Professional Documents
Culture Documents
)i<}
diameter of 3 to 4 in (7.6 td 10.2 cm) and its grounded outer sheath
has a diameter of about 12 in (30.5 cm). Using an average inner
diameter of 3.5 in (8.9 cm), the surge impedance of the 242 kV SF6
bus can be calculated from the following formula: 1 (6.7) (67) (624) (0) (4.6)
Z138log
4k
r2
rI
a) Breaker and a Half Scheme
24 s-l-- 40 1
(9.1) (7.3) (122) t
12
(3.6)
12
(3.6)
E (12.2)
Aw ,,1 24
(7.3)
(17
(5.2) -
s
1622
BSL/BIL Ratio terminals of the substation. In the following analysis it will therefore
be assumed that the lightning arresters will be installed only on each
The ratio BSL/BIL in an air insulated substation with conven- line entrance terminal of the substation.
tional equipment is substantially less than unity (0.60 - 0.86
depending upon the piece of equipment) and a comparison of the Type of Arrester
withstand voltage vs. time characteristic of air and SF6 insulated
equipment appears as shown in Fig. 2. Air and porcelain insulated For purpose of this discussion, two types of lightning arresters
conventional equipment can withstand very high voltages for very are considered - conventional and gas insulated. A conventional
short times; however, as the duration of the voltage increases, the arrester is defined as the typical arrester now used in conventional
withstand voltage falls off considerably. On the other hand, SF6 gas overhead substations. The conventional arrester is air insulated and has
insulated equipment exhibits a withstand voltage vs. time character- porcelain housings which are exposed to atmospheric contamination.
istic that is nearly flat especially when compared to its conventional The gas insulated arrester has no exposed porcelain or contamination
counterpart.2 Thus the ratio of the Basic Switching Impulse Insulation since it is completely enclosed in a grounded housing filled with.SF6
Level (BSL) to the Basic Lightning Impulse Insulation Level (BIL) is gas. Thus there are two alternate ways of placing the lightning arrester
close enough to unity in SF6 so that a BSL/BIL = 1.0 can be used for at the gas insulated substation terminals - either a conventional
engineering purposes in gas insulated systems. arrester connected to the overhead line just outside the gas insulated
substation or a gas insulated lightning arrester connected to the SF6
This flat characteristic also effects the relationship between the bus just inside the gas insulated substation.
chopped wave impulse insulation levels and the full wave (BIL) level.
Conventional air insulation has 2 and 3 As chopped wave levels of 1.29 The first alternative of placing a conventional arrester on the
and 1.15 times the BIL whereas again the ratio for SF6 insulated overhead line adjacent to the gas insulated system has several
equipment is essentially unity. advantages. First of all, it is more economical since a conventional
arrester is less expensive than a gas insulated arrester. This is due to
the tank required to house the gas insulated arrester and the additional
voltage compensation required. Secondly, the technology of conven-
AIR iNSULATION tional arresters is more extensively developed and more firmly
'a
established than its gas insulated counterpart. However, the gas
insulated arrester has one important advantage - the absence of
z -- - -- SF6- INSULATION exposed porcelain to atmospheric contamination.
2
The gas insulated arrester also has the significant advantage of
z versatility or flexibility. It-can be located anywhere that is desired
SURGE DURATION within the gas insulated substation and as a result can be physically
located closer to the transformer, circuit breaker and other pieces of
.1 i 10 100 1000 Ps equipment that it is called upon to protect. Thus if it becomes
necessary to place the arrester near a particular piece of equipment or
Fig. 2. Insulation Levels of Air and SF6 if a system becomes too large to be protected by single arresters at the
substation terminals, a gas insulated arrester could be placed inside the
substation at the exact location it is needed. A conventional arrester
LIGHTNING ARRESTERS does not offer this versatility since it cannot be connected inside the
gas insulated system.
