You are on page 1of 5

Energy Research Institute @ NTU

Optimization of Chilled Water Systems using a


Belimo Energy Valve™: A Case Study in the Tropics
This report studies the effect of limiting the water flow on a Air-Conditioning in Singapore
cooling coil at the Nanyang Technological University in
Singapore. One Air Handling Unit (AHU) providing 100% In Singapore’s hot and humid climate
it is important to maintain a comfort-
fresh air to the Chemistry Lab in the Building of Physical and table indoor environment. Almost all
Mathematical Sciences was equipped with a Belimo Energy non-residential buildings in Singapore
Valve™ and the flow was limited in order to optimize the are heavily air-conditioned and air-
hydraulic system performance. conditioning accounts for almost 50%
of the energy consumption (NEA,
The peak chilled water flow through the cooling coil was 2010).
reduced from 25 L/s to 18 L/s, and the overall reduction in Besides the high daily temperatures,
average day-time flow from 18.5 to 15.1 L/s (18.4%). The which peak at around 35°C, ventilation
minimum chilled water delta-T increased from 3.3 to 4.5 °C systems also need to dehumidify the
fresh supply air which results in a high
and the average chilled water delta-T increased from 5.4 to
latent load.
6.3 °C. If the savings of reduced flow and increased delta-T
were extrapolated to the entire chemistry block, annual At Nanyang Technological University
(NTU), a 2 km2 campus housing
pumping energy would be reduced by 76,700-90,500 kWh academic, office, residential and retail
(12.8 – 15.0%) and annual cooling energy by 175,000 – buildings with a total Gross Floor Area
220,000 kWh (3.3-4.2%). of 1,202,500 m2, the annual electricity
consumption is 208,500 MWh. Being a
research intensive university, NTU also
has several laboratories which need a
large amount of conditioned fresh air
to comply with international safety
standards (ASHRAE, 2010). Thus,
energy efficient air-conditioning is a
priority.

Figure 1: Building of Physical and Mathematical Sciences (SPMS)


at Nanyang Technological University (NTU); Source: NTU

Low Delta-T Syndrome in Although the chilled water plants To overcome degrading cooling
are designed to maintain almost a output, a Belimo Energy Valve™ was
Large Campuses constant delta-T, in reality the installed at an Air Handling Unit
delta-T falls short of the design (AHU) supplying conditioned fresh
A common obstacle to achieving
intent. The result is high pumping air to a 1,000 m2 research facility in
energy efficient cooling at the NTU
energy consumption and decreased the NTU campus. This paper
campus, much like buildings in most
cooling efficiency of the cooling presents the results of measuring
large campuses with central cooling
plant leading facility managers to the effective cooling energy transfer
plants, is the degrading difference
believe that additional cooling by the AHU cooling coil, before and
between supply and return chilled
capacity is required (Hyman L.B., after the installation of the Energy
water temperature, commonly
2004). Valve.
known as ‘low delta-T syndrome’.
Page 1 of 5
Cooling Network campus. The chilled water demand laboratories and offices located
of the SPMS building, along with 2 within the building. For this study,
The ‘Chemistry Block’ of the School surrounding buildings, is provided the roof top unit AHU CR4-1, which
of Physical and Mathematical by a central cooling plant. supplies 100% fresh air to 8
Sciences (SPMS) department, is one Multiple AHUs and FCUs use the laboratories and office spaces, was
of the most air-conditioning chilled water to cool and de- chosen as a test-bed.
intensive buildings in the NTU humidify the air supplied to several

AHU CR4-1

Figure 2: Air handling unit (AHU) schematic of the Chemistry Block at SPMS NTU with the highlighted AHU CR4-1
used for testing

Air Handling Unit demand, the AHU supplies 8 m3/s supplied to the AHU at ~8°C and
(28,800 CMH) of fresh air and has a returned back between 12°C to
performance maximum cooling capacity of 500 18°C.
AHUs typically cool outdoor air kW. Sensors were installed to It was also observed that the
below dew point to control the measure the performance of the increase in chilled water flow rate,
moisture in the air supplied to the AHU, including supply air conditions in response to a higher cooling
building. AHUs must then employ a after the pre-cooling and the heat- demand, resulted in lower chilled
reheat control strategy, to maintain recovery coils. Most of the cooling water return temperatures, i.e.
set point supply air conditions and and the moisture removal is done lower delta-T (Figure 8). As a result
indoor thermal comfort. AHU CR4-1, by the Pre-Cooling Coil whilst the of decreasing delta-T, the cooling
supplies 100% fresh air at a Dry Bulb supply air conditions are controlled output of the pre-cooling coil enters
Temperature and Relative Humidity by the Heat-Recovery Coils. It was the waste zone in which cooling
set point of 22.5°C and 55%. At peak observed that the chilled water was capacity shows diminishing returns.

