Professional Documents
Culture Documents
Fire Detection
In general, the fire detection system shall have the following objectives:
- To alert operator at control room and give them the location.
- To alert any personnel at location of the fire event so that they are aware
and could take any necessary action.
Based on these, there are four main types of the fire detection devices (fire
detector):
- Smoke detector.
- Heat detector.
Each detector has a unique purpose and suitability for a specific application.
Thus the detector type should be selected based on the safety (loss prevention)
study. It will depend on the speed of response required, consequences to
facility, and the area of the fire events.
Smoke detectors
The most used smoke detectors are ionization type and photoelectric type. The
ionization type utilizes a constant current that produced by electrode from an
ionization of some isotope. Any particle that goes through the chamber and
interrupt the ionization will make a reduction of constant current. Thus alarm
will be activated. The photoelectric type utilizes a scattered light from smoke
particles to measure the smoke present. Any particles that interrupt the light
line (it will be scattered) will cause the detector activated.
The smoke detector (both ionization and photoelectric type) are very sensitive
and shall not be used at dirty environments, smoky atmosphere, and open areas
where there is an unpredictable air flows. For example, smoke detector shall
not be used at kitchen, mechanical workshop, etc.
Another type of smoke detectors that most used at offshore oil & gas industries
are High Sensitive Smoke Detectors. This detector usually placed on the very
critical areas such as cable ducting, control room, and electrical room. This
detector take a sample of each sample location by an air-sampling tubes and
then draw the sample to a centralized detector which analyze any small present
of smoke. It will allow the system to give very fast and earliest alert to an
operator of fire event (event it still on the smoke forming stage).
Flame Detectors
Flame detectors are categorized as fast response devices. It senses the flame on
a line of sight. A fire consists of three part, smoke, heat, and flame. This
detector is utilizing at application when flame is the first part of fire that
formed, such as a hydrocarbon leak area.
- Fixed type.
- Fusible plugs.
Fusible Plugs
Fusible plugs are a metal cylinder that has a sealed metal with low melting
point. It is connected to a pneumatic tubing loop. When the ambient
temperatures reach the melting point of the seal metal, then the seal will broke
and causing a pneumatic air leak through it. This leak will be detected by a
pressure switch and it will initiate an alarm that activates a very large capacity
valve to operate. This large capacity valves (called deluge valve) will spout a fire
water to extinguish fires. The fusible plug is designed to protect a closed vessel
from a fire. When a closed vessel exposed to a fire, it can causing a dangerous
rise in internal pressure of vessels and causing a blow up. Therefore usually it
put out around a closed vessel.
COORDINATION OF RELAY AND UNDER VOLTAGE RELAY:
COORDINATION OF RELAY
If any fault occurs in motor, the neares relay has to trip ‘D’ breaker itself, so that it won’t affect the
other system. Similarly if any fault occurs after ‘A’ breaker, the nearest is A breaker’s relay. So ‘A’
should trip and other system not affected.
Normally the operating and tripping of breaker time will be around 350 msec.
If after ‘A’ breaker fault occurs ‘A’ will trip at 350msec if it fails ‘B’ will trip at 700msec, I ‘B’ also
fails ‘C’ will trip 1 sec. This is called the co-ordination of Relays.
This relay operates when under voltage occurs in a connected system, normally this relay setting
be 80% of the applied voltage. This relay is used to trip the equipments connected, during under
voltage condition. These relay having two types, instantaneous and IDMT (Inverse Definite
Minimum Time)
IDMT relay are all dis type and the setting can be done through plug setting arrangement.
AC – Alternating current where the voltage is alternating from peak voltage (on both +ve –ve side)
to ZERO voltage periodically.
A. 0.75, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95, 10, 150, 185, 240, 300, 400,
600, (Dimensions are in Square mm).
A. Cable glands are used to protect against mechanical damages o cables during
entering in junction box, MCC etc. it also give earth continuity of cable Armor and
equipment body.
Q. What type of Cable gland used in Oil Field?
A. In explosion proof areas double compression glands are used to avoid the gasses
entering in the electrical apparatus.
