Professional Documents
Culture Documents
Revision 3
Contents
1.0 Introduction 1
2.0 Scope 1
3.0 Definitions 2
4.0 Responsibilities 14
4.1 Location Management 14
4.2 Task Supervisor or PIC 15
4.3 Employee 15
4.4 Escort 15
4.5 Contractors and Visitors 15
12.0 References 72
12.1 ANSI (American National Standards Institute) 72
12.2 ASTM (American Society for Testing and Materials) Standard on
Electrical Protective Equipment for Workers, 7th Edition. 73
12.3 CFR (Code of Federal Regulations) 73
12.4 IEEE (Institute of Electrical and Electronics Engineers) 73
12.5 NFPA (National Fire Protection Association) 74
12.6 Applicable State and Local Codes 74
1.0 INTRODUCTION
Most incidents and injuries related to electrical systems can be
avoided by following the safe work practices described in this
document. Besides the personal pain of suffering an injury, incidents
can result in lost time, medical costs, equipment damage, production
loss, and legal costs.
2.0 SCOPE
This document provides the minimum safety knowledge and
procedures that will allow both individuals and facilities to work
with, or in proximity to, energized high and low voltage sources (in
the language of applicable safety standards, this is formally
designated to be “working near” or “working on” live parts - see
Section 3.0 Definitions). Each individual or facility, however, is
responsible for customizing the information presented here to allow
for details and activities specific to the affected facility.
This practice sets minimum safety rules and safe work
recommendations for the design, operation and maintenance of high
and low voltage systems throughout ChevronTexaco facilities. It is
imperative that, at a minimum, these guidelines be met or exceeded to
enhance employee safety. If more stringent local governmental codes
or accepted employee safety practices, design criteria, etc., exist,
follow those codes or standards.
This document applies to all employees, contractors, and visitors
while in proximity to energized conductors, energized exposed parts
of electrical equipment, or such conductors and equipment that
potentially may become energized.
This practice applies to new or modified high and low voltage
installations. Existing installations need not be physically modified to
comply with this document unless qualified personnel consider such
modifications necessary to protect affected persons from a recognized
hazard.
For the purpose of this practice, low voltage means 1000 volts
nominal or less phase-to-phase or conductor-to-conductor, and high
voltage means voltages above 1000 volts ac, phase-to-phase.
Knowledge of this practice by itself does not make a person a NFPA 70E Part II 1.3
qualified electrical worker. Each site should establish guidelines for NFPA 70E Part II 1-5.4.1
informal and formal training, as well as levels of experience needed
for workers in the electrical field or other workers whose job function
would expose them to a potential electrical hazard.
3.0 DEFINITIONS
The terms listed in this section are used throughout this practice.
Becoming familiar with them prior to reading the document will help
clarify the material.
OSHA 1910.269(x) Affected Employee (or Affected Person)
OSHA 1910.147(b)
(modified) An employee whose job requires him or her to operate a machine or
use equipment that is being serviced or maintained while under
lockout or tagout, or whose job requires him or her to work in an area
in which such servicing or maintenance is being performed.
An employee whose job includes erecting, installing, constructing,
repairing, adjusting, inspecting, operating, or maintaining the
equipment or manufacturing process from a non-electrical
perspective.
ANSI
American National Standards Institute
Approved
Methods, devices, tools, equipment or practices acceptable to the
Company and/or regulatory body having jurisdiction.
Arc Flash Protective Equipment
Equipment used to safeguard personnel from momentary electrical
arcs. May include flame resistant clothing, flash suits, face
protection, hand protection, and/or foot protection.
ASTM
American Society for Testing and Materials
OSHA 1910.269(x) Attendant
An employee assigned to remain immediately outside the entrance to
an enclosed or other designated location to render assistance as
needed to employees inside the space.
OSHA 1910.269(x) Authorized Employee (or Authorized Person)
(modified)
OSHA 1910.147(b) An employee who locks out or tags out machines or equipment in
(modified) order to perform servicing or maintenance on that machine or
equipment. An “affected employee” becomes an “authorized
employee” when duties include performing service or maintenance
covered under this practice and includes performing the lockout/
tagout procedures.
An employee who has been given, by his or her employer, the
training, authority, and responsibility to perform a specific
assignment in an electrical area.
Enclosed Space
A working space, such as a manhole, vault, tunnel, or shaft, that has a
limited means of egress or entry, is designed for periodic employee
entry under normal conditions, and does not contain a hazardous
atmosphere. Under abnormal conditions, however, it may contain a
hazardous atmosphere.
Note: Spaces that are enclosed but not designed for employee entry
under normal operating conditions are not considered enclosed
spaces for the purposes of this practice. Similarly, spaces that are
enclosed and that are expected to contain a hazardous atmosphere
are not considered to be enclosed spaces for the purposes of this
practice.
NESC Energized (Alive, Live)
OSHA 1910.269(x)
Electrically connected to a source of potential difference, or
electrically charged as to have a potential significantly different from
the earth in the vicinity.
OSHA 1910.269(x) Energy Isolating Device
OSHA 1910.147(b)
A physical device that prevents the transmission or release of energy,
including, but not limited to, a manually operated electric circuit
breaker, a disconnect switch, a manually operated switch, a slide gate,
a slip blind, a line valve, blocks, and any similar device with a visible
indication of the position of the device.
Push buttons, selector switches, and other control-circuit-type
devices are not energy isolating devices.
OSHA 1910.269(x) Energy Source
OSHA 1910.147(b)
(modified) Any electrical, mechanical, hydraulic, pneumatic, chemical, nuclear,
thermal, or other energy source that could cause injury to personnel.
Equipotential Grounding (Earthing)
A grounding (earthing) scheme which places the worker in an
envelope of equal potential. When everything that the worker can
touch is of the same potential, no current can flow through the worker
between two different touch points.
OSHA 1910.269(x) Equipment (Electrical)
A general term including material (fittings, devices, appliances,
fixtures, etc.) that is used as part of, or in connection with, an
electrical installation.
Escort
A “qualified employee” (see definition below) who accompanies
non-qualified employees or visitors in the vicinity of electrical
equipment or lines.
Location Manager
General manager of the facility.
Low Voltage
Any electrical circuit that normally operates at 1000 volts nominal or
less phase-to-phase or conductor-to-conductor. However, where
governmental codes stipulate voltages less than 1000 volts phase-to-
phase as high voltage, that voltage should be used as the upper limit.
NESC Manhole
OSHA 1910.269(x)
A subsurface enclosure which personnel may enter for the purpose of
installing, operating, and maintaining submersible equipment or
cable.
Mobile Equipment
This includes but is not limited to cranes, bucket trucks, aerial lifts,
and similar types of equipment.
Near Proximity
A minimum clearance of 10 feet (305 cm) to energized lines and
equipment operating at 50 kV, or less. This distance increases
4 inches (10 cm) for every 10 kV over 50 kV.
Non-hazardous Work
Work that is not considered to be “prohibited,” “restricted,” or
“limited” work. An example is working on control circuits below
50 V ac or dc to ground.
Note: Energized parts that operate at less than 50 volts are not
required to be de-energized to satisfy an “electrically safe work
condition.” However, consideration should be given to the capacity
of the source, any overcurrent protection between the energy source
and the worker, and whether the work task related to the source
operating at less than 50 volts increases exposure to electrical burns
or to explosion from an electric arc.
Non-insulated Conductor
A conductor that has no insulating properties other than air.
Operating System Lock
A keyed lock placed on an electrical distribution system to prevent
unintentional opening of a disconnect. Operating system locks may
be “unique” or “common lock” systems. This is not a personal safety
lock (see Safety Lock, below).
Person-in-Charge (PIC)
A person in charge of work or employees, regardless of his or her
title. Examples include a supervisor, foreman, lineman in charge, lead
people, etc. or a qualified employee who has been authorized and
designated to be locally in charge of Company work.
Potentially Energized
A non-insulated conductor or device that, by nature of design or
location, may be energized by an adjacent energized conductor,
switch closure, or back-feed.
Prohibited Approach Boundary NFPA 70E
Tagout Device
A prominent warning device, such as a tag and a means of
attachment, which can be securely fastened to an energy-isolating
device in accordance with an established procedure, to indicate that
the energy-isolating device and the equipment being controlled must
not be operated until the tagout device is removed.
“Ten (10) Foot” Rule
An unqualified person must maintain a minimum distance of 10 feet
from live parts (see Limited Approach Boundary, Appendix A, Table
A-6).
To prevent physical contact with energized or isolated ungrounded
power lines, equipment or machines should be operated as follows:
the minimum clearance between the lines and every part of the
equipment or machine or its load should be 10 feet (305 cm) for lines
rated 50 kV or below; this distance is increased 4 inches (10 cm) for
each 10 kV above 50 kV.
Touch Potential NFPA 70E
4.0 RESPONSIBILITIES
4.3 Employee
The employee is the person most responsible for his or her own
safety.
• “Qualified” and “authorized” employees should remain
knowledgeable about applicable electrical safety concerns as
contained in this practice, or other practices.
• “Affected” employees should be aware of electrical hazards
where electrical work is not the primary task but where the
opportunity for contact exists (i.e., during lockout/tagout, when
working near open crane rails or motor control centers and
switchgear, around cable ladders, and resetting devices and
equipment).
4.4 Escort
The escort is a “qualified” employee whose responsibility is to
safeguard the people in his or her care and to ensure that safety
regulations are observed.
OSHA 1910.269(l)(1) Only persons qualified in the techniques required to work on live
parts should do this work. Safety conditions outlined in this practice
should be utilized for all work on or near live parts.
NFPA 70E Part II 2.3.8 When persons qualified for live part work must do work on live parts,
OSHA 1910.333(a)(2) and they should insulate and use barriers, as appropriate.
(c)(2)
OSHA 1910.269(l)(2)(i-iii)
and(l)(3)
NFPA 70E Part II To cross the prohibited approach boundary and enter the prohibited
Appendix A, A-1.2.2 - space is considered the same as making contact with live parts. Any
A-1.2.4 work on live parts should utilize the procedures defined under
“Working Inside the Prohibited Approach Boundary” (see
Appendix B, item D).
5.2.1 Hazards
Two primary hazards to consider when working on or near energized
equipment are:
• Flash hazard (relates to the thermal energy of an electrical arc).
• Shock hazard.
The following are examples of activities that could create an
electrical arc:
• Doing any switching with doors open on switchgear or motor
starters.
• Installing or removing circuit breakers or motor starter
contactors with the switchgear bus energized.
• Working on motor control centers with open doors (unless the
power components at 480 or 600 volts are well guarded) or when
removing or installing starters.
• Installing or removing safety grounds.
• Taking voltage measurements.
• Working on live parts.
NFPA 70E Part II 2-1.3.3 5.2.2 Flash Hazard Analysis and Arc Flash Protective
Equipment
Flash hazard analysis should be done before a person approaches any
exposed electrical conductor or circuit part that has not been placed in
an electrically safe work condition.
OSHA 1910.269(l)(6)(i-iii) Establish a flash protection boundary and require that all personnel
crossing the boundary wear appropriate arc flash protective
equipment. This will provide protection from vaporized metal, arc
radiation, or hot gases should an arc flash occur on the equipment.
Two qualified employees should be present to perform the following OSHA 1910.269(l)(1)(i)
types of work:
• Installation, removal, or repair of lines that are energized at more
than 600 volts.
• Installation, removal, or repair of de-energized lines if there is
exposure to contact with other parts energized at more than 600
volts.
• Installation, removal, or repair of any other equipment if the
employee is exposed to parts energized at more than 600 volts.
• Work that uses mechanical equipment (other than insulated aerial
lifts) near parts energized at more than 600 volts.
Two qualified employees do not need to be present to perform the OSHA 1910.269(l)(1)(ii)
following work functions:
• Routine switching if employer verifies that site conditions allow
this function to be performed safely.
• Work using live-line tools, as long as the employee cannot make
contact with live parts through inadvertent reach.
• Emergency repairs to the extent necessary to safeguard the
general public.
OSHA 1910.333(c)(4) Employees may not enter any space that contains live parts unless
NFPA 70E Part II 2-3.4 adequate illumination is provided.
The employer should ensure that, to the extent that other safety-
related conditions permit, the employee works in a position so that a
slip or shock will not bring the employee into contact with live parts.
NFPA 70E Part II 2-3.10 When an employee works in a confined or an enclosed space that
OSHA 1910.333(c)(5) contains live parts, insulating materials such as protective shields or
barriers should be used to prevent inadvertent contact.
5.5.1 Preparation
Best Practice Written Switching Order
A written switching order is recommended before any switching is
performed on the high voltage distribution power system (this does
not include switching of individual motors). The switching order
should be:
• Written by a qualified employee.
