Title : PHASE SEGREGATED


BUSBAR DIFFERENTIAL PROTECTION
MULTILIN B90
F87BB - EF1101
AS PER SETTING PLN P3BS
Type : FIELD TEST REPORT

Contract :

PEKERJAAN PENGADAAN DAN PEMASANGAN GITET 275/150 KV BETUNG

05.PJ/132/UIP.III/2014 GITET BETUNG 275 KV


Contract specific number Name

by
on
by
on
by Nopi Rianto Pasti Malau Andry Winartha 10
B
on 23.09.2014 23.09.2014 23.09.2014
by Pasti Malau Sudung Malau Demak MS ORIGINAL ISSUE 4
A
on 31.08.2001 31.08.2001 31.08.2001
Ind Rev Prepared Checked Approved Modification Sheets

PT. GRID SOLUTIONS INDONESIA


FA SECTION

J K T A G I 0 8 H N B A 0 0 0 3
Place of issue File number

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 2
F87B Rev. B

SUMMARY SHEET REVISION

1 LIST OF EQUIPMENT USED 2 B

2 CHARACTERISTICS 3 B

3 GENERAL INSPECTION 3 B

4 RELAY TEST 4 B

1 - LIST OF TEST EQUIPMENT USED

Identification Test corresponding to paragr.


Designation
Number 3 4 5 … … …

H……… Secondary Injector, OMICRON CMC 356 X X

H……… Digital Multi Meter, Fluke 179 X X

X X
Note Book

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 3
F87B Rev. B

2 CHARACTERISTICS

- Circuit : Advance Differential F87B (+EF 1101)

- Relay Type : B90J16HKHF8NH67L8NN67S8NUXXW7H - Serial No : AA6C150001153

- Relay current In : 1/5 A

- DC Supply ( modules ) : 110 - 250 V - Frequency : 50 Hz

- Communication Protocol : IEC 61850

- Setting range :

w Current range : 0,025 - 15 A


step : 0,005 A

w Time multiplier range : 0 - 10 sekon

w Reset Time multiplier range : 0 - 100 sekon

w Curve IDMT, RI, DMT : IDMT

3 GENERAL INSPECTION

- Wiring conformity in accordance with DWG : ok

- Module earthing checks : CONNECTED ok

- Current transformer shorting switches closed : ok

- Test plug checks : ok

- Availibility and value of auxiliary voltage supply ( DC ): 110 Volt

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 4
F87B Rev. B

4. SETTING CHECKS
4.1 Measurement Check

Current Input (Diameter 1) (I1)

CT ratio : 2000 : 1A

Phase Current Injection Expected Value (A) Measure Value (A) Error (%) Result

R 1A 2000 2000 0.0 Pass

S 1A 2000 2001 0.1 Pass

T 1A 2000 2000 0.0 Pass

Current Input (Diameter 2) (I2)

CT ratio : 2000 : 1A

Phase Current Injection Expected Value (A) Measure Value (A) Error (%) Result

R 1A 2000 1998 -0.1 Pass

S 1A 2000 1998 -0.1 Pass

T 1A 2000 1998 -0.1 Pass

Current Input (Diameter 3) (I3)

CT ratio : 2000 : 1A

Phase Current Injection Expected Value (A) Measure Value (A) Error (%) Result

R 1A 2000 1999 -0.1 Pass

S 1A 2000 1999 -0.1 Pass

T 1A 2000 1999 -0.1 Pass

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 5
F87B Rev. B

4. SETTING CHECKS
4.1 Measurement Check

Current Input (Diameter 4) (I4)

CT ratio : 2000 : 1A

Phase Current Injection Expected Value (A) Measure Value (A) Error (%) Result

R 1A 2000 2001 0.1 Pass

S 1A 2000 2001 0.1 Pass

T 1A 2000 2001 0.1 Pass

4.2 Current Sensivity Check

Current Input (Diameter 1) (I1)

ID>1 Setting : 0.50 A

Expected Measured (A) Actual Measured (A)


Phase Result
Pick Up Drop Off
Pick Up Drop Off
Min Max Min Max

R 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

S 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

T 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

Setting :
a. ID>1 = 0,5 pu
b. Slope k1 = 25%
c. ID>2 = 1,5 pu
d. Slope k2 = 60%

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 6
F87B Rev. B

4. SETTING CHECKS

4.2 Current Sensivity Check

Current Input (Diameter 2) (I2)

ID>1 Setting : 0.50 A (0,5 pu)

Expected Measured (A) Actual Measured (A)


Phase Result
Pick Up Drop Off
Pick Up Drop Off
Min Max Min Max
R 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

S 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

T 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

Current Input (Diameter 3) (I3)

ID>1 Setting : 0.50 A (0,5 pu)

Expected Measured (A) Actual Measured (A)


Phase Result
Pick Up Drop Off
Pick Up Drop Off
Min Max Min Max

R 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

S 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

T 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

Current Input (Diameter 4) (I4)

ID>1 Setting : 0.50 A (0,5 pu)

Expected Measured (A) Actual Measured (A)


Phase Result
Pick Up Drop Off
Pick Up Drop Off
Min Max Min Max

R 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

S 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

T 0.48 0.55 0.48 0.51 0.51 A 0.480 A Pass

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 7
F87B Rev. B

4. RELAY TEST
TIME TEST
ID>1 Setting : 0.50 A ;T:0s ; Curve : Instanious Time
D1
Timing (mili second)
Phase Current Inject T Result
Nominal Value Measured value

1 x Is= 0.5 A 30 25 Pass


R
2 x Is= 1 A 30 20 Pass

1 x Is= 0.5 A 30 25 Pass


S 0s
2 x Is= 1 A 30 20 Pass

1 x Is= 0.5 A 30 25 Pass


T
2 x Is= 1 A 30 20 Pass
ID>1 Setting : 0.50 A ;T:0s ; Curve : Instanious Time
D2
Timing (mili second)
Phase Current Inject T Result
Nominal Value Measured value