The application of lightning arresters in the gas insulated system
centers around the following considerations: Arrester Rating, Number As will be shown in Fig. 6 and the accompanying discussion,
and Location of Arresters, and Type of Arrester. Each of these factors there is little difference between the protection given by a conven-
will be discussed separately and the philosophy will be developed for tional arrester on the overhead line near the terminals and a gas
application of lightning arresters to a gas insulated system. insulated arrester on the SF6 bus at the terminals. The following
analysis therefore will be assumed to apply equally well to either case
Arrester Rating (provided the two types of arresters have the same or similar sparkover
and discharge characteristics).
At each of the system voltages considered, from 72.5 kV to
765 kV, several different lightning arester ratings will be used. For INSULATION COORDINATION
voltages of 242 kV and above, effectively grounded systems are
assumed and the arrester ratings used in the analysis are selected As has been previously pointed out, the insulation coordination
accordingly. analysis developed in this paper will consider system voltages from
72.5 kV to 765 kV. At each of the several system voltages, various
Since there still are some ungrounded systems at 145 kV and lightning arrester ratings will be used as explained in the preceding
below, a greater range of arrester ratings is selected to adequately section on arresters. The BIL ratings will be selected based upon the
handle both grounded and ungrounded systems. Based on the above results of the actual calculations as well as some consideration of the
considerations, the several arrester ratings shown in the final reference already established conventional BIL ratings. Even though the BIL
graph (Fig. 5) were chosen as representative values for each system ratings for conventional stations are used as a guide or starting point,
voltage level. it soon becomes evident that the gas insulated substation permits
lower BIL ratings than its conventional counterpart at certain voltage
Number and Location of Arresters levels. All the variables - system voltage, arrester rating, separation
distance - are listed in a reference graph (Fig. 5), and for each set of
Normal practice in conventional substations is to place lightning variables, a maximum impulse voltage is given for equipment in the gas
arresters as close as possible to the transformer. The goal is to provide insulated substation. Thus the reference curves provide a summary of
as much protection as possible to the transformer since it is not only this paper which can be used for design purposes by the substation
the single most expensive piece of equipment in the substation but design engineer.
also the most susceptible to permanent overvoltage damage. To
protect the other equipment in the substation, such as circuit
breakers, disconnect switches, etc., additional lightning arresters' are Gas Insulated Lightning Arrester at Bus Terminal
usually required at other locations throughout the substation.
The calculation of the impulse voltages in the substation involves
Because of the compact size and extremely short bus runs of the the direct solution of rather complicated traveling wave problems. It
gas insulated substation, the number of required lightning arresters is can be solved either by using Laplace transforms, graphically, or by
greatly reduced. In fact, typical lengths in a gas insulated system are so using a computer program. The initial work was done graphically but
short (usually 50 to 100 ft (15.25 to 30.5 m) total straight length] for the calculation of the final values, a single-phase-transient-digital
that, in almost all cases, lightning arresters are needed only at the computer program was used.
1623
The basic system studied is shown on Fig. 3a. A lightning surge is The maximum voltage at the transformer terminal was calculated
assumed to originate on the transmission line and travel toward the for 200, 100 and 50 ft (61, 30.5 and 15.25 m) of SF6 bus.
junction of the line and the gas insulated bus. The rate of rise of this
surge depends on the system voltage, conductor size and the distance On shorter bus runs the reflections return much faster due to
the surge originates from the bus, which is a function of the system shorter travel times and therefore the voltage buildup is faster. This
lightning outage rate. faster voltage buildup causes the arrester to sparkover at a higher
voltage, but since the travel time for the negative discharge is so much
Using the method of Reference. 3 and assuming typical system shorter the maximum voltage at the transformer terminal is lower (see
constants and operating characteristics, the incoming surge would have Fig. 3c, d) for 100 and 50 ft of bus than for 200 ft of bus.
