You are on page 1of 28

Aquatron

Automatic Water Stills
A4000 A4000D & A8000

Assembly and
operating instructions

Version 2.2

Downloaded from www.Manualslib.com manuals search engine


Contents

Location and Services 3

A4000 - Components, Assembly, Operation & Spares 4

A4000D - Components, Assembly, Operation & Spares 9

A8000 - Components, Assembly, Operation & Spares 14

Distillate Collection & Reservoir System 19



Connection of Aquatron Stills to Deionised and Pre-treated Water Supplies 20

Cleaning 22

Fault Finding 23

Circuit & Wiring Diagrams 24

The Aquatron Water Still complies with the


following European Directives:
89/336/EEC - E.M.C. DIRECTIVE
Amended by 92/31/EEC and 93/68/EEC
73/23/EEC - L.V.D. Amended by 93/68/EEC

Limitations of use
This product meets the applicable E.C. harmonised
standards for radio frequency interference and may
be expected not to interfere with, or be affected by
other equipment with similar qualifications. We
cannot be sure that other equipment used in its
vicinity will meet these standards and we cannot
guarantee that interference will not occur in practice.
Where there is a possibility that injury, damage or loss
might occur if equipment malfunctions due to radio
frequency interference, or for general advice before
use, please contact the Technical Service Department
of Bibby Scientific Ltd.

Downloaded from www.Manualslib.com manuals search engine


Location & Services 4. Drain
A waste water drain is required. It is important that the
In order to obtain the optimum performance from your new distance between the drain and the water still is kept as short
Aquatron careful consideration should be given to the intended as possible to reduce the possibility of pressure build-up.
location and the availability of services such as water, electricity Similarly, the drain pipe from the still should fall straight,
and drain. without any kinks or bends, to allow an unimpeded flow. It is
also recommended that the unit is connected to properly earth
Please study the following notes before commencing installation.
bonded water supplies and drainage systems.
Before Use
5. Storage Tank
If the equipment is not used in the manner described in this
A suitable reservoir, the WR20 for instance, is required for the
manual then its performance and operation will be impaired.
collection of the distillate. This should be positioned beneath
Aquatron water stills are designed to operate under the following the still ensuring that the distillate can flow into the reservoir
conditions: without hindrance.
❖ For indoor use only. 6. Maintenance
❖ Ambient temperature +5°C to +40°C. The location of the still should facilitate easy access for routine
❖ Altitude up to 2000m. cleaning and maintenance. With regards to the latter, it is
❖ Relative humidity not exceeding 80%. recommended that a space of at least 50cm be provided on the
❖ Mains supply voltage fluctuates not greater than ±10% of normal. right hand side of the water still cabinet. This is to allow the
❖ Over voltage Category II IEC60364-4-443. removal of the side cover and replacement of the heating
❖ Polluting degree 2 IEC664. element.
1. Bench Wall Mounting 7. Warranty
Aquatron models A4000 and A8000 can be either bench or Bibby Scientific Ltd warrants this instrument to be free from
wall mounted and a bracket is provided for the latter purpose. defects in material and workmanship, when used under normal
A gap of at least 50cm should be left at the right hand end of laboratory conditions, for a period of three (3) years. In the
the unit to allow access to the heating elements. event of a justified claim Bibby Scientific will replace any
For reasons of weight, models A4000D and A8000 are best defective component or replace the unit free of charge.
bench mounted, but if it is desired to elevate the unit then a This warranty does NOT apply if damage is caused by fire,
stout shelf should be used. accident, misuse, neglect, incorrect adjustment or repair,
damage caused by incorrect installation, adaptation,
2. Electricity Supply modification, fitting of non approved parts or repair by
N.B. The Aquatron Water Still is classified as unauthorised personnel.
“Permanently Connected Equipment” and should be
connected to the electricity supply by a qualified This Warranty does not include the heater element which
electrician in the manner described in the electrical is only guaranteed for up to 1000 hours in use.
installation section of this manual.
The Aquatron stills are available in three models, A4000,
A4000D & A8000.
A suitable supply for the A4000 is rated at 3kW, 220-240v,
50/60Hz~ single phase. A suitable supply for the A4000D &
A8000 is rated at 6kW, 220-240v, 50/60Hz~ single phase.
A4000 units should be connected to the mains supply via a
double pole 30mA Residual Current Breaker with over current
protection (RCBO) isolating circuit breaker rated at 15A.
A4000D and A8000 units should be connected to the mains
supply via a double pole 30mA Residual Current Breaker with
over current protection (RCBO) isolating circuit breaker rated at
32A.
If you have any doubts about the suitability of your supply,
consult a qualified electrician before installing your Aquatron
still.

3. Water Supply
A cold water supply is required for coolant and feed purposes.
This may be from the mains supply or a header tank having a
flow capacity of at least 1 litre/min. for the A4000 and 2 litres/
min. for the A8000 and A4000D. The pressure range should be
within 3-100 p.s.i. (0.2–7 x 105Nm-2).
If the feed water quality is poor and likely to contain particulate
matter, such as rust or silt, it is advisable to fit a pre-filter unit
before the still.

Downloaded from www.Manualslib.com manuals search engine


A4000
Fig. 1

4
6 7
Lid 8
9 10

3 11
1 2 12

13

14

15

End
Plate

16

20
17
24 23 22 21 19 18

List of Major Components – A4000

Item Description Part Item Description Part


no. number no. number

1 Perspex Screen M484 13 Solenoid Assembly A4000/SA


2 Boiler WBA 14 Mains Water Mini Valve Assembly 7001059 (S)
3 Funnel WF48 15 Reservoir Water Level Sensor WLS
4 Condenser WC48/M2 16 Distillate Outlet Pipe (Bench Mounted) –
5 Wall Mounting Bracket M510G 17 Cooling Water Pipe to Drain (16mm) –
6 Green ‘Mains On’ Indicator 700691 (S) 18 Heater Assembly A4000/HA
7 White ‘On/Off’ Switch 700988 (S) 19 Thermostat WT4
8 Amber ‘Reservoir Full’ Indicator 700987 20 Rotaflo Stopcock A4000/RCOCK
9 White ‘Clean’ Switch 700988 (S) 21 Distillate Outlet (Wall Mounted) –
10 Reservoir Pressure Switch WPS 22 Boiler Level Control WL48
11 Heaters Connector Terminal A4000/HTB 23 Boiler Plastic Coupling WBC1
12 Water Flow Sensor Assembly I/A4000HK/1 24 Boiler Retaining Spring 700007

Downloaded from www.Manualslib.com manuals search engine


A4000 Assembly 7. Take the boiler level control WL48 (Fig. 1, item 22). Remove the
end split nut and central part of the boiler plastic coupling (Item
Your Aquatron A4000 has been designed with ease of assembly 23) leaving the other split nut in place, and the internal seal
specifically in mind. Please study the installation diagram and the in the boiler level control. Ensure the Rotaflo stopcock is fully
enclosed DVD before commencing the installation. Follow the closed (screwed down).
sequence of instructions and do not connect the mains electricity 8. Take the 16mm earth spigot located inside the A4000 and
supply until directed. place the 16mm tubing part of it into a beaker of hot water for
1. From the outer packaging remove all the components including approximately 20 – 30 seconds; this will make the tubing more
the metal cabinet containing the glass boiler. supple. Connect the 16mm tubing to the boiler level control
(Item 22) drain connection (below the Rotaflo stopcock). Secure
2. Before unpacking the individual components, identify them on with a tie wrap.
the check list below:
9. Take the 1m length of 16mm hose from hose kit I/WH48/1/B.
A4000 Unit containing boiler.
Place one end into a beaker of hot water for approximately
Condenser – WC48/M2 20 – 30 seconds. Thread the tube through hole (Fig. 1, item
Heater – W48H 17) until approximately 300mm of tubing is inside the cabinet.
Boiler Level Control – WL48 Connect to the 16mm earth spigot and secure with a tie wrap.
Funnel – WF48 10. Pull the 16mm hose back out of the cabinet until a gap of
Reservoir Water Level Sensor – WLS approximately 5mm exists between the boiler level control and
the boiler connection.
Output Hose Assembly – I/A4000HK/2
Hose Kit – I/WH48/1/B 11. Place the boiler plastic coupling split nut and central part onto
the boiler connection. Connect the boiler level control to
Wall Mounting Bracket – M510G
the boiler, ensuring that the internal seal of the boiler plastic
3. Remove the perspex viewing screen (Fig. 1, item 1) from the coupling is fitted inside the boiler connection and the boiler
unit by lifting it up using the finger recess. Remove the internal level control connection. Tighten the boiler plastic coupling.
packaging carefully. Snip the temporary ties holding the boiler
12. Loosen the black cap on top of the boiler level control. Fit the
retaining springs (Item 24).
funnel into the top of the boiler level control and tighten the
4. Remove the end plate and lid by removing the retaining screws. black cap.
5. Ensure that the sealing O ring and the stabilising O ring are 13. Take the hose assembly I/A4000HK/2 and connect the end
correctly positioned on the vapour tube of the boiler. Fit the marked ‘2’ to the top connection of the condenser. Connect
condenser (Fig. 1, item 4) to the vapour tube ensuring that the the other end marked ‘3’ to the boiler level control.
distillate outlet faces the front and the two water connections
14. Identify the water flow sensor assembly (Fig. 1, item 12) inside
are parallel to the unit Fig 1a. When slight resistance is felt
the cabinet. Connect the red connector marked ‘1’ to the
when fitting the condenser, press down slightly on the top
bottom connection of the condenser. It may be necessary to
of the condenser until a gap of approximately 19mm exists
slightly twist the condenser to release any kinks in the water
between the condenser and the boiler.
sensor assembly.

Cooling water outlet 15. Remove the heater black cap and rubber ring from the boiler.
Place the black cap onto the heater until it is approximately
25mm from the electrical connectors end. Push the rubber ring
onto the heater and into the black cap.
Condenser
16. Fit the heater into the boiler and screw on the black cap. When
the black cap is tight push the heater through the black cap
until the end of the heater sits in the nodule at the end of the
boiler.
Do not overtighten the screw cap as this may cause the
Sealing o-ring boiler to break, or push the heater in too far as this may
break the nodule.