• Reviewed by at least one other qualified employee.
• Signed and dated by both people before it is used.
Best Practice Job Briefing for Switching Procedures
Before starting any switching, hold a job briefing. The person in
charge of the switching order and all employees involved in the
switching should attend.
At a minimum, review the following items:
• Reason switching is being performed.
• One line drawing and/or power system status board to assure that
all involved understand what will occur.
• Each step of the switching order.
• The job assignments for all involved (who will do what).
• Safety issues and required PPE.
• If required:
– Electrical clearance requirements and/or Lockout/tagout
issues.
– Location of safety grounds - to be installed or removed and
by whom.
– Other issues (such as operational limitations).
Best Practice 5.5.2 During Switching
During switching, follow the written switching order in the order in
which the steps are written, check off each switching step when
completed, and record the time of completion.
The following switching procedures are recommended:
• The person receiving a switching command should repeat the
switching command and have it confirmed by the person issuing
the order before executing the command.
• If switching commands are given by radio, use a unique
switching channel. Cross talk on the radio during switching
could cause a switching error.
Note: Garments worn as underlayers that neither ignite nor melt and
drip in the course of an exposure to electric arc and related thermal
hazards may provide additional thermal protection. An incidental
amount of elastic used on non-melting-fabric underwear or socks is
permitted.
The employer must ensure that conductive articles are not worn in OSHA 1910.269(l)(6)
close proximity or within reaching distance of live parts. This
includes such items as rings, metal watchbands, unrestrained metal-
framed eyewear, metal dangling jewelry and key chains.
5.6.2 Head Protection NFPA 70E Part II 3-3.3
OSHA 1910.335(a)(1)(iv)
Wear Class E hard hats when working in near proximity to energized
or potentially energized conductors or non-insulated, exposed
equipment parts (See ANSI Z89.1).
Keep hard hats clean and in good condition and do not alter them in
any manner, except for the addition of company-approved markings.
5.6.3 Eye Protection NFPA 70E Part II 3-3.4
OSHA 1910.335(a)(1)(v)
Wear approved safety glasses with non-conductive sideshields at all
times when working with or in close proximity to potentially
energized conductors or exposed non-insulated parts. (See ANSI
Z87.1).
Goggles and/or face shields may also be needed for the task.
– The work on the live parts does not expose the worker to
accidental contact with other live parts in the vicinity of the
task.
– Leather gloves are used if necessary for arc flash protection.
Note: This exception does not apply to working on 277 volt phase-to-
neutral circuits, since the system phase-to-phase voltage rating is 480
volts (480Y/277 volts, three-phase, four-wire).
OSHA 1910.137(b)(2)(viii) Only use gloves that have been dielectrically tested within the
previous six (6) months. (ref. ASTM F496)
ASTM F496 Inspect and air test gloves before each use and immediately following
any incident that can reasonably be suspected as having caused
damage. Air testing is performed by trapping air in the glove and
examining for pin hole or other apparent leakage. (See Appendix K.)
Store gloves in an approved glove bag or an equivalent protective
location. If possible, store gloves with the cuffs down.
Do not exceed the rating on the glove.
Maximum Use
Class Test Voltage (AC)
Voltage (AC)
Remove each live-line tool from service at least every two years and
give it the following examination and tests:
• Thoroughly examine the tool for defects.
• If defects or contaminants that could affect the insulating
qualities or mechanical integrity of the tool are found, the tool
may be repaired and refinished or permanently removed from
service.
• If no defects are detected and no contaminants found, clean and
wax the tool using only a wax approved for live-line tools.
• Use a test method that tests the entire working length of the tool.
• Tools made of fiberglass-reinforced plastic should be tested with
wet conditions applied over the entire working length of the tool.
• If the tool is made of fiberglass-reinforced plastic (FRP), the test OSHA 1910.269(j)(1)(i)
consists of applying 100,000 volts per foot (30 cm) of length for IEEE Std. 978
5 minutes. (ref. IEEE 978)
• Other high voltage tests are acceptable if the employer can
demonstrate that these are equivalent (such as IEEE Std. 978-
1984).
Visually inspect cord-connected portable power tools, extension NFPA 70E Part II 4-3.3
cords, and other cord-connected equipment before each use.
Periodically inspect all extension cords.
Observe the following precautions for any cord- and plug-connected NFPA 70E Part II 4-3.1
equipment not supplied by premises wiring:
• Use a tool equipped with a cord containing an equipment- OSHA 1910.269(i)(2)(ii)
grounding conductor connected to the tool frame and to a ground
at the other end (if the ground in the work environment increases
the hazard, it may be omitted);
OR
• Use a tool of the double-insulated type;
OR
• Use a tool connected to the power supply through an isolating
transformer with an ungrounded secondary.
cable cannot be visibly traced from the point of the cut to one of the
two ends.
5.9 Lockout/Tagout
NFPA 70E Part II Chapter 5 This section applies to servicing and maintaining machines and
OSHA 1910.269(d) equipment where unexpected equipment startup or release of stored
OSHA 1910.147 energy could cause injury. (Reference 29 CFR1910.147).
NFPA 70E 5-1, 2-1.3.2 Conductors and parts of electric equipment that have been de-
energized but have not been locked out or tagged out in accordance
with this Practice are treated as energized parts. For information
about work on energized parts, see Section 5.2.
OSHA 1910.269(d)(8)(ii) When servicing is performed by a group of employees, procedures
OSHA 1910.269(d)(8)(ii)(A), should ensure a level of protection equal to that of individual lockout/
(B), (C), (D) tagout devices.
• Assign one authorized employee the primary responsibility for
the group.
• The designated authorized employee determines the exposure
status of individual group members.
• When more than one crew is involved, assign one authorized
employee the responsibility to coordinate affected groups and
ensure continuity of protection.
• Each person should install a personal lock and tag before start of
work on a machine or equipment. Each person then removes his
or her personal lock and tag at the end of work on a machine or
equipment.
OSHA 1910.269(d)(8)(iii) • During shift changes, procedures should be in place to ensure the
continuity of lockout/tagout protection. There should be an
orderly transfer of lockout/tagout devices between off-going and
on-coming employees.
The procedures in this section apply to exposure to electrical hazards
from work on, near, or with conductors or equipment in electric
utilization installations provided that:
• The procedures address electrical safety hazards.
5.10 Grounding
NFPA 70E Part II Use approved clothing (see the Appendix C “Hazard Risk Category
Table 3-3.9.1 Classifications” table”), rubber gloves with protectors, hard hat, and
eye protection when testing for voltage and placing/removing
grounding devices.
NFPA 70E Part II 2-1.1.3(f), Use visible maintenance grounds (of adequate size to withstand the
3-4.2.2, 3-4.2.3 available short circuit current, see Appendix M) to assure that the
OSHA 1910.269(n)(4) conductors tested as de-energized remain safe.
ASTM F855
OSHA 1910.269(n)(5) • Before any ground is installed, first test the lines or equipment
for absence of voltage unless a previously installed ground is
present.
• Before installing grounds, visually inspect the grounding
equipment to confirm the equipment’s integrity.
OSHA 1910.269(n)(3) • Install temporary protective grounding equipment at the work
NFPA 70E Part II 3-4.2.1 location.
• If installation of grounds at the work location is not feasible,
install grounds on each side of the work location, as close to the
work location as possible.
• Single-point grounding (equipotential grounding, see Section
5.10.2) is an acceptable means of grounding.
• Ground static capacitors (surge protection capacitors and power
factor correction capacitors) before work is done on them even if
there is no possibility of their becoming energized. Wait five
minutes between isolating the capacitor and applying the
grounds.
Caution: Grounds left on equipment when re-energized present a
short circuit hazard. Use a positive method of control to assure
removal before re-energizing (tags, leaving doors or covers open,
leaving the ground cables clearly visible, use of magnetic ground
signs, etc.).
Grounding Previously Energized Part
OSHA 1910.269(n)(6) Before grounding any previously energized part:
• First connect one end of the grounding device to an effective
ground.
• Next, test the previously energized parts for voltage.
• If the parts are free from voltage, the grounding may be
completed.
Using live-line tools, bring the grounding device into contact with the
previously energized part and securely attach it.
• If the test indicates that the parts are not free from voltage, DO
NOT attach the grounds to the part.
• Determine the source of the voltage to ensure that the presence of
this voltage does not prohibit completion of the grounding.
Removing Grounds
Grounds may be removed temporarily for testing. During the test
procedure, consider the previously grounded lines and equipment as
energized.
5.11.1 In General
OSHA 1910.269(p)(1)(i) Inspect the critical safety components of mechanical elevating and
rotating equipment before use on each shift. Check the lower and
upper controls to ensure they are functioning correctly. Follow the
manufacturer’s recommended checklist for the inspection.
OSHA 1910.269(p)(1)(ii) No vehicular equipment with an obstructed view to the rear can be
used for off-highway job sites unless one of the following provisions
is met:
• The vehicle has a reverse signal alarm louder than the
surrounding noise level
OR
• A designated employee signals that it is safe to make
movements.
Heavy equipment, with or without attachments, should have roll-over OSHA 1910.269(p)(1)(iv)
protection that meets the requirements of 29 CFR 1926, Subpart W.
Use lifting equipment within its maximum load rating. OSHA 1910.269(p)(3)
6.2 Substations
Design and construct all new substations in accordance with national
and local codes and in such a manner as to afford maximum
protection of the public, qualified employees and non-qualified
employees.
When modifying existing substations, all efforts should be made to
upgrade the station to current practices.
When designing, modifying or constructing substations, follow these
recommendations:
• Always provide and maintain sufficient access and working
space.
• For all new or revised 600 volt to 38 kV distribution systems,
consider designs that have no accessible conductors and use
insulated cable and dead-front switchgear. (Generally, this
excludes incoming power feeds.)
• Connect all equipment and structures to a common ground grid.
• Draw-out-type breakers should be in the open position when
removed or inserted. The control circuit should also be blocked
or rendered inoperative if design permits.
• Locate all live parts, including the energized racks of static
capacitors, to provide personnel clearance in accordance with
Appendix A, Table A-1.
• Enclose substations that are not totally enclosed and that have
exposed, energized parts by fences at least seven feet
(2.1 meters) in height, with gates secured by suitable locks.
OSHA 1910.269(u)(3) • Ground all conductive fences around substations.
NESC 92E
• When fences are expanded or a section is removed, maintain the
grounding to prevent electrical shock hazards.
• Use bridging (bonding) conductors at all gates to ensure
electrical continuity to the fence on each side of the gate and to
the gate itself.
6.8 Signage
Signs are essential for conveying information regarding a potential
electrical shock hazard. They are also used to convey information
regarding operation and/or maintenance.
6.8.1 Design
Consider the following for signage requirements:
• Material — Make signs out of a durable material that is
appropriate for the anticipated environmental conditions and
expected length of exposure.
• Colors and shapes — Make the color and shape of the sign
consistent with regulatory and consensus practices requirements.
• Lettering — Use large and highly visible lettering and anticipate
dark or low-light situations.
• International symbols — Use internationally accepted symbols
as much as practicable.
6.8.2 Location
OSHA 1910.269(u)(4)(iii) At a minimum, place signs of warning/information as follows:
(v)(4)(iii)
• On all doors, gates, and fence locations for substations.
• On doors to switchgear rooms and on other similar
compartments where potentially energized exposed electrical
parts are located.
• On all transmission and/or distribution structures where
employee or public presence may be expected.
• In the case of multi-support structures, locate the signs on each
supporting member.
• Where a low-voltage bus is supplied from two or more sources
and presents a back-feed opportunity to the high-voltage system
(and an interlock system is not provided), conspicuously display
a sign that warns of this potential problem.
• If temporary alterations must be made to secondary load supply
systems in order to maintain power supply continuity at the
secondary voltage level (thus presenting a back-feed
opportunity), then conspicuously display a sign warning of this
potential problem until the need for the temporary alteration is
abated.
• At roadways or railways where horizontal or vertical clearance
from energized or potentially energized sources is minimal.
(Refer to Appendix A, Table A-2.)
6.9.3 Other
Indicate the voltage of exposed parts at outdoor switchgear or
transformer locations.
Identify disconnects that have no load interrupting or fault closing
rating with clear signs to prevent improper operation.
If a “backfeed” is possible, identify with a warning sign.
If there is an external or “foreign” voltage source, identify the source
with a warning sign.
Identify clearly all disconnect devices and the equipment with which
they are associated.
Identify clearly the rear doors of switchgear compartments.
7.1 Substations
OSHA 1910.269(u)(6) When entering an attended substation, employees other than those
assigned to station work should report to the employee in charge.