a rate-of-rise of 700 to 900 kV/4sec. The slight variations between
specific systems does not have too much effect on the final result and SF6 - BUS
thereforb an incoming surge of 800 kV/gsec was assumed for all
440 n
calculations. 73 OnB
'' Z D~z2 3e a)
In the system shown in Fig. 3a, a gas insulated lightning arrester
is installed on the entrance terminal of the SF6 bus. The assumed VOLTAGE
sparkover values and discharge characteristics of the arresters are kV
shown on Table I. The values in the table are expressed in p.u. of the 600
impedance between the overhead line and the SF6 bus (Zl- = 320 to
440 Q2 versus Z2 = 75 Q, see Fig. 3a) reflections and refractions occur 200-
b)
according to the following relationships. 1,4
Z2-zl
er=Z+Z
1 2
ef time
0 .5 1.0 15 mS
2Z2
e +Z2 ef
e=2w
=Z kV
of bus is 0.2 pis. This time delay of the voltage buildup can be seen in 600
Fig. 3b.
The transformer which terminates the SF6 bus was represented
as a capacitance to ground. The capacitance acts as a short circuit at
the first insitant but passes through a transition stage to its final fully
charged condition, when it acts as an open circuit. The reflected wave d)
from. the capacitance is initially negative and therefore it reduces the
rate of rise of the voltage at the arrester. This can be seen in Fig. 3b,
between 0.4 and 0.5 ,us, where the slope of the arrester voltage is flat.
The larger the capacitance value the longer the charging time and
therefore the slower the voltage buildup at the arrester and the
transformer. A value of 1600.pF was assumed to give conservative
results.
1.5 us
The surge will be reflected and re-reflected between the overhead
line terminal and the transformer. Each reflection adds to the voltage Fig. 3. Voltage Buildup in a 242 kV System with a 192 kV Arrester
at the arrester and the transformer. When the arrester sparkover inside the Gas Insulated System.
voltage is reached, the,. arrester discharges (at time ts). The voltage
buildup at the transformer continues until the negative arrester
discharge wave arrives, which in the case of 200 ft (61 m) of bus is b) 200 ft (61.0 m) of SF6 Bus
0.2 psec after sparkover, and causes the transformer voltage to decay c) 100 ft (30.5 m) of SF6 Bus - - - at the Transformer
very rapidly from its maximum value. d) S0ft (15.25 m) of SF6 Bus -at the Transition Point (Arrester)
1624
The maximum voltages at the transformer terminal as seen in Fig. kV
3b, c, d for 200, 100 and 50 ft (61, 30.5 and 15.25 m) of bus are
plotted as Curve A in Fig. 4.
2500 BIL LIGHTNING ARRESTER SYSTEM
Common practice is to design for a 20% margin between the RAT WJG VOLTAGg
maximum surge voltage and the equipment BIL. To show this margin
a second curve (Curve B) is plotted on Fig. 4 which is 20% higher than 2300 kV
the maximum voltage curve. For example, for 50 ft of bus a BIL of 612 kV
2175 kV 765 kV
670 kV is required; for 200 ft' of bus however the BIL should be 578 kV
735 kV. I
.'2050 W
As discussed earlier, the length of bus between the transition 2000
1925 kV
point and the transformer in a gas insulated station is'very short
compared with a conventional substation. For- example, Fig. 1 shows 1800 kV
that this length is usually less than J150 ft (45.7 m). Also these long
bus runs usually have some taps which cause additional reflections and - 1675 kV
thereby reduce the voltage at the transformer. In the following 444 kV
analysis therefore the maximum value of 200 ft (61 m) of untapped 1550 kYV
gas insulated bus was used as a quite conservative design criteria. 1500 420 kV 550 kV
1425 k 396 k
Figure 4 shows that the maximum impulse voltage plus a 20%
safety margin at the end of a 200 ft long gas insulated bus is 735 kV. 1300 kV
The next highest standard BIL level is 750 kV (shown as Curve C).
