steady state condition for >200% for any short circuit
The transformer shall have an configuration. After the first 10ms, it
input voltage and load variations within insulation class H+. The temperature
the quoted limits. shall limit the current to >150% for 5s,
limit of the insulation class of the then it shall shut down.
material shall not be exceeded when
6.2.2 Voltage transient response
operating at full load and within 6.12 Automatic upgrade of inverter
The inverter transient voltage shall not ambient temperature limits. rated power
exceed Class 1 limits when subjected
to application or removal of 100% load 6.7 Overload The inverter shall automatically
as defined by EN62040-3. upgrade its power as a function of
The inverter shall be capable of ambient and operating temperatures,
6.3 Frequency regulation supplying an overload of 125% for 10 as shown in Figure 5. In the most
minutes and 150% for one minute of common conditions (25°C) 90-NET
The inverter output frequency shall be the nominal power. shall provide 10% more power than
controlled to achieve the following nominal. In these conditions the
performances: 6.8 Inverter shutdown battery charge will be reduced
In the event of an internal failure the correspondingly.
6.3.1 Steady state
inverter shall be immediately For example:
The inverter steady-state output disconnected from the critical load and @40°C, Idc tot. = 0.75(Idc inv) + 0.25
frequency, when synchronised to shut down by the control unit. The UPS (Ibatt)
reserve supply, shall not deviate by device or the parallel-operated UPS @25°C, Idc tot. = 0.83(Idc inv) + 0.17
more than ±0.75% adjustable to systems shall continue to supply the (Ibatt)
±1.5%, ±2.5%, ±6%.
Output Power
6.3.2 Frequency slew rate
115

The frequency slew rate shall be ≤ 1Hz


per second.
112

6.3.3 Frequency Control 110

The output frequency of the inverter


shall be controlled by a quartz
105
oscillator which can be operated as a
free running unit or as a slave for
100 Ambient
synchronised operation with a Temperature
separate AC source. The accuracy of
15 25 30 40
the frequency control shall be ±0.05%
when free-running. Figure 5. Automatic power upgrade

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 08
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

7 Electronic Static Switch


7.1 General This automatic retransfer delay time
• Uninterrupted automatic retransfer back to inverter from reserve shall be 5
The electronic static switch shall be a from the reserve supply, as soon seconds. The transfer time when out
fully rated, high speed, solid-state as the inverter regains the capacity of synchronisation shall be 20
transfer device and rated for to supply the load. milliseconds to prevent damage to the
continuous duty operation. Each AC load by phase reversal.
phase of the input shall be individually • The uninterrupted transfer from the
fitted with fast acting fuses to prevent inverter to the reserve supply shall
7.1.3 Overload
cascading failures. be inhibited in the following
situations: The electronic static switch shall be
The following transfer and retransfer - reserve supply voltage outside capable of supporting the following
operations shall be provided by the limits overloads:
electronic static switch: - failure of electronic bypass switch. 125% for 10 minutes
150% for 1 minute
• Uninterrupted automatic transfer to • The uninterrupted automatic
700% for 600 milliseconds
the reserve supply in the event of: retransfer may be inhibited in the
1000% for 100 milliseconds
- inverter output overload following situations:
- DC voltage outside limits - manual switching to reserve supply
7.1.4 Manual maintenance bypass
- over-temperature via the maintenance switch
- inverter failure - failure in output switch behind It shall be possible to implement a
inverter manual uninterrupted bypass of the
• If inverter and reserve supply are - UPS output overload. complete system in order to enable
not synchronised at the time of a maintenance work to be carried out on
necessary transfer, a switching 7.1.1 Voltage the system. The reserve supply will
delay can be set to protect the continue to feed the load. In this case
critical load. This prevents possible The nominal voltage of the reserve line
the UPS will be voltage-free as it will
damage to the load by shall be 230/400VRMS. Any transfer
be disconnected from the supply
unintentional phase shift. A delay from inverter to reserve line will be
networks. In this case, maintenance
of 20ms will be preset as a inhibited if the voltage is beyond a limit
work on the UPS can be carried out
standard value. of ±10% (standard setting) of the
without affecting the connected
nominal voltage.
• Uninterrupted manual transfer/ electric load.
retransfer to and from the reserve 7.1.2 Transfer time (double conversion)
supply shall be initiated from the
control panel. The switching time for a transfer from
the inverter to the reserve supply or
• Uninterrupted automatic transfer/ vice versa shall be less than 0.5ms
retransfer to and from the reserve when synchronised. The system shall
supply by activation of the line ensure that the inverter is stable and
interactive mode. operating normally before permitting a
retransfer of the load back to inverter.

09 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

8 Monitoring and control, Interfaces


8.1 General possible through navigation push buttons “Warning and Alarm” summary page
located below the screen. This navigation directly from the default page. Warnings
The UPS shall incorporate the necessary group includes two buttons “up” and and alarms shall be identified by text
controls, instruments and indicators to “down” for menu scrolling and two strings and codes. In battery operation,
allow the operator to monitor the system software-assigned push buttons: the the display shall switch between warning
status and performance, and take action function linked to these two buttons is code and estimated backup time in
where appropriate. Furthermore, displayed on the lower right and lower left minutes.
interfaces allowing extended monitoring corners of the LCD during navigation.
and control, in addition to service After 30 seconds of inactivity (i.e. without
functions shall be available. 90-NET A single-line diagram of the UPS is buttons being pressed) the display
features a mimic panel with graphical continuously displayed on the default reverts to the default page.
LCD display as described in the section page (for reference see figure 1). The
below. main functional blocks and power paths The text displayed by the LCD shall be
of the UPS are displayed using simple available in English, Italian, French,
8.2 Mimic panel universal technical symbols, instantly German, Spanish Portuguese, Turkish
communicating the overall status of the and Chinese, selectable by the user.
The control panel of 90-NET includes a UPS. The same screen also permanently
back-lit Liquid Crystal Display (LCD of displays the output load percentage
eight lines x 12 characters, displaying measurement, using three histograms
graphic diagrams and symbols) for (one for each output phase). In the case
complete UPS monitoring and control. of the UPS not in normal functioning
Complete access to all LCD menus is mode, it is possible to access the

Graphical LCD
screen

Navigation buttons:
left soft-key,
up and down button,
right soft-key

“Inverter Off” push


button
“Inverter On”
push button
“Alarm” LED

“System Normal” “Reset” push button


LED (e.g. audible signal
silence for warning
and alarm conditions)
ON OFF

Commands key lock

“Warning” LED
KEYBOARD

8.3 Start and Stop Inverter push The control shall incorporate a safety
buttons Start inverter operation feature to prevent inadvertent
operation yet still allow for rapid
The Start and Stop push buttons are shutdown in the event of an
integrated into the mimic panel board, emergency. To stop the inverter the
and have the following predefined user must press and hold the Stop
functions: button for two seconds. An audio
Stop inverter operation alarm shall be activated during this
delay time.