Upon reporting, these employees should receive special safety
instructions and a job briefing.
OSHA 1910.269(u)(4)(iv) 7.1.1 Enclosures
Keep substation enclosures locked at all times except while work is
being performed.
OSHA 1910.269(k) 7.1.2 Storing Materials
Keep substation lots free of debris. Do not store materials and
equipment not necessary for distribution and transmission system
repair and maintenance (R & M) in substation lots.
Establish specific storage locations for distribution and transmission,
repair and maintenance materials. Specifically identify and
periodically inspect the storage location. The Location Manager or
his or her designee should approve storage areas.
7.1.3 Inspections
Periodically inspect substations to determine the general condition of
all equipment, including grounding systems.
Qualified employees should perform the inspection.
7.3 Rights-of-Way
Maintain rights-of-way in a clear and orderly condition, and keep
trees and brush well clear of overhead lines.
Prohibit any vehicle that could inadvertently come within 10 feet
(305 cm) of an energized line (see the definition of “Ten (10) Foot”
Rule in Section 3.0) from parking in this area. Examples would be
aerial lifts, mobile cranes, dump trucks, dumpsters, and high lift fork
trucks.
7.3.1 Storage of Materials in Rights-of-Way OSHA 1910.269(k)
8.1 Documentation
Maintain test records on all equipment, rubber goods, and live-line
tools.
8.3 Tools
Establish and maintain records for each person considered a OSHA 1910.269(a)(2)(vii)
“qualified” employee as defined in Section 3.0 of this practice. The
records should include:
• Name and identification
• Date and time of training
• Content of training (such as a course outline or on-the-job
demonstration of skill)
• Basis for acceptance as “qualified” (e.g., test grade,
demonstration of skill, and work location)
9.3.1 Responsibilities
The Employer (e.g., ChevronTexaco) should verify, both through OSHA 1910.269(a)(2)(iii)
regular supervision and inspections conducted at least annually, that NFPA 70E Part II 5-1.2.1
each employee is complying with the required safety-related work OSHA 1910.269(d)(2)
practices.
Note: It is recommended that the facility conduct periodic audits of
the required electrical safe work practices.
Supervisors should make sure procedures are in place and that NFPA 70E Part II 1-3
employees are trained in those procedures.
Employees must follow safe work practice procedures, including NFPA 70E Part II 1-3
using PPE, and understand how an employee’s qualification status
relates to the current task.
• Acceptable methods of insulating/isolating persons from shock NFPA 70E Part II 1-5.3 and
and the most appropriate method for shock isolation/insulation 2-3.8
during both work and rescue.
9.4 “Qualified Employee” Training OSHA 1910.332(b)(3)
Affected employees should be instructed in the purpose and use of OSHA 1910.269(d)(2)(vi)(B)
the energy-control procedure.
All other employees who may work in areas where energy control is OSHA 1910.269(d)(2)(vi)(C)
utilized should be instructed about the procedure and the prohibition
against restarting locked/tagged out machines.
9.7.1 Tagout Only OSHA 1910.269(d)(2)(vii)
9.8 Retraining
Authorized and affected employees should be retrained when the OSHA 1910.269(d)(2)(viii)
following occurs:
• A work assignment changes.
• Equipment changes.
• Energy control procedures change.
• When a periodic inspection reveals inadequacies in the program.
10.2 Contractors
Contractors should be aware of and comply with the following:
• At a minimum, all applicable Facility safety specifications apply
to contractor personnel.
• Contractors are responsible for ensuring that equipment they
supply and use meets Facility safety and health practices.
• Key contractor personnel should be trained in the
ChevronTexaco Electrical Safe Work Practice.
• Contractors need to understand or be informed of, the potential
electrical shock hazards associated with their work.
• Contractors need to notify the appropriate Facility representative
of any changing work conditions that relate to potential electric
shock hazards.
As contractor employees are replaced or added, or contractor work is
further sublet, the primary contractor is responsible for advising or
informing new contractor employees of all electrical safety
considerations that may apply to them under this, or other applicable
rules or specifications.
OSHA 1910.335(b)(3) 10.3 Non-qualified and Non-authorized Personnel
NFPA 70E Part II 2-1.3.5
NFPA 70E Part II 3-4.9 Any person without “qualified” or “authorized” training requires an
escort within areas where physical safe work distance clearances (see
Appendix A, Table A-1 and Table A-2) cannot be met. In general, this
includes all secured electrical installations and conductor/bus
minimal clearance from buildings, rooftops, or other structures.
Examples of non-qualified and non-authorized personnel may
include non-trained visitors, non-electrical maintenance employees
(e.g., grass cutters, painters, roof repair personnel), potential
contractor personnel, and equipment vendors.
12.0 REFERENCES
Engineering Standards, Latest Edition Applies
Appendix A
Clearance and Approach Boundaries Figures and Tables
Live Part
Nominal
Horizontal Clearance of
Voltage Vertical Clearance of Clearance Guard to Live
Unguarded Parts
Phase to Unguarded Parts Parts
Phase
(Table derived from Table 124-1 NESC C2-2002. From IEEE Std. C2-2002. Copyright 2001
IEEE. All rights reserved.)
Minimum Basic Vertical Clearance of Wires, Conductors and Cables Above Ground, Rails or
Water1,2
Note: Voltages are phase-to-ground for effectively grounded circuits.
2. Roads and other areas subject to 15.5 4.7 16.5 5.0 18.5 5.6
truck traffic
4. Other land traversed by vehicles 15.5 4.7 16.5 5.0 18.5 5.6
6. Water areas not subject to 14.0 4.0 15.0 4.6 17.0 5.2
sailboating
8. Areas subject to sailboat Clearances above ground shall be 5 feet (1.5 meters) greater than item 7
launching above.
Where wires, conductors, or cables run along and within the limits of highway or other road right-of-way, but do not
overhang the roadway
10. Roads in rural districts where it 13.5 4.1 14.5 4.4 16.5 5.0
is unlikely that vehicles will cross
under the line
1. For unguarded rigid live parts (fuse cutouts, pole transformer bushing, etc.) clearance, refer to
Table 232-2 NESC C2-2002.
2. For clearances of insulated conductors see Table 232-1 NESC C2 -2002.
3. Increase distances 4 in. (10 cm) for each 10 kV over 22 kV phase to ground.
(Table is based on Table 232-1 NESC C2-2002. From IEEE Std. C2-2002. Copyright 2001 IEEE.
All rights reserved.)
Minimum Clearance
Application 751 V - 22 kV1
Phase to Ground
Feet Meters
A. Buildings
· Vertical
- Over roofs accessible to mobile equipment but not subject to truck 13.5 4.1
traffic
· Vertical over or under catwalks and other surfaces upon which personnel 13.5 4.1
walk
1. Distances shall increase 4 in. (10 cm) for each 10kV over 22 kV phase to ground.
(Table is based on Table 234-1 NESC C2-2002 From IEEE Std. C2-2002. Copyright 2001 IEEE.
All rights reserved.)
in. cm in. cm in cm
(Table is based on Table 235-5 NESC C2-2002 From IEEE Std. C2-2002. Copyright 2001 IEEE.
All rights reserved.)
1. Rules 230C1, C2, and C3 cover cables supported on effectively grounded bare messengers or neutral
conductors, cables having effectively grounded sheaths or shields, or 5 kV non-shielded cables supported
and cabled together on effectively grounded bare messengers.
2. This clearance may be reduced to 4 ft. (1.20 m) where supply conductors of 750 V to 8.7 kV cross a com-
munication line more than 6 ft. (1.80 m) horizontally from a communications structure.
3. This type crossing is not recommended.
4. Trolley and electrified railroad contact conductors of more than 750V should have at least 6 ft. (1.80 m) of
clearance.
(Table is based on Table 233-1 NESC C2-2002. See the NESC table and notes for complete
details. From IEEE Std. C2-2002. Copyright © 2001 IEEE. All rights reserved.)
(Reprinted with permission from NFPA 70E-2000, Standard for Electrical Safety Requirements
for Employee Workplaces, copyright © 2000, National Fire Protection Association, Quincy, MA
02269. This is not the complete and official position of the NFPA on the referenced subject, which
is represented only by the standard in its entirety)
Approach Boundaries
Restricted Prohibited
Limited Approach Boundary Approach Approach
Nominal System Boundary Boundary
Voltage Range,
Phase to Phase Exposed Includes
Exposed Fixed
Moveable Inadvertent
Circuit Part
Conductor Movement Adder
301 - 750 10 ft. 0 in. 3 ft.6 in. 1 ft. 0 in. 0 ft. 1 in.
46.1 - 72.5 kV 10 ft. 0 in. 8 ft.0 in. 3 ft. 3 in. 2 ft. 1 in.
72.6 - 121 kV 10 ft. 8 in. 8 ft.0 in. 3 ft. 2 in. 2 ft. 8 in.
138 - 145 kV 11 ft. 0 in. 10 ft.0 in. 3 ft. 7 in. 3 ft. 1 in.
161 - 169 kV 11 ft. 8 in. 11 ft.8 in. 4 ft. 0 in. 3 ft. 6 in.
230 - 242 kV 13 ft. 0 in. 13 ft.0 in. 5 ft. 3 in. 4 ft. 9 in.
345 -362 kV 15 ft. 4 in. 15 ft.4 in. 8 ft. 6 in. 8 ft. 0 in.
500 - 550 kV 19 ft. 0 in. 19 ft.0 in. 11 ft. 3 in. 10 ft. 9 in.
765 - 800 kV 23 ft. 9 in. 23 ft. 9 in. 14 ft. 11 in. 14 ft. 5 in.
Notes:
1. Affected Persons, persons who are not authorized or qualified must not cross the limited approach boundary.
(See Appendix B, Item B.1; Section 5.2.3)
2. Authorized Persons, specifically task trained, may work inside the limited approach boundary. However, in no
case should an authorized person be allowed to work as close to live parts as the restricted approach boundary
allowed for a qualified person. (See Section 5.2.3)
3. Qualified persons may work up to the restricted approach boundary. For a qualified person to cross the restricted
approach boundary he/she should follow the rules outlined in Appendix B, Item B.2; Section 5.2.3)
4. Qualified Persons who cross the prohibited approach boundary should follow work procedures required to make
contact with live parts. To cross the prohibited approach boundary is considered the same as making contact with
live parts. (See Appendix B, Item B.2)
Appendix B
Limits of Approach
A. Preparing for Approach to Live Parts
Observing a safe approach distance from live parts is an effective means of maintaining electrical
safety. As the distance between a person and the live parts is decreased, the potential for electrical
accident increases.
B. Safe Approach Distance
1. Unqualified Persons
Unqualified persons are safe when they maintain a distance from the live parts, including the
longest conductive object being handled, so that they cannot contact or enter a specified air
insulation distance to the live parts. This safe approach distance is the limited approach boundary.
Unqualified persons must not cross the flash protection boundary unless they are wearing
appropriate personal protective clothing and are under the close supervision of a qualified person.
Note that the flash protection boundary may be greater than the limited approach boundary for
higher capacity systems.
2. Qualified Persons
Determine the flash protection boundary and, if the boundary is to be crossed, use appropriate arc-
flash protective equipment.
For a person to cross the limited approach boundary and enter the limited space, he or she must be
qualified to perform the job/task. An exception to this is that an “authorized person” is permitted
to cross the limited approach boundary if he or she is specifically trained for the task to be done.
To cross the restricted approach boundary and enter the restricted space, the qualified person
must:
– Have a plan that is documented and approved by authorized management.
– Use personal protective equipment appropriate for working on live parts and rated for the
voltage and energy level involved.
– Be certain that no part of the body enters the prohibited space.
– Minimize the risk due to inadvertent movement by keeping as much of the body out of
the restricted space, using only protected body parts in the space as necessary to
accomplish the work.
To cross the prohibited approach boundary and enter the prohibited space is considered the same
as making contact with live parts, the qualified person must:
– Have specified training to work on live parts and be approved by authorized
management.
– Have a documented plan justifying the need to work that close and have it approved by
authorized management.
– Perform a risk analysis.
– Use personal protective equipment appropriate for working on live parts and rated for the
voltage and energy level involved.
Appendix C
Flame Resistant Clothing Recommendations
based upon the incident energy exposure associated with the specific task. As an alternative, the
PPE requirements outlined in Table C-1 (extracted from NFPA 70E Table 3-3.9.1) may be used.
For additional information refer to Tables C-2 and C-3 (NFPA Tables 3-3.9.2 and 3-3.9.3), and
Table C-4 (NFPA Table F-1).