The 242 kV gas insulated bus with a 192 kV arrester at the transition -1175 kV
point should be designed for a BIL of 750 kV in order to withstand
lightning surges safely. 1050 kV 294 kV
1000 975 kV
- 276 kY
258 wV
362 kV
900 kV
VOLTAGE
kV 825 kV
750 kV 192 kV 242 kV
800
CURVE C 750 KV
650 kV 180kV
CURVE - 20S
550SV
k44k Y
600 CURVE A ,MAXIMUM VOLTAGE AT THE 120kV 145 kV
TRANSFORMER TERMINAL 500 450 WkV_ 0k
CJRVE E
CURVE D , 15% 350 kV .72k
400 ARRESTER SWITCHING SURGE 300 kV 0kV 725kV
SPARKOVER VOLTAGE
200'
0
DISTANCE 50 -100 200 ft.
0 (1525) (30.5) (61) m
0 50 100 200 ft.
(525) (30.5) (61) (m)
Fig. 5. Maximum Impulse Voltages versus SF6 Bus Length
Fig. 4. Maximum Voltages in a 242 kV System with a 192 kV
Arrester near the Transition Point.
i 440 X:
100
RECOMMENDATIONS
Knowing the arrester rating and maximum bus length, the system
designer could use Fig. 5 to determine the BIL required for his
individual gas insulated substation. The main purpose of this paper
however is to determine a set of recommended standard BIL ratings
that would apply to-all systems. Fig. 5 was used to develop these
k
ratings and the recommended levels are shown in Table III. A brief
600 description of how these levels were obtained follows.
In the generation of Fig. 5, bus lengths of up to 200 ft (61 m)
were considered possible. Also the maximum arrester ratings con-
sidered practical were shown. The probability of having both the
maximum arrester rating and the 200 ft (61 m) bus length'however is
considered too small to penalize all systems. A compromise was
therefore made for each system to arrive at what is considered to be
the maximum practical BIL for each system voltage rating. The
combinations of bus lengths and arrester ratings assumed for each
system voltage to arrive at the BIL recommendation is shown in
Table III.
For example, there are a few ungrounded 72.5 kV systems so a
72 kV arrester rating may be required. The bus lengths of this low
voltage however are much shorter than 200 feet (61 m). Fig. 5 shows
that if the bus length is 90 ft (27.4 m), or less, a 300 kV BIL can be
Fig. 7. Voltage Buildup in a 242 kVSystem, with a SF6 Getaway protected by the 72 kV arrester. Note that if there is a rare instance
Link and a 192 kVArrester at the Substation Terminal. where the bus length is greater than 90 ft (27.4 m), it is probable that
the arrester rating is less than 72 kV and the 300 kV BIL is still
satisfactory. Note that for the 362 kV and higher systems, two
- -- at the Arrester combinations of bus lengths and arrester ratings are shown in
-- - - at the Transformer Table III. This data again shows the probable worst combinations that
at the Transition Point will occur on operating systems.
1626
One important point needs to be emphasized at this time. The' REFERENCES
curves given in Fig. 5 represent the maximum voltages (including a'
20% margin) occurring on the system. The wave shape of these 1. Central Station Engineers, Westinghouse Electric Corporation,
voltages are representative of chopped impulse waves rather than full Electrical Transmission and Distribution Reference Book, East
impulse waves. Since the ratio of chopped wave to full BIL is Pittsburgh, Pa., 1950, pp. 524, 527, 610-642.
essentially unity for SF6, the levels expressed in Table III are both
BIL and chopped wave level. Thus the 550 kV BIL recommended for 2. Boeck, W., Troger, H., "SF6 Insulated Switchgear for Ultra-High
145 kV gas insulated equipment is not the same as a 550 kV BIL for Voltages (UHV)", Cigre 23-08, 1972 Session.
conventional equipment since the 550 kV BIL for SF6 implies a
550 kV chopped wave level while conventional 550 kV BIL circuit 3. Clayton, J. M., and Powell, R. W., "Application of Arresters for
breakers have 2 and 3 Ms chopped wave levels of 710 kV and 633 kV Complete Lightning Protection of Substations," AIEE Trans-
respectively. 0 actions, February, 1959, pp. 1608 - 1614.