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 10
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

8 Monitoring and control, Interfaces


8.4 Keyboard lock users, once the lock is set in the Off operator attempts to perform any of
position, to disable any command the following actions, a message
The mimic panel shall be equipped which may be entered through the reading “COMMANDS DISABLED”
with a front panel key that allows mimic panel. In this state, if the will appear on the LCD:

Start Inverter Stop Inverter Reset Fault

Set/reset Battery Test Set/reset Autonomy Test Set/reset Boost Charge

Test PFC Set/reset Service Input Set/reset I/O Configuration

LIFE Manual Call Reset Delay Call

8.5 General Status LED

Three LED indicators shall render it


possible to obtain a quick and general
understanding of the status of the
UPS, as described below.

OK LED (green) Normal Operation


When this light is on (not flashing), the system is running normally and neither warnings nor
alarms are present. During mains failures (all other conditions at being nominal level), this LED
will flash.

Warning LED (yellow) Warning Condition(s) present


This indication shall be activated by the presence of anomalous conditions, which could affect
the nominal functioning of the UPS. These conditions did not originate with the UPS, but may
be caused either by the surrounding environment or by the electrical installation (mains side and
load side). It shall be possible to read the description of the active warning(s) by browsing the
relevant LCD display menus.

Alarm LED (red) Alarm Condition


When this light is on, immediate attention should be given to the severity of the alarm, and
service should be called promptly. It shall be possible to read the description of the active
alarm(s) by browsing the relevant LCD display menus.

8.6 LCD display menus description This menu shall display alarms, phase current. It shall be possible to display
to neutral voltages, frequency the total time the load has been
By using the appropriate push buttons measurements, inverter heatsink supplied by the inverter, and by
it shall be possible to browse the temperature and cooling air reserve, the number of mains failures
following menus: temperature. and the total duration of these failures.
Rectifier/Charger and Battery Reserve Supply Listed below are the most significant
This menu shall display rectifier status, This menu shall display alarms, phase messages which may be displayed by
alarms, voltage, total DC current, to neutral voltages and frequency the graphical LCD in the various
battery current with polarity and measurements. menus. The exhaustive messages list
battery temperature. When the and menus description is published in
inverter is supplied by the battery, the Load/Static Switch the User Manual.
module shall display remaining This menu shall display alarms,
autonomy time. A change in load shall current per phase, frequency
cause the autonomy indicator to measurements, load percentage
instantaneously display the new capacity per phase and the peak factor
autonomy time. Ipk/Irms for each phase of the load
Inverter

11 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

8 Monitoring and control, Interfaces


8.6.1 Heading

Alarms/indications
System In Alarm E.P.O. Active Auto Test
Life Service Mode Do Not Insert Bat Dial In Progress
Data Transf. Active Slave Connection Routine Call
Manual Call Emergency Call Life Buffer Full
Rescheduled Call Eprom Checksum Fault Eeprom Fault
Insuff.Ventilation Ventilator Life End Commissioning Mode
Cu Communication Lost Parallel Reserve Fault Pob Fault

8.6.2 Rectifier

Alarms/indications
Alarm Active E.P.O. Active Charger Off
Hardware Test Float Mode Charge Mode
Equalise Mode Recharge Inhibit Battery Test
Rectifier Phase Up Battery Autonomy Test Mains Transf.Protect
Insulation Failure Input Switch Open Primary Supply Fail
Phase Sequence Error Dc Sw Control Fault User Dc Voltage Low
Dc Voltage Low Dc Voltage High Batt. Charge Inhibit
Testing Autonomy Dc Feedback Fault Dc Hw Control Fault
Dc Sw Control Fault Block Rect. Overtemp Rectifier in PFC Mode

8.6.3 Charger and Battery

Alarms/indications
Alarm Active E.P.O. Active Battery Connected
Batt. Disconnected Batt.Breaker Open Battery Operation
Temperature Alarm Battery Fault Battery Fuse Blown
Insulation Failure Shutdown Imminent Battery Stand-By
Battery SCR Fault
Battery Almost Ended

8.6.4 Inverter

Alarms/indications
Alarm Active E.P.O. Active Inverter Running
Inverter Fault Inverter Turning On Inverter Turning Off
Inverter Not Running Remote Inv. Stopped Overtemperature
Shutdown Imminent Dc Voltage Low Overload
Load Too High Inverter Dc Voltage High Extern Fast Turn Off
Inverter Start Failed Heat Sink Overtemperature Transformer Overtemperature
Desaturation Inverter Voltage High Inverter Voltage Low
Inverter Frequency Error Inverter Short Circuit Dc Component On Ph.1
Dc Component On Ph.2 Dc Component On Ph.3 I3t Overload Ph.1
I t Overload Ph.2
2
I t Overload Ph.3
2
Max Output Power
Temp. Sensor Fault

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 12
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

8 Monitoring and control, Interfaces


8.6.5 Reserve

Alarms/indications
Alarm Active E.P.O. Active Reserve Valid
Reserve Not Valid Reserve Not Avail Res. Transf. Protect
Mains Synchro. Inhibit Reserve Supply Warning Backfeed Prot Active
Overload Phase 1, 2, 3 Not Ok Reserve Supply Fault
Reserve Hw Fault Bypass Sens. Fault

8.6.6 Load

Alarms/indications
Alarm Active E.P.O. Active Load On Reserve
Load On Inverter Load On Bypass Load Not Supplied
Insulation Failure System Output Sw Open Sys.Bypass Sw Closed
Output Switch Open Overload Load Too High
Bypass Switch Closed

13 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

8 Monitoring and control, Interfaces


8.7 Interfaces The other slot shall be available for 8.7.2 Computer relay interface
connectivity options. Please refer to
8.7.1 Slot card bay Chloride Connectivity Solutions for Volt-free contacts shall be incorporat-
further details about the available slot ed conforming to the requirements of
90-NET shall be equipped with two slot expansion cards. If no cards are fitted IBM AS/400 and other computer
bays, available for communication card into the slots, the DB9 ports described types. This interface shall be via a 9-pin
options. One of the slots shall be in sections 8.7.3 and 8.7.4 can be used D socket wired as follows:
equipped with the LIFE.net slot modem, for other connectivity applications.
fitted as standard (user removable).

Pin Signal Explanation


1 BYPASS ACTIVE (NC) Bypass mode: contact between pin 1 and 5 is open
2 LOW BATTERY (NC) Just before end of discharge (in battery mode): contact between pin 2 and 5 is open
3 SUMMARY ALARM (NC) UPS fault, contact between pin 3 and pin 5 is open
4 AC FAIL (NC) Mains failure: contact between pin 4 and pin 5 is open
5 SWITCH COM Common connection for all floating contacts
6 BYPASS ACTIVE (NO) Bypass mode: contact between pin 6 and pin 5 is closed
7 LOW BATTERY (NO) Just before end of discharge (in battery mode): contact between pin 7 and pin 5 is closed
8 SUMMARY ALARM (NO) UPS fault, contact between pin 8 and pin 5 is closed
9 AC FAIL (NO) Mains failure: contact between pin 9 and pin 5 is closed

The Floating contacts shall be rated at 24V, 1A.