Vapour tube N E
Distillate
Outlet PCB
L
Stabilising o-ring

Heater
Relay Terminal
Blocks Heater
Fig. 1a lead

6. Take the 1m length of 8mm hose from hose kit I/WH48/1/B


and connect one end to the distillate outlet of the condenser
(Fig. 1a). Secure with a tie wrap. Pass the other end of the tube Thermostat
through the cabinet hole, Fig. 1, item 21 if to be wall mounted,
or hole, Item 16 if bench mounted.
Fig. 1b

Downloaded from www.Manualslib.com manuals search engine


17. Thread the two heater connectors through the hole into the The A4000 is classed as permanently connected equipment. The
electrical control compartment and connect to the heater earth spigots should pass a high current (ie. >200mA).
terminal block. Brown to Brown, Blue to Blue, (Fig. 1b).
The equipment is supplied with 1.5m of flexible, triple
SAFETY: It could be possible to mis-locate the heater core, circular cable to the following specification:
crimps on to the heater terminal block tags. Ensure 1.5mm², to BS 6500 or equivalent and <HAR> or BASEC
that the heater crimps are properly located onto approved.
the heater terminal block tags and fully locked on.
Connection to the mains electrical supply should be via a
Attempt to pull the crimp off the tag to ensure full
double pole 30mA Residual Current Breaker with Overcurrent
attachment.
protection (RCBO) isolating circuit breaker switch with a
18. Refit the end plate and lid. continuous current carrying capacity of 15A at 250V and
overcurrent of 15A.
19. Move the unit to its working location. If it is to be wall
mounted use the mounting bracket (Fig. 1, item 5). Ensure a DO NOT SWITCH ON ELECTRICAL SUPPLY.
space of at least 50cm to the right of the unit to allow access.
22. Connect the reservoir water level sensor WLS (Fig. 1, item 15) to
20. Connect the cold water supply to the mains water inlet. The the A4000 and secure with a tie wrap.
tubing selected should have a safe working pressure of at
Place the glass pressure bell in the collection reservoir, following
least equal to the pressure of the water supply and should be
the instructions given on page 19.
adequately secured with hose clips.
23. Operate the A4000 Waterstill as per Operating Instructions and
DO NOT TURN ON WATER SUPPLY
check for leaks.
21. THIS EQUIPMENT MUST BE EARTHED!
24. Fit the Perspex viewing screen
Carry out the electrical installation. This should only be carried
out by a suitably qualified electrician.

A4000 Installation Diagram


I/A4000HK/1 A4000 Installation Diagram
8mm Earth Spigot
I/A4000HK/2
I/WH48/1/B 16mm Earth Spigot
Reservoir
Water Level
Condenser Sensor

2
Electrics

Water Flow Switch Solenoid


1

Mains Water
Boiler Inlet Mini
Thermostat &
Thermostat Glass Valve

Funnel

Heater To Distillate
Reservoir

Boiler
Level
Control
3
16mm tubing x 1m - I/WH48/1/B

Rotaflo Stopcock To Drain

Thursday, 17 July 2014

Downloaded from www.Manualslib.com manuals search engine


A4000 Operation 13. To avoid excess wastage of coolant water, make further
adjustments to the mini valve assembly. Slowly reduce the flow
The following instructions apply to the A4000 water still where the rate until the flow control switch switches off the heater, then
water feed to the boiler is via the mains supply or a header tank. increase the flow until the power is restored.

1. Before switching on either the mains electricity or water supply, 14. Refit the Perspex screen.
identify the control switches and indicator lights on the front of
15. Safety Cut-Outs – All Aquatron water stills are protected by
the cabinet.
the following safety devices.
Green Light – When illuminated this shows that there is mains
Flow Control Switch – Monitors the flow of coolant water
supply voltage to the unit. Under no circumstances should the
into the still and shuts off the heating element if the flow is
cabinet end-panel be removed when this light is illuminated.
insufficient.
White ‘On/Off’ Switch – This is the primary switch for
Thermostat Cut-Out – In normal operation the water within
controlling water and electricity inside the still. The switch
the glass will be at 100°C. In single fault conditions, i.e. in
illuminates when pressed in the ON position.
the event of water supply failure, the content will increase
Amber Light – When illuminated, this indicates that the to 112°C where upon a resettable thermostat will operate.
distillate collection reservoir is full as detected by the level Once switched, the thermostat has to be manually reset. This
control. is achieved by unscrewing the black knob located inside the
cabinet and pressing the reset button.
White ‘Clean’ Light – This shuts off the heating element but
allows water to flow into the boiler when the still is being Reservoir Control – Is positioned in the collection reservoir
commissioned or cleaned. When pressed in the CLEAN position and switches off both the electricity and water supplies when
the switch illuminates. the reservoir is full of distillate water. The water supply is shut
off after around 7 minutes after the reservoir is full to allow the
2. Carefully check the following:
heating element to cool.
The appropriate electricity, water and drain services have been
provided. If in doubt, consult the LOCATION & SERVICES It is recommended that the operation of the flow switch and
SECTION of this manual. reservoir control is checked on a regular basis.

The ON/OFF switch on the control panel is in the OFF position. a. Simulation of Mains Water Supply Failure
Turn off the mains water supply at the tap. This should switch
The CLEAN switch is pressed in the CLEAN position.
off the heating element. Turning the tap on again will switch
The Rotaflo stopcock on the boiler level control is closed. the heater on.

The reservoir water level sensor is fitted to the distillate b. Simulation of Reservoir Full Condition
collection vessel. Lower the glass pressure bell of the reservoir water level sensor
The dummy shorting plug is fitted to the boiler level control DIN into the distillate to a depth of 150mm. This will switch off the
socket on the cabinet. heating element immediately and the cooling water after 7
minutes. Raising the bell will cause both to be switched back
3. Ensure all earth leads are connected to the earth point. on.
4. Check all glassware for any damage. 16. Switching Off – Push the CLEAN switch to the ON position.
5. Switch on the electricity supply – the green light illuminates. Wait until the residual heat contained in the heating element
has dispersed and no boiling is evident. Turn off water supply.
6. Press the ON/OFF switch to the ON position – the switch will Push ON/OFF switch to OFF position. Isolate from mains
illuminate. electricity supply.
7. Recheck that the CLEAN switch is in the CLEAN position and
illuminated.
8. Turn on the mains water supply and using the mini valve
assembly, adjust the flow rate to approximately 1 litre/min. This
can be achieved by observing the drain water from the boiler
level control and adjusting the mini valve assembly accordingly.
9. Check for water leaks.
10. Observe the boiler now filling with water to cover the heating
element. When water has reached the pre-set limit, the excess
will discharge to drain. Check the water drains freely and does
not back up into the boiler level control.
11. Switch the CLEAN button off by pressing it a second time. The
switch light goes out.
12. The heater will now warm up and eventually run at a red glow.
If the flow rate is insufficient, the heater will not switch on. This
will require adjustment of the mini valve assembly to be opened
further. After about 2 – 3 minutes of operation distilled water
will emerge from the outlet pipe falling into the collection
reservoir.

Downloaded from www.Manualslib.com manuals search engine


A4000 Spares
Boiler WB4
Funnel WF48
Condenser WC48/M2
‘Mains On’ Green Indicator 700691(S)
‘On/Off’ White Switch 700988(S)
‘Reservoir Full’ Amber Indicator 700987
‘Clean’ White Switch 700988(S)
Reservoir Pressure Switch WPS
Heater Terminal Block A4000/HTB
Solenoid Assembly A4000/SA
Water Flow Sensor Assembly and Hoses I/A4000HK/1
Condenser to Boiler level control Hose (Output Hose Assembly) I/A4000HK/2
Reservoir Water Level Sensor WLS
Mains Water Mini Valve Assembly 7001059(S)
Thermostat Glass Tube WTT48
Thermostat WT4
Boiler Level Control WL48
Boiler Plastic Coupling WBC1
Heater Assembly A4000/HA
Heater Assembly 220V A4000/HA220
Boiler Retaining Spring 700007
Rotaflow Stop Cock Assembly A4000/RCOCK
6 Way Electrical Terminal Block A4000/ETB
Ceramic Terminal Block A4000/CTB
5 DIN Socket Assembly A4000/DIN
Boiler Vapour Tube Sealing O Ring I/M502
Boiler Vapour Tube Stabilising O Ring I/QR38/24
Relay Assembly A4000/RA
PCB 700804(ES)
Distillate Output and Boiler Level Control Drain Hose Kit I/WH48/1/B
Wall Mounting Bracket M510G
Black Phenolic Screw Cap I/QC38/25

Downloaded from www.Manualslib.com manuals search engine


A4000D
Fig. 2

5
6
7
Lid 8
9

4 10
3
2
11

12
1

13

14

End
Plate

25
15

24 23 22 21 20 19 16

18 17

List of Major Components – A4000D

Item Description Catalogue Item Description Catalogue


no. number no. number

1 Perspex Screen M484 14 Reservoir Water Level Sensor WLS


2 Boiler (2 off) WB4 15 Distillate Outlet Pipe –
3 Funnel WF48 16 Drain Pipe from W4L2A –
4 Condenser (2 off) WC48/M2 17 Cooling Water Pipe to Drain (8mm) –
5 Green ‘Mains On’ Indicator 700691(S) 18 Cooling Water Pipe to Drain (16mm) –
6 White ‘On/Off’ Switch 700988(S) 19 Thermostat (2 required) WT4
7 Amber ‘Reservoir Full’ Indicator 700987 20 Heater Assembly (2 required) A4000/HA
8 White ‘Clean’ Switch 700988(S) 21 Boiler Level Control (rear) W4L2A
9 Reservoir Pressure Switch WPS 22 Rotaflo Stopcock A4000/RCOCK
10 Terminal Strip for Heaters A4000/HTB 23 Boiler Level Control (front) WL48
11 Water Flow Sensor Assembly I/A4000DHK/1 24 Boiler Plastic Coupling WBC1
12 Solenoid Assembly A4000/SA 25 Retaining Springs 7000007
13 Mains Water Inlet Valve Assembly 7001059(S)

Downloaded from www.Manualslib.com manuals search engine


A4000D Assembly 9. Fit the condenser to the vapour tube of the rear boiler ensuring
that the distillate outlet faces the front and the two water
Your Aquatron A4000D has been designed with ease of assembly connections are parallel to the unit. When slight resistance is
specifically in mind. Please study the installation diagram and the felt when fitting the condenser, press down slightly on the top
enclosed DVD before commencing the installation. Follow the of the condenser until a gap of approximately 19mm exists
sequence of instructions and do not connect the mains electricity between the condenser and the boiler.
supply until directed.
10. Pass the free end of the 8mm tubing through the hole (Fig. 2,
1. From the outer packaging remove all the components including item 15).
the metal cabinet containing the glass boiler.
11. Take the rear Boiler Level Control W4L2A and connect the 8mm
2. Before unpacking the individual components, identify them on x 300mm vinyl tubing from hose kit I/WH48/3/B to the side arm
the check list below: and tie wrap (Fig. 2b). Remove the end split nut and central
part of the boiler plastic coupling leaving the other split nut
A4000D Unit containing 2 boilers.
on, and the internal seal in the boiler level control. Ensure the
Condenser – WC48/M2 x2 Rotaflo stopcock is fully closed (screwed down).
Heater – W48H x2
12. Connect the tubing of the 8mm earth spigot hose assembly to
Boiler Level Control (Front) – WL48 the drain of the rear boiler level control W4L2A and tie wrap.
Boiler Level Control (Rear) – W4L2A
13. Take the 8mm x 1m vinyl tubing from hose kit I/WH48/3/B and
Funnel – WF48 connect to the 8mm earth spigot hose assembly in step 12 and
Reservoir Water Level Sensor – WLS tie wrap. Pass the free end of the 8mm tubing through the hole
Hose Kit – I/WH48/3/B (Fig. 2, item 16).