A third point to consider concerns the transformer insulation. 4. Bewley, L. V., Traveling Waves on Transmission Systems,' New
The curves given in Fig. S and the BIL levels recommended in York, Dover Publications, Inc., 1951, pp. 45 - 65.
Table III are applicable to the entire gas insulated substation (includ-
ing SF6 bus, disconnect switches, junction boxes, circuit breakers and, 5. Klumb, F. R., "SF6 System Moves Power ... Up the Tower!",
if considered part of the gas insulated substation, the transformer). Electric Light and Power, Transmission/Distribution Edition, July
However, the proposed BIL levels are based upon the assumption that 1972 pp. 46 - 48.
lightning arresters are located only at the terminals of the gas insulated
substation. Thus, any transformer must have a high enough BIL rating
so that it can 'be adequately protected by a lightning arrester which is
up to 200 ft (61 m) away. The transformer BIL rating however could TABLE I
be lowered by placing a lightning arrester at (or near) the transformer
terminals. The decision concerning whether or not to place an arrester
at the transformer is solely economic and depends upon the cost of an Lightning Arrester Characteristics
additional gas insulated arrester compared to the cost of a higher BIL (Expressed in p.u. of the Arrester Rating)'
level transformer. Such an economic consideration is beyond the
scope of this paper. For that matter the gas insulated arresters could Maximum Front-of-Wave Sparkover 1.9 p.u.
be located anywhere in the gas insulated system and Fig. 5 would still Maximum Switching Surge Sparkover 1.6 p.u.
be valid. The decision concerning lightning arrester location for Maximum Discharge Voltage - 1.5 KA 1.2
transformer protection will have to be made for each particular gas 3.0 KA 1.3
insulated substation by the design engineer utilizing the voltage curves 5 KA 1.38
given in Fig. 5. The primary purpose of this paper is to recommend 10 KA 1.56
BIL ratings for gas insulated bus and equipment and not for 20 KA 1.8
transformers. Fig. 5 and Table III should be interpreted with this fact
in mind.
TABLE II
1628
In considering the flat characteristic nature of SF6, the arrester The last comment is on the length of the bus. The maximum bus
'sparkover characteristic of a conventional arrester, when "deporce- length treated in the analysis seems to be rather short particularly in
lained" and placed in a SF6 environment, would be expected to change. higher system voltages. Longer bus length will give a different problem
The authors use the listings in Table I for both the conventional and on the location of the arresters.
the gas-insulated arresters. If the characteristic does not change, how is
this accomplished in light of Figure 1, which appears to indicate that
the sparkover levels of the impulse and switching surge ranges will be H. W. Anderl, C. L. Wagner, and T. H. Dodds: The purpose of this paper
essentially equal? If the characteristic is not modified by the environ- was to provide a starting point for the standardization of insulation
ment, is this true of all arresters on the market? Relatively little has levels for gas insulated substations. The authors have proposed a set of
been published on studies of the effects of various gases on arresters. If values with the aim of provoking discussion from those who disagree.
the characteristic can change when merely "de-porcelained" and placed These discussions would then form the basis of starting work in the
in the gas enclosure, standards may have to be modified to incorporate various IEEE, EEI, NEMA and ANSI committees.
this contingency. The authors are appreciative of the excellent discussions that have
Again, since the insulation level of the protected equipment is been presented and from their quality and the content it is apparent that
flat and consequently more predictable, might it be possible to reduce the basic purpose of the paper has been accomplished. Messrs. Morioka,
the 20% margin in the impulse region in Figure 4 down to the 15% appli- Nagai, Nitta and Shibuya feel the paper's values are too low and Messrs.
cable to the switching surge region? Beehler, Phelps, McElroy and Garrity feel they are too high. Now it is up
In the authors' discussion of their results in Figures 3, 6 and 7, to the industry committees to evaluate which should be selected.