Tables 3-3.9.1, 3-3.9.2, 3-3.9.3 and F-1 reprinted with permission from NFPA 70E-2000, Standard
for Electrical Safety Requirements for Employee Workplaces, copyright ® 2000, National Fire
Protection Association, Quincy, MA 02269. This is not the complete and official position of the
NFPA on the referenced subject which is represented only by the standard in its entirety.
Hazard/
Task (Assumes Equipment is Energized, and Work is V-rated V-rated
Risk
Done Within the Flash Protection Boundary) Gloves Tools
Category
Panelboards or Switchboards rated >240 V and up to 600 V (with molded case or insulated case
circuit breakers) - See Notes 1 and 3
600 V Class Motor Control Centers (MCCs) - See Notes 2 (except as indicated) and 3
Hazard/
Task (Assumes Equipment is Energized, and Work is V-rated V-rated
Risk
Done Within the Flash Protection Boundary) Gloves Tools
Category
600 V Class Switchgear (with power circuit breakers or fused switches) - See Notes 5 and 6
- Insertion or removal 2* Y N
Hazard/
Task (Assumes Equipment is Energized, and Work is V-rated V-rated
Risk
Done Within the Flash Protection Boundary) Gloves Tools
Category
Hazard/
Task (Assumes Equipment is Energized, and Work is V-rated V-rated
Risk
Done Within the Flash Protection Boundary) Gloves Tools
Category
Legend:
V-rated Gloves are gloves, rated and tested for the maximum line-to-line voltage upon which work will be done.
V-rated Tools are tools rated and tested for the maximum line-to-line voltage upon which work will be done.
2* means that a double-layer switching hood and hearing protection are required for this task in addition to the other
Hazard/Risk Category 2 requirements of Table 3-3.9.2 of Part II (ChevronTexaco Note -- Instead of a switching
hood, an 8 cal/cm2 rated faceshield may be used for this task. See Appendix E of this Practice.)
Y = yes (required)
N = no (not required)
Notes:
1. 25 kA short circuit current available, 0.03 second (2 cycle) fault clearing time
2. 65 kA short circuit current available, 0.03 second (2 cycle) fault clearing time
3. For < 10 kA short circuit current available, the Hazard/Risk Category required may be reduced by one Number
4. 65 kA short circuit current available, 0.33 second (20 cycle) fault clearing time
5. 65 kA short circuit current available, up to 1.0 second (60 cycle) fault clearing time
6. For < 25 kA short circuit current available, the Hazard/Risk Category required may be reduced by one Number
Table C-2 Protective Clothing and Personal Protective Equipment (PPE) Matrix
(Extracted from NFPA 70E-2000, Part II, Table 3-3.9.2)
-1
Hazard/Risk Category Number 0 1 2 3 4
(Note 3)
· Shirt (long-sleeve) X
FR Clothing (Note 1)
· Long-sleeve Shirt X X X (Note 9) X
FR Protective Equipment
· Flash Suit Jacket (2-Layer) X
Head Protection
· Hard Hat X X X X
Eye Protection
· Safety Glasses X X X AL AL AL
· Safety Goggles AL AL AL
Legend:
AN = As Needed
AL = Select one in group
AR = As Required
X = Minimum Required
Notes:
1. See Table 3-3.9.3. (ATPV is the Arc Thermal Performance Exposure Value for a garment in cal/cm2.)
2. If voltage-rated gloves are required, the leather protectors worn external to the rubber gloves satisfy this
requirement.
3. Class -1 is only defined if determined by Notes 3 or 6 of Table 3-3.9.1 of Part II.
4. “Regular weight” (minimum 12 oz./yd2 fabric weight), untreated, denim cotton blue jeans are acceptable in lieu of
FR pants. The FR pants used for Hazard/Risk Category 1 shall have a minimum ATPV of 5.
5. Alternate is to use FR coveralls (minimum ATPV of 5) instead of FR shirt and FR pants.
6. If the FR pants have a minimum ATPV of 8, long pants of untreated natural fiber are not required beneath the FR
pants.
7. Alternate is to use FR coveralls (minimum ATPV of 5) over untreated natural fiber pants and T-shirt.
8. A double-layer switching hood and hearing protection are required for the tasks designated 2* in Table 3-3.9.1 of
Part II.
9. Alternate is to use two sets of FR coveralls (each with a minimum ATPV of 5) over untreated natural fiber clothing,
instead of FR coveralls over FR shirt and FR pants over untreated natural fiber clothing.
* ATPV is defined in the ASTM PS58 standard arc test method for flame resistant (FR) fabrics as the incident
energy that would just cause the onset of a second degree burn (1.2 cal/cm 2) EBT is reported according to
ASTM PS58 and is defined as the highest incident energy which did not cause FR fabric breakopen and did not
exceed the second degree burn criteria. EBT is reported when ATPV cannot be measured due to FR fabric
breakopen.
* Note other PPE required for the specific tasks listed in Tables 3-3.9.1 and 3-3.9.2, which include double-layer FR
flash hoods, FR hardhat liners, safety glasses or safety goggles, hard hat, hearing protection, leather gloves,
voltage-rated gloves, and voltage-rated tools.
Appendix D
Sample Calculation of Flash Protection Boundary DC, Arc in
Open Air Ema, and Arc in Cubic Box Emb
Note: Dc = distance in feet of person from arc source for a just curable burn
For systems which are 600 volts and below, the flash protection boundary is 4.0 feet, based on the product
of clearing times of 0.1 seconds and the available fault currents of 50 kA or any combination not to exceed
300 kA cycles (5,000 ampere seconds).
At voltage levels above 600 volts, the flash protection boundary is the distance at which the incident
energy level equals 1.2 cal/cm2.
The flash protection boundary can alternatively be calculated as shown below.
A. Sample Calculation - Flash Protection Boundary Dc (just curable burn distance)
1. Calculation is on a 4,160-volt bus.
2. Transformer MVA (and base MVA) = 10 MVA.
3. Transformer impedance on 10 MVA base = 5.5%.
4. Circuit breaker clearing time = 6 cycles.
Note: Required formulas are located in NFPA 70E-2000, Part II, Appendix B-2
Calculate the short-circuit current:
Isc = {[MVA Base x 106] / [1.732 x V]} x {100 / %Z}
= {[10 x 106] / [1.732 x 4,160]} x {100 / 5.5}
= 25,000
Calculate the power in the arc:
P = 1.732 x 4,160 x 25,000 x 10-6 x .7072
P = 90 MW
Calculate the curable burn distance Dc
Dc = {2.65 x [1.732 x 4,160 x 25,000 x 10-6] x 0.1}1/2
= 6.8 or 7 feet
Or, calculate the curable burn distance Dc using an alternative method:
Dc = [53 x 10 x .1]1/2 = 7.28 feet
B. Sample Calculation — Arc in Open Air Ema
Incident Energy produced by a three-phase arc on systems rated 600 volts and below:
Calculate Maximum open arc incident energy Ema
Ema = (5271)(DA)-1.9593 (tA)[0.0016(Isc)2 - 0.0076(Isc) +0.8938] = Ema in cal/cm2
C.3 Sample Calculation — Arc in Cubic Box Emb -- 480 volt motor starter “bucket” with
upstream protection time of 0.10 second
Incident Energy produced by a three-phase arc on systems rated 600 volts and below:
Calculate Maximum arc in cubic box incident energy Emb
Emb = (1038.7)( DB)-1.4738 (tA)[0.0093(Isc)2 - 0.3453(Isc) + 5.9675] = Emb in cal/cm2
For Isc = 35 kA, tA = 0.10 seconds, DB = 18 inches
Emb = (1038.7)(18)-1.4738 (0.10)[0.0093(35)2 - 0.3453(35) + 5.9675] = 7.7 cal/cm2
Note: This would require a Category 2 PPE system.
Appendix E
Recommended Personal Protective Equipment
Manufacturer and
Item Available Sizes Color
Model No. (Note 6)
Clothing (Note 1)
Insulated Coveralls Workrite, 590NMX-60 Short, Regular, Long Royal Blue, Navy, Khaki
6.0 oz. Nomex IIIA over Chest sizes 34 - 56
9 oz. Nomex insulation
(Note 3)
Optional Insulated Hood Workrite, 577NMX-60 One size fits all Royal Blue, Navy, Khaki
for above, will fit over hard
hat
Men’s Utility Shirt Workrite, 290NMX-45 Sleeve lengths: Short, Light Blue, Navy, Khaki
(long sleeve), Regular, Long
4.5 oz. Nomex IIIA Chest sizes 34 - 54
Women’s Utility Shirt Workrite, 2914xx Sleeve lengths: Short, xx = SL (Light Blue),
(long sleeve), Regular, Long SN (Navy), SK (Khaki)
4.5 oz. Nomex IIIA Sizes 4 - 24
Men’s Utility Shirt Workrite, 290NMX-60 Sleeve lengths: Short, Light Blue, Navy, Khaki
(long sleeve), Regular, Long
6.0 oz. Nomex IIIA Chest sizes 34 - 54
Men’s Western Style Shirt Workrite, 228IND-70 Sleeve lengths: Short, Medium Blue, Navy, Royal
(long sleeve), Regular, Long Blue
7.0 oz. Indura Chest sizes S - XXL
Men’s Utility Shirt Workrite, 298IND-70 Sleeve lengths: Short, Medium Blue,
(long sleeve), Regular, Long Khaki
7.0 oz. Indura Chest sizes S - XXL
Men’s Dress Uniform Shirt Bulwark, SCG2LD Regular, S - 3XL Light Blue Denim
(long sleeve), Long M - 3XL
7.0 oz. Indura
Men’s Industrial Pants Workrite, 400NMX-75 Waist 28 - 34, Inseam to Royal Blue, Navy, Spruce
7.5 oz. Nomex IIIA 34; Waist 35 - 50, Inseam
to 36
Manufacturer and
Item Available Sizes Color
Model No. (Note 6)
Men’s Jean-cut Pants Workrite, 410NMX-75 Waist 28 - 34, Inseam to Royal Blue, Navy
7.5 oz. Nomex IIIA 34; Waist 35 - 50, Inseam
to 36
Men’s Denim Jean Bulwark, PCJ2DD Waist 28 - 50, Inseam to Blue Denim
Twill Weave, 37
11.5 oz. Indura
Women’s Industrial Pants Workrite, 4317Sx Sizes 4 - 24, Inseam to 34 x = B (Royal Blue),
7.5 oz. Nomex IIIA N (Navy)
Women’s Work Pant, Twill Bulwark, PCW3NV Sizes 4 - 24, Inseam to 34 Navy
Weave, 9 oz Indura
Hard Hat Liner Workrite, 7900SZ One size fits all Black
4.5 oz. Nomex IIIA over
9 oz. Nomex insulation
Rainwear
PVC on a 1.6 oz. Nomex/ Nasco, ArcLite™ 1000 Small - 5X Large (contact Burnt Orange
Kevlar Blend (Note 4) Series (1103JBO for Nasco for sizing)
jacket, 1101TBO for
overall)
PVC on a 2.7 oz Nomex/ Nasco, ArcTuff™ 2000 Small - 5X Large (contact Yellow, Fluorescent
Kevlar Blend (Note 4) Series Nasco for sizing) Orange
Manufacturer and
Item Available Sizes Color
Model No. (Note 6)
Faceshield (for up to 8
cal/cm2 exposure -- i.e.,
Hazard/Risk Category 2)
Face-Fit™ Faceshield, 8 x Oberon, For use with integral Hard Slight green tint
14 in, Arc-X™ Resin 21ARCAF-C+500 Cap (supplied) -- Other
0.080 inch thick window, models available to fit
with anti-fog coating user's specific hard hat
Flash Hood
10 oz Nomex IIIA with a 6 Nasco, ArcHood N/A Yellow, Orange, with other
oz double-layer front, colors available
ArcShield™ plastic
chemical “alloy” window,
light greenish amber tint.
Rated 45 cal/cm2
Hand Protection -
Voltage-Rated Gloves
(Note 5)
Manufacturer and
Item Available Sizes Color
Model No. (Note 6)
Glove Liners for use with Salisbury (see Salisbury One size fits all N/A
all rubber gloves under catalog)
various weather
conditions (cotton, fleece,
wool, and thermal)
Notes:
1 Other women’s workwear is available for maternity wear; contact Workrite.
2 This garment qualifies as “2 layers” of FR clothing. A cost-effective “Hazard/Risk Category 4” FR
clothing system could include this garment worn over 4.5 oz. Nomex coveralls and untreated natural
fiber shirt or T-shirt and untreated natural fiber pants, worn with an appropriately rated switching
hood.
3 This garment qualifies as “3-layer” FR clothing. A cost-effective “Hazard/Risk Category 4” FR cloth-
ing system could include this garment worn over an untreated natural fiber shirt, T-shirt, and denim
blue jeans, worn with an appropriately rated switching hood.