8.7.3 Service port simultaneously with the correspond- standard. If this slot modem is
ing slot bay as described in section removed, this port may be used for
90-NET will be equipped with one D 8.7.1. other connectivity applications. For
type connector with 9 pins for serial the connector pin-out please refer to
RS232C communication. For the 8.7.4 LIFE.net serial port the installation manual.
connector pin-out please refer to the
installation manual. 90-NET shall be fitted with a slot
This RS232 port cannot be used modem for LIFE.net connection as

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 14
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

8 Monitoring and control, Interfaces

8.8 Available signalisations and the display and/or PPVIS for a wide set most significant functions; the
control signals of functions. Emergency Power Off exhaustive list is published in the User
(EPO) is programmed as standard: this Manual:
The UPS can handle up to 12 Input/ command electronically shuts down
Output control signals (8 inputs, 4 the rectifier, the inverter and the
outputs) that can be programmed via bypass switch. Listed below are the

Fan (On-Off) In Battery Compartment Battery Fuse Monitor


Battery Compartment Overheated Micro Switch UPS Doors
Backfeed Protection Generator On
Hydrogen Present Remote Inverter Stop
SBS Bypass Switch Closed Insufficient Ventilation
SBS Output Switch Open

8.9 LIFE.net The communication of UPS data to the The service centre shall analyse
Chloride LIFE Command Centre shall historical data and issue a regular
In order to increase the overall be transmitted via the integrated detailed report to the customer
reliability of the system, 90-NET will be modem at the following intervals: informing him of the UPS operational
delivered with the LIFE.net communi- condition and any critical states.
cation kit, providing connection to • ROUTINE: settable at intervals of The LIFE.net centre allows the
Chloride’s LIFE.net monitoring service. between five minutes and two possibility of activating the LIFE-SMS
LIFE.net shall allow the remote days (typically once a day) delivery system option, where the
monitoring of the UPS through customer may receive SMS
telephone lines or GSM link in order to • EMERGENCY: when a problem notification which will be activated in
ensure the maximum reliability of the occurs or parameters are beyond the event of one of the following:
UPS throughout its operational life. The tolerance limits
monitoring shall be a real 24-hour, 365 • Mains power failure
day service thanks to a unique feature • MANUAL: following a request
that allows trained Service Engineers from the command centre • Mains power recovery
to remain in constant electronic
contact with the service centre, and During the call the command • Reserve line failure
therefore the UPS. The UPS shall centre shall:
• Load supplied by reserve.
automatically dial-up the service
centre at defined intervals to provide • Identify the UPS connected
detailed information that shall be
analysed in order to predict near term • Request the data stored in the UPS
problems. In addition, it shall be memory since the last connection
possible to control the UPS remotely.
• Request real-time information from
the UPS (selectable)

15 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

9 Mechanical data
9.1 Enclosure The enclosure shall be installed with at Standard colour of the enclosure shall
least 400 mm of free space between be RAL 7035 (light grey).
The UPS shall be housed in a space- the device and roof of the enclosure in
saving modular enclosure with front order to allow cooling air to exit 9.5 Access to integrated subassem-
doors and removable panels unhindered. blies
(protection as standard to IP 20). The
enclosure shall be made of zintec 9.3 Cable entry All internal subassemblies shall be
coated sheet steel. The doors shall be accessible for typical and most
lockable. Cable entry shall be from the bottom frequent maintenance from the front
or bottom-side of the cabinet. Top of the unit via hinged doors. Rear
9.2 Ventilation cable entry shall be available as an access shall not be required for
option. installation or servicing. The UPS shall
Forced redundant air cooling will be forkliftable from the front after the
ensure that all the components are 9.4 Enclosure design removal of the bottom trim panels.
operated within their specification.
Airflow shall be controlled according to All surfaces of the enclosure shall be
demand. The cooling air entry shall be finished with an electrostatically
in the base and the air exit at the top of applied epoxy coat. The coating shall
the device. have a thickness of at least 60 microns.

10 Environmental conditions

The UPS shall be capable of 10.1 Ambient temperature 10.3 Altitude


withstanding any combination of the
environmental conditions listed below. 0° to 40°C The maximum altitude without
It shall operate without mechanical or Maximum average daily temperature derating shall be 1000 metres above
electrical damage or degradation of (24 hr) 35°C sea level or 1500 metres at 25°C. The
operating characteristics. Maximum temperature (8 hr) 40°C derating shall be 1.2% for every 100
metres above 1000 metres.
10.2 Relative humidity

Up to 90% (non condensing) for


temperature of 20°C.

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 16
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

11 Technical data (60 to 200 kVA)

UPS Unit Rating 60 80 100 120 160 200


11.1 Rectifier input

Nominal input voltage (V) 400 3Ph

Maximum permissible input voltage (V) 480

Tolerance on voltage assuming float @ 2.27V per cell (%)(1) ±15

Min. input voltage without battery discharge (%)(1)(9) -25

Nominal frequency (selectable) (Hz) 50 (60)

Tolerance on frequency(10) (%) ±10

Maximum input power @400V, Recharge Mode (kVA) 85 111 139 168 222 278

Power factor @400V, PFC Mode (±0,02) 0.92

Power factor @400V, Float Mode >0.80

Input current distortion @ maximum input power (%) ≤30

Walk in/Soft start (programmable) (seconds) 10 (1-90)

Rectifier Hold-Off (programmable) (seconds) 1 (1-180)

Inrush current / Imax input ratio(8) ≤1

Efficiency of rectifier in float(2): Half load % 98.9


Full load % 98.9
11.2 Rectifier output
Battery voltage for recommended number
of cells (see 11.8) Float for VRLA @ 20°C (V) 449
Recharge (V)* 475
*Only for wet stationary lead batteries

Battery float voltage temperature


compensation (direct sensing) -0.11% per °C

Current ripple into battery for a 10 min


autonomy as per VDE0510, Advanced Battery Care mode(3) <0.05C10

Voltage stability in steady state condition for 100%


load variations or allowed input parameters variations (%) <1

Voltage ripple in float condition (%) <2

DC current supplied to inverter in float (A) 115 153 190 229 303 379

Battery recharge current setting range (A) 5-25 5-25 10-40 10-40 15-65 15-65

Maximum DC current (A) 150 195 245 295 390 490

11.3 Inverter input

DC voltage range (V) 326-540

DC current when inverter at full load (0.8PF)


and minimum DC voltage (A) 158 210 260 315 417 521

17 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

11 Technical data (60 to 200 kVA)

UPS Unit Rating 60 80 100 120 160 200


11.4 Inverter output

Nominal apparent power @ PF 0.8 lagging 40°C (kVA) 60 80 100 120 160 200

Nominal active power (kW) 48 64 80 96 128 160

Nominal output current (A) 87 116 145 174 232 290

Nominal apparent and active power @ PF >0.8,


lagging or leading, 40°C See note (7)

Overload at nominal output voltage and


0.8 PF for 10 min (%) 125

Overload at nominal output voltage and


0.8 PF for 1 min (%)(6) 150

Short circuit current capacity for 5 seconds (10ms) (%) 150 (200)

Nominal output voltage (selectable) (V) 400 (380/415) 3Ph + n

Nominal frequency (selectable) (Hz) 50 (60)

Voltage stability in steady state condition


for input DC variations and 100% load variations (%) ±1

Voltage stability in dynamic condition for 100%


nominal load step variations or DC input variations (%) Complies with IEC/EN 62040-3, Class 1