3. Remove the perspex viewing screen (Fig. 2, item 1) from the 14. Place the boiler plastic coupling split nut and central part onto
unit by lifting it up using the finger recess. Remove the internal the rear boiler connection. Connect the boiler level control to
packaging carefully. Snip the temporary ties holding the boiler the boiler, ensuring that the internal seal of the boiler plastic
retaining springs (Item 25). coupling is fitted inside the boiler connection and the boiler
level control connection. Tighten the boiler plastic coupling.
4. Remove the cabinet end plate and lid by removing the retaining
screws. 15. Connect the plug of the rear boiler level control to the DIN
socket connector.
5. Withdraw the metal thermostat probe (Fig. 2, item 19) from the
glass tube inside the front boiler.
3 Fig 2b: Rear
6. Remove the front boiler by releasing the retaining springs. To boiler
level
socket
7. Ensure that the sealing O ring and the stabilising O ring are
correctly positioned on the vapour tube of the rear boiler Water
(Fig 2a). Vent pipe flow
sensor
assembly
 Condenser and hoses
distillate
outlet tube 1
Cooling water outlet
Side arm Rotaflo
2 Stopcock

Lower drain
Condenser outlet

8mm Earth spigot


hose assembly

To drain
W4L2A

Sealing o-ring
From distillate of first condenser

16. Refit the front boiler. Refit the thermostat probe removed in
Vapour tube step 5.
Distillate 17. Fit the condenser to the front boiler vapour tube ensuring
Outlet
that the distillate outlet faces the front and the two water
connections are parallel to the unit. When slight resistance is
Stabilising o-ring felt when fitting the condenser, press down slightly on the top
of the condenser until a gap of approximately 19mm exists
between the condenser and the boiler.
18. Connect the free end of the 8mm x 300mm tubing connected
Fig. 2a to the rear boiler level control side arm, to the distillate outlet of
the front condenser (Fig. 2c).
19. Take the front Boiler Level Control WL48, remove the end
8. Select 8mm tubing x 1m from hose kit I/WH48/3/B and connect
split nut and central part of the boiler plastic coupling leaving
one end to the distillate outlet connection (Bottom) of one of
the other split nut on, and the internal seal in the boiler level
the condensers (Fig. 2a). Secure with a tie wrap.
control. Ensure the Rotaflo stopcock is fully closed (screwed
down).

10

Downloaded from www.Manualslib.com manuals search engine


Fig. 2c 3 connections onto the heater terminal block. Brown to Brown,
Front Blue to Blue (Fig. 2d).
4
SAFETY: It could be possible to mis-locate the heater
crimps on to the heater terminal block tags. Ensure that
Water flow the heater crimps are properly located onto the heater
sensor
Vent assembly terminal block tags and fully locked on. Attempt to pull
pipe
Distillate To drain the crimps off the tags to ensure full attachment.
1

2
Rotaflo N E
stopcock

5 PCB L
Heater lead (back)
16mm Earth spigot
hose assembly
Heater
To drain Relay
Terminal
WBC1 Blocks
Outlet of
WL48 To W4L2A level control Relay
level control
Heater
lead
20. Take the 16mm earth spigot and place the 16mm tubing part of (front)
it into a beaker of hot water for approximately 20 – 30 seconds;
Thermostat
this will make the tubing more supple. Connect the 16mm (Rear)
tubing to the front boiler level control drain connection (below
the Rotaflo stopcock). Secure with a tie wrap.
Thermostat
21. Take the 1m length of 16mm hose from hose kit I/WH48/3/B. (Front)
Place one end into a beaker of hot water for approximately
20 – 30 seconds. Thread the tube through the hole (Fig. 2, item
18) until approximately 300mm of tubing is inside the cabinet. Fig. 2d
Connect to the 16mm earth spigot and secure with a tie wrap.
22. Pull the 16mm hose back out of the cabinet until a gap of 31. Refit the end plate and lid.
approximately 5mm exists between the boiler level control and
32. Move the unit to its working location. Ensure a space of at least
the boiler connection.
50cm to the right of the unit to allow access.
23. Place the boiler plastic coupling split nut and central part
33. Connect the cold water supply to the mains water inlet. The
onto the boiler connection. Connect the boiler level control to
tubing selected should have a safe working pressure of at
the boiler, ensuring that the internal seal of the boiler plastic
least equal to the pressure of the water supply and should be
coupling is fitted inside the boiler connection and the boiler
adequately secured with hose clips.
level control connection. Tighten the boiler plastic coupling.
DO NOT TURN ON WATER SUPPLY
24. Locate the tube assemblies inside the cabinet and connect the
numbered connectors as follows: 34. THIS EQUIPMENT MUST BE EARTHED!
1 – Bottom connection of rear condenser. Carry out the electrical installation. This should only be carried
2 – Bottom connection of front condenser. out by a suitably qualified electrician.
3 – Top connection of rear condenser. The A4000D is classed as permanently connected equipment.
4 – Top connection of front condenser. The earth spigots should pass a high current (ie. >200mA).
5 – Front Boiler Level Control. The equipment is supplied with 1.5m of flexible, triple
core, circular cable to the following specification:
25. Pass the remaining length of 8mm tubing through hole (Fig. 2,
4.0mm², to BS 6500 or equivalent and <HAR> or BASEC
item 17).
approved.
26. Loosen the black cap on the boiler level control. Fit the funnel
Connection to the mains electrical supply should be via a
into the top of the boiler level control and tighten the black
double pole 30mA Residual Current Breaker with Overcurrent
cap.
protection (RCBO) isolating circuit breaker switch with a
27. Remove the heater black cap and rubber ring from the rear continuous current carrying capacity of 30A at 250V and
boiler. Place the black cap onto one of the heaters until it is overcurrent of 30A.
approximately 25mm from the electrical connectors end. Push
These devices should be sited near to the equipment and clearly
the rubber ring onto the heater and into the black cap.
marked ‘Disconnect device for Aquatron water still’
28. Fit the heater into the boiler and screw on the black cap. When
DO NOT SWITCH ON ELECTRICAL SUPPLY.
the black cap is tight push the heater through the black cap
until the end of the heater sits in the nodule at the end of the 35. Connect the reservoir water level sensor WLS (Fig. 2, item 14) to
boiler. the A4000D and secure with a tie wrap. Place the glass pressure
bell in the collection reservoir, following the instructions given
Do not overtighten the screw caps as this may cause the
on page 19.
boiler to break, or push the heaters in too far as this may
break the nodule. 36. Operate the A4000D Waterstill as per Operating Instructions
and check for leaks.
29. Repeat steps 27 & 28 for front heater.
37. Fit the Perspex viewing screen.
30. Pass the electrical cables of the heaters up into the electrical
control compartment via the two orifices. Push the spade

11

Downloaded from www.Manualslib.com manuals search engine


A4000D Installation Diagram
A4000D Installation Diagram
I/A4000DHK/1
8mm Earth Spigot
I/A4000DHK/2

I/WH48/3/B
16mm Earth Spigot
I/WH48/3/B

3 Reservoir
Water Level
4 Sensor

To Boiler
Level Socket Electrics

Water Flow Switch Solenoid

1
2
Mains Water
Inlet Mini
Rear Thermostat and Valve
Front Boiler Thermostat Glass
Boiler

To Distillate
Reservoir

Restrictor
Heater
Second Stage
Boiler Level Control 8mm Earth Spigot
Boiler
Level To Drain
Funnel Control 5
8mm tubing x 1m - I/WH48/3/B
To Drain
16mmRotaflow
tubing x 1m Stopcock
- I/WH48/3/B

Rotaflo Stopcock

A4000D Operation The CLEAN switch is pressed in the ON position.