1 x Is= 0.5 A 30 22 Pass


R
2 x Is= 1 A 30 19 Pass

1 x Is= 0.5 A 30 22 Pass


S 0s
2 x Is= 1 A 30 19 Pass

1 x Is= 0.5 A 30 22 Pass


T
2 x Is= 1 A 30 19 Pass

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 8
F87B Rev. B

4. RELAY TEST
TIME TEST
ID>1 Setting : 0.50 A ;T:0s ; Curve : Instanious Time
D3
Timing (mili second)
Phase Current Inject T Result
Nominal Value Measured value

1 x Is= 0.5 A 30 23 Pass


R
2 x Is= 1 A 30 20 Pass

1 x Is= 0.5 A 30 23 Pass


S 0s
2 x Is= 1 A 30 20 Pass

1 x Is= 0.5 A 30 23 Pass


T
2 x Is= 1 A 30 20 Pass
ID>1 Setting : 0.50 A ;T:0s ; Curve : Instanious Time
D4
Timing (mili second)
Phase Current Inject T Result
Nominal Value Measured value

1 x Is= 0.5 A 30 21 Pass


R
2 x Is= 1 A 30 19 Pass

1 x Is= 0.5 A 30 21 Pass


S 0s
2 x Is= 1 A 30 19 Pass

1 x Is= 0.5 A 30 21 Pass


T
2 x Is= 1 A 30 19 Pass

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 9
F87B Rev. B

5. SLOPE TEST
Idifferential (pu)

TRIPPING
AREA

Operation
Diff oper level Id=In Characteristic

Restrain (pu)

Setting : Phase Comparison = 25%


Id Low Set 0.5 A Current = 500 A
Slope 25 %
Phase Comparison = 60%
Current = 1200 A

Injection Secondary Result


Expected Ph Indication
I1 [A] Angle I2 [A] Angle I1 [A] k1
Setting
R 0.2 0 0.2 0
Id>1 0,5 A S 0.2 -120 0.2 -120 400 20% No Trip
k1 25% T 0.2 120 0.2 120

Injection Secondary Result


Expected Ph Indication
I1 [A] Angle I2 [A] Angle I1 [A] k1
Setting
R 0.256 0 0.256 0
Id>1 0,5 A S 0.256 -120 0.256 -120 518 25.9% Trip
k1 25% T 0.256 120 0.256 120

Setting :
a. ID>1 = 0,5 pu
b. Slope k1 = 25%
c. ID>2 = 1,5 pu
d. Slope k2 = 60%

This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 10
F87B Rev. B

5. STABILITY TEST

UNSTABLE CONDITION [Diameter 1 - Diameter 2]


Winding 1 [Side D1] Winding 2 [Side D2] CT 1 CT 2
Phase Led Trip Time
Injected [A] Angle Injected [A] Angle Ratio Ratio
R 0.5 0 0.5 0 2000/1 2000/1 Trip 36 ms
S 0.5 -120 0.5 -120 2000/1 2000/1 Trip 36 ms
T 0.5 120 0.5 120 2000/1 2000/1 Trip 36 ms
STABLE CONDITION [Diameter 1 - Diameter 2]
Winding 1 [Side D1] Winding 2 [Side D2] CT 1 CT 2
Phase Led Trip Time
Injected [A] Angle Injected [A] Angle Ratio Ratio
R 0.5 0 0.5 180 2000/1 2000/1 - 0
S 0.5 -120 0.5 60 2000/1 2000/1 - 0
T 0.5 120 0.5 300 2000/1 2000/1 - 0

UNSTABLE CONDITION [Diameter 1 - Diameter 3]


Winding 1 [Side D1] Winding 2 [Side D3] CT 1 CT 2
Phase Led Trip Time
Injected [A] Angle Injected [A] Angle Ratio Ratio
R 0.5 0 0.5 0 2000/1 2000/1 Trip 34 ms
S 0.5 -120 0.5 -120 2000/1 2000/1 Trip 34 ms
T 0.5 120 0.5 120 2000/1 2000/1 Trip 34 ms
STABLE CONDITION [Diameter 1 - Diameter 3]
Winding 1 [Side D1] Winding 2 [Side D3] CT 1 CT 2
Phase Led Trip Time
Injected [A] Angle Injected [A] Angle Ratio Ratio
R 0.5 0 0.5 180 2000/1 2000/1 - 0
S 0.5 -120 0.5 60 2000/1 2000/1 - 0
T 0.5 120 0.5 300 2000/1 2000/1 - 0

UNSTABLE CONDITION [Diameter 1 - Diameter 4]


Winding 1 [Side D1] Winding 2 [Side D3] CT 1 CT 2
Phase Led Trip Time
Injected [A] Angle Injected [A] Angle Ratio Ratio
R 0.5 0 0.5 0 2000/1 2000/1 Trip 23 ms
S 0.5 -120 0.5 -120 2000/1 2000/1 Trip 23 ms
T 0.5 120 0.5 120 2000/1 2000/1 Trip 23 ms
STABLE CONDITION [Diameter 1 - Diameter 4]
Winding 1 [Side D1] Winding 2 [Side D3] CT 1 CT 2
Phase Led Trip Time
Injected [A] Angle Injected [A] Angle Ratio Ratio
R 0.5 0 0.5 180 2000/1 2000/1 - 0
S 0.5 -120 0.5 60 2000/1 2000/1 - 0
T 0.5 120 0.5 300 2000/1 2000/1 - 0

Tested by : Witnessed by : Approved by: Date Test :