comparisons are made directly between the maximum voltage peaks in Considering first the factors which might cause the values to be
these figures at the transformer and the BIL level of the transformer. too low, Messrs. Morioka, Nagai, Nitta and Shibuya question whether
Why did the authors feel it unnecessary to consider the severity or the paper's 800 kV/,usec rate-of-rise might be too low. They state that
disruptive effect of the surge in addition to its magnitude? The waves it is Japanese practice to assume a lightning stroke close in to the sub-
illustrated in their figures have considerably less energy than the station entrance terminal with a resulting higher rate-of-rise of surge
standard wave used in obtaining the BIL level of the transformer. voltage. They requested the authors' comments.
As mentioned in the paper, the 800 kV/,usec value was based on the
method of Reference 3. Assuming a probability of failure of once in
60 years and a line lightning flashover rate of 2/100 miles/year, the stroke
George N. Lester, (Allis-Chalmers Corp., Boston, Mass. 02136): The isdistance seen to originate at least 4400 feet out from the station. In this
authors have provided an interesting report of their analytical investi- surge front and assuming normal conductor sizes and configurations the
gation of possible BIL requirements for gas insulated substations. This attenuates to approximately 800 kV/,usec by the time it
is a timely study in that presently there is an ideal opportunity to plan arrivesWhileat the station.
and agree within the industry on insulation requirements for this these assumptions are felt to be quite severe, the authors
equipment consistent with surge protective device capabilities, specific- also calculated the condition assuming a line flashover rate of 5/100
ally where a reduction of requirements, compared with conventional miles/year. This means that the stroke could originate within 1800
of the terminal and the rate-of-rise is increased to 1600 kV/psec.
outdoor apparatus, may be realistic and justified. This work will serve as feet
Even with this extremely severe assumption, the resulting voltage at the
a good reference point for continued evaluation of these needs.
The authors' comment on one point would be appreciated. In the transformer was raised only 40 to 50 kV.
circuit arrangement studied, the reflection point inside the station was These discussors, as well as Mr. Graybill, questioned our assumption
the transformer, which was initially represented as a capacitance. It that the BIL and BSIL are equal for the gas insulated substation. They
would seem that a possibly more realistic, and slightly more severe raised the excellent point that from a practical standpoint this equip-
condition would be for this reflection point to be an open circuit in ment cannot be kept perfectly clean and therefore conducting particles
the system can cause a reduction in the BSIL, whether it be the 10 to
breaker, or disconnect switch. What variations would appear in the 15% quoted or the approximately 40% quoted by
plots of Figures 3b, 3c, and 3d and Figure 5 if such an open switching Messrs. Morioka, Nagai,Graybill
by Mr.
Nitta and Shibuya.
device were between the transition point and the transformer? Even using the 1.4 ratio of BIL to BSIL, however, Fig. 4 of the
paper shows that there should be no problem with switching surges.
Manuscript received February 20, 1973. Due to the lower switching surge sparkover level of the arrester and the
essentially flat surge voltage profile throughout the substation (due to
the long fronts of the switching surge), the ratio of the required BIL
(750 kV) to the required BSIL (500 kV) is in the case of Fig. 4 equal to
S. Morioka, N. Nagai, T. Nitta, and Y. Shibuya, (Mitsubishi Electric 1.5 which exeeds even the 1.4 factor above.
Corp., Amagasaki, Japan): The paper is a valuable contribution in the The comments on the effect of contamination on the rating of the
new field of insulation coordination of gas insulated substations. The external lightning arrester are not clear. If it is meant that a lower rated
discussers feel that some of the suppositions used in the analysis may arrester,a for example 180 kV, can be used inside the gas system instead
not be practical in the light of their experience. of, say 192 kV rated external arrester due to contamination, then the
The rate of rise of voltage 800kV/,sec, the authors used for the authors disagree. In fact, Messrs. Beehler, Phelps, McElroy and Garrity
incoming surge in the analysis may not be adequate. According to the commented on this point by stating that all lightning arresters must be
authors' reference (3), the value corresponds to the case the lightning designed to operate under contaminated conditions.