The Rotaflo stopcocks on the front and rear boiler level controls
The following instructions apply to the A4000D water still where are closed.
the water feed to the boiler is via the mains supply or a header
tank. The float switch on the rear boiler level control W4L2A is set
at the factory. However, check that this has not been disturbed
1. Before switching on either the mains electricity or water supply, during transit. A rough check is that the distance from the top
identify the control switches and indicator lights on the front of of the large screw cap of the W4L2A to the top of the glass
the cabinet. guide tube should be approximately 15-20mm (Fig 2e).
Green Light – When illuminated this shows that there is mains
supply voltage to the unit. Under no circumstances should the 15 - 20mm
cabinet end-panel be removed when this light is illuminated.
White ‘On/Off’ Switch – This is the primary switch for
controlling water and electricity inside the still. The switch
To boiler level
illuminates when pressed in the ON position. socket
Amber Light – When illuminated, this indicates that the
distillate collection reservoir is full as detected by the level
Guide
control. tube
White ‘Clean’ Light – This shuts off the heating element but
allows water to flow into the boiler when the still is being
Hose
commissioned or cleaned. When pressed in the CLEAN position assembly 2
the switch illuminates.
2. Carefully check the following:
The appropriate electricity, water and drain services have been Float switch
provided. If in doubt, consult the LOCATION & SERVICES
SECTION of this manual. Distillate feed
from front still To drain
The ON/OFF switch on the control panel is in the OFF position. Fig 2e

12

Downloaded from www.Manualslib.com manuals search engine


The reservoir water level sensor is fitted to the distillate off around 7 minutes after the reservoir is full to allow the
collection vessel. heating element to cool.
The dummy shorting plug is fitted to the boiler level control DIN It is recommended that the operation of the flow switch and
socket on the cabinet. reservoir control is checked on a regular basis.
3. Ensure all earth leads are connected to the earth point. a. Simulation of Mains Water Supply Failure
4. Check all glassware for any damage. Turn off the mains water supply at the tap. This should switch
off the heating element. Turning the tap on again will switch
5. Switch on the electricity supply – the green light illuminates. the heater on.
6. Press the ON/OFF switch to the ON position – the switch will b. Simulation of Reservoir Full Condition
illuminate.
Lower the glass pressure bell of the reservoir water level sensor
7. Recheck that the CLEAN switch is in the ON position and into the distillate to a depth of 150mm. This will switch off the
illuminated. heating element immediately and the cooling water after 7
8. Turn on the mains water supply and using the mini valve minutes. Raising the bell will cause both to be re-supplied.
assembly, adjust the flow rate to approximately 2 litre/min. 16. Switching Off – Push the CLEAN switch to the ON position.
This can be achieved by observing the drain water from the Wait until the residual heat contained in the heating element
boiler level control and adjusting the mini valve assembly has dispersed and no boiling is evident. Turn off water supply.
accordingly. Push ON/OFF switch to OFF position. Isolate from mains
9. Check for water leaks. electricity supply.

10. Observe that the front boiler is now filling with water to cover
the heating elements. When the water has reached the pre-set
limit, the excess will discharge to drain. Check the water drains
freely and does not back up into the boiler level control.
A4000D Spares
11. Switch the CLEAN button off by pressing it a second time. The Boiler WB4
switch light goes out. Funnel WF48
The heater on the front boiler will now warm up and eventually Condenser WC48/M2
run at a red glow. After a short time distilled water will emerge ‘Mains On’ Green Indicator 700691(S)
from the outlet pipe. This should feed into the empty rear boiler
‘On/Off’ White Switch 700988(S)
via the rear boiler level control WL42A.
‘Reservoir Full’ Amber Indicator 700987
12. Allow the rear boiler to fill with single distilled water (for
approximately 20 – 30 minutes), keeping an eye on the level. ‘Clean’ White Switch 700988(S)
Note that the heater of the second stage only comes on when Reservoir Pressure Switch WPS
the level of single distilled water in the rear boiler is at about Heater Terminal Block A4000/HTB
the equator. It may be necessary to adjust the level of the float
switch of the rear boiler level control (WL42A) to achieve this Solenoid Assembly A4000/SA
condition. Water Flow Sensor Assembly and Hoses I/A4000DHK/1
Lifting the guide tube increases the level at which the heating Reservoir Water Level Sensor WLS
element will switch on. Mains Water Mini Valve Assembly 7001059(S)
Lowering the guide tube decreases the level at which the Thermostat Glass Tube WTT48
element will switch on. Thermostat WT4
Double distilled water ultimately flows from outlet pipe (Fig. Boiler Level Control (Front) WL48
2, item 15). This should fall away from the still with no kinks, Boiler Level Control (Rear) W4L2A
restrictions or U bends.
Boiler Plastic Coupling WBC1
13. To avoid excess wastage of coolant water, make further
Heater Assembly A4000/HA
adjustments to the mini valve assembly. Slowly reduce the flow
rate until the flow control switch switches off the heater, then Heater Assembly 220V A4000/HA220
increase the flow until the power is restored. Boiler Retaining Spring 700007
14. Safety Cut-Outs – All Aquatron water stills are protected by Condenser to Boiler Level Control Assembly I/A4000DHK/2
the following safety devices. Rotaflow Stopcock Assembly A4000/RCOCK
Flow Control Switch – Monitors the flow of coolant water Relay Assembly A4000/RA
into the still and shuts off the heating element if the flow is
PCB 700804(ES)
insufficient.
6 Way Electrical Terminal Block A4000/ETB
Thermostat Cut-Out – In normal operation the water within
Ceramic Terminal Block A4000/CTB
the glass will be at 100°C. In single fault conditions, i.e. in
the event of water supply failure, the content will increase to 5 DIN Socket Assembly A4000/DIN
112°C where upon a resettable thermostat will operate. Once Boiler Vapour Tube Sealing O Ring I/M502
switched, the thermostat has to be manually reset. This is
Boiler Vapour Tube Stabilising O Ring I/QR38/24
achieved by unscrewing the black knob located inside the
cabinet and pressing the reset button. 4 DIN Socket Assembly A4000D/DIN

Reservoir Control – Is positioned on the collection reservoir Distillate Output and Boiler Level
and switches off both the electricity and water supplies when Control Drain Hose Kit I/WH48/3/B
the reservoir is full of distillate water. The water supply is shut Black Phenolic Screw Cap I/QC38/25

13

Downloaded from www.Manualslib.com manuals search engine


A8000
Fig. 3

6 8
7 9
Lid
10

11
3
2
12

1
13

14

15

End
Plate

16
25 24 23 22 21 20 19 17

18

List of Major Components – A8000


Item Description Catalogue Item Description Catalogue
no. number no. number

1 Perspex Screen M484 14 Mains Water Inlet Valve Assembly 7001059(S)


2 Boiler WB8 15 Reservoir Water Level Sensor WLS
3 Funnel WF48 16 Distillate Outlet Pipe (Bench Mounted) –
4 Condenser (2 off) WC48/M2 17 Cooling Water Pipe to Drain (8mm) –
5 Wall Bracket M510G 18 Cooling Water Pipe to Drain (16mm) –
6 Green ‘Mains On’ Indicator 700691(S) 19 Thermostat WT8
7 White 'On/Off' Switch 700988(S) 20 Heater Assembly (2 Required) A4000/HA
8 Amber ‘Reservoir Full’ Indicator 700987 21 Rotaflo Stopcock A4000/RCOCK
9 White ‘Clean’ Switch 700988(S) 22 Distillate Outlet Pipe (Wall Mounted) –
10 Reservoir Pressure Switch WPS 23 Boiler Level Control WL48
11 Terminal Strip for Heaters A4000/HTB 24 Boiler Plastic Coupling WBC1
12 Water Flow Sensor Assembly I/A8000HK/1 25 Retaining Springs 7000007
13 Solenoid Assembly A4000/SA

14

Downloaded from www.Manualslib.com manuals search engine


A8000 Assembly Connect number 2 to the lower water inlet of the condenser.
Connect number 4 to the upper water outlet of the condenser
Your Aquatron A8000 has been designed with ease of assembly (Fig. 3b).
specifically in mind. Please study the installation diagram and the  4
enclosed DVD before commencing the installation. Follow the
sequence of instructions and do not connect the mains electricity
3
supply until directed.
1. From the outer packaging remove all the components
including the metal cabinet containing the glass boiler.
2. Before unpacking the individual components, identify them on
the check list below:
2 1
A8000 Unit containing boiler.
Condenser – WC48/M2 x2
Heater – W48H x2 5
Boiler Level Control – WL48
Funnel – WF48
Reservoir Water Level Sensor – WLS
Hose Kit – I/WH48/2/B
Wall Mounting Bracket – M510G Fig. 3b
3. Remove the perspex viewing screen (Fig. 3, item 1) from the
unit by lifting it up using the finger recess. Remove the
internal packaging carefully. Snip the temporary ties holding 8. Fit the second condenser (Fig. 3, item 4) to the right hand
the boiler retaining springs (Item 25). vapour tube ensuring that the distillate outlet faces the front
and the two water connections are parallel to the unit. When
4. Remove the cabinet end plate and lid by removing the
slight resistance is felt when fitting the condenser, press down
retaining screws.
slightly on the top of the condenser until a gap of
5. Ensure that the sealing O rings and the stabilising O rings are approximately 19mm exists between the condenser and the
correctly positioned on the vapour tubes of the boiler. boiler.

 9. Looking inside the cabinet, identify the vinyl tubing assemblies


Cooling water outlet
fitted with numbered screw thread connectors. Make the
following connections:
Connect number 1 to the lower water inlet of the condenser.

Condenser Connect number 3 to the upper water outlet of the condenser


(Fig. 3b).
10. From the hose kit I/WH48/2/B take the 1m length of 8mm
tubing fitted with the T piece.
11. Connect the 180mm length of tubing from the T piece to the
Sealing o-ring distillate outlet of the condenser on the left hand side. Secure
with a tie wrap.
12. Connect the 100mm length of tubing from the T piece to the
distillate outlet of the condenser on the right hand side.
Vapour tube Secure with a tie wrap.
Distillate 13. Pass the free end of the tubing through:
Outlet
The cabinet base (Fig. 3, item 22) if wall mounted.
Stabilising o-ring The cabinet side (Fig. 3, item 16) if bench mounted.
14. Take the boiler level control WL48 (Fig. 3, item 23). Remove
the end split nut and central part of the boiler plastic coupling
(Item 24) leaving the other split nut on, and the internal seal
Fig. 3a in the boiler level control. Ensure the Rotaflo stopcock is fully
closed (screwed down).
6. Fit one of the condensers (Fig. 3, item 4) to the left hand 15. Take the 16mm earth spigot and place the 16mm tubing part
vapour tube ensuring that the distillate outlet faces the front of it into a beaker of hot water for approximately 20 – 30
and the two water connections are parallel to the unit. When seconds; this will make the tubing more supple. Connect the
slight resistance is felt when fitting the condenser, press down 16mm tubing to the boiler level control (Item 23) drain
slightly on the top of the condenser until a gap of connection (below the Rotaflo stopcock). Secure with a tie
approximately 19mm exists between the condenser and the wrap.
boiler (Fig. 3a).
16. Take the 1m length of 16mm hose from hose kit I/WH48/2/B.
7. Looking inside the cabinet, identify the vinyl tubing assemblies Place one end into a beaker of hot water for approximately 20
fitted with numbered screw thread connectors. Make the – 30 seconds. Thread the tube through hole (Fig. 3, item 18)
following connections: until approximately 300mm of tubing is inside the cabinet.
Connect to the 16mm earth spigot and secure with a tie
wrap.