4 A cost-effective “Hazard/Risk Category 4” FR clothing system could include this garment worn over
4.5 oz. Nomex fabric, worn with an appropriately rated switching hood. The burnt-orange ArcLite™/
Nomex layered system has been tested and met an ATPV of 40.
5 Where more than one “high voltage” level exists at a facility (e.g., 4.16 kV and 13.8 kV), recommend
keeping only the highest “Class” of high voltage glove available for use.
6 Company addresses, phone numbers, and website links:
Bulwark®
545 Marriott Drive
Nashville, TN 37214
(800-667-0700 --United States and Canada call toll free)
http://www.bulwark.com/
Manufacturer and
Item Available Sizes Color
Model No. (Note 6)
Oberon Company
435 Coggeshall Street
P.O. Box 61008
New Bedford, MA 02746-0008
(800-322-3348 -- United States and Canada call toll free)
http://www.oberoncompany.com/index.en.html
Workrite®
500 East Third Street
P.O. Box 1192
Oxnard, CA 93032-1192
(805-483-0175, 800-521-1888 -- United States and Canada call toll free)
http://www.workrite.com/
Appendix F
Work Area Protection
A. Introduction
Work area protection is the adequate safeguarding or protecting of pedestrians, motorists, workers and
equipment by the use of adequate barriers, warning signs, lights, flags, high visibility vests, traffic cones,
high-level standards, barricade rope or flagpersons on approaches and in the vicinity of work areas,
excavations, open manholes or parked equipment.
Work area protection is accomplished by the use of good informative and protective devices keeping in
mind that a safe installation requires the use of these devices in relation to the location of the employees
and the equipment involved. The use of these devices must be coupled with proper planning, design,
installation, inspection, maintenance and the use of good common sense and will greatly minimize the
possibility of accidents. It is of the utmost importance that the work area be properly identified and that
warning devices say what they mean, to convey the message to the employees well in advance of arrival at
the work area.
The employee must be warned in advance, then regulated and guided safely through or around the work
area. Proper work area protection should be planned to ensure the safety and protection of the public and
the equipment.
High visibility vests or equivalent should be worn by employees whenever working in or around vehicular
traffic areas. If work is to be done at night, wear reflectorized material.
B. Devices to be Used
Only those signs, standards, barricades, flags and cones that conform to federal, state or local codes should
be used.
All state and local traffic codes should be followed when providing work area protection.
During night operations or in periods of reduced visibility, take special precautions. Use adequate
warning equipment, which may include flashing lights, flares or area illumination.
Remove warning devices and equipment as soon as the hazard is eliminated.
Store warning devices and equipment in a proper manner when not in use or removed form the work area.
C. Flagpersons
Use flagpersons or other appropriate traffic controls whenever there is any doubt that effective protection
can be provided by signs, signals and barricades and where state or local standards dictate their use.
Flagpersons should:
Wear a blaze orange warning vest or other high visibility garment. Warning garments worn at night should
be of a reflectorized material.
Place themselves in a protected position to reduce possibility of injury from traffic.
Insure they can fully observe the operation and guide vehicular traffic in such a manner as to minimize the
possibility of accidents or injury.
Face traffic when giving signals.
Appendix G
Job Briefing Checklist
Planning Checklist
Identify
o What are the hazards? o Potential for arc flash
Ask
o Can the equipment be de-energized? o Is a “standby person” required?
Check
o Job plans o Safety procedures
Know
o What is the job?
o Who is in charge?
Think
o About the extra event … What if? o Use the right tools and equipment, including PPE
o Confined space rescue available if required? o Is the required emergency equipment available?
o Extinguisher? o
Appendix H
Substation Project Installation Safety Assessment Checklist
18. Live line tools are used for all high voltage work. o o o
Appendix I
Substation Inspection Checklist
2. Gates Locked o o o
3. Fence Secure o o o
NAME OF EQUIPMENT
TRANSFORMER
Name on transformer
Top Oil Temperature
Oil Level
Tank Pressure, psi
Fan operation
Pump operation
Oil leaks?
Abnormal noises?
Condition of:
· Paint
· Bushings
· Terminals, bushing studs, other electrical connections -
evidence of corrosion or heating?
· Radiators
CIRCUIT BREAKER
Name on circuit breaker
Oil leaks?
Condition of:
· Paint
· Bushings
· Terminals, bushing studs, other electrical connections -
evidence of corrosion or heating?
SWITCHES
Name on switch
Switch operating handle and operating pipe bonded to
ground?
Switching ground mat available and bonded to ground?
Switch fully closed or open?
Evidence of corrosion or heating?
STATION BATTERIES
Condition of batteries and terminals
Volts
Battery Station Ventilation
BATTERY CHARGER
Volts
Condition of eyewash station
NAME OF EQUIPMENT
ENCLOSED SWITCHGEAR
Names on switches
“Feed to”, Fed From” information on switch
Condition of cabinet:
· Paint
· Doors closed
· Sign of corrosion or heating?
· Cabinet grounded
OTHER EQUIPMENT
General Comments:
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
Appendix J
Electrical Control Room Inspection Checklist
General Comments:
Appendix K
Test Procedure for Daily Inspection of Rubber Gloves
Inspect insulating rubber gloves and air test the gloves daily, before use, and any other time when it could
be reasonably suspected that damage has occurred.
The following procedure outlines the air test:
Appendix L
Safety Tags
Appendix M
Grounding Cable and Jumper Ratings
Withstand Rating
Grounding Cable Size, Continuous
AWG
Symmetrical kA rms Ultimate Capacity2 Symmetrical kA rms 60 Hz Current
60 Hz
Rating,
A rms
15 cycles 30 cycles 6 cycles 15 cycles 30 cycles 60 cycles
Copper Aluminum3 60 Hz
(250 ms) (500 ms) (100 ms) (250 ms) (500 ms) (1 s)
1. Withstand and ultimate short circuit properties are based on performance with surges not exceeding 20%
asymmetry factor.
2. Ultimate capacity represents a calculated symmetrical current which the cable or jumper is capable of con-
ducting for the specified time. These currents are based upon the fusing (melting) current-time values for
copper, derived from I. M. Onderdonk’s equation with an ambient temperature of 40oC.
3. Aluminum cables must be two AWG sizes larger than copper for equal current ratings.
Appendix N
Equipotential Grounding Techniques
Remote Grounding
Personal Grounding
Appendix O
Principles of Electrical Safety
Understand, accept, and practice all of the following safety principles:
Maintain Distance
An effective way to maintain safety is to keep a safe distance from live parts.
Test Before Touch
Consider every electrical conductor or circuit part energized until proven otherwise.
De-energize if Possible
De-energize all equipment before you work "on" or "near" exposed electrical conductors or circuit parts.
Recognize Potential Hazard
Installing barriers, barricades, and de-energizing (switching) are potentially hazardous tasks.
Plan Every Job
Plan every job carefully, regardless of size.
Anticipate Unexpected Events
Before beginning work, ask "What if..?" and decide what you will do if something goes wrong.
Use the Right Tool for the Job
Identify the tools required and do not perform the task until you have the correct tool.
Use Procedures as Tools
Establish and adhere to procedures to accomplish a job safely.
Isolate the Equipment (put in an Electrically Safe Work Condition)
Lock, Tag, Try and Test.
Identify the Hazard
Identify and address each hazard.
Minimize the Hazard
Use insulating barriers, safety grounds, and safe work practices.
Protect the Person
Avoid exposure to electrical hazards wherever possible. Use appropriate personal protective equipment
(PPE) for each potential hazard.
Assess People’s Abilities
Evaluate each person’s qualifications, capabilities, and physical and mental state at the time a potentially
hazardous task is to be done.
Audit These Principles
Audit the principles frequently to verify that they reflect current practices.
Appendix P
OSHA Regulations (Standards - 29 CFR)
Text version
Regulations (Standards - 29
CFR)
Electrical protective devices. - 1910.137
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
(a)(1)
(a)(1)(i)
(a)(1)(ii)
(a)(1)(ii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 2 of 12
(a)(1)(ii)(B)
(a)(1)(ii)(C)
(a)(1)(ii)(D)
(a)(1)(ii)(E)
..1910.137(a)(1)(ii)(F)
(a)(1)(ii)(F)
(a)(1)(ii)(G)
(a)(1)(ii)(H)
(a)(1)(iii)
(a)(1)(iv)
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 2 of 12
(a)(1)(ii)(B)
(a)(1)(ii)(C)
(a)(1)(ii)(D)
(a)(1)(ii)(E)
..1910.137(a)(1)(ii)(F)
(a)(1)(ii)(F)
(a)(1)(ii)(G)
(a)(1)(ii)(H)
(a)(1)(iii)
(a)(1)(iv)
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 3 of 12
glove.
(a)(2)
"Electrical requirements."
(a)(2)(i)
(a)(2)(i)(A)
The proof test shall reliably indicate that the equipment can
withstand the voltage involved.
(a)(2)(i)(B)
..1910.137(a)(2)(i)(C)
(a)(2)(i)(C)
(a)(2)(ii)
When the a-c proof test is used on gloves, the 60-hertz proof-test
current may not exceed the values specified in Table I-2 at any
time during the test period.
(a)(2)(ii)(A)
If the a-c proof test is made at a frequency other than 60 hertz, the
permissible proof-test current shall be computed from the direct
ratio of the frequencies.
(a)(2)(ii)(B)
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 4 of 12
For the test, gloves (right side out) shall be filled with tap water
and immersed in water to a depth that is in accordance with Table
I-4. Water shall be added to or removed from the glove, as
necessary, so that the water level is the same inside and outside
the glove.
(a)(2)(ii)(C)
(a)(2)(iii)
..1910.137(a)(2)(iv)
(a)(2)(iv)
(a)(3)
(a)(3)(i)
(a)(3)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 5 of 12
(a)(3)(ii)(A)
(a)(3)(ii)(B)
(b)
(b)(1)
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 6 of 12
(b)(2)
..1910.137(b)(2)(i)
(b)(2)(i)
(b)(2)(ii)
(b)(2)(iii)
(b)(2)(iii)(A)
(b)(2)(iii)(B)
(b)(2)(iii)(C)
(b)(2)(iii)(D)
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 7 of 12
(b)(2)(iii)(E)
..1910.137(b)(2)(iv)
(b)(2)(iv)
(b)(2)(v)
(b)(2)(vi)
(b)(2)(vii)
(b)(2)(vii)(A)
(b)(2)(vii)(B)
Any other class of glove may be used for similar work without
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 8 of 12
..1910.137(b)(2)(viii)
(b)(2)(viii)
(b)(2)(ix)
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 9 of 12
(b)(2)(x)
(b)(2)(x)(A)
Rubber insulating line hose may be used in shorter lengths with the
defective portion cut off.
(b)(2)(x)(B)
(b)(2)(x)(C)
..1910.137(b)(2)(x)(D)
(b)(2)(x)(D)
(b)(2)(xi)
(b)(2)(xii)
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 10 of 12
Note: The d-c voltages listed in this table are not appropriate for
proof testing rubber insulating line hose or covers. For this
equipment, d -c proof tests shall use a voltage high enough to
indicate that the equipment can be safely used at the voltages
listed in Table I-4. See ASTM D 1050-90 and ASTM D 1049-88 for
further information on proof tests for rubber insulating line hose
and covers.
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 11 of 12
| |
| AC proof test | DC proof test
|____________________|__________________________
| | | |
Class of glove | mm. | in. | mm. | in.
___________________|___________|________|___________|______________
| | | |
0..................| 38 | 1.5 | 38 | 1.5
1..................| 38 | 1.5 | 51 | 2.0
2..................| 64 | 2.5 | 76 | 3.0
3..................| 89 | 3.5 | 102 | 4.0
4..................| 127 | 5.0 | 153 | 6.0
___________________|___________|________|___________|_____________
Footnote(1) The water level is given as the clearance from the cuff
of the glove to the water line, with a tolerance of + or - 13 mm. (+
or - 0.5 in.).
Footnote(2) If atmospheric conditions make the specified clearances
impractical, the clearances may be increased by a maximum of 25 mm.
(1 in.).
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
Electrical protective devices. - 1910.137 Page 12 of 12
___________________________________________________________________
|
Type of equipment | When to test
___________________________|______________________________________
|
Rubber insulating line hose| Upon indication that insulating value
| is suspect.
Rubber insulating covers | Upon indication that insulating value
| is suspect.
Rubber insulating blankets | Before first issue and every 12 months
| thereafter(1).
Rubber insulating gloves | Before first issue and every 6 months
| thereafter(1).
Rubber insulating sleeves | Before first issue and every 12 months
| thereafter(1).