Voltage stability in steady state for 100%


unbalanced loads (0, 0, 100) (%) ±3

Output frequency stability


In synchro with the mains (selectable) (%) ±0.75 (1.5, 2.5, 6)
With internal quartz oscillator (%) ±0.05

Frequency slew rate (Hz/sec) <1

Output voltage distortion with 100% linear load (%) <3

Output voltage distortion @ reference


non linear load as for IEC/EN 62040-3 (%) <5

Load crest factor without derating (Ipk/Irms) 3:1

Phase angle precision with balanced loads (degrees) <±1

Phase angle precision with 100%


unbalanced loads (degrees) <±2

DC/AC efficiency(2): Half load 92.0 92.5 93.0 93.0 93.5 93.5
Full load 93.0 93.0 93.5 93.5 94.0 94.0

Neutral conductor sizing see Chapter 6.5

Output power upgradability with temperature: At 25°C (%) 110


At 30°C (%) 105
At 40°C (%) 100

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 18
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

11 Technical data (60 to 200 kVA)

UPS Unit Rating 60 80 100 120 160 200


11.5 Reserve static switch

Nominal voltage (selectable) (V) 400 (380/415) 3Ph + n

Nominal frequency (selectable) (Hz) 50 (60)

Frequency range (selectable) (%) ±0.75 (1.5, 2.5, 6.0)

Voltage range (%) ±10

Maximum operating voltage (V) 480/277

Maximum overload capacity For 10 minutes (%) 125


For 1 minute (%) 150
For 600 milliseconds (%) 700
For 100 milliseconds (%) 1000

SCR I2t @ Tvj=130°C; 8.3-10ms (A2s) 80k 80k 80k 80k 320k 320k
ITSM @ Tvj=130°C; 10ms (A) 4k 4k 4k 4k 8k 8k

Fuse Rating (Vac/A) 660/250 660/250 660/250 660/350 660/500 660/500


Pre-arching I t (A s)
2 2
4.4k 4.4k 4.4k 10.5k 23.8k 23.8k
I t @ 400Vac (A s)
2 2
31.5k 31.5k 31.5k 33.5k 105k 105k

Transfer time when in synchro (double conversion)


Inverter to reserve (ms) <0.5
Reserve to inverter (ms) <0.5

Transfer time without synchro (ms) <20

Retransfer delay (sec) <5

11.6 System data

Maximum input power @400V, Recharge Mode (kVA) 85 111 139 168 222 278

Heat dissipation: PFC Mode (kW) 4.2 5.6 6.5 7.8 9.6 12.0
Rapid recharge (kW) 4.4 5.8 6.8 8.1 10.0 12.6
Digital interactive (kW) 1.5 2 2.5 3 4 5

AC/AC efficiency(2): Half load double conv. (%) 91.0 91.5 92.0 92.0 92.5 92.5
Full load double conv. (%) 92.0 92.0 92.5 92.5 93.0 93.0
Digital Interactive (%) 97 97 97 97 97 97

Noise @ 1 metre as per ISO 3746 (dBA ± 2dBA) 62 62 62 64 65 65

Protection degree with open doors IP20

Mechanical dimensions: Height (mm) 1780


Width (mm) 820 820 1020 1020 1420 1420
Depth (mm)(4) 858
No of cabinet 1

Colour Frame (RAL scale) 7035


Bottom panel (RAL scale) 7035

Weight (net, ± 2%) (kg) 595 595 615 700 1050 1050
Floor area (m )
2
0.70 0.70 0.87 0.87 1.22 1.22
Floor loading (kg/m )
2
850 850 707 804 860 860
Cable entry Bottom/Side
Access Front
Cooling Forced Ventilation

19 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

11 Technical data (60 to 200 kVA)

UPS Unit Rating 60 80 100 120 160 200

UPS Safety CE marking, IEC/EN 62040-1-2

EMC EN 50091-2

Surge withstand IEC/EN 61000-4-5, level 3

Performances and Test IEC/EN 62040-3

UPS classification (according to IEC/EN 62040-3) VFI - SS - 111

11.7 Environmental

Temperature: Storage (°C) -25/70


Operating (°C) 0/40
Max average daily (24hrs) (°C) 35
Maximum (8hrs) (°C) 40

Maximum relative humidity @ 20°C (non condensing) (%) up to 90

Elevation without derating (m) 1000


(-1.2% Pn every 100m above 1000m)

11.8 Battery

Optimum battery temperature (°C) 15-25

DC power (kW) 52 69 86 103 136 170

Recommended no. cells: VRLA(5) 198


WET 198
NiCd 310

End of discharge voltage (V) 326

Current at end of discharge voltage (A) 158 210 262 315 417 521

Battery current setting range (A) 5-25 5-25 10-40 10-40 15-65 15-65

(1) @ 192cells and nominal output power;


(2) for tolerance see IEC/EN 60146-1-1 or DIN VDE 0558;
(3) valid only in PFC Mode;
(4) including front handle; without handle 830mm
(5) permitted number of cells = 192-204
(6) only with battery connected
(7) Units rated 60, 80 and 120kVA can supply loads with PF up to 0.8, leading or lagging, at full nominal output power. For the same ratings, loads with PF up
to 0.9, leading or lagging, can be supplied at full nominal output power with limitation in the maximum value of battery recharge current. Please contact Chloride
Technical Support for further details. For 100, 160 and 200 kVA, for loads with PF> 0.8 or leading please contact ChlorideTechnical Support.
(8) Imax input can be deduced from the maximum input power @ 400V, recharge mode
(9) Without battery discharge means 2V / cell
(10) With nominal input voltage and battery connected

Note:
The data shown are typical and not definable in other ways; furthermore the data refer to 25°C ambient temperature and PF= 1 where not specified.
Not all the external data shown apply simultaneously and may be changed without prior warning.

Data apply to the 6-pulse version, if not otherwise specified. For 12-pulse see chapter 13.
If the options described in chapter 13 are added, the data shown in table 11 may vary. For test conditions and measurement tolerances not specified, refer to
the “Witness Test Report”.

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 20
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

12 Technical data (250 to 800 kVA)

UPS Unit Rating 250 300 400 500 600 800


12.1 Rectifier input

Nominal input voltage (V) 400 3Ph

Maximum permissible input voltage (V) 480

Tolerance on voltage assuming


float @ 2.27V per cell (%)(1) +15/-10

Min. input voltage without battery discharge (%)(1)(9) -20

Nominal frequency (selectable) (Hz) 50 (60)

Tolerance on frequency(10) (%) ±10

Maximum input power @400V, Recharge Mode (kVA) 348 418 557 696 835 1113

Power factor @400V, PFC Mode (±0.02) 0.90

Power factor @400V, Float Mode >0.80

Input current distortion @ maximum input power (%) ≤5

Walk in/Soft start (programmable) (seconds) 10 (1-90)

Rectifier Hold-Off (programmable) (seconds) 1 (1-180)

Inrush current / Imax input ratio(8) ≤4

Efficiency of rectifier in float(2): Half load % 97.9


Full load % 97.9

12.2 Rectifier output


Battery voltage for recommended number
of cells (see 12.8) Float for VRLA @ 20°C (V) 545
Recharge (V)* 576
*Only for wet stationary lead batteries