15

Downloaded from www.Manualslib.com manuals search engine


17. Pull the 16mm hose back out of the cabinet until a gap of 28. THIS EQUIPMENT MUST BE EARTHED!
approximately 5mm exists between the boiler level control and
Carry out the electrical installation. This should only be carried
the boiler connection.
out by a suitably qualified electrician.
18. Place the boiler plastic coupling split nut and central part onto
The A8000 is classed as permanently connected equipment.
the boiler connection. Connect the boiler level control to the
The earth spigots should pass a high current (ie. >200mA).
boiler, ensuring that the internal seal of the boiler plastic
coupling is fitted inside the boiler connection and the boiler The equipment is supplied with 1.5m of flexible, triple core,
level control connection. Tighten the boiler plastic coupling. circular cable to the following specification:
4.0mm², to BS 6500 or equivalent and <HAR> or BASEC
19. Loosen the black cap on the boiler level control. Fit the funnel
approved.
into the top of the boiler level control and tighten the black
cap. Connection to the mains electrical supply should be via a
double pole 30mA Residual Current Breaker with Overcurrent
20. Connect the tubing connector number 5 to the boiler level
protection (RCBO) isolating circuit breaker switch with a
control (Fig 3b).
continuous current carrying capacity of 30A at 250V and
21. Take the remaining length of 8mm tubing from the 8mm earth overcurrent of 30A.
spigot and feed through the hole (Fig. 3, item 17).
These devices should be sited near to the equipment and
22. Unscrew the two black plastic screw caps and rubber rings clearly marked ‘Disconnect device for Aquatron water still’
from the boiler. Place the black caps onto the heaters until
DO NOT SWITCH ON ELECTRICAL SUPPLY.
they are approximately 25mm from the electrical connectors
end. Push the rubber ring onto the heaters and into the black 29. Connect the reservoir water level sensor WLS (Fig. 3, item 15)
cap. to the A8000 and secure with a tie wrap. Place the glass
pressure bell in the collection reservoir, following the
23. Fit the heaters into the boiler and screw on the black caps.
instructions given on page 19.
When the black caps are tight push the heaters through the
black caps until the end of the heaters sit in the nodules at the 30. Operate the A8000 Waterstill as per Operating Instructions
end of the boiler. and check for leaks.
Do not overtighten the screw caps as this may cause the 31. Fit the Perspex viewing screen.
boiler to break, or push the heaters in too far as this
may break the nodule.
24. Thread the four heater connectors through the holes into the
electrical control compartment and connect to the heater
terminal blocks. Brown to Brown, Blue to Blue (Fig. 3c).
SAFETY: It could be possible to mis-locate the heater
crimps on to the heater terminal block tags. Ensure that
the heater crimps are properly located onto the heater
terminal block tags and fully locked on. Attempt to pull
the crimps off the tags to ensure full attachment.

N E

PCB
L
Heater lead (back)

Relay Heater
Terminal
Blocks
Relay

Heater
lead
Thermostat (front)

Fig. 3c

25. Refit the end plate and lid.


26. Move the unit to its working location. If it is to be wall
mounted use the mounting bracket Fig. 3 (Item 5). Ensure a
space of at least 50cm to the right of the unit to allow access.
27. Connect the cold water supply to the mains water inlet. The
tubing selected should have a safe working pressure of at least
equal to the pressure of the water supply and should be
adequately secured with hose clips.
DO NOT TURN ON WATER SUPPLY

16

Downloaded from www.Manualslib.com manuals search engine


A8000 Installation Diagram

I/A8000HK/1
8mm Earth Spigot
I/A8000HK/2
I/WH48/2/B
16mm Earth Spigot
Reservoir
4 Water Level
Sensor
Condensers

3 Electrics

1 Water Flow Switch Solenoid

Mains Water
Boiler Thermostat & Inlet Mini
Thermostat Glass Valve
Funnel

Heaters To Distillate
Reservoir
Restrictor

Boiler
Level
Control 5 To Drain

16mm tubing x 1m - I/WH48/2/B

Rotaflo Stopcock To Drain

A8000 Operation The ON/OFF switch on the control panel is in the OFF position.
The CLEAN switch is pressed in the CLEAN position.
The following instructions apply to the A8000 water still where the
water feed to the boiler is via the mains supply, or a header tank. The Rotaflo stopcock on the front boiler level control is closed.
1. Before switching on either the mains electricity or water The reservoir water level sensor is fitted to the distillate
supply, identify the control switches and indicator lights on the collection vessel.
front of the cabinet.
The dummy shorting plug is fitted to the boiler level control
Green Light – When illuminated this shows that there is DIN socket on the cabinet.
mains supply voltage to the unit. Under no circumstances
should the cabinet end-panel be removed when this light is 3. Ensure all earth leads are connected to the earth point.
illuminated. 4. Check all glassware for any damage.
White ‘On/Off’ Switch – This is the primary switch for 5. Switch on the electricity supply – the green light illuminates.
controlling water and electricity inside the still. The switch
illuminates when pressed in the ON position. 6. Press the ON/OFF switch to the ON position – the switch will
illuminate.
Amber Light – When illuminated, this indicates that the
distillate collection reservoir is full as detected by the level 7. Recheck that the CLEAN switch is in the CLEAN position and
control. illuminated.

White ‘Clean’ Light – This shuts off the heating element but 8. Turn on the mains water supply and using the mini valve
allows water to flow into the boiler when the still is being assembly, adjust the flow rate to approximately 2 litres/min.
commissioned or cleaned. When pressed in the CLEAN This can be achieved by observing the drain water from the
position the switch illuminates. boiler level control and adjusting the mini valve assembly
accordingly.
2. Carefully check the following:
9. Check for water leaks.
The appropriate electricity, water and drain services have been
provided. If in doubt, consult the LOCATION & SERVICES
SECTION of this manual.

17

Downloaded from www.Manualslib.com manuals search engine


10. Observe the boiler now filling with water to cover the heating
elements. When water has reached the pre-set limit, the
A8000 Spares
excess will discharge to drain. Check the water drains freely
and does not back up into the boiler level control.
Boiler WB8
11. Switch the CLEAN button off by pressing it a second time. The
switch light goes out. Funnel WF48
12. The heaters will now warm up and eventually run at a red
Condenser WC48/M2
glow. If the flow rate is insufficient, the heaters will not switch
on. This will require adjustment of the mini valve assembly to ‘Mains On’ Green Indicator 700691(S)
be opened further. After about 2 – 3 minutes of operation
distilled water will emerge from the outlet pipe falling into the ‘On/Off’ White Switch 700988(S)
collection reservoir.
‘Reservoir Full’ Amber Indicator 700987
13. To avoid excess wastage of coolant water, make further
adjustments to the mini valve assembly. Slowly reduce the flow
‘Clean’ White Switch 700988(S)
rate until the flow control switch switches off the heaters,
then increase the flow until the power is restored. Reservoir Pressure Switch WPS
14. Refit the Perspex screen.
Heater Terminal Block A4000/HTB
15. Safety Cut-Outs – All Aquatron water stills are protected by
the following safety devices. Solenoid Assembly A4000/SA
Flow Control Switch – Monitors the flow of coolant water Water Flow Sensor Assembly and Hoses I/A8000HK/1
into the still and shuts off the heating element if the flow is
insufficient. Condenser to Boiler Level Control Hose Assembly I/A8000HK/2
Thermostat Cut-Out – In normal operation the water within
Reservoir Water Level Sensor WLS
the glass will be at 100°C. In single fault conditions, i.e. in the
event of water supply failure, the content will increase to Mains Water Mini Valve Assembly 7001059(S)
112°C where upon a resettable thermostat will operate. Once
switched, the thermostat has to be manually reset. This is Thermostat Glass Tube WTT48
achieved by unscrewing the black knob located inside the
cabinet and pressing the reset button. Thermostat WT8
Reservoir Control – Is positioned on the collection reservoir
Boiler Level Control WL48
and switches off both the electricity and water supplies when
the reservoir is full of distillate water. The water supply is shut Boiler Plastic Coupling WBC1
off around 7 minutes after the reservoir is full to allow the
heating element to cool. Heater Assembly A4000/HA
It is recommended that the operation of the flow switch and
Heater Assembly 220V A4000/HA220
reservoir control is checked on a regular basis.
a. Simulation of Mains Water Supply Failure Boiler Retaining Spring 700007
Turn off the mains water supply at the tap. This should switch
Distillate Output and Boiler Level Control
off the heating element. Turning the tap on again will switch
the heater on. Drain Hose Kit I/WH48/2/B

b. Simulation of Reservoir Full Condition Rotaflow Stop Cock Assembly A4000/RCOCK


Lower the glass pressure bell of the reservoir water level
sensor into the distillate to a depth of 150mm. This will switch Relay Assembly A4000/RA
off the heating element immediately and the cooling water
after 7 minutes. Raising the bell will cause both to be PCB 700804(ES)
re-supplied.
6 Way Electrical Terminal Block A4000/ETB
16. Switching Off – Push the CLEAN switch to the ON position.
Wait until the residual heat contained in the heating element Ceramic Terminal Block A4000/CTB
has dispersed and no boiling is evident. Turn off water supply.
Push ON/OFF switch to OFF position. Isolate from mains 5 DIN Socket Assembly A4000/DIN
electricity supply.
Boiler Vapour Tube Sealing O Ring I/M502

Boiler Vapour Tube Stabilising O Ring I/QR38/24

Black Phenolic Screw Cap I/QC38/25

Wall Mounting Bracket M510G

18

Downloaded from www.Manualslib.com manuals search engine


Distillate Collection WR20 & WS20
& Reservoir System Reservoir System
Each Aquatron water still is supplied with a Reservoir Water Level
To pressure switch
Sensor (WLS).
on Aquatron
This automatically switches off the heating
elements and coolant water supply when
the distillate collection reservoir is filled Distillate 50mm
with distilled water. from
Aquatron
Note that the control is fitted with a ‘delay Metal
timer’ which switches off the coolant Clip Reservoir
water supply approximately 7 minutes after water
level sensor
the heating elements. This is to allow time
for the heaters to cool and for boiling to
cease.
Reservoir
The control also automatically switches on Water
the heating elements and coolant water Level
WR20
supply when the level of distillate in the Sensor
collection reservoir falls.
It is possible to fit the glass pressure bell of
the control to most types of reservoir and 140mm
container by means of a metal clip WFC/1
which is provided with the Reservoir Water
Level Sensor Assembly (WLS).
WR20
Alternatively, Bibby Scientific offer a purpose Reservoir
designed reservoir collection system WR20 fitted with a special stand
adapter to hold the bell.