___________________________|_______________________________________
Footnote(1) If the insulating equipment has been electrically
tested but not issued for service, it may not be placed into service
unless it has been electrically tested within the previous 12 months.
http://www.osha-slc.gov/OshStd_data/1910_0137.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 1 of 18
Text version
Regulations (Standards - 29
CFR)
The control of hazardous energy
(lockout/tagout). - 1910.147
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
Scope, application and purpose -
(a)(1)
Scope
(a)(1)(i)
This standard covers the servicing and maintenance of machines
and equipment in which the unexpected energization or start up
of the machines or equipment, or release of stored energy could
cause injury to employees. This standard establishes minimum
performance requirements for the control of such hazardous
energy.
(a)(1)(ii)
This standard does not cover the following:
(a)(1)(ii)(A)
Construction, agriculture and maritime employment;
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 2 of 18
(a)(1)(ii)(B)
Installations under the exclusive control of electric utilities for the
purpose of power generation, transmission and distribution,
including related equipment for communication or metering; and
(a)(1)(ii)(C)
Exposure to electrical hazards from work on, near, or with
conductors or equipment in electric utilization installations, which is
covered by Subpart S of this part; and
..1910.147(a)(1)(ii)(D)
(a)(1)(ii)(D)
Oil and gas well drilling and servicing.
(a)(2)
Application.
(a)(2)(i)
This standard applies to the control of energy during servicing
and/or maintenance of machines and equipment.
(a)(2)(ii)
Normal production operations are not covered by this standard
(See Subpart O of this Part). Servicing and/or maintenance which
takes place during normal production operations is covered by this
standard only if:
(a)(2)(ii)(A)
An employee is required to remove or bypass a guard or other
safety device; or
(a)(2)(ii)(B)
An employee is required to place any part of his or her body into an
area on a machine or piece of equipment where work is actually
performed upon the material being processed (point of operation)
or where an associated danger zone exists during a machine
operating cycle.
Note: Exception to paragraph (a)(2)(ii): Minor tool changes
and adjustments, and other minor servicing activities, which take
place during normal production operations, are not covered by this
standard if they are routine, repetitive, and integral to the use of
the equipment for production, provided that the work is performed
using alternative measures which provide effective protection (See
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 2 of 18
(a)(1)(ii)(B)
Installations under the exclusive control of electric utilities for the
purpose of power generation, transmission and distribution,
including related equipment for communication or metering; and
(a)(1)(ii)(C)
Exposure to electrical hazards from work on, near, or with
conductors or equipment in electric utilization installations, which is
covered by Subpart S of this part; and
..1910.147(a)(1)(ii)(D)
(a)(1)(ii)(D)
Oil and gas well drilling and servicing.
(a)(2)
Application.
(a)(2)(i)
This standard applies to the control of energy during servicing
and/or maintenance of machines and equipment.
(a)(2)(ii)
Normal production operations are not covered by this standard
(See Subpart O of this Part). Servicing and/or maintenance which
takes place during normal production operations is covered by this
standard only if:
(a)(2)(ii)(A)
An employee is required to remove or bypass a guard or other
safety device; or
(a)(2)(ii)(B)
An employee is required to place any part of his or her body into an
area on a machine or piece of equipment where work is actually
performed upon the material being processed (point of operation)
or where an associated danger zone exists during a machine
operating cycle.
Note: Exception to paragraph (a)(2)(ii): Minor tool changes
and adjustments, and other minor servicing activities, which take
place during normal production operations, are not covered by this
standard if they are routine, repetitive, and integral to the use of
the equipment for production, provided that the work is performed
using alternative measures which provide effective protection (See
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 3 of 18
(a)(2)(iii)(A)
Work on cord and plug connected electric equipment for which
exposure to the hazards of unexpected energization or start up of
the equipment is controlled by the unplugging of the equipment
from the energy source and by the plug being under the exclusive
control of the employee performing the servicing or maintenance.
(a)(2)(iii)(B)
Hot tap operations involving transmission and distribution systems
for substances such as gas, steam, water or petroleum products
when they are performed on pressurized pipelines, provided that
the employer demonstrates that-
(a)(2)(iii)(B)(1)
continuity of service is essential;
(a)(2)(iii)(B)(2)
shutdown of the system is impractical; and
(a)(2)(iii)(B)(3)
documented procedures are followed, and special equipment is
used which will provide proven effective protection for employees.
(a)(3)
Purpose.
(a)(3)(i)
This section requires employers to establish a program and utilize
procedures for affixing appropriate lockout devices or tagout
devices to energy isolating devices, and to otherwise disable
machines or equipment to prevent unexpected energization, start
up or release of stored energy in order to prevent injury to
employees.
(a)(3)(ii)
When other standards in this part require the use of lockout or
tagout, they shall be used and supplemented by the procedural and
training requirements of this section.
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 4 of 18
(b)
Definitions applicable to this section.
Affected employee. An employee whose job requires him/her to
operate or use a machine or equipment on which servicing or
maintenance is being performed under lockout or tagout, or whose
job requires him/her to work in an area in which such servicing or
maintenance is being performed.
Authorized employee. A person who locks out or tags out
machines or equipment in order to perform servicing or
maintenance on that machine or equipment. An affected employee
becomes an authorized employee when that employee's duties
include performing servicing or maintenance covered under this
section.
Capable of being locked out. An energy isolating device is
capable of being locked out if it has a hasp or other means of
attachment to which, or through which, a lock can be affixed, or it
has a locking mechanism built into it. Other energy isolating
devices are capable of being locked out, if lockout can be achieved
without the need to dismantle, rebuild, or replace the energy
isolating device or permanently alter its energy control capability.
Energized. Connected to an energy source or containing residual
or stored energy.
Energy isolating device. A mechanical device that physically
prevents the transmission or release of energy, including but not
limited to the following: A manually operated electrical circuit
breaker; a disconnect switch; a manually operated switch by which
the conductors of a circuit can be disconnected from all ungrounded
supply conductors, and, in addition, no pole can be operated
independently; a line valve; a block; and any similar device used to
block or isolate energy. Push buttons, selector switches and other
control circuit type devices are not energy isolating devices.
Energy source. Any source of electrical, mechanical, hydraulic,
pneumatic, chemical, thermal, or other energy.
Hot tap. A procedure used in the repair, maintenance and services
activities which involves welding on a piece of equipment
(pipelines, vessels or tanks) under pressure, in order to install
connections or appurtenances. it is commonly used to replace or
add sections of pipeline without the interruption of service for air,
gas, water, steam, and petrochemical distribution systems.
Lockout. The placement of a lockout device on an energy isolating
device, in accordance with an established procedure, ensuring that
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 5 of 18
(c)
General -
(c)(1)
Energy control program. The employer shall establish a program
consisting of energy control procedures, employee training and
periodic inspections to ensure that before any employee performs
any servicing or maintenance on a machine or equipment where
the unexpected energizing, startup or release of stored energy
could occur and cause injury, the machine or equipment shall be
isolated from the energy source and rendered inoperative.
(c)(2)
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 6 of 18
Lockout/tagout.
(c)(2)(i)
If an energy isolating device is not capable of being locked out, the
employer's energy control program under paragraph (c)(1) of this
section shall utilize a tagout system.
(c)(2)(ii)
If an energy isolating device is capable of being locked out, the
employer's energy control program under paragraph (c)(1) of this
section shall utilize lockout, unless the employer can demonstrate
that the utilization of a tagout system will provide full employee
protection as set forth in paragraph (c)(3) of this section.
(c)(2)(iii)
After January 2, 1990, whenever replacement or major repair,
renovation or modification of a machine or equipment is performed,
and whenever new machines or equipment are installed, energy
isolating devices for such machine or equipment shall be designed
to accept a lockout device.
(c)(3)
Full employee protection.
(c)(3)(i)
When a tagout device is used on an energy isolating device which is
capable of being locked out, the tagout device shall be attached at
the same location that the lockout device would have been
attached, and the employer shall demonstrate that the tagout
program will provide a level of safety equivalent to that obtained by
using a lockout program.
..1910.147(c)(3)(ii)
(c)(3)(ii)
In demonstrating that a level of safety is achieved in the tagout
program which is equivalent to the level of safety obtained by using
a lockout program, the employer shall demonstrate full compliance
with all tagout-related provisions of this standard together with
such additional elements as are necessary to provide the equivalent
safety available from the use of a lockout device. Additional means
to be considered as part of the demonstration of full employee
protection shall include the implementation of additional safety
measures such as the removal of an isolating circuit element,
blocking of a controlling switch, opening of an extra disconnecting
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 7 of 18
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 8 of 18
them; and
..1910.147(c)(4)(ii)(D)
(c)(4)(ii)(D)
Specific requirements for testing a machine or equipment to
determine and verify the effectiveness of lockout devices, tagout
devices, and other energy control measures.
(c)(5)
Protective materials and hardware.
(c)(5)(i)
Locks, tags, chains, wedges, key blocks, adapter pins, self -locking
fasteners, or other hardware shall be provided by the employer for
isolating, securing or blocking of machines or equipment from
energy sources.
(c)(5)(ii)
Lockout devices and tagout devices shall be singularly identified;
shall be the only devices(s) used for controlling energy; shall not be
used for other purposes; and shall meet the following
requirements:
(c)(5)(ii)(A)
Durable.
(c)(5)(ii)(A)(1)
Lockout and tagout devices shall be capable of withstanding the
environment to which they are exposed for the maximum period of
time that exposure is expected.
(c)(5)(ii)(A)(2)
Tagout devices shall be constructed and printed so that exposure to
weather conditions or wet and damp locations will not cause the tag
to deteriorate or the message on the tag to become illegible.
(c)(5)(ii)(A)(3)
Tags shall not deteriorate when used in corrosive environments
such as areas where acid and alkali chemicals are handled and
stored.
..1910.147(c)(5)(ii)(B)
(c)(5)(ii)(B)
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 9 of 18
(c)(6)
Periodic inspection.
(c)(6)(i)
The employer shall conduct a periodic inspection of the energy
control procedure at least annually to ensure that the procedure
and the requirements of this standard are being followed.
(c)(6)(i)(A)
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 10 of 18
(c)(6)(ii)
The employer shall certify that the periodic inspections have been
performed. The certification shall identify the machine or
equipment on which the energy control procedure was being
utilized, the date of the inspection, the employees included in the
inspection, and the person performing the inspection.
(c)(7)
Training and communication.
(c)(7)(i)
The employer shall provide training to ensure that the purpose and
function of the energy control program are understood by
employees and that the knowledge and skills required for the safe
application, usage, and removal of the energy controls are acquired
by employees. The training shall include the following:
(c)(7)(i)(A)
Each authorized employee shall receive training in the recognition
of applicable hazardous energy sources, the type and magnitude of
the energy available in the workplace, and the methods and means
necessary for energy isolation and control.
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 11 of 18
(c)(7)(i)(B)
Each affected employee shall be instructed in the purpose and use
of the energy control procedure.
(c)(7)(i)(C)
All other employees whose work operations are or may be in an
area where energy control procedures may be utilized, shall be
instructed about the procedure, and about the prohibition relating
to attempts to restart or reenergize machines or equipment which
are locked out or tagged out.
(c)(7)(ii)
When tagout systems are used, employees shall also be trained in
the following limitations of tags:
..1910.147(c)(7)(ii)(A)
(c)(7)(ii)(A)
Tags are essentially warning devices affixed to energy isolating
devices, and do not provide the physical restraint on those devices
that is provided by a lock.
(c)(7)(ii)(B)
When a tag is attached to an energy isolating means, it is not to be
removed without authorization of the authorized person responsible
for it, and it is never to be bypassed, ignored, or otherwise
defeated.
(c)(7)(ii)(C)
Tags must be legible and understandable by all authorized
employees, affected employees, and all other employees whose
work operations are or may be in the area, in order to be effective.
(c)(7)(ii)(D)
Tags and their means of attachment must be made of materials
which will withstand the environmental conditions encountered in
the workplace.
(c)(7)(ii)(E)
Tags may evoke a false sense of security, and their meaning needs
to be understood as part of the overall energy control program.
(c)(7)(ii)(F)
Tags must be securely attached to energy isolating devices so that
they cannot be inadvertently or accidentally detached during use.
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 12 of 18
(c)(7)(iii)
Employee retraining.
..1910.147(c)(7)(iii)(A)
(c)(7)(iii)(A)
Retraining shall be provided for all authorized and affected
employees whenever there is a change in their job assignments, a
change in machines, equipment or processes that present a new
hazard, or when there is a change in the energy control
procedures.
(c)(7)(iii)(B)
Additional retraining shall also be conducted whenever a periodic
inspection under paragraph (c)(6) of this section reveals, or
whenever the employer has reason to believe that there are
deviations from or inadequacies in the employee's knowledge or
use of the energy control procedures.