Battery float voltage temperature


compensation (direct sensing) -0.11% per °C

Current ripple into battery for a 10 min


autonomy as per VDE0510, Advanced Battery Care mode(3) <0.05C10

Voltage stability in steady state condition for 100%


load variations or allowed input parameters variations (%) <1

Voltage ripple in float condition (%) <2

DC current supplied to inverter in float (A) 390 466 621 777 932 1243

Battery recharge current setting range (A) 15-80 15-80 20-110 25-135 25-160 30-210

Maximum DC current (A) 500 600 800 1000 1200 1600

12.3 Inverter input

DC voltage range (V) 396-600

DC current when inverter at full load (0.8PF)


and minimum DC voltage (A) 537 641 855 1069 1283 1710

21 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

12 Technical data (250 to 800 kVA)

UPS Unit Rating 250 300 400 500 600 800


12.4 Inverter output

Nominal apparent power @ PF 0.8,


lagging 40°C (kVA) 250 300 400 500 600 800

Nominal active power (kW) 200 240 320 400 480 640

Nominal output current (A) 362 435 580 725 870 1159

Nominal apparent and active power @ PF >0.8,


lagging or leading, 40°C See note (7)

Overload at nominal output voltage


and 0.8 PF for 10 min (%) 125

Overload at nominal output voltage


and 0.8 PF for 1 min (%)(6) 150

Short circuit current capacity for 5 seconds (10ms) (%) 150 (200)

Nominal output voltage (selectable) (V) 400 (380/415) 3Ph + n

Nominal frequency (selectable) (Hz) 50 (60)

Voltage stability in steady state condition


for input DC variations and 100% load variations (%) ±1

Voltage stability in dynamic condition


for 100% nominal load step variations
or DC input variations (%) Complies with IEC/EN 62040-3, Class 1

Voltage stability in steady state for 100%


unbalanced loads (0, 0, 100) (%) ±3

Output frequency stability


In synchro with the mains (selectable) (%) ±0.75 (1.5, 2.5, 6)
With internal quartz oscillator (%) ±0.05

Frequency slew rate (Hz/sec) <1

Output voltage distortion with 100% linear load (%) <3

Output voltage distortion @ reference


non linear load as for IEC/EN 62040-3 (%) <5

Load crest factor without derating (Ipk/Irms) 3:1

Phase angle precision with balanced loads (degrees) <±1

Phase angle precision with 100%


unbalanced loads (degrees) <±2

DC/AC efficiency(2): Half load 93.5 94.0 94.0 94.0 94.0 94.0
Full load 94.0 94.5 94.5 94.5 94.5 94.5

Neutral conductor sizing see Chapter 6.5

Output power upgradability


with temperature: At 25°C (%) 110
At 30°C (%) 105
At 40°C (%) 100

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 22
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

12 Technical data (250 to 800 kVA)

UPS Unit Rating 250 300 400 500 600 800


12.5 Reserve static switch
Nominal voltage (selectable) (V) 400 (380/415) 3Ph + n

Nominal frequency (selectable) (Hz) 50 (60)

Frequency range (selectable) (%) ±0.75 (1.5, 2.5, 6.0)

Voltage range (%) ±10

Maximum operating voltage (V) 480/277

Maximum overload capacity For 10 minutes (%) 125


For 1 minute (%) 150
For 600 milliseconds (%) 700
For 100 milliseconds (%) 1000

SCR I2t @ Tvj=130°C; 8.3-10ms (A2s) 320k 320k 1125k 1125k 4500k 4500k
ITSM @ Tvj=130°C; 10ms (A) 8k 8k 15k 15k 30k 30k

Fuse Rating (Vac/A) 660/500 660/500 660/1000 660/1000 660/1000 x2 660/1000 x2


Pre-arching I2t (A2s) 37k 37k 180k 170k 680k 680k
I2t @ 400Vac (A2s) 115k 115k 520k 520k 2080k 2080k

Transfer time when in synchro


(double conversion): Inverter to reserve (ms) <0.5
Reserve to inverter (ms) <0.5

Transfer time without synchro (ms) <20

Retransfer delay (sec) 5

12.6 System data

Maximum input power @400V, Recharge Mode (kVA) 348 418 557 696 835 1113

Heat dissipation: PFC Mode (kW) 17.3 19.4 25.9 32.4 38.8 51.8
Float Mode (kW) 41.7 55.7
Rapid recharge (kW) 18.6 21.0 28.0 35.0 42.0 56.0
Digital interactive (kW) 6.2 7.4 9.9 12.3 14.8 19.7

AC/AC efficiency(2): Half load double conv. (%) 91.5 92.0 92.0 92.0 92.0 92.0
Full load double conv. (%) 92.0 92.5 92.5 92.5 92.5 92.5
Digital Interactive (%) 97.0

Noise @ 1 metre as per ISO 3746 (dBA ± 2dBA) 68 68 70 72 76 76

Protection degree with open doors IP20

Mechanical dimensions: Height (mm) 1780 1780 1780 1780 1780 1780
Width (mm) 1620 1620 1620 2020 3270 3270
Depth (mm)(4) 858 858 858 858 858 858
No. of cabinets 1 1 1 1 2 2

Colour Frame (RAL scale) 7035


Bottom panel (RAL scale) 7035

Weight (net, ±2%) (kg) 1860 1860 2095 2495 4050 4050
Floor area (m )
2
1.39 1.39 1.39 1.73 2.80 2.80
Floor loading (kg/m )
2
1338 1338 1507 1442 1446 1446
Cable entry Bottom/Side
Access Front
Cooling Forced Ventilation

23 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

12 Technical data (250 to 800 kVA)

UPS Unit Rating 250 300 400 500 600 800

UPS Safety CE marking, IEC/EN 62040-1-2

EMC EN 50091-2

Surge withstand IEC/EN 61000-4-5, level 3

Performances and Test IEC/EN 62040-3

UPS classification (according to IEC/EN 62040-3) VFI - SS - 111

12.7 Environmental

Temperature: Storage (°C) -25/70


Operating (°C) 0/40
Max average daily (24hrs) (°C) 35
Maximum (8hrs) (°C) 40
Maximum relative humidity @ 20°C (non condensing) (%) up to 90
Elevation without derating (m) (-1.2% Pn every 100 m above 1000 m) 1000
12.8 Battery

Optimum battery temperature (°C) 15-25

DC power (kW) 213 254 339 423 508 677

Recommended no. cells: VRLA (5)


240
WET 240
NiCd 375

End of discharge voltage (V) 396

Current at end of discharge voltage (A) 538 645 855 1069 1283 1710

Battery current setting range (A) 15-80 15-80 20-110 25-135 25-160 30-210

(1) @ 234 cells and nominal output power;


(2) for tolerance see IEC/EN 60146-1-1or DIN VDE 0558;
(3) valid only in PFC Mode;
(4) including front handle; without handle 830 mm
(5) permitted number of cells = 234-246
(6) only with battery connected
(7) All units can supply loads with PF up to 0.8, leading or lagging, at full nominal output power. For the same ratings, loads with PF up to 0.9, leading or lag-
ging, can be supplied at full nominal output power with limitation in the maximum value of battery recharge current. Please contact Chloride Technical Support
for further details.
(8) Imax input can be deduced from the maximum input power @400V, recharge mode.
(9) Without battery discharge means 2V / cell.
(10) With nominal input voltage and battery connected

Note:
The data shown are typical and not definable in other ways; furthermore the data refer to 25°C ambient temperature and PF= 1 where not specified.
Not all the external data shown apply simultaneously and may be changed without prior warning.
If the options described in chapter 13 are added, the data shown in table 12 may vary. For test conditions and measurement tolerances not specified, refer to
the “Witness Test Report”.