A. Mineral Insulated Copper Conductor and it is used for fire alarm systems and
Lightings systems at Hazardous area without using conduits and Magnesium oxide is
used as mineral.
A. Cold Compound joint kits. Hot Compound joint kits and Heat Shrinkable joint kits,
Hot Compound Termination and Heat Shrinkable Termination kits,
A. Ferrule is used to connect two conductors during jointing. Three types are Crimping
Type and Soldering Type for High Voltage Cables as well as for Medium Voltage Cables
and for Low voltages ferrules are PVC Insulated.
A. Lead Covered Cables are used in Oil Fields due to avoid damages of PVC Insulation,
by hydrocarbon gases and chemical corrosion.
A. Crimping type and Soldering type lugs are used for cable terminations.
A. As follows:
Trace the cable fault through cable fault locator and cable route through cable route
locator
If the cable resistance is high use the burnout test kit
All these relay will have instantaneous tripping as well as IDMT (Inverse Definite Minimum Time)
delay tripping or only IDMT or instantaneous.
OVERCURRENT RELAY:
This relay operates when a over current of short circuit noticed in the load.
Normally these relays will be having plug setting for current selection.
IDMT is normally used for over current. Instantaneous will be actuated only during short circuit
and for this normally the setting will be 10 times the normal current.
Whatever the current fall in the secondary of C. T. will flow through over current relays 50 / 51.
When any fault occurs between phases & earth, this relay will operate.
This relay connected to the zero balanced (residually connected) C. T. connection as shown in the
diagram. Normal over current will not pass through this relay, at point 0 the current will be zero.
When a fault occurs between phase and earth, there will be unbalance and that unbalance current
will pass through relay (50 N / 51 N).
RESTRICTED EARTH FAULT RELAY:
This relay protects only the zone connected in between the neutral C. T. and residually
connected C. T. in the phase side i.e., it is protecting star winding of the transformer. When any
unbalance or earth fault occurs after the phase C. T. there will be unbalance currents neutral C. T.
as well as residually connected phase CT and both currents nullified at point ‘O’. So there won’t
be any current flow in the relay and the relay won’t operate.
When fault occurs in the winding there will be a current flow in the neutral CT only. The current
will operate the 87TG relay.
DIFFERENTIAL RELAY
This relay protects the Zone connected between the CTs – i.e. it is protecting only the transformer.
The CT connection is in winding side and in winding side, this is because to compensate vector
difference. The CT ration is also to be selected according to the transformation ratio.
When there is fault after the transformer secondary (i.e. after the secondary CT) there won’t be
any difference of primary and secondary currents, are balanced in the Restraining coil.
When a fault occurs in the transformer, that current will be transformed to primary side only. So
that there will be different in the currents of primary and secondary. That unbalanced current will
pass through the operating coil and the relay will operate.
COORDINATION OF RELAY
If any fault occurs in motor, the neares relay has to trip ‘D’ breaker itself, so that it won’t affect the
other system. Similarly if any fault occurs after ‘A’ breaker, the nearest is A breaker’s relay. So ‘A’
should trip and other system not affected.
Normally the operating and tripping of breaker time will be around 350 msec.
If after ‘A’ breaker fault occurs ‘A’ will trip at 350msec if it fails ‘B’ will trip at 700msec, I ‘B’ also
fails ‘C’ will trip 1 sec. This is called the co-ordination of Relays.
This relay operates when under voltage occurs in a connected system, normally this relay setting
be 80% of the applied voltage. This relay is used to trip the equipments connected, during under
voltage condition. These relay having two types, instantaneous and IDMT (Inverse Definite
Minimum Time)
IDMT relay are all dis type and the setting can be done through plug setting arrangement.
AC – Alternating current where the voltage is alternating from peak voltage (on both +ve –ve side)
to ZERO voltage periodically.
FREQUENCY –
In AC, the voltage which completes one cycle of Sin wave form is called frequency and the unit is
‘HERTZ’ (Hz)
Summary
The following important information in this chapter is summarized below.
Globe valves are used in systems where good throttling characteristics and low
seat leakage are desired and a relatively high head loss in an open valve is
acceptable.
Ball valves allow quick, quarter turn on-off operation and have poor throttling
characteristics.