(c)(7)(iii)(C)
The retraining shall reestablish employee proficiency and introduce
new or revised control methods and procedures, as necessary.
(c)(7)(iv)
The employer shall certify that employee training has been
accomplished and is being kept up to date. The certification shall
contain each employee's name and dates of training.
(c)(8)
Energy isolation. Lockout or tagout shall be performed only by
the authorized employees who are performing the servicing or
maintenance.
(c)(9)
Notification of employees. Affected employees shall be notified
by the employer or authorized employee of the application and
removal of lockout devices or tagout devices. Notification shall be
given before the controls are applied, and after they are removed
from the machine or equipment.
..1910.147(d)
(d)
Application of control. The established procedures for the
application of energy control (the lockout or tagout procedures)
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 13 of 18
shall cover the following elements and actions and shall be done in
the following sequence:
(d)(1)
Preparation for shutdown. Before an authorized or affected
employee turns off a machine or equipment, the authorized
employee shall have knowledge of the type and magnitude of the
energy, the hazards of the energy to be controlled, and the method
or means to control the energy.
(d)(2)
Machine or equipment shutdown. The machine or equipment
shall be turned off or shut down using the procedures established
for the machine or equipment. An orderly shutdown must be
utilized to avoid any additional or increased hazard(s) to employees
as a result of the equipment stoppage.
(d)(3)
Machine or equipment isolation. All energy isolating devices
that are needed to control the energy to the machine or equipment
shall be physically located and operated in such a manner as to
isolate the machine or equipment from the energy source(s).
(d)(4)
Lockout or tagout device application.
(d)(4)(i)
Lockout or tagout devices shall be affixed to each energy isolating
device by authorized employees.
..1910.147(d)(4)(ii)
(d)(4)(ii)
Lockout devices, where used, shall be affixed in a manner to that
will hold the energy isolating devices in a "safe" or "off" position.
(d)(4)(iii)
Tagout devices, where used, shall be affixed in such a manner as
will clearly indicate that the operation or movement of energy
isolating devices from the "safe" or "off" position is prohibited.
(d)(4)(iii)(A)
Where tagout devices are used with energy isolating devices
designed with the capability of being locked, the tag attachment
shall be fastened at the same point at which the lock would have
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 14 of 18
been attached.
(d)(4)(iii)(B)
Where a tag cannot be affixed directly to the energy isolating
device, the tag shall be located as close as safely possible to the
device, in a position that will be immediately obvious to anyone
attempting to operate the device.
(d)(5)
Stored energy.
(d)(5)(i)
Following the application of lockout or tagout devices to energy
isolating devices, all potentially hazardous stored or residual energy
shall be relieved, disconnected, restrained, and otherwise rendered
safe.
..1910.147(d)(5)(ii)
(d)(5)(ii)
If there is a possibility of reaccumulation of stored energy to a
hazardous level, verification of isolation shall be continued until the
servicing or maintenance is completed, or until the possibility of
such accumulation no longer exists.
(d)(6)
Verification of isolation. Prior to starting work on machines or
equipment that have been locked out or tagged out, the authorized
employee shall verify that isolation and deenergization of the
machine or equipment have been accomplished.
(e)
Release from lockout or tagout. Before lockout or tagout
devices are removed and energy is restored to the machine or
equipment, procedures shall be followed and actions taken by the
authorized employee(s) to ensure the following:
(e)(1)
The machine or equipment. The work area shall be inspected to
ensure that nonessential items have been removed and to ensure
that machine or equipment components are operationally intact.
(e)(2)
Employees.
(e)(2)(i)
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 15 of 18
The work area shall be checked to ensure that all employees have
been safely positioned or removed.
(e)(2)(ii)
After lockout or tagout devices have been removed and before a
machine or equipment is started, affected employees shall be
notified that the lockout or tagout device(s) have been removed.
(e)(3)
Lockout or tagout devices removal. Each lockout or tagout
device shall be removed from each energy isolating device by the
employee who applied the device. Exception to paragraph (e)
(3): When the authorized employee who applied the lockout or
tagout device is not available to remove it, that device may be
removed under the direction of the employer, provided that specific
procedures and training for such removal have been developed,
documented and incorporated into the employer's energy control
program. The employer shall demonstrate that the specific
procedure provides equivalent safety to the removal of the device
by the authorized employee who applied it. The specific procedure
shall include at least the following elements:
(e)(3)(i)
Verification by the employer that the authorized employee who
applied the device is not at the facility:
(e)(3)(ii)
Making all reasonable efforts to contact the authorized employee to
inform him/her that his/her lockout or tagout device has been
removed; and
(e)(3)(iii)
Ensuring that the authorized employee has this knowledge before
he/she resumes work at that facility.
..1910.147(f)
(f)
Additional requirements.
(f)(1)
Testing or positioning of machines, equipment or
components thereof. In situations in which lockout or tagout
devices must be temporarily removed from the energy isolating
device and the machine or equipment energized to test or position
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 16 of 18
(f)(1)(iii)
(f)(2)(ii)
The on-site employer shall ensure that his/her employees
understand and comply with the restrictions and prohibitions of the
outside employer's energy control program.
(f)(3)
Group lockout or tagout.
(f)(3)(i)
When servicing and/or maintenance is performed by a crew, craft,
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 17 of 18
(f)(3)(ii)(D)
Each authorized employee shall affix a personal lockout or tagout
device to the group lockout device, group lockbox, or comparable
mechanism when he or she begins work, and shall remove those
devices when he or she stops working on the machine or
equipment being serviced or maintained.
(f)(4)
Shift or personnel changes. Specific procedures shall be utilized
during shift or personnel changes to ensure the continuity of
lockout or tagout protection, including provision for the orderly
transfer of lockout or tagout device protection between off-going
and oncoming employees, to minimize exposure to hazards from
the unexpected energization or start -up of the machine or
equipment, or the release of stored energy.
Note: The following appendix to §1910.147 services as a non-
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
The control of hazardous energy (lockout/tagout). - 1910.147 Page 18 of 18
http://www.osha-slc.gov/OshStd_data/1910_0147.html 11/9/2001
Typical minimal lockout procedures - 1910.147AppA Page 1 of 4
Text version
Regulations (Standards - 29
CFR)
Typical minimal lockout procedures -
1910.147AppA
OSHA Regulations (Standards - 29 CFR) - Table of Contents
General
Lockout Procedure
_____________________________________________________________________
Purpose
http://www.osha-slc.gov/OshStd_data/1910_0147_APP_A.html 11/9/2001
Typical minimal lockout procedures - 1910.147AppA Page 2 of 4
_____________________________________________________________________
Sequence of Lockout
___________________________________________________________________
_____________________________________________________________________
http://www.osha-slc.gov/OshStd_data/1910_0147_APP_A.html 11/9/2001
Typical minimal lockout procedures - 1910.147AppA Page 3 of 4
_____________________________________________________________________
_____________________________________________________________________
(5) Lock out the energy isolating device(s) with assigned individual
lock(s).
_____________________________________________________________________
_____________________________________________________________________
http://www.osha-slc.gov/OshStd_data/1910_0147_APP_A.html 11/9/2001
Typical minimal lockout procedures - 1910.147AppA Page 4 of 4
(2) Check the work area to ensure that all employees have been
safely positioned or removed from the area.
http://www.osha-slc.gov/OshStd_data/1910_0147_APP_A.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 1 of 107
Text version
Regulations (Standards - 29
CFR)
Electric Power Generation, Transmission,
and Distribution. - 1910.269
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
"General."
(a)(1)
"Application."
(a)(1)(i)
(a)(1)(i)(A)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 2 of 107
(a)(1)(i)(B)
(a)(1)(i)(B)(1)
(a)(1)(i)(B)(2)
(a)(1)(i)(B)(3)
..1910.269(a)(1)(i)(C)
(a)(1)(i)(C)
(a)(1)(i)(D)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 3 of 107
(a)(1)(i)(E)
(a)(1)(i)(E)(1)
(a)(1)(i)(E)(2)
Paragraphs (a)(2), (b), (c), (g), (k), (p), and (r) of this section
apply to line-clearance tree -trimming operations performed by line-
clearance tree trimmers who are not qualified employees.
(a)(1)(ii)
(a)(1)(ii)(A)
(a)(1)(ii)(B)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 4 of 107
..1910.269(a)(1)(iii)
(a)(1)(iii)
(a)(2)
"Training."
(a)(2)(i)
(a)(2)(ii)
(a)(2)(ii)(A)
(a)(2)(ii)(B)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 5 of 107
(a)(2)(ii)(C)
..1910.269(a)(2)(ii)(D)
(a)(2)(ii)(D)
Note: For the purposes of this section, a person must have this
training in order to be considered a qualified person.
(a)(2)(iii)
(a)(2)(iv)
(a)(2)(iv)(A)
(a)(2)(iv)(B)
(a)(2)(iv)(C)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 6 of 107
Note: OSHA would consider tasks that are performed less often
than once per year to necessitate retraining before the performance
of the work practices involved.
(a)(2)(v)
..1910.269(a)(2)(vi)
(a)(2)(vi)
(a)(2)(vii)
The employer shall certify that each employee has received the
training required by paragraph (a)(2) of this section. This
certification shall be made when the employee demonstrates
proficiency in the work practices involved and shall be maintained
for the duration of the employee's employment.
(a)(3)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 7 of 107
(b)
"Medical services and first aid." The employer shall provide medical
services and first aid as required in 1910.151 of this Part. In
addition to the requirements of 1910.151 of this Part, the following
requirements also apply:
..1910.269(b)(1)
(b)(1)
(b)(1)(i)
(b)(1)(ii)
(b)(2)
(b)(3)
"First aid kits." Each first aid kit shall be maintained, shall be
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 8 of 107
..1910.269(c)
(c)
(c)(1)
(c)(2)
(c)(2)(i)
(c)(2)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 9 of 107
(c)(3)
..1910.269(d)
(d)
(d)(1)
(d)(2)
"General."
(d)(2)(i)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 10 of 107
(d)(2)(ii)
(d)(2)(ii)(A)
(d)(2)(ii)(B)
..1910.269(d)(2)(ii)(B)(1)
(d)(2)(ii)(B)(1)
(d)(2)(ii)(B)(2)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 11 of 107
(d)(2)(ii)(C)
(d)(2)(iii)
..1910.269(d)(2)(iv)
(d)(2)(iv)
(d)(2)(iv)(A)
(d)(2)(iv)(B)
(d)(2)(iv)(C)
(d)(2)(iv)(D)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 12 of 107
(d)(2)(v)
(d)(2)(v)(A)
..1910.269(d)(2)(v)(B)
(d)(2)(v)(B)
(d)(2)(v)(C)
(d)(2)(v)(D)
(d)(2)(v)(E)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 13 of 107
(d)(2)(vi)
The employer shall provide training to ensure that the purpose and
function of the energy control program are understood by
employees and that the knowledge and skills required for the safe
application, usage, and removal of energy controls are acquired by
employees. The training shall include the following:
..1910.269(d)(2)(vi)(A)
(d)(2)(vi)(A)
(d)(2)(vi)(B)
(d)(2)(vi)(C)
(d)(2)(vii)
(d)(2)(vii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 14 of 107
(d)(2)(vii)(B)
..1910.269(d)(2)(vii)(C)
(d)(2)(vii)(C)
(d)(2)(vii)(D)
(d)(2)(vii)(E)
Tags may evoke a false sense of security, and their meaning needs
to be understood as part of the overall energy control program.
(d)(2)(vii)(F)
(d)(2)(viii)
(d)(2)(viii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 15 of 107
(d)(2)(viii)(B)
..1910.269(d)(2)(viii)(C)
(d)(2)(viii)(C)
(d)(2)(ix)
(d)(3)
(d)(3)(i)
Locks, tags, chains, wedges, key blocks, adapter pins, self -locking
fasteners, or other hardware shall be provided by the employer for
isolating, securing, or blocking of machines or equipment from
energy sources.
(d)(3)(ii)
(d)(3)(ii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 16 of 107
..1910.269(d)(3)(ii)(A)(1)
(d)(3)(ii)(A)(1)
(d)(3)(ii)(A)(2)
(d)(3)(ii)(B)
(d)(3)(ii)(C)
(d)(3)(ii)(D)
(d)(3)(ii)(E)
Each lockout device or tagout device shall include provisions for the
identification of the employee applying the device.
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 17 of 107
..1910.269(d)(3)(ii)(F)
(d)(3)(ii)(F)
(d)(4)
(d)(5)
Note: See also paragraph (d)(7) of this section, which requires that
the second notification take place before the machine or equipment
is reenergized.