If it is meant that gas insulated arresters are better from a possible
surge is originated about 4000 feet away from the substation. In usual contamination
Japanese practice, the protection against the direct lightning at the etc.) then the authors standpoint (like not having to periodically wash them,
closer location is taken into account. The lightning surge will have agree.
greater rate of rise of voltage in this situation not only due to the short maximum The final point raised concerns the opinion that the 200 foot
distance but due to the reflection at the transition point. What is the conceivablebus length may be too short at the higher voltages. It is
suggestion of the authors on the problem? that where the substation is fed from overhead lines, the
Secondly, the discussers would like to comment about the authors large phase spacings of the 500 and 765 kV lines may cause longer bus
quotation that BIL and BSIL are the same in case of SF6 gas insulation. runs. However, it is probable that "Getaway Bus Links" will be used to
In their experience, it is true when the electrode area is small like a gap connect the substation terminals to the overhead line terminals. As
commonly used in laboratory experiment. The value of BSIL is some- shown on Figure 7 of the paper, by installing lightning arresters at the
times considerably lower than BIL in practical gas insulated substation. junction of the getaway and the substation, the surge voltages can still
This is typically shown in Fig. 2 of T-73-033-8 which is presented by be limited to-the recommended values.
one of the discussers (S. Morioka) at this meeting. From the figure, it It should also be remembered that the calculations assumed a
can be said that the BIL/BSIL ratio possibly reaches 1.4. In this case, straight clean bus run from the lightning arrester to the transformer. In
BSIL as well as BIL will be a very important factor to be examined in actual stations there will be a number of stubs and additional line take
the insulation coordination of gas insulated substations. offs in this path which will reduce the magnitude of the surges. More
Thirdly, the authors seem to put limited importance on the type detailed studies on actual bus layouts are needed to evaluate this factor.
of arrester in selecting arrester rating. Most of the failures are attributed Turning now to the other side of the question, Messrs. Beehler,
to the contamination of the porcelain housing in case of the conven- Phelps, McElroy and Garrity raise several excellent points on factors
tional arrester. From this point, the reduction of the rating should be which might indicate that the proposed values are too high. In fact, they
limited as far as this type of arresters are used. On the other hand, the expressed "surprise" that the proposed 2050 kV minimum BIL for 765
gas insulated arrester is free from contamination and seems to be more kV systems given in Figure 5 was the same level of present outdoor
promissing in this application. What is the authors' opinion on this switchgear equipment. This is not quite correct. While it is true that
point? the BIL's of the two are the same, the key to the reduced insulation is
Manuscript received February 21, 1973. Manuscript received April 18, 1973.
1629
that the proposed chopped wave level of the gas insulated equipment is The authors also thank Mr. Graybill for his comments, especially
also 2050 kV. This is opposed to the 2 gsec chopped wave level of his reference to the paper being useful to Working Group 70.1 of the
existing 765 kV breakers being 1.29 times 2050 or 2645 kV. In reality, IEEE Substations Committee. His comments on the effect of conduct-
therefore, there is a reduction of insulation proposed of almost 30 ing particles on the switching surge insulation level are interesting and
percent. have been discussed above.
In spite of this reduction, the discussors bring up two points We also agree with his comments on the protection of cables
which might indicate an even further reduction down to say a 1675 kV feeding the gas insulated station. Since our paper was concerned only
BIL and chopped wave level. First they state that the 20 percent margin with the insulation of the station itself, very little attention was devoted
between the maximum surge voltage and the BIL (or chopped wave to the protection of the cable itself. This requires a separate study when
level) is not "common practice". The authors admit to this error. the application arises.