Plug valves are often used to direct flow between several different ports
through use of a single valve.
Diaphragm valves and pinch valves are used in systems where it is desirable for
the entire operating mechanism to be completely isolated from the fluid.
Check valves automatically open to allow flow in one direction and seat to
prevent flow in the reverse direction.
A stop check valve is a combination of a lift check valve and a globe valve and
incorporates the characteristics of both
Safety/relief valves are used to provide automatic overpressurization protection
for a system.
ZONE ‘0’ In which an explosive gas – air mixture is continuously present for a long period.
ZONE ‘1’ In which an explosive gas air mixture is likely to occur under normal operation.
ZONE ‘2’ In which an explosive gas air mixture is not likely to occur in normal operation and if it
occurs it exist only for short time.
ZONE ‘1’ Any type of protection suitable foe Zone 0 and Ex‘d’, EX ‘b’, Ex‘p’,Ex ‘e’
ZONE ‘2’ Any type of protection suitable for Zone 0 or Zone 1 and Ex’N’ or ‘n’ Ex ‘O’, Ex ‘q’
GAS GROUP
IEC USA
Representative Gas
1 Methane I D
2 Propane IIA D
3 Ethylene IIB C
4 Hydrogen IIC B
5 Carbon Disulphide IIC
6 Acetylene IIC A
H. T. MOTORS: Motor workings with voltage 3.3 KV and above are HT motors. This motor normally
used for higher loads as the operating current cab be reduced. Normally these motors are
connected. These motors are having some special cooling arrangements like forced air cooling,
condenser type cooling in which water is circulated to cool the temperature inside. Instead of a
ball bearing, sleeve bearings are also used. For cooling the bearing, separate oil us used.
Motor is provided with the differential relay protection connected between Start side CTs and
Phase side CTs as shown.
VELOCITY AND DISPLACEMENT: Vibration can be measured in terms of how fast the part moves.
This is called the Peak Velocity and is measured in inches/seconds or millimeter/seconds.
Velocity is a function of both displacement vibrations.
Vibrations can be measured in terms of how far the move back and forth. This is called the peak to
peak displacement measured in mils. 1 mil = 25.4 microns
BEARINGS: The bearings used in electrical machineries are ball bearings, Roller Bearings,
Tapered Roller Bearings, Thrust Bearings, Sleeve Bearings, Needle Bearings etc, generally on
load side of the machine Roller Bearings are used.
Z - Shield bearing
1. Remove motor pulley with 3 leg puller if the motor is small and medium size. For large pulley
Hydraulic puller may be used.
3. Remove outer bearing cover on both ends and remove end shields with markings.
Now the motor is dismantled totally while assembling reverses the above procedure.
1. O/H TRANSMISSION
Corona is a type of electrical discharge at the surface of conductors at high voltage because of
voltage stress, it occurs at foul weather, depends on pressure, temperature, humidity, pollution
level, in air and condition of conductor surface.
5 KW/KM.
Lightning arrestors employ some form of non linear type of resistance like thyrite or matrosil
whose resistance decreas3es rapidly with increase of applied voltage. But as soon as energy has
been dissipated resistance is restored to a high value which suppresses the arc across the gap
effectively when line voltage returns to normal.
4. What are the points to be checked when carrying out inspection of O/H lines?
a) Frequency weekly/monthly depending in location
b) Check points non growth of trees, birds’, nests, cracks of insulators, faulty line regulation
structure for mechanical defect-corrosion.
TRANSFORMER
Transformers Transformation Ratio
V1/V2=N1/N2=I1/I2=K or NS/NP=VS/VP=IP/IS=K
It is the gas and oil operated relay. It has two circuits, one is trip and second is alarm. Any minor
fault develops that time the evaporated gas will actuate the alarm circuit; otherwise any major
fault rush of oil will actuate the Trip Circuit.
a) Buchholz relay
b) Overheated relay
c) Earth fault relay
d) Temperature sensor
The oil should withstand 30KV for 1 minute gap with a gap of 2.5mm
It is a small container, contains silica gel and oil. It absorbs the moisture from the atmospheric air
and allow the fresh air to the conservator.