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 24
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

13 Options
Where options described in this It shall also be possible to monitor the rectifier UPS version (available only up
chapter are added to the UPS, the data insulation resistance when the rectifier to 200kVA) shall limit the THDi to less
presented in the standard technical isolation is not present by taking the than 7%. The input power factor will
data tables may vary. Some options measurement when the input rectifier depend on the output load fraction.
may not be available contemporarily on switch is open or the rectifier is
the same UPS. switched off. 6 pulse 6 pulse +
7% filter
13.1 Parallel configurations 13.7 Battery Management Modules 5th harmonic 29 % 4%
(only upon request) 7th harmonic 5% 3%
See chapter 14.
With measuring modules connected 11th harmonic 7% 3%
13.2 Remote alarm unit to the battery blocks, enhanced 13th harmonic 1% 1%
battery management shall be possible
A remote alarm panel shall be available 17th harmonic 3% 2%
offering the following features:
to display important individual 19th harmonic 1% 1%
messages from the UPS. • Measurement of the condition of Total THDi 30 % 7%
Upon request, it shall be possible to each individual battery block by
display up to four UPS systems. The means of separate battery
length of the connecting cable must measuring modules (BMM) 13.12 12-pulse rectifier @ THDi < 5%
not exceed 300 m. (optional for 60 – 200kVA, standard
• Analysis of each battery block with from 250kVA).
13.3 External battery circuit breaker measurement of the minimum and
This version shall consist of two 6
This option shall include a fully rated maximum voltage values.
pulse rectifiers phase shifted by 30
circuit breaker and an additional degrees; with an additional inductive
auxiliary contact for monitoring its 13.8 Isolation transformer
reactance on both rectifier branches.
position. The circuit breaker shall be This option shall be a double wound This shall attenuate the 5th, 7th, 17th
housed in a wall-mounted box and transformer housed in a matching and 19th harmonics in order to achieve
designed for battery systems which cubicle. The transformer shall a THDi of approximately 5%. The 12-
are mounted on racks. Furthermore, incorporate an electrostatic screen as pulse rectifier shall be housed within
the circuit breaker shall serve as a standard. The option shall be used to the UPS cubicle. When this option is
safety element for the cross section of isolate the rectifier/output/reserve fitted (for 60 – 200kVA range), the
the power cable between UPS and the from the mains AC input. Starting from overall AC/AC efficiency shall be
remotely placed battery system. 250 kVA cable entry shall be from the reduced by 2.5%, the generated
top; smaller versions shall have entry acoustic noise increased by I dBA, the
13.4 Backfeed protection (only upon from the bottom. The transformer power factor in PFC Mode reduced to
request) cabinets do not include switching 0,90±0,02 and the input voltage
devices. This option may significantly tolerance is –10% @ 192 cells. The
This option shall prevent any potential
affect the reserve line inrush current, input inrush current shall be limited to
risk from electric shock on the UPS
influencing the sizing of the upstream <4Imax input.
input AC terminals in the event of
failure by the reserve static switch protection devices. For further
12 pulse +
SCR. The option shall include a contact information please contact the
5% filter
which activates an external isolating Chloride Technical Support; optional
low inrush current isolation transformers 5th harmonic 1%
device such as an electromechanical
relay. The external isolating device is not may be provided on request. 7th harmonic 1%
included in the option. Alternatively, it 11th harmonic 4%
shall be possible to incorporate this 13.9 Top cable entry
13th harmonic 2%
device inside the UPS cabinet. This option shall allow power cable 17th harmonic -
entry from the top of the UPS.
13.5 Additional RFI filters (only upon 19th harmonic -
request) 13.10 Dust filters Total THDi 5%
Feed-through RFl filters shall be This option shall improve the 13.13 Multiple Bus Synchronization
available housed in a matching cubicle. protection degree of the air entrance Module (MBSM)
They allow a reduction of the from IP20 to lP40 for specific
conducted emissions up to the Class B applications such as a dusty The synchronisation kit shall be used
of standard EN50091-2. environment. The filter shall be housed to synchronise UPS systems in order
in the UPS cubicle (IP20). to ensure perfect operation with
13.6 Battery leakage alarm CROSS system static switches. To
13.11 Input harmonic filters for 6 achieve this, all UPS must be
ln conjunction with the rectifier interconnected. The MBSM box allows
isolation transformer option, the pulse versions (only upon request)
for communication between up to six
battery leakage alarm shall monitor the The input current harmonic distortion UPS. For more than six UPS cascaded
insulation resistance on the DC bus. filter mounted within the 6 pulse MBSM boxes should be used.

25 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

13 Options
13.14 Empty battery cubicle 13.17 Customer interface board 13.21 PPVIS surveys Monitoring
Software
Matching empty battery cubicles shall It shall be possible to increase the
be available including: number of input/outputs described in In addition to full monitoring capability,
section 8.8 by the adding of an this powerful software connectivity
• Cubicle additional board. These input/outputs tool allows complete access to the
can be used to monitor smoke, fire UPS configuration parameters.
• Disconnecting means and water detectors, as specified by Therefore the user must attend a
• Connection terminals the user. Each board shall comprise: specialist training session with
Chloride Service Engineers before
Three cubicle sizes shall be available: • Four digital inputs (from voltage being granted access to PPVis.
free contacts)
Width Depth Height Weight The survey images as displayed below
(mm) (mm) (mm) (kg) • Two outputs - voltage free contacts supply the user with essential
Type A 820 858* 1780 220 (1A 230V AC/DC) information on the connected UPS:
Type B 1020 858* 1780 250
13.18 Telephone switch for LIFE.net State indication - power flux survey
Type C 1020 1058* 1980 350
The installation of the telephone
* including front handle; without switch for LIFE.net shall allow the user
handle 830 mm to use a telephone line normally
reserved for other purposes (e.g. fax
13.15 Empty options cubicle or telephone).
A matching cubicle shall be available 13.19 MopUPS Shutdown and
for customised applications such as: monitoring software
• Input/Output voltage matching The main function of MopUPS
transformers • Current state of components (UPS)
software shall be the safe shutdown of • Display of output voltage, UPS
• Customised distribution boards the operating system in the event of a performance and load currents
power failure. Other functions include: • Number of power failures
• Customised applications. • Battery cell voltage
1. Automatic communications for events;
e-mail, SMS, etc. • Available backup time
The options cubicle shall be available
in four sizes: 2. Saving to file of event log and status
information The oscilloscope - measuring of
Width Depth Height Weight 3. Viewing and monitoring of UPS in network or load conditions
(mm) (mm) (mm) (kg) realtime
4. Programmed system shutdown • Dual-carrier measurement of the
Type A 820 858* 1780 180 curves of input, output voltages or
5. Remote monitoring of UPS
Type B 1020 858* 1780 200 connected to network server using currents.
Type C 1420 858* 1780 250 Named Pipes or TCP/IP • Flexible definable trigger conditions
capable of being coupled with the
Type D 1020 1058* 1980 300
13.20 ManageUPS adapter most varied events, such as when
* including front handle; without a mains failure occurs
handle 830 mm This option shall include a complete
package (including slot card adapter) to
13.16 Use as Frequency Converter ensure monitoring and control of the
networked UPS through TCP/IP
90-NET may be programmed for use protocol. The adapter permits:
as a frequency converter (50Hz in –
60Hz out or 60Hz in – 50Hz out) for • UPS monitoring from NMS via
operations without a battery bank SNMP
connected. In this operational mode,
the data shown in tables 11 and 12 • UPS monitoring from PC via a Web
may vary (e.g. output overload browser.
capability). Please contact Chloride
• Dispatch of e-mail messages on
Technical Support for details.
occurrence of events

ManageUPS, in conjunction with


MopUPS, shall also permit safe
shutdown of the operating systems.

