You are on page 1of 8

Distribution : Controlled X Uncontrolled Available on computer X

Document status : TO :

F.I ( Information )

F.C ( Comments ) PT. PLN(PERSERO)


F.E ( Execution )

F.A X ( Application )

Title :
48V DC POWER
DISTRIBUTION BOARD

Type : FIELD TEST REPORT

Contract :

SCATTERED PACKAGE 7
500 kV GIS EXTENSION KEMBANGAN AND
500 kV & 150 kV CONVENTIONAL SUBSTATION

309.PJ/041/DIR/2011 500 kV GIS EXT KEMBANGAN SUBSTATION


Contract specific number Site Name

A by Satria.P Nosarimba Iwan.S


Customize for Package 7 Project
on 7/2/2019 7/2/2019 7/2/2019
Ind Rev Established Checked Approved Modification Sheets

PT. GRID SOLUTIONS INDONESIA

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTION INDONESIA 48V DC POWER Ref.
DISTRIBUTION BOARD Chapt.

Sheet : 2

SUMMARY SHEET

1 - LIST OF TEST EQUIPMENT USED 1

2 - DISTRIBUTION BOARD SPECIFICATIONS 2

3 - PRELIMINARY CHECKS 3

4 - ELECTRICAL TEST 4

5 - SWITCHGEAR DESCRIPTION AND SETTINGS 6

1 - LIST OF TEST EQUIPMENT USED

Test corresponding to paragr.


Identification
Designation
Number
2 3 4 5 6 7

Digital Multimeter Fluke X

Insulation Tester, Kyoritsu X

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTION INDONESIA 48V DC POWER Ref.
DISTRIBUTION BOARD Chapt.

Sheet : 3

2 - DISTRIBUTION BOARD SPECIFICATIONS

- Circuit : +EQ 3421 ( 48V DC Distribution Board )

- Manufacturer : PT. EXABB

- Type : LV - Free Standing

- Rated Voltage : 48 Volt DC

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTION INDONESIA 48V DC POWER Ref.
DISTRIBUTION BOARD Chapt.

Sheet : 4

DESCRIPTION REQUIREMENT TEST RESULT

3 - PRELIMINARY CHECKS

- Distribution board components


presence and conformity
with applicable drawings :

Refer To Drawing OK

- Main busbar continuity Connected OK

- Distribution board grounding Connected OK

- Hinged door and chassis connected


to the frame by ground braids Connected OK

- Door lock operation operated properly OK

- Mechanical interlocks :
Incoming operated properly OK

- Connection conformity
with applicable drawings.
Sarulla Geothermal Power Plant Project

VISUAL INSPECTION
Please check visually:
a. DC Board room equipped with extinguiser equipment Equipped OK
b. DC Board equipped with safety tag Equipped OK
c. Check DC Board placement match with layout Refers to drawing OK
d. Check DC board already earthed Connected OK
e. DC Board in Clean condition Clean OK
f. Check labelling MCB matc with electrical diagram Refers to drawing OK

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTION INDONESIA 48V DC POWER Ref.
DISTRIBUTION BOARD Chapt.

Sheet : 5

DESCRIPTION REQUIREMENT TEST RESULT

4 - ELECTRICAL TESTS

4.1 Electrical continuity


between all metal parts

- Maximum resistance reading 0.4 ohm 0.2 Ohm

4.2 Insulation resistance test

- Busbar (+) to busbar (-) > 20 MΩ >1.05 GΩ


- Busbar (+) to Ground > 20 MΩ >1.05 GΩ
- Busbar (-) to Ground > 20 MΩ >1.05 GΩ

4.3 Circuit breaker test

- Mechanical checks :
. Rack in/out NA
.Tripping OK

- Electrical checks :
. Position and fault
information report Operated Operated

4.4 Electrical testing of board

- Measurement indicator test OK

- Energizing :

. Cable connections OK

. Energizing, voltage monitoring OK


and polarity check

. Alarm report
- Check alarm contact for MCB trip Contact operated OK

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTION INDONESIA 48V DC POWER Ref.
DISTRIBUTION BOARD Chapt.
Sheet : 6

4.5 - VOLTAGE INDICATOR +EQ 3421

- Circuit : Digital

Indicator

- Manufacturer : Accuenergy - Type : Volt meter

- Class :

- Input : DC

4.6 - AMPERE INDICATOR +EQ 3421

- Circuit : Digital

Indicator

- Manufacturer : Accuenergy - Type : Ampere meter

- Class :

- Input : DC

INJECTED ( V ) DISPLAY ( V ) % ERROR RESULT

50 51 2.00 OK

INJECTED ( A ) DISPLAY ( A ) % ERROR RESULT

50 51 2.00 OK
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTION INDONESIA 48V DC POWER Ref.
DISTRIBUTION BOARD Chapt.
Sheet : 7

5. SWITCHGEAR DESCRIPTION AND SETTINGS

5.1 EQ 3421

MARK PROTECTED CIRCUIT MCB TYPE RATING REMARKS

Q9401 500KV PLC TELE PROT 1 S802C ABB 10 A OK

Q9402 500KV PLC TELE PROT 2 S802C ABB 10 A OK

Q9403 500KV PLC TELE PROT 3 S802C ABB 10 A OK

Q9404 500KV MUX TELE PROT 1 S802C ABB 10 A OK

Q9405 500KV MUX TELE PROT 2 S802C ABB 10 A OK

Q9406 500KV MUX TELE PROT 3 S802C ABB 10 A OK

Q9407 PABX S802C ABB 10 A OK

Q9408 SAS PANEL FOR MODEM S802C ABB 10 A OK

Q9409 SPARE S802C ABB 10 A OK

Q9410 SPARE S802C ABB 10 A OK

Q9411 SPARE S802C ABB 10 A OK

Q9412 SPARE S802C ABB 10 A OK

Q941 INCOMING SACE Tmax ABB 160 A OK

Tested By Witnessed By Witnessed By Verified By


PT. PLN (PERSERO) PT. PLN (PERSERO) PT. PLN (PERSERO)
PT GRID SOLUTIONS INDONESIA
PUSMANPRO UPMK-1 UPPJJBB-3 PUSERTIF

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.