Document status : TO :
F.I ( Information )
F.A X ( Application )
Contract :
by
on
by
on
by Nopi Rianto Pasti Malau Andry Winartha 10
B
on 23.09.2014 23.09.2014 23.09.2014
by Pasti Malau Sudung Malau Demak MS ORIGINAL ISSUE 4
A
on 31.08.2001 31.08.2001 31.08.2001
Ind Rev Prepared Checked Approved Modification Sheets
J K T A G I 0 8 H N B A 0 0 0 3
Place of issue File number
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 2
F87B Rev. B
2 CHARACTERISTICS 3 B
3 GENERAL INSPECTION 3 B
4 RELAY TEST 4 B
X X
Note Book
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 3
F87B Rev. B
2 CHARACTERISTICS
- Setting range :
3 GENERAL INSPECTION
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 4
F87B Rev. B
4. SETTING CHECKS
4.1 Measurement Check
CT ratio : 2000 : 1A
Phase Current Injection Expected Value (A) Measure Value (A) Error (%) Result
CT ratio : 2000 : 1A
Phase Current Injection Expected Value (A) Measure Value (A) Error (%) Result
CT ratio : 2000 : 1A
Phase Current Injection Expected Value (A) Measure Value (A) Error (%) Result
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 5
F87B Rev. B
4. SETTING CHECKS
4.1 Measurement Check
CT ratio : 2000 : 1A
Phase Current Injection Expected Value (A) Measure Value (A) Error (%) Result
Setting :
a. ID>1 = 0,5 pu
b. Slope k1 = 25%
c. ID>2 = 1,5 pu
d. Slope k2 = 60%
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 6
F87B Rev. B
4. SETTING CHECKS
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 7
F87B Rev. B
4. RELAY TEST
TIME TEST
ID>1 Setting : 0.50 A ;T:0s ; Curve : Instanious Time
D1
Timing (mili second)
Phase Current Inject T Result
Nominal Value Measured value
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 8
F87B Rev. B
4. RELAY TEST
TIME TEST
ID>1 Setting : 0.50 A ;T:0s ; Curve : Instanious Time
D3
Timing (mili second)
Phase Current Inject T Result
Nominal Value Measured value
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 9
F87B Rev. B
5. SLOPE TEST
Idifferential (pu)
TRIPPING
AREA
Operation
Diff oper level Id=In Characteristic
Restrain (pu)
Setting :
a. ID>1 = 0,5 pu
b. Slope k1 = 25%
c. ID>2 = 1,5 pu
d. Slope k2 = 60%
This document is the property of PT. GSI and cannot be used, reproduced or transmitted to thirds without prior written permission.
PT. GRID SOLUTIONS INDONESIA BUSBAR DIFFERENTIAL Ref.
FA Section PROTECTION Chapt.
GE B90 Sheet : 10
F87B Rev. B
5. STABILITY TEST
1/7/2017