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 26
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

13 Options
Battery display - Recognition of 13.22 J-Bus protocol level systems such as Simatic S5, S7,
parasitic effects in the early stages Symadyn D, PC/PG and field units. The
(optional for single blocks) An optional kit shall ensure the following information shall be
compatibility of 90-NET with the J-Bus transmitted by 90-NET:
• Measuring of the condition of each protocol on RS485 port.
individual battery block shall be • Status of the unit
monitorable by means of separate 13.23 Profi Bus protocol
battery measuring modules (BMM) • Alarm information, information on
By installing a Profibus-DP connection faults
• By clicking the mouse the user may 90-NET shall be linked up to higher
analyse each battery block with level automatic systems. The Profibus • Voltage levels at UPS output
measurements of the minimum –DP bus system enables very fast
and maximum voltage values. cyclical data exchange between higher- • Control information

Compatibility Table
LIFE.net MopUPS ManageUPS PPVIS
LIFE.net No Yes Yes
MopUPS No Yes Yes*
ManageUPS Yes Yes Yes
PPVIS Yes Yes* Yes
* use LIFE.net port for MopUPS

14 Parallel configurations
The 90-NET series of uninterruptible Under normal operating conditions, power of the system using a non-
power supply systems shall be the power delivered to the load shall redundant parallel configuration
connectable in parallel for multi- be shared between the number of (redundancy coefficient = 0). In this
module configurations between units UPS units connected to the parallel case all connected UPS units shall
of the same rating. The maximum bus. In case of overload the configuration deliver the rated power, and in the
number of UPS in parallel may deliver Pov x N without transferring event of a unit failure or overload the
configuration shall be eight (seven for the load onto the reserve, where: system shall transfer the load to reserve.
systems with a centralised static
switch and for HFC systems). Pov = Max overload power of a A maximum of eight UPS may be
The parallel connection of UPS shall single UPS connected in parallel. There shall be
increase reliability and power. N = Number of UPS units in three alternative paralleling methods:
parallel. modular parallel, centralised parallel
Reliability. with COC and high fault clearance
If the installation requires more than In the event of failure by one of the (HFC) parallel mode.
one unit in redundant configuration the UPS units, the faulty unit shall be
power of each UPS should not be disconnected from the parallel bus and Performance features.
lower than Ptot/(N-1) where: the load shall be supplied from the The performance features of the
remaining units without any break in parallel system are related to the UPS
Ptot = Total load power supply continuity. systems employed. The distribution of
N = Number of UPS units in parallel the load is divided equally between the
1 = Minimum coefficient of Power. individual UPS systems.
redundancy It shall be possible to increase the

27 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

14 Parallel configurations
14.1 Modular

The UPS systems of the 90-NET series


shall be capable of operating in parallel U. V. W. U1. V1. W1. U. V. W. U1. V1. W1.
modular configuration. For this UPS 1 UPS 2 UPS n
purpose UPS systems of the same
rating shall be connected in parallel to
form multi-module configurations.
The parallel connection of UPS shall
either improve reliability, the total
output power, or both. Provided 90-NET
is supplied with the parallel kit option,
up to eight equal UPS units can be
operated in parallel for power upgrade
or increase of redundancy. This option
can also be added on at a later date.
The option shall consist of one BATT BATT

subassembly POB (Parallel Operation


Board) and 25 pole, screened data
lines to the neighbouring UPS
modules. A multi-module system
shall be controlled and monitored
automatically by controlling the
individual UPS systems.
The reserve lines and inverters
included in each UPS share the load.
The load sharing among the UPS Load
parallel system (“load on inverter”
mode) shall be achieved with a
tolerance of less than 5% at any
system load fraction (0 - 100%). Figure 6. Modular parallel systems (manual service bypass switch is not present
in 600 and 800kVA models, and has to be provided externally)
14.1.1 System bypass switches

A system bypass switch shall be


available as an option for the modular
parallel configuration. For parallel
systems including more than two UPS,
a system bypass switch must be
provided within the installation, U. V. W. U. V. W.

including two power disconnect UPS 1 UPS 2 UPS n COC


switches. The ratings available shall be: SQ2

Height Weight Depth Weight


(mm) (mm) (mm) (kg)
400 A 1780 620 858* 300
800 A 1780 620 858* 400
1600 A 1780 1020 858* 500
2500 A 1780 1020 858* 600
BATT BATT
* including front handle; without
handle 830 mm

14.2 Centralised parallel with COC


U2. V2. W2. N U2. V2. W2. N

The centralised paralleling architecture


Load
enables UPS with inhibited bypass to
be connected in parallel. Hereby the
reserve supply to the loads works with
one central equipment (COC).

Figure 7. Centralised parallel systems with COC

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 28
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

14 Parallel configurations
Now a single UPS block consists of the 14.4 COC monitoring and control Load/Bypass Switch
following subassemblies:
The COC shall incorporate the neces- This module displays alarms, load
• Rectifier sary controls, instruments and indica- voltage phase to neutral, current per
tors to allow the operator to monitor phase, frequency measurements,
• Microprocessor, IGBT inverter the system status and performance, percentage load capacity per phase
as well as take any appropriate action. and the peak factor lpk/Irms of each
• Static switch, inline to the inverter
phase of the load current. It is possible
Mimic panel to display the total time the load has
• Matching battery
The COC shall have a mimic panel with been supplied by inverter, by reserve
The centralised switch COC (common light emitting diodes (LEDs) to indicate and time on parallel.
output cubicle ) see Figure 7. The COC the following conditions, see Figure 8:
includes:

• Electronic static switch and UPS (A-H) normal operation green


reserve supply Reserve supply normal operation green
• Manual maintenance bypass Load static switch normal operation green
switch (switches are not included
in COC above 800A)
UPS (A-H) alarm green flashing
Centralised configuration offers maxi- Reserve supply alarm green flashing
mum flexibility in positioning UPS Load static switch alarm green flashing
blocks. Vector control ensures that dif-
ferent UPS blocks of a centralised paral-
lel system can be placed at different
localities. Power cables from the mains
and to loads may be of different lengths.