Figure 3: Control description of the AHU Page 2 of 5


The Belimo Energy Valve™ a)

The Belimo Energy Valve ™, an intelligent control


valve, was installed in the chilled water loop of
the Pre-Cooling Coil in AHU CR4-1, as shown in
Figure 4. The objective of this installation was to
improve delta-T by optimizing the cooling coil of
the AHU.
The Energy Valve has a built-in web server used
to monitor performance and easily configure the b) Balancing Valve Existing Control Valve

T
Pre-
Cooling
Coil

T
Temp. Existing Connection
Sensor Energy Valve Previous Connection

Figure 4: a) The Belimo Energy Valve™;


b) Installation schematic of the pre-cooling coil

device. For example the maximum flow and the delta-T


Manager can be adjusted. The integrated data logger stores
data with a resolution of 30s for one month and a
compressed dataset for a whole year. This helps to observe
system performance and offers many possibilities because
flow rate, Delta-T, transferred energy and other values are
available in order to diagnose and optimize the system. In
Figure 5: Belimo Energy Valve™ installed on the this report, all the data which is related to the waterside of
SPMS building rooftop the cooling coil was recorded by the Energy Valve.

Figure 6: Integrated Web-Interface for configuring the Energy Valve and visualizing the current performance
Page 3 of 5 and recorded data
Effect of Flow Limitation on Cooling Output and Supply Air conditions

The objective of the flow limiting a)


exercise was to observe the cooling
power output of the Pre-Cooling
Coil in the AHU when the maximum
flow (Vmax) was decreased from 25
L/s to 18L/s. The supply air con-
ditions were monitored to ensure
that the set points were achieved to
avoid occupant discomfort or
disruption to laboratory operations
(Figure 7).
The decrease in Vmax resulted in a b)
higher delta-T during peak load
conditions as shown in Figure 9,
which complies with heat-exchan-
ger physics. By avoiding low delta-T
during peak cooling demand, load- Figure 7: The influence of a) 25L/s flow limit and b) 18L/s flow limit on
flow mismatches could be reduced supply air temperature
and the cooling capacity of the
cooling plant could be maximised. network. Since AHU CR4-1 repre- affected by this study. System
By limiting flow to one AHU, sents only a small fraction of the savings were therefore estimated
additional capacity is made total cooling output of the central by extrapolating the savings from
available to possibly starved units cooling plant, it is unlikely that the the studied AHU.
further along in the hydraulic efficiency of the plant will be

a)

b)

Figure 8: Heat exchanger performance with a flow limit of a) 25L/s and b) 18L/s, shown as delta-T and power
versus flow

Page 4 of 5
Energy Savings Potential humidity. The result is an increase 6.3 °C. For a given cooling load,
of less than 5% of relative humidity there is a significant improvement
The peak flow was reduced from 25 at the set point temperature of in the chiller efficiency caused by a
L/s to 18 L/s, and the overall 22.5°C. In other words limiting the decrease in the temperature dif-
reduction in average day-time flow flow has a large impact on energy ference between the condenser
from 18.5 to 15.1 L/s (18.4%). The but a very small impact on the room loop and the evaporator loop. Due
reduction in average flow results in comfort according to ASHRAE Stan- to the small fraction of chilled water
a significant reduction of pumping dard 55. consumption by AHU CR4-1, the
energy consumption. However, The reduction in average flow impact on the central plant cannot
since the 3.4 L/s reduction is only a results in an increased average be observed directly.
small fraction of the flow supplied chilled water delta-T because the If the savings of reduced flow and
by the secondary pumps, the overall two parameters are inversely increased delta-T were extrapolated
effect could not be measured. At related in water-to-air heat ex- to the entire chemistry block,
the same time, a 1°C increase in the changers. The minimum chilled annual pumping energy would be
average supply air temperature is water delta-T during daytime reduced by 76,600-90,500 kWh and
observed. Because this coil needs to operating hours increased from 3.3 annual cooling energy by 175,000-
dehumidify, the impact of limiting to 4.5 °C and the average chilled 220,000 kWh with a high efficiency
was considered with respect to water delta-T increased from 5.4 to centrifugal chiller.

Figure 9: Comparison of cooling performance between the baseline case and flow limitation during daytime
operating hours (0800hrs – 1900hrs)

Summary flow and improved the cooling chilled water system operation not
performance of the chilled water only reduces pumping energy
The effect of the Flow Limitation system. The limiting exercise consumption, but the reduced
control strategy using the Energy effectively reduced the maximum chilled water flow also creates
Valve was assessed during this chilled water flow rate of the AHU greater flow capacity for other
study. It is evident that the Energy by 28%, while minimally impacting zones, particularly zones which are
Valve has reduced the excess water comfort. This improvement in far away from the pumps.

Energy Research Institute @ NTU Mr. Bharath Seshadri Dr. Marc Thuillard Belimo Automation AG
Dr. Vincent Partenay
Nanyang Technological University Mr. Stefan Mischler Brunnenbachstraβe 1
Mr. Emmanuel Blonkowski
1 CleanTech Loop, Singapore 637141 Mr. Nilesh Y. Jadhav Mr. Forest Reider 8340 Hinwil, Switzerland
Page 5 of 5

You might also like