Fitting the Reservoir Control WLS to Collection Vessels


1. Position the distillate collection reservoir in a suitable location.
This should be below the water still so that the vinyl rubber
Bibby Scientific offer a purpose designed reservoir system for the
tubing transporting the distilled water from the still can fall collection of distilled water from your Aquatron.
down to the reservoir without restrictions, kinks or U bends.
WR20 – A 20 litre Pyrex glass reservoir complete with Rotaflo stop
2. Take the Reservoir Water Level Sensor WLS and connect the cock and special lid.
free end of the rubber tubing to the nozzle of the pressure
switch located on the side of the Aquatron cabinet. Secure WS20 – Reservoir stand, 43cm high for use with WR20.
with a tie wrap. The lid of the reservoir has a side arm for connection to the
distillate feed from the Aquatron and a vent fitted with a
bacteriological filter to maintain the purity of the water. A screw
thread fitting is also provided to support the Reservoir Water Level
Sensor (WLS).

Location & Assembly


Nozzle of 1. Locate the reservoir in a position which is below the level of
Pressure the water still.
Switch
2. Fit the Rotaflo drain cock to the lower ground glass socket of
the reservoir and secure with the plastic joint clip.
3. Take the bacteriological filter and connect this to the top of
the glass feed-pipe using the vinyl tubing provided. Fit the
feed pipe and filter into the reservoir lid via the large screw
cap fitting.
4. Fit the Reservoir Water Level Sensor (WLS) to the lid via the
small screw cap fitting. Note that the system of the glass
3. Use the metal clip to fit the glass pressure bell inside the pressure bell should extend approximately 50mm above the
distillate collection reservoir. screw cap.

4. Position the bell so that the open end is 140mm below the 5. Place the assembled lid into the socket of the reservoir.
desired distillate level. 6. Take the rubber tubing from the Reservoir Water Level Sensor
(WLS) and connect to the small plastic nozzle on the side of
the Aquatron cabinet.
7. Take the vinyl plastic tubing from the distillate outlet of the
water still and connect to the side arm of the feed pipe on
the reservoir lid. Ensure that the tubing falls down to the
reservoir without any restrictions, kinks or U bends.

19

Downloaded from www.Manualslib.com manuals search engine


Connection of Aquatron A4000
stills to deionised and 1. Ensure the unit is isolated from the mains.

pre-treated water supplies 2. Remove the perspex viewing screen, cabinet roof and cabinet
end panel.

Many laboratories prefer to feed their water stills with deionised or 3. Lift out the front switch panel from the cabinet groove by
pre-treated water to obviate the need for boiler cleaning and unscrewing the countersunk screw at the top of the panel.
This will allow better access to the plumbing system.
descaling.
4. Unscrew the tubing connector marked ‘3’ from the boiler
Your new Aquatron can be easily converted to a deionised water
level control as shown in the A4000 Installation Diagram on
feed by use of a simple accessory – the Water Feed Conversion
page 6.
Kit, Part No A4000/WCK (A4000) or A4000D/WCK (A4000D &
A8000). This kit permits the still to operate with most types of 5. Connect the splice (Sannar-004) to the tubing connector
deioniser and also piped supplies of pre-treated water. marked ‘3’ disconnected in step 4.

The sequence of operations to fit the kit is detailed below and 6. Connect tubing assembly (I/WCK/05) to the other end of the
should be used in conjunction with the instructional video which splice in step 5.
accompanies the kit. The video is also accessible on You Tube 7. Thread the earth cable from tubing assembly (I/WCK/05)
(youtube.com/bibbyscientific) or http://www.stuart-equipment. through the access hole in bottom of the electrical
com/product.asp?dsl=131 compartment and connect to the main earth point.
A4000/WCK 8. Thread the tubing from tubing assembly (I/WCK/05) through
the last hole on the side of the cabinet to the drain.
Earthed Pipe
Jubilee Clip 9. Take tubing assembly (I/WCK/02) and connect to the
Deioniser Kit
(700198) deionised / pre-treated water solenoid, and secure with a
(I/WCK/02)
jubilee clip.
10. Connect the other end of the tubing assembly (I/WCK/02) to
Splice the boiler level control.
(Sannar-004)
11. Thread the earth cable from tubing assembly (I/WCK/02)
through the access hole in bottom of the electrical
compartment and connect to the main earth point.
12. Unscrew the black cap from the boiler level control and
remove the funnel and seal.
13. Fit the boiler level control black cap over the float switch
Straight
assembly (I/WCK/01(E)) and fit to the boiler level control
Connector
ensuring that the end of the guide tube locates in the well at
(700408) Float Switch the base.
Assembly Tubing
(I/WCK/01(E)) 14. Remove the dummy plug from the DIN connector and
Assembly
connect the float switch assembly connector.
(I/WCK/05)
15. Remove the dummy cap from the deionised / pre-treated
A4000D/WCK Earthed Pipe
water inlet and fit the straight hose connector (700408).
Deioniser Kit 16. Connect the straight hose connector (700408) to the outlet
(I/WCK/02) of the deionised / pre-treated water supply. Note the tubing
selected should have a safe working pressure of at least equal
to the pressure of the water supply and should be
adequately secured with hose clips.
17. Refit the front switch panel.
Jubilee Clip
(700198) 18. Refit the perspex viewing screen, cabinet side panel and
cabinet roof.

A4000D
1. Ensure the unit is isolated from the mains.
Plug
(Sannar-002) 2. Remove the perspex viewing screen, cabinet roof and cabinet
end panel.
3. Lift out the front switch panel from the cabinet groove by
Straight unscrewing the countersunk screw at the top of the panel.
Connector This will allow better access to the plumbing system.
(700408) 4. Unscrew the tubing connector marked ‘5’ from the boiler
level control as shown in the A4000D Installation Diagram on
page 12.
Float Switch
5. Connect the plug (Sannar-002) to the tubing connector
Assembly
marked ‘5’ disconnected in step 4.
(I/WCK/01(E))
6. Take tubing assembly (I/WCK/02) and connect to the
deionised / pre-treated water solenoid, and secure with a
jubilee clip.

20

Downloaded from www.Manualslib.com manuals search engine


7. Connect the other end of the tubing assembly (I/WCK/02) to
the boiler level control. Operation
8. Thread the earth cable from tubing assembly (I/WCK/02) 1. Before switching on either the mains electricity or water
through the access hole in bottom of the electrical supply, identify the control switches and indicator lights on the
compartment and connect to the main earth point. front of the cabinet.

9. Unscrew the black cap from the front boiler level control and Green Light – When illuminated this shows that there is
remove the funnel and seal. mains supply voltage to the unit. Under no circumstances
should the cabinet end panel be removed if this light is
10. Fit the front boiler level control black cap over the float switch illuminated.
assembly (I/WCK/01(E)) and fit to the front boiler level control
ensuring that the end of the guide tube locates in the well at White ‘on/off’ Switch – This is the primary switch for
the base. controlling water and electricty inside the still. The switch
illuminates when pressed in the ‘on’ position.
11. Remove the dummy plug from the DIN connector and connect
the float switch assembly connector. Amber Light – When illuminated this indicates that the
distillate collection reservoir is full as detected by the level
12. Remove the dummy cap from the deionised / pre-treated control.
water inlet and fit the straight hose connector (700408).
White ‘Clean’ Switch – This shuts off the heating element
13. Connect the straight hose connector (700408) to the outlet of but allows water to flow into the boiler when the still is being
the deionised / pre-treated water supply. Note the tubing commissioned or cleaned. When pressed in the ‘Clean’
selected should have a safe working pressure of at least equal position the switch illuminates.
to the pressure of the water supply and should be
adequately secured with hose clips. 2. Carefully check:
i. the appropriate electricity, water and drain services have
14. Refit the front switch panel. been provided. If in doubt, consult the Location and Servces
section on page 3.
15. Refit the perspex viewing screen, cabinet side panel and
cabinet roof. ii. the on/off switch on the control panel is in the off position.
iii. the clean switch is pressed in the clean position.
A8000 iv. the Rotaflo stopcock on the boiler level control is closed.
1. Ensure the unit is isolated from the mains. v. the reservoir pressure switch is fitted to the distillate
collection vessel.
2. Remove the perspex viewing screen, cabinet roof and cabinet
end panel. vi. the dummy shorting plug has been removed from it’s socket
and replaced with the lead from the float switch assembly
3. Lift out the front switch panel from the cabinet groove by
(I/WCK/01(E)).
unscrewing the countersunk screw at the top of the panel.
This will allow better access to the plumbing system. 3. Switch on the electricity supply – the green indicator light will
illuminate.
4. Unscrew the tubing connector marked ‘5’ from the boiler level
control as shown in the A8000 Installation Diagram on page 4. Press the on/off switch to the on position – the switch will
17. illuminate.
5. Connect the plug (Sannar-002) to the tubing connector 5. Recheck that the clean switch is in the clean position and
marked ‘5’ disconnected in step 4. illuminated.
6. Take tubing assembly (I/WCK/02) and connect to the deionised 6. Turn on the mains water supply and using the mini valve
/ pre-treated water solenoid, and secure with a jubilee clip. assembly, adjust the flow rate to approximately 1 litre/min for
A4000 and 2 litres/min for A4000D and A8000. This can be
7. Connect the other end of the tubing assembly (I/WCK/02) to
achieved by observing the drain water from the boiler
the boiler level control.
level control and adjusting the mini valve assembly accordingly.
8. Thread the earth cable from tubing assembly (I/WCK/02) Check the mains water flows to drain without restriction.
through the access hole in bottom of the electrical
7. Turn on the supply of deionised or pre-treated water. Observe
compartment and connect to the main earth point.
that deionised water enters the boiler via the float switch
9. Unscrew the black cap from the boiler level control and assembly in the boiler level control.
remove the funnel and seal.
8. Allow deionised water to flow into the boiler until the heating
10. Fit the boiler level control black cap over the float switch element(s) is covered by approximately 10mm of water. At this
assembly (I/WCK/01(E)) and fit to the boiler level control level the flow of deionised water into the boiler should be
ensuring that the end of the guide tube locates in the well at automatically cut off by the float switch assembly in the boiler
the base. level control.
11. Remove the dummy plug from the DIN connector and connect 9. Switch off the clean button by pressing it for a second time –
the float switch assembly connector. the switch light extinguishes. The heater(s) will start to warm
up and eventually run at a red glow. (If heater(s) fails to glow,
12. Remove the dummy cap from the deionised / pre-treated check that the flow of mains water is adequate).
water inlet and fit the straight hose connector (700408).
10. Allow distillation to commence and observe that the float
13. Connect the straight hose connector (700408) to the outlet of switch assembly allows fresh deionised water to enter the
the deionised / pre-treated water supply. Note the tubing boiler and maintain a satisfactory operating level. If the
selected should have a safe working pressure of at least equal deionised supply fails then the WCK kit fitted will switch off
to the pressure of the water supply and should be the heater until it is restored.
adequately secured with hose clips.
14. Refit the front switch panel.
15. Refit the perspex viewing screen, cabinet side panel and
cabinet roof.