It shall be possible to modify the paral-


lel configuration of 90-NET from cen-
tralised to modular and vice versa (pro-
vided a COC is included in the system).
This modification may be done at any
time by simply disconnecting or con-
necting the COC to the parallel UPS.
COC
14.3 High Fault Clearance Parallel Figure 8.
Mode
Display
It shall be possible to allow simultane- A 40 character illuminated LCD (two
ous operation of both the UPS reserve lines x 20 characters) shall be provided
lines (within each UPS) and the com- to enable the operating parameters of
mon reserve line in the COC. Transfer the UPS to be monitored. The LCD
to reserve will therefore involve the messages shall be accessed by push
parallel operation of all the available buttons. The text shall be available in
reserve lines (both UPS and COC). As English, Italian, French, German, Spanish
a result of such a paralleling of reserve and Portuguese, selectable by the user.
static switches, the overall I2t capacity
of the system shall be multiplied by By using the appropriate user switches
four. The increased short circuit capac- it shall be possible to display the
ity of the high fault clearance parallel following:
mode of operation will result in
increased ability to clear faults down- UPS
stream from the UPS and hence This module shall display alarms and
greater overall selectivity. HFC parallel status for the connected UPS in the
mode shall only be feasible if all parallel system.
reserve lines originate from the same
Reserve Supply
distribution. All modules within the
This module shall display alarms,
HFC system (UPS and COC) will share
voltage phase to neutral and frequency
the load equally (provided that the
measurements.
installation is balanced respect to the
current distribution).

29 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

14 Parallel configurations
Signalling COC

Heading
Alarms/indications
EPO active System normal System test mode System in alarm

LIFE.net (optional)
Alarms/indications
Service active LIFE.net connection in progress Active LlFE.net connection

UPS
Alarms/indications
UPS (*) current limit UPS (*) shutdown imminent UPS (*) voltage and frequency irregular

UPS (*) in alarm

Reserve, Load
Alarms/indications
Backfeed active (option) Overload Static switch blocked on inverter
Bypass switch closed Reserve supply fault Static switch blocked on reserve
Load not supplied Reserve phase sequence error Static switch fault
Load on reserve Reserve frequency fault Reserve switch open
UPS (*) in alarm Reserve voltage high Overtemperature
Output switch open Reserve voltage low Out of synchronisation

(*) lndicates the UPS involved.

Help procedure

The LCD display shall provide assisted


start-up, shutdown, bypass and return
to normal routines.

Control push button

In the right part of the display there


shall be a further push button to
control the COC. This push button shall
enable the load to be transferred or re-
transferred from the inverter to
reserve or reserve to inverter
depending on the original condition.
The control shall incorporate a safety
feature to prevent inadvertent
operation.

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 30
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

14 Parallel configurations

14.5 COC Technical data Rating 400A 800A 1600A 3200A 4000A
Electrical data

Nominal current (A) 400 800 1600 3200 4000

Power @ 380V (kVA) 263 526 1052 2112 2640

Power @ 400V (kVA) 277 554 1107 2208 2760

Power @ 415V (kVA) 287 574 1149 2304 2880

Nominal voltage (selectable) (V) 400 (380/415)

Nominal frequency (selectable) (Hz) 50 (60)

Voltage range (%) ± 10


Frequency range (selectable) (%) ±0.75 (1.5, 2.5, 6)

Maximum operating voltage (V) 277 (480 PH-PH)

Maximum overload capacity for 10 minutes (%) 125 125 125 125 125
for 1 minute (%) 150 150 150 150 150
for 600 milliseconds (%) 700 700 500 500 500
for 100 milliseconds (%) 1000 1000 700 700 700

SCR I2t @ Tvj=130°C; 8.3-10ms (A2s) 320k 1125k


ITSM @ Tvj=130°C; 10ms (A) 8k 15k
Contact Chloride
Fuse Rating (Vac/A) 660/500 660/1000k Technical Support
Pre-arching I2t (A2s) 23.8k 142k
I2t @ 400Vac (A2s) 175k 630k

Efficiency (when on reserve) AC/AC (%) 99.5

Transfer time when in synchro lnverter to reserve (ms) <0.5


Reserve to inverter (ms) <0.5

Transfer time without synchro (ms) <20

Retransfer delay (s) 5

System data

Noise @ I metre as per ISO 3746 (dBA) 60 60 62 64 65

Protection degree with door open IP20

Mechanical dimensions Height (mm) 1780 1780 1780 1780 1980


Width (mm) 1020 1020 820 1020 1020
Depth (mm) 858* 858* 858* 858* 1058*
*including front handle; without handle 830/1030 mm

Switches: included included not included not included not included

No. of cabinets 1

Weight (kg) 350 400 400 500 650

Floor area (m2) 0.85 0.85 0.68 0.85 1.05

Floor loading (kg/m2) 412 471 588 588 619

Cable entry Top/Bottom/Side

Access Front

Ventilation Forced ventilation (active when SS is closed)

31 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

14 Parallel configurations

14.5 COC Technical data Rating 400A 800A 1600A 3200A 4000A

Environmental data

Temperature Operating temperature (° C) 0-40


Maximum average daily (24 hrs) (° C) 35
Maximum (8 hrs) (° C) 40

Maximum relative humidity @ 20°C (non condensing) (%) up to 90

Elevation without derating (m) (-1,2% Pnom every 100 m


above 1000 m) 1000

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 32
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

Planning and Installation

33 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

Planning and Installation

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 34
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

Planning and Installation

35 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

Planning and Installation

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 36
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

Planning and Installation

37 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

Planning and Installation

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 38
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

Notes

39 MKA4CAT0UK90NET/Rev. 13-12/2007/UK
CHLORIDE 90-NET
UPS Systems from 60 to 800 kVA

Notes

MKA4CAT0UK90NET/Rev. 13-12/2007/UK 40
Chloride UPS Systems HQ
WORLD HEADQUARTERS
Via Fornace 30
40023 Castel Guelfo (BO)
Italy

T +39 0542 632 111


F +39 0542 632 120
E enquiries@chloridepower.com

www.chloridepower.com

Closest Chloride Contact in Australia: Closest Chloride Contact in UAE:


Chloride Power Protection Chloride UPS Systems Middle East
Ground Floor Building 5, Office 104
16 Giffnock St, North Ryde Dubai Internet City - Dubai
NSW 2113 UAE
Australia PO Box 72536

T +61 2 9888 1266 T +971 4 391 3205


F +61 2 9888 1966 F +971 4 391 6803
E australia.sales@chloridepower.com E middleeast.sales@chloridepower.com

www.chloridepower.com/au www.chloridepower.com/middle-east

Closest Chloride Contact in UK: Closest Chloride Contact in USA:


Chloride Power Protection Chloride Power Protection
George Curl Way 27944 North Bradley Road
Southampton, Hampshire Libertyville
SO18 2RY IL 60048
United Kingdom USA

T +44 (0) 23 8061 0311 T +1 800 239 2257


F +44 (0) 23 8061 0852 F +1 800 833 6829
E uk.enquiries@chloridepower.com E usa.info@chloridepower.com

www.chloridepower.co.uk www.chloridepower.com/us

MKA4CAT0UK90NET

For a full list of contacts please visit our website at www.chloridepower.com

Certificate No. EMS 76732 Certificate No. FM 11043

You might also like