1. YPM of Transformer
CONTROL VALVE
1.Globe valve
2.Butterfly valve
3.Ball vale
3. What is a double seated control valve? Where in general it is used?
A control valve whose trim has two seats n plugs. A double seated control valve
is commonly used in high differential, huge capacity, turbulent flow lines.
CONTROL VALVE
ON-OFF VALVE
It is a trim having a single seat n plug and balance holes on its plug. A single
seated balanced trim is used in a process line where the DP across the valve is
high. These kind of trims are useful in reducing the vibration on the valve body
and also assists in closing the valve.
ON-OFF VALVE
Reverse acting : Stem retracts when air pr in actuator increases. Air to retract.
as the number of u.s. gallons per minute of water that will flow through a
valve in the wide open position with a ressure drop of a valve in wide open
calculations.
Stem travel: The scale that shows the stem movement in inches orcentimeter.
Gland packing: A sealing system in the valve body which prevents the process
fluid coming out through the valve stem.
A control valve is said to be over sized when a minimum signal to the valve
(minimum opening of the valve) brings process to the set point rapidly. This
situation leads to an imbalance and high gain in the control loop. The problem
can be solved by changing the valve trim to a reduced trim size or by replacing
the control valve for the correct size.
On a pneumatic control valve, this is the minimum and maximum air pressure to
be applied to achieve the full stroke length of the actuator.
A higher bench set actuator is selected when the control valve is operating on a
high pressure process line.
Valve Positioner is a unit used on a control valve to ensure actuator stem takes a
position proportional to the input signal. It positions the diffrent types of valve
actuators of different capacities and spring ranges by converting the low
pr/capacity signal 3-15psi or 4-20a into high pr and large capacities. Iie to
increase the speed of the response of the valve. To compensate the forcing
effects of the fluids causing an unbalanced valve plug. To minimize frictional
effects of glanding packing actuator stem packing. To split the valve travel and
for reversing the valve action to the output of the controller by reversing the
action, and change the valve characteristics. In case the require stroke length
isn't achieved, then the positioner either increases or decreases its output until
the valve achieves the desired stroke length.
11.Why is a valve positioner preferred even on a control valve having a bench set
20-100 kPa?
13. What is ‘gland packing’? Name the types of commonly used gland packings?
A sealing system in the valve body which prevents the process fluid coming out
through the valve stem. Commonly used gland packing are Teflon, Graphite,
Asbestos..etc
A greasing ring placed in the valve bonnet across the gland packing. The unit
provides lubrication to the valve stem when it travels up and down.
3) How do you decide the boost charge current rate for given ampere hour rating of battery?
C/5
ie 100AH/5 = 20 Ampere
4) How do you check the battery condition?
By conducting Discharge Test
7) What is the float voltage for Alkaline and Lead acid Cells?
Alkaline - 1.42V
Lead Acid - 2.4V
8) What is the specific gravity values of battery cells? How to measure?
1) 1280 for fully charged lead acid cells.
2) 1260 for half charged lead acid cells.
3) 1180 for dead cell( lead acid cells).
4) 1200 for fully charged nickel cadmium cells and discharged condition same value.
Specific gravity can be measured by " Hydrometer"
Capacitors :
APP is All poly polypropylene type capacitor. It consists one layer of aluminium foil and
other of polypropylene. Polypropylene is the dielectric medium that is placed in between
aluminium layers during wrapping process. Actually every technology is superior it only
depends on the situation. You can take an example of truck tyre it can not be used in two-
wheeler.APP is like that but it has more watt losses as compare to MPP. Its life is more but
costlier than MPP and running cost will be high due to losses.
Mixed -dielectric capacitor consists of polypropylene film having aluminum layer on its other
side itself and another dielectric medium like craft paper dipped in biodegradable oil/ resin
placed in between of MPP film during wrapping process Or MPP film dipped in resin/
biodegradable oil. It has better life than MPP,slightly costlier than MPP,same losses like
MPP, low losses and running cost is lessor than APP.
In mixed die- electric another technology is using gas as a other die-electric medium. But
this technology is banned in Europe & America as it release harmful gases dangerous for
human beings during its bursting but in India it is still in use.