Common practice is to provide a 20 percent margin between the voltage Mr. Graybill mentions that the ratio of the outer sheath radius to
at the arrester and the BIL of the equipment in applications where the the inner conductor ratio varies between 2.1 and 3.5 in actual bus
arrester is relatively close to the equipment. The 20 percent margin is designs. This results in a range of bus surge impedances of from 45 to
used to partially compensate for the voltage rise due to the actual separ- 75 ohms. The 242 kV design value used in the paper of 73.8 ohms is
ation distance between the arrester and the equipment taking into therefore on the higher end of the range. As Mr. Graybill states this
account also the increased chopped wave level of conventional equip- makes our results conservative since the lower surge impedance values
ment above its BIL. They are therefore correct that if the actual surge will result in lower surge voltages.
voltage and the chopped wave level of the equipment are known the full Mr. Melvold questioned whether the characteristics of the "de-
20 percent margin is not required. porcelained" arresters would change to the flat characteristic of Fig. 2
Note that if the full 20 percent margin were eliminated, the proposed rather than have the different impulse and switching surge sparkover
level of 2175 kV from Table III would be reduced to 1812 kV and the characteristics as shown in Table I. If such were the case, he questions
2050 kV level from Fig. 5 would be reduced to 1708 kV. This latter whether the internal and external arrester applications would be the
value is almost down to the discussors 1675 kV level. The authors do same. Actually, the gas insulated arresters are not "de-porcelainized".
not feel that this much reduction is warranted. Perhaps a compromise Rather, the conventional weather shed porcelain on the conventional
of a 5 to 10% margin would be more appropriate. arrester is simply replaced by a smooth porcelain but is still hermetically
The discussors also bring up the point that perhaps a more refined sealed to prevent gas leakage into the arrester. The characteristics of the
method of insulation coordination using probability techniques should arrester assembly are unaffected so the application results are the same.
be used and in this the authors heartily agree, especially after observing His comments on the disruptive effects of the chopped wave type
the curves in Mr. Morioka's reference paper on the effect of contact surges is certainly true and this effect is the same as was discussed
area on the bus insulation levels. This will require further test data by previously in the comments on Messrs. Beehler, Phelps, McElroy and
the bus designers to supply the critical flashover (CFO) and standard Garrity's question. The 20 percent margin should probably be reduced
deviations (a) for various bus lengths so that the methods of the dis- as previously discussed.
cussors can be used intelligently. Mr. Lester commented that a more realistic and severe assumption
Messrs. Beehler, Phelps, McElroy and Garrity also question whether could be made that the reflection point in the substation should be an
BIL's of 2050 or 2175 kV are also being proposed for transformers. open breaker rather than a transformer termination since the apparent
This question brings up an important ommission from the paper. capacitance of the transformer tends to slope off the wave and reduce
Throughout the paper, the chopped wave insulation was the level of the resulting surge magnitude. In one respect we agree and for the case
concern and as explained above all surges were compared to this level. of Fig. 3b, if the transformer were replaced by an open breaker the
When the authors discussed transformers, we neglected to mention that maximum voltage would be 670 kV, an increase of 6.5 percent. How-
there is a turn-up in the volt-time characteristics of transformers so that ever, from Fig. 1, it would appear that an open breaker would never be
the 2050 or 2175 kV values are really the chopped wave transformer 200 feet away from a line terminal as might a transformer. This condi-
insulation levels. Assuming a 1.15 chopped wave factor this would mean tion was therefore not considered in our conclusions. As discussed
the BIL's proposed would be 1780 or 1890 kV or the closest standard previously, however, when further studies on actual substations are
BIL to these values. These values also could be reduced if the 20 percent ,made, this factor should be considered.
margin were reduced as discussed above. Also as discussed in the paper, The authors would again like to thank the discussors for their
additional arresters could be applied at the transformer terminals if excellent comments. They form an invaluable addition to the paper in
further reductions were desired. We thank the discussors for bringing up its role as a starting point for industry consideration of standard in-
this question to allow clarification on this point. dustry consideration of standard insulation levels for gas insulated
The arrester contamination point has been discussed previously. substations.
1630