ASSAM ELECTRICITY GRID CORPORATION LIMITED

Regd. Office: 1st floor, Bijulee Bhawan, Paltan Bazar, Guwahati-781001


CIN: U40101AS2003SGC007238
Phone: 0361-2739520/ Fax: 0361-2739513 Web: www.aegcl.co.in

No. AEGCL/GM(P&E)/132/33kV AIIMS S/s/J-6/Pt-II/2020/ / Date: /08/2021

To
The Chief General Manager (PP&D),
O/o the MD, AEGCL, Bijulee Bhawan,
Paltanbazar, Guwahati-01

Sub: Regarding re-submission of drawings and GTP of 132kV and 33kV Isolators of M/s Ultima make by M/s
Shyama Power India Limited against Construction of 25 MVA, 132/33 kV Substation at AIIMS Campus
(Changsari).

Ref: 1. NOA no. AEGCL/MD/Tech-765/AIIMS/2018/SS&TL/Pt-1/14 dated 16/07/20


2. Your letter no.: AEGCL/MD/Tech-765/AIIMS/2018/SS&TL/Pt-1/94 dated 01/03/21
and Letter from M/s SPIL vide no. SPIL:AEGCL:AIIMS:26022021-01 dated 26/02/21
3. Our letter no. AEGCL/GM(P&E)/132/33KV AIIMS S/S/J-6/Pt-I/2020/30/201 dated 06/03/21
4. Your letter no.: AEGCL/MD/Tech-765/AIIMS/2018/SS&TL/Pt-II/22 dated 07/04/21
and Letter from M/s SPIL vide no. SPIL:AEGCL:AIIMS:05042021-01 dated 05/04/21
5. Our letter no. AEGCL/GM(P&E)/132/33KV AIIMS S/S/J-6/Pt-I/2020/40/284 dated 13/04/21

Sir,
With reference to the above, this is to inform you that M/s SPIL had submitted drawings and GTP of 132kV
and 33kV Isolators of M/s Ultima make against 132/33kV AIIMS S/s (reference no. 2). Since the manufacturer is
completely new for AEGCL, the firm was asked to submit complete Type test reports and Performance certificates of
the Isolators along with some modifications in the GTP/ drawings vide our letter under reference no.3. Accordingly, M/s
SPIL has submitted the revised GTP and drawings along with partial Type test reports and other credentials for 132kV
and 33kV Isolators of M/s Ultima make (reference no. 4). The same were checked and the following observations were
made:
1. M/s SPIL had not submitted performance certificates of Isolators of M/s Ultima make.
2. The type tests carried out are on 145kV Double break Isolator instead of 145kV Centre break Isolator as
per bid requirement.
3. Mechanical Endurance test report not submitted for 145kV Isolators.
4. The short circuit withstand current and peak withstand current for 36kV Isolators are not as per
specification.
5. Temperature rise test report not submitted for 36kV Isolators.
Pertaining to the points mentioned above, it was intimated vide our letter under reference no. 5 that the
drawings and GTPs of M/s Ultima make Isolators cannot be approved at this end.
Now, M/s SPIL has re-submitted the previous drawings and GTP along with reply of M/s Ultima against our
earlier comments. Based on the reply of M/s Ultima, the following points may kindly be noted:
1. Vendor approval letter and supply invoice cannot be treated as certificate of successful performance.
2. Type test reports may be accepted only if it is carried out of equipment of similar rating and type.
3. Short circuit current rating of the offered 33kV Isolator is not as per requirement as per approved SLD.

General Manager, Planning & Design, AEGCL


Narengi, Guwahati-781026, Assam
Email:gmpne.aegcl@gmail.com
Further, it may be mentioned that M/s SPIL had offered isolators of Siemens and Switchgear & Structurals
make along with their technical bid.
Due to the shortcomings listed above and in our previous letters, M/s SPIL may kindly be intimated that the
Isolators of M/s Ultima make cannot be approved at this end as already mentioned in our previous letter. M/s SPIL may
be requested to submit documents from another reputed manufacturer of 132kV and 33kV Isolators, preferably from
any of the vendors which were offered along with their technical bid.
This is for favour of your kind information and further necessary action.
Yours Faithfully,

General Manager (P&D)


AEGCL, Narengi-26