21

Downloaded from www.Manualslib.com manuals search engine


Cleaning 15. Repeat steps 11-14 two or three times until the boiler has
been thoroughly flushed through.
When any of the Aquatron stills have been used to produce
16. The still is re-started by finishing the cleaning cycle at step 12.,
distilled water directly from a mains water supply, there will
then pushing the CLEAN switch to the OFF position (switch is
inevitably be a build up of scale in the boiler and on the heating
not illuminated).
element(s). To obtain optimum performance from the still, the scale
should be removed on a regular basis. The time span between Before collecting the distillate the still should be allowed to
cleaning depends entirely upon the hardness of the water supply. run for about 10 minutes with the distillate running to drain.
In very hard water areas it may be necessary to clean the still once This will ensure that any residual acid is removed.
a week, whereas in soft water areas several weeks may elapse
Note – The amount of acid required will depend upon the
before cleaning is necessary.
degree of scaling. If after performing the cleaning cycle
It should not of course be necessary to de-scale the second stage deposits are left in the boiler, it may be necessary to repeat
boiler on the A4000D or when the stills have been operated from the cleaning cycle using a fresh quantity of acid.
a deioniser.
The benefits gained from regular cleaning cannot be over
Cleaning the still involves the use of 10% formic acid or kettle emphasised.
descaler. As a safety precaution, protective clothing, gloves, mask
and goggles should be worn during cleaning.
Note – The cabinet and perspex screen should be cleaned using a
dilute detergent solution only.
It is possible to descale the Aquatron water still without
dismantling the glassware by following these instructions in
conjunction with Control of Substances Hazardous to Health
(COSHH) Regulations 2002.
Method
1. Push the CLEAN switch to the CLEAN position – the switch
illuminates.
2. Observe that the heating element(s) has switched off. Allow
boiling to stop and water to cool.
3. Push ON/OFF switch to OFF position.
4. Remove the perspex screen.
5. Open the Rotaflo stop cock on the boiler level control WL48,
allow the boiler to empty to ¾ of its full capacity, and close
the stop cock.
6. Carefully add about 100ml of 10% formic acid solution or
kettle descaler into the glass funnel of the WL48.
7. Push the ON/OFF switch to the ON position, the boiler will
refill to its operating level.
8. Push the ON/OFF switch to the OFF position.
9. Allow the chemical reaction within the boiler to continue until
all the deposits have been removed.
Note – If scale has built up above the operating level, the
boiler may be completely filled by either lifting the drain pipe
or restricting the flow of water to drain. This operation must
be carefully controlled so that the boiler does not over fill and
cause water to be forced over the funnel top.
10. Open the Rotaflo stop cock and allow contents of the boiler
to drain completely.
Note – If the acid added to the boiler has not been completely
neutralised, the liquid flowing to drain may be strongly acid.
Necessary safety precautions should be observed around the
drain position and any effluent control procedures followed.
11. Close Rotaflo stop cock.
12. Push ON/OFF switch to ON position and allow boiler to fill
with water. Again the boiler may be completely filled by
following procedure detailed in step 8.
13. Push ON/OFF switch to OFF position.
14. Drain the boiler by opening the Rotaflo stop cock.

22

Downloaded from www.Manualslib.com manuals search engine


Fault Finding 6. Distillate quality low.
Check the condition of the boiler and clean if heavily scaled.
In the event of operating difficulties with your Aquatron, it is
suggested that the following basic checks are made. (Please note 7. Distillate collection reservoir floods.
that these checks should only be carried out by suitably qualified
Check the location of the reservoir water level sensor WLS
personnel).
inside the reservoir. See the Distillate Collection section of this
If these checks fail to identify and remedy the problem then you manual.
are advised to seek the help of your supplier or the Service
Check that the WLS pipe connections between the glass bell
Department of Bibby Scientific Ltd.
and Aquatron are secure and air tight.
1. Unit completely inoperative – No mains green indicator on.
8. Cleaning blocked water filters.
Check the electricity supply to the Aquatron and ensure that a
Your Aquatron is fitted with a built in water filter to prevent
fuse has not blown at the supply fuse board. (This check
the ingress of particulate matter into the plumbing system.
should be conducted by a qualified electrician).
The filter can be examined and cleaned if necessary by
2. Heater(s) not on – Mains green indicator light on, water
unscrewing the black plastic screw cap which secures the
flowing.
mains water mini valve assembly.
a. Check the Aquatron switches are in the correct mode, i.e:
A similar filter is also incorporated on the same side of the
ON/OFF switch is in the ON position. cabinet for use with pre-treated water supplies. Access is via
the black screw cap which secures the hose nozzle.
CLEAN switch is in the OFF position.
9. Persistent tripping of the RCBO.
Check that the reservoir indicator light is NOT illuminated
and indicating a full collection reservoir. This is likely to be due to the integrity of the heater which
should therefore be replaced.
b. Check that the fuse, located on the PCB inside the electrical
chamber of the cabinet, has not blown. (This check should
be conducted by a qualified electrician).
Additional Checks for Aquatrons fed with deionised or pre-treated
c. Check that the flow of cooling water is sufficient. water.
A4000 requires a flow rate of at least 1 litre/min. a. Boiler does not fill.
A4000D & A8000 require a flow rate of at least 2 litres/min. Check that supply of pre-treated water is switched on.
If the flow rate is NOT sufficient then: Check input water filter on side of cabinet is not blocked (See
step 8).
Check the mains water supply is turned on.
Check water feed conversion kit A4000/WCK or A4000D/
Check the mains water mini valve assembly is open.
WCK is correctly fitted and adjusted. See the Connection of
Check the water inlet filter is not blocked (See note 8). Stills to Deionised / Pre-Treated Water Supplies section of
this manual.
Check the flow of water is not impeded by blockages or
restrictions. b. Heater(s) not on.

3. Heater(s) not on – Water not flowing, mains green indicator Check water level in boiler is above the heating element.
light on.
Check water feed conversion kit A4000/WCK or A4000D/
Check that the thermostat has not operated. Confirm this by WCK is correctly fitted and adjusted. See the Connection of
pressing the thermostat reset button located inside the main Stills to Deionised / Pre-Treated Water Supplies section of
chamber of the cabinet. this manual.

If the thermostat has cut out then the cause should be


identified at once.
Check that the boiler contains sufficient water.
Check that the plumbing connections are not leaking.
Check that the stop cock on the boiler level control WL48 is
closed.
4. Heater in second stage boiler of A4000D not on.
Check the setting of the boiler level control W4L2A. See the
A4000D Assembly section of this manual.
Check thermostat has not operated. See notes under step 3.
5. Water level in boiler too high – Choking of condenser.
Check that the flow of water into the boiler is not excessive.
Control flow by adjusting the mains water mini valve assembly.
Check that the coolant water drain pipe falls away from the
Aquatron without restrictions or U bends.
If level of water in the second stage boiler of model A4000D is
too high, then:
Check setting of the float switch in boiler level control W4L2A.
See A4000D Assembly section of this manual.

23

Downloaded from www.Manualslib.com manuals search engine


Circuit diagram for A4000

RESERVOIR
ON/OFF CLEAN FULL
T1 (S) (WHITE) (AMBER)
3,6,9 (WHITE)
IC1
C1 C2 RL4
MR1 1000uF 33uF (E)(S)
25V 16V
2,5,7,8,1 1N4007

D1 12 - WAY
1N4007
1 SOCKET

+12 D3 D2 10
T 125 m AL 1N4007
CLEAN
1N4007 PRESSURE
(S) SWITCH
R1 R2
68K 1K (S)
RL2 RL1
(S) (S) C3
2200uF
TR1 16V

FLOW
(SEE SWITCH
NOTE)* (S)
12 - WAY
4 1 2 3 1 SOCKET 3
2 4
4 - WAY SOCKET
A4000/PCB (S) 1 5
(S)
*NOTE
SKT1 IS USED IN CONJUNCTION WITH THE DE-IONISED FEED CONVERSION KIT, WCK/N.
IF THE STILL IS NOT FITTED WITH WCK/N, PINS 1 & 5 ARE CONNECTED TOGETHER
WITH THE 'DIN' PLUG SUPPLIED WITH THE STILL.
ON/OFF
(S)
2
3
4
PINS 1 & 5, BOILER WATER LEVEL REED SWITCH.
}
PINS 2 & 4 DE-IONISED FEED SOLENOID REED SWITCH.
WHEN USED WITH WCK/N

1 5
SKT1/1 (SEE NOTE)* (E) DENOTES E.M.C. CRITICAL COMPONENT

(S) DENOTES SAFETY CRITICAL COMPONENT

RL3/1 (E)(S)
THERMOSTAT
E
(S)
SV1 (S) SV2 (S) HEATER
COOLING DE - IONISED MAINS ON
WATER WATER (GREEN)
SOLENOID SOLENOID (S)

Wiring diagram for A4000 Circuit Diagram for A4000 AQUATRON Water Still

PINK (E) DENOTES E.M.C. CRITICAL


10 COMPONENT
11 (S) DENOTES SAFETY CRITICAL
COMPONENT
VIOLET WHITE
12
BLACK
Earthed Hose
7
4 5
3
2 1
SKT1 (SEE NOTE)* Assembly 1
RED YELLOW
9
PRESSURE
RED 1 2
3 SWITCH
CLEAN (S)
RED SWITCH
12 - WAY PLUG 3
4

YELLOW WHITE
WHITE Earthed Hose
1 Assembly 3
RED
6
RESERVOIR
ON/OFF CLEAN FULL
BLACK
BLACK BLACK
5
1N4007
1 FLOW
BLACK PINK SWITCH
2 2 (S)
RL3 (E)(S) BLUE
3
YELLOW SV2 (S)
3 4
ORANGE BLUE
2 5
4 - WAY PLUG BLUE 6 SV1 (S)
BLUE
4
BROWN BROWN MAINS ON
1 (S) BLUE
ON/OFF
(S) BROWN L
THERMOSTAT (S)
*NOTE BROWN BROWN BLUE N
SKT1 IS USED IN CONJUNCTION WITH THE DE-IONISED FEED CONVERSION KIT,
WCK/N RL3/1 (E)(S) HEATER
IF THE STILL IS NOT FITTED WITH WCK/N, PINS 1 & 5 ARE CONNECTED
TOGETHER WITH THE 'DIN' PLUG SUPPLIED WITH THE STILL.
PINS 1 & 5, BOILER WATER LEVEL REED SWITCH WHEN USED WITH WCK/N
PINS 2 & 4, DE-IONISED FEED SOLENOID }

24 WIRING DIAGRAM FOR A4000 AQUATRON WATER STILL

Downloaded from www.Manualslib.com manuals search engine


Circuit diagram for A4000D

RESERVOIR
ON/OFF CLEAN FULL
T1(S) (WHITE) (AMBER)
3,6,9 (WHITE)
IC1
C1 C2 RL3 RL4
MR1 1000uF 33uF (E)(S) (E)(S)
25V 16V
2,5,7,8,1
1N4007 1N4007
D1 12 - WAY
1N4007
1 SOCKET

+12 D3 D2 10
CLEAN REAR
T 125 m AL 1N4007 1N4007 PRESSURE BOILER
(S) SWITCH FLOAT
R1 R2
68K 1K (S) SWITCH
RL2 RL1
(S) (S) C3
2200uF
TR1 16V

FLOW
(SEE NOTE)* SWITCH
12 WAY SKT1/2 (S)
4 1 2 3 1 SOCKET 3
2 4
4 - WAY SOCKET
A4000/PCB (S) 1 5
(S)
*NOTE

SKT1 IS USED IN CONJUNCTION WITH THE DE-IONISED FEED CONVERSION KIT, WCK/N.
IF THE STILL IS NOT FITTED WITH WCK/N, PINS 1 & 5 ARE CONNECTED TOGETHER
WITH THE 'DIN' PLUG SUPPLIED WITH THE STILL.
ON/OFF
(S)
2
3
4 PINS 2 & 4 DE-IONISED FEED SOLENOID REED SWITCH. }
PINS 1 & 5, FRONT BOILER WATER LEVEL REED SWITCH. WHEN USED WITH WCK/N

1 5
SKT1/1 (SEE NOTE)* (E) DENOTES E.M.C. CRITICAL COMPONENT

(S) DENOTES SAFETY CRITICAL COMPONENT

RL3/1 (E)(S)
TT1(S)
E
SV1 (S) SV2 (S) FRONT FRONT
COOLING DE-IONISED HEATER THERMOSTAT MAINS ON
WATER WATER (GREEN)
SOLENOID SOLENOID RL4/1 (E)(S) (S)
TT2(S)

REAR REAR
HEATER THERMOSTAT

Circuit Diagram for A4000D AQUATRON Water Still


Wiring diagram for A4000D

PINK (E) DENOTES E.M.C. CRITICAL


10 COMPONENT
11 (S) DENOTES SAFETY CRITICAL
COMPONENT

VIOLET WHITE
12

BLACK 4 5
7 3
1 SKT1 (SEE NOTE)*
2

RED YELLOW
9
PRESSURE
SWITCH
1 2 (S)
RED
3
CLEAN
RED SWITCH
12 - WAY PLUG 3 4
WHITE
1 YELLOW WHITE
RED
6
ON/OFF RESERVOIR
CLEAN FULL
BLACK
BLACK
5
1N4007
BLACK PINK
2
RL3 (E)(S)
REAR BOILER 1 FLOW
1N4007 FLOAT SWITCH
BLACK SWITCH
ORANGE PINK (S)
8 2
RL4 (E)(S) BLUE
3
YELLOW SV2 (S)
3 4
ORANGE BLUE
2 5
SV1 (S)
4 - WAY PLUG BLUE BLUE 6
4
BROWN BROWN
1 MAINS ON BLUE
(S)
ON/OFF
(S) BROWN L
FRONT THERMOSTAT (S)
*NOTE BROWN BROWN BLUE N
SKT1 IS USED IN CONJUNCTION WITH THE DE-IONISED FEED CONVERSION
KIT, WCK/N. RL3/1 (E)(S)
FRONT HEATER
IF THE STILL IS NOT FITTED WITH WCK/N, PINS 1 & 5 ARE CONNECTED
TOGETHER WITH THE 'DIN' PLUG SUPPLIED WITH THE STILL. BROWN
PINS 1 & 5, FRONT BOILER WATER LEVEL REED SWITCH WHEN USED
PINS 2 & 4, DE-IONISED FEED SOLENOID }
WITH WCK/N
REAR THERMOSTAT (S)
BROWN BROWN BLUE

RL4/1 (E)(S) REAR HEATER

WIRING DIAGRAM FOR A4000D AQUATRON WATER STILL

25

Downloaded from www.Manualslib.com manuals search engine


Circuit diagram for A8000

RESERVOIR
ON/OFF CLEAN FULL
T1 (S) (WHITE) (AMBER)
3,6,9 (WHITE)
IC1
C1 C2 RL3 RL4
MR1 1000uF 33uF (E)(S) (E)(S)
25V 16V
2,5,7,8,1
1N4007 1N4007
D1 12 - WAY
1N4007
1 SOCKET

+12 D3 D2 10
T 125 m AL 1N4007
CLEAN
1N4007 PRESSURE
(S) SWITCH
R1 R2
68K 1K (S)
RL2 RL1
(S) (S) C3
2200uF
TR1 16V

FLOW
(SEE SWITCH
NOTE)* (S)
12 - WAY
4 1 2 3 1 SOCKET 3
2 4
4 - WAY SOCKET
A4000/PCB (S) 1 5
(S)
*NOTE
SKT1 IS USED IN CONJUNCTION WITH THE DE-IONISED FEED CONVERSION KIT, WCK/N.
IF THE STILL IS NOT FITTED WITH WCK/N, PINS 1 & 5 ARE CONNECTED TOGETHER
WITH THE 'DIN' PLUG SUPPLIED WITH THE STILL.
ON/OFF
(S)
2
3
4
PINS 1 & 5, BOILER WATER LEVEL REED SWITCH.
}
PINS 2 & 4 DE-IONISED FEED SOLENOID REED SWITCH. WHEN USED WITH WCK/N
1 5
SKT1/1 (SEE NOTE)* (E) DENOTES E.M.C. CRITICAL COMPONENT

(S) DENOTES SAFETY CRITICAL COMPONENT

RL3/1 (E)(S)

E
SV1 (S) SV2 (S) FRONT
COOLING DE - IONISED HEATER
MAINS ON
WATER WATER (GREEN)
SOLENOID SOLENOID RL4/1 (E)(S) (S)

REAR THERMOSTAT
HEATER (S)

Circuit Diagram for A8000 AQUATRON Water Still


Wiring diagram for A8000

PINK (E) DENOTES E.M.C. CRITICAL


10 COMPONENT

11 (S) DENOTES SAFETY CRITICAL


COMPONENT

VIOLET WHITE
12

BLACK 4 5
7 3
1 SKT1 (SEE NOTE)*
2

RED YELLOW
9 PRESSURE
SWITCH
1 2 (S)
RED
3
CLEAN
RED SWITCH
12 - WAY PLUG 3 4
WHITE
1 YELLOW WHITE
RED
6
ON/OFF RESERVOIR
CLEAN FULL
BLACK
BLACK
5
1N4007
BLACK PINK
2
RL3 (E)(S)
REAR BOILER 1
1N4007 FLOAT SWITCH FLOW
BLACK SWITCH
8 ORANGE PINK (S)
2
RL4 (E)(S) BLUE
3
YELLOW SV2 (S)
3 4
ORANGE BLUE
2 5
SV1 (S)
4 - WAY PLUG BLUE BLUE 6
4
BROWN BROWN
1 MAINS ON BLUE
(S)
ON/OFF
(S) BROWN L
*NOTE BROWN BROWN BLUE N
SKT1 IS USED IN CONJUNCTION WITH THE DE-IONISED FEED CONVERSION
KIT, WCK/N. RL3/1 (E)(S)
FRONT HEATER
IF THE STILL IS NOT FITTED WITH WCK/N, PINS 1 & 5 ARE CONNECTED
TOGETHER WITH THE 'DIN' PLUG SUPPLIED WITH THE STILL. BROWN
PINS 1 & 5, BOILER WATER LEVEL REED SWITCH WHEN USED
PINS 2 & 4, DE-IONISED FEED SOLENOID }
WITH WCK/N
THERMOSTAT (S)
BROWN BROWN BLUE

RL4/1 (E)(S) REAR HEATER

26 WIRING DIAGRAM FOR A8000 AQUATRON WATER STILL

Downloaded from www.Manualslib.com manuals search engine


Bibby Scientific Ltd - Stone - Staffs - ST15 0SA - UK
Tel +44 (0) 1785 812121 - Fax +44 (0) 1785 813748

27

Downloaded from www.Manualslib.com manuals search engine


Bibby Scientific UK (Group HQ) Bibby Scientific - France Bibby Scientific - Middle East
Beacon Road, Bâtiment le Deltaparc Silic pars Nord 2, PO Box 27842
Stone, 7 rue du Canal, Engomi 2433,
Staffordshire BP 55437 Villepinte, Nicosia, Cyprus
United Kingdom ST15 OSA 95944 ROISSY Charles de Gaulle, Tel: +357 22 660 423
Tel: +44 (0) 1785 812121 France Fax: +357 22 660 424
Fax: +44 (0) 1785 810405 Tel: +33 (0) 1 48 63 78 00 Email: sales@bibby-scientific.me
Email: sales@bibby-scientific.com Fax: +33 (0) 1 48 63 78 01 Web: www.bibby-scientific.com
Web: www.bibby-scientific.com Email: contact@bibby-scientific.com
Web: www.bibby-scientific.fr

Downloaded from www.Manualslib.com manuals search engine

You might also like