(d)(6)
(d)(6)(i)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 18 of 107
..1910.269(d)(6)(ii)
(d)(6)(ii)
(d)(6)(iii)
All energy isolating devices that are needed to control the energy to
the machine or equipment shall be physically located and operated
in such a manner as to isolate the machine or equipment from
energy sources.
(d)(6)(iv)
(d)(6)(iv)(A)
(d)(6)(iv)(B)
(d)(6)(iv)(B)(1)
(d)(6)(iv)(B)(2)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 19 of 107
..1910.269(d)(6)(v)
(d)(6)(v)
(d)(6)(vi)
(d)(6)(vii)
(d)(7)
(d)(7)(i)
(d)(7)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 20 of 107
The work area shall be checked to ensure that all employees have
been safely positioned or removed.
..1910.269(d)(7)(iii)
(d)(7)(iii)
(d)(7)(iv)
(d)(7)(iv)(A)
(d)(7)(iv)(B)
(d)(7)(iv)(C)
..1910.269(d)(8)
(d)(8)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 21 of 107
"Additional requirements."
(d)(8)(i)
(d)(8)(i)(A)
(d)(8)(i)(B)
(d)(8)(i)(C)
(d)(8)(i)(D)
(d)(8)(i)(E)
..1910.269(d)(8)(ii)
(d)(8)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 22 of 107
(d)(8)(ii)(A)
(d)(8)(ii)(B)
(d)(8)(ii)(C)
(d)(8)(ii)(D)
..1910.269(d)(8)(iii)
(d)(8)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 23 of 107
(d)(8)(iv)
(d)(8)(v)
(d)(8)(v)(A)
(d)(8)(v)(B)
The system operator shall place and remove lockout and tagout
devices in place of the authorized employee under paragraphs (d)
(4), (d)(6)(iv), and (d)(7)(iv) of this section.
..1910.269(d)(8)(v)(C)
(d)(8)(v)(C)
(e)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 24 of 107
(e)(1)
"Safe work practices." The employer shall ensure the use of safe
work practices for entry into and work in enclosed spaces and for
rescue of employees from such spaces.
(e)(2)
..1910.269(e)(3)
(e)(3)
(e)(4)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 25 of 107
Note: The evaluation called for in this paragraph may take the form
of a check of the conditions expected to be in the enclosed space.
For example, the cover could be checked to see if it is hot and, if it
is fastened in place, could be loosened gradually to release any
residual pressure. A determination must also be made of whether
conditions at the site could cause a hazardous atmosphere, such as
an oxygen deficient or flammable atmosphere, to develop within
the space.
(e)(5)
(e)(6)
..1910.269(e)(7)
(e)(7)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 26 of 107
(e)(8)
(e)(9)
(e)(10)
..1910.269(e)(11)
(e)(11)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 27 of 107
(e)(12)
(e)(13)
"Air supply." The air supply for the continuous forced air ventilation
shall be from a clean source and may not increase the hazards in
the enclosed space.
(e)(14)
..1910.269(f)
(f)
(g)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 28 of 107
(g)(1)
(g)(2)
"Fall protection."
(g)(2)(i)
(g)(2)(ii)
Body belts and safety straps for work positioning shall meet the
requirements of 1926.959 of this Chapter.
(g)(2)(iii)
(g)(2)(iv)
..1910.269(g)(2)(v)
(g)(2)(v)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 29 of 107
(g)(2)(vi)
(g)(2)(vi)(A)
(g)(2)(vi)(B)
(g)(2)(vi)(C)
(g)(2)(vii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 30 of 107
(g)(2)(viii)
(g)(2)(ix)
..1910.269(h)
(h)
(h)(1)
(h)(2)
(h)(2)(i)
(h)(2)(ii)
(h)(2)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 31 of 107
(h)(2)(iv)
..1910.269(h)(3)
(h)(3)
(i)
(i)(1)
(i)(2)
(i)(2)(i)
(i)(2)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 32 of 107
(i)(2)(ii)(A)
..1910.269(i)(2)(ii)(B)
(i)(2)(ii)(B)
(i)(2)(ii)(C)
(i)(3)
(i)(3)(i)
(i)(3)(ii)
(i)(3)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 33 of 107
(i)(3)(iv)
(i)(4)
(i)(4)(i)
..1910.269(i)(4)(ii)
(i)(4)(ii)
(i)(4)(iii)
(i)(4)(iv)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 34 of 107
(i)(4)(v)
(i)(4)(vi)
(j)
"Live-line tools."
(j)(1)
..1910.269(j)(1)(i)
(j)(1)(i)
100,000 volts per foot (3281 volts per centimeter) of length for 5
minutes if the tool is made of fiberglass-reinforced plastic (FRP), or
(j)(1)(ii)
75,000 volts per foot (2461 volts per centimeter) of length for 3
minutes if the tool is made of wood, or
(j)(1)(iii)
Note: Live-line tools using rod and tube that meet ASTM F711-89,
Standard Specification for Fiberglass-Reinforced Plastic (FRP) Rod
and Tube Used in Live-Line Tools, conform to paragraph (j)(1)(i) of
this section.
(j)(2)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 35 of 107
"Condition of tools."
(j)(2)(i)
Each live-line tool shall be wiped clean and visually inspected for
defects before use each day.
(j)(2)(ii)
(j)(2)(iii)
(j)(2)(iii)(A)
..1910.269(j)(2)(iii)(B)
(j)(2)(iii)(B)
(j)(2)(iii)(C)
(j)(2)(iii)(C)(1)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 36 of 107
(j)(2)(iii)(C)(2)
(j)(2)(iii)(D)
The test method used shall be designed to verify the tool's integrity
along its entire working length and, if the tool is made of fiberglass-
reinforced plastic, its integrity under wet conditions.
(j)(2)(iii)(E)
(j)(2)(iii)(E)(1)
75,000 volts per foot (2461 volts per centimeter) of length for 1
minute if the tool is made of fiberglass, or
(j)(2)(iii)(E)(2)
50,000 volts per foot (1640 volts per centimeter) of length for 1
minute if the tool is made of wood, or
(j)(2)(iii)(E)(3)
..1910.269(k)
(k)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 37 of 107
(k)(1)
(k)(2)
(k)(2)(i)
(k)(2)(i)(A)
(k)(2)(i)(B)
(k)(2)(ii)
Note: Requirements for the size of the working space are contained
in paragraphs (u)(1) and (v)(3) of this section.
(l)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 38 of 107
..1910.269(l)(1)
(l)(1)
(l)(1)(i)
(l)(1)(i)(A)
(l)(1)(i)(B)
(l)(1)(i)(C)
(l)(1)(i)(D)
(l)(1)(i)(E)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 39 of 107
..1910.269(l)(1)(ii)
(l)(1)(ii)
(l)(1)(ii)(A)
(l)(1)(ii)(B)
(l)(1)(ii)(C)
(l)(2)
(l)(2)(i)
..1910.269(l)(2)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 40 of 107
(l)(2)(ii)
The energized part is insulated from the employee and from any
other conductive object at a different potential, or
(l)(2)(iii)
(l)(3)
(l)(3)(i)
(l)(3)(ii)
(l)(4)
(l)(5)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 41 of 107
..1910.269(l)(5)(i)
(l)(5)(i)
(l)(5)(ii)
(l)(5)(iii)
(l)(6)
"Apparel."
(l)(6)(i)
(l)(6)(ii)
(l)(6)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 42 of 107
the hazards of flames or electric arcs does not wear clothing that,
when exposed to flames or electric arcs, could increase the extent
of injury that would be sustained by the employee.
..1910.269(l)(7)
(l)(7)
(l)(8)
(l)(9)
(l)(10)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 43 of 107
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 44 of 107
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 45 of 107
(m)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 46 of 107
..1910.269(m)(1)
(m)(1)
(m)(2)
"General."
(m)(2)(i)
(m)(2)(ii)
(m)(2)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 47 of 107
..1910.269(m)(2)(iv)
(m)(2)(iv)
(m)(3)
(m)(3)(i)
(m)(3)(ii)
(m)(3)(iii)
(m)(3)(iv)
..1910.269(m)(3)(v)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 48 of 107
(m)(3)(v)
(m)(3)(vi)
(m)(3)(vii)
(m)(3)(viii)
(m)(3)(ix)
(m)(3)(x)
(m)(3)(x)(A)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 49 of 107
..1910.269(m)(3)(x)(B)
(m)(3)(x)(B)
Determine that all employees in the crew are clear of the lines and
equipment;
(m)(3)(x)(C)
(m)(3)(x)(D)
(m)(3)(xi)
(m)(3)(xii)
Tags may not be removed unless the associated clearance has been
released under paragraph (m)(3)(x) of this section.
(m)(3)(xiii)
Only after all protective grounds have been removed, after all
crews working on the lines or equipment have released their
clearances, after all employees are clear of the lines and
equipment, and after all protective tags have been removed from a
given point of disconnection, may action be initiated to reenergize
the lines or equipment at that point of disconnection.
..1910.269(n)
(n)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 50 of 107
(n)(1)
(n)(2)
(n)(2)(i)
(n)(2)(ii)
(n)(2)(iii)
(n)(3)
..1910.269(n)(4)
(n)(4)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 51 of 107
(n)(4)(i)
(n)(4)(ii)
(n)(5)
(n)(6)
(n)(7)
(n)(8)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 52 of 107
..1910.269(n)(9)
(n)(9)
(o)
(o)(1)
(o)(2)
"General requirements."
(o)(2)(i)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 53 of 107
The employer shall establish and enforce work practices for the
protection of each worker from the hazards of high-voltage or high-
power testing at all test areas, temporary and permanent. Such
work practices shall include, as a minimum, test area guarding,
grounding, and the safe use of measuring and control circuits. A
means providing for periodic safety checks of field test areas shall
also be included. (See paragraph (o)(6) of this section.)
(o)(2)(ii)
..1910.269(o)(3)
(o)(3)
(o)(3)(i)
(o)(3)(ii)
(o)(3)(ii)(A)
(o)(3)(ii)(B)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 54 of 107
(o)(3)(ii)(C)
(o)(3)(iii)
..1910.269(o)(3)(iv)
(o)(3)(iv)
(o)(4)
"Grounding practices."
(o)(4)(i)
(o)(4)(i)(A)
All conductive parts accessible to the test operator during the time
the equipment is operating at high voltage shall be maintained at
ground potential except for portions of the equipment that are
isolated from the test operator by guarding.
(o)(4)(i)(B)
(o)(4)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 55 of 107
..1910.269(o)(4)(iii)
(o)(4)(iii)
(o)(4)(iii)(A)
(o)(4)(iii)(B)
(o)(4)(iv)
(o)(4)(v)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 56 of 107
(o)(4)(v)(A)
(o)(4)(v)(B)
..1910.269(o)(4)(vi)
(o)(4)(vi)
(o)(5)
(o)(5)(i)
Control wiring, meter connections, test leads and cables may not
be run from a test area unless they are contained in a grounded
metallic sheath and terminated in a grounded metallic enclosure or
unless other precautions are taken that the employer can
demonstrate as ensuring equivalent safety.
(o)(5)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 57 of 107
opened.
(o)(5)(iii)
..1910.269(o)(5)(iv)
(o)(5)(iv)
(o)(6)
"Safety check."
(o)(6)(i)
(o)(6)(ii)
(o)(6)(ii)(A)
That barriers and guards are in workable condition and are properly
placed to isolate hazardous areas;
(o)(6)(ii)(B)
(o)(6)(ii)(C)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 58 of 107
(o)(6)(ii)(D)
(o)(6)(ii)(E)
(o)(6)(ii)(F)
..1910.269(p)
(p)
"Mechanical equipment."
(p)(1)
"General requirements."
(p)(1)(i)
(p)(1)(ii)
(p)(1)(ii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 59 of 107
(p)(1)(ii)(B)
(p)(1)(iii)
The operator of an electric line truck may not leave his or her
position at the controls while a load is suspended, unless the
employer can demonstrate that no employee (including the
operator) might be endangered.
(p)(1)(iv)
..1910.269(p)(2)
(p)(2)
"Outriggers."
(p)(2)(i)
(p)(2)(ii)
If the work area or the terrain precludes the use of outriggers, the
equipment may be operated only within its maximum load ratings
for the particular configuration of the equipment without outriggers.
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 60 of 107
(p)(3)
(p)(4)
(p)(4)(i)
..1910.269(p)(4)(ii)
(p)(4)(ii)
(p)(4)(iii)
(p)(4)(iii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 61 of 107
(p)(4)(iii)(B)
(p)(4)(iii)(C)
..1910.269(p)(4)(iii)(C)(1)
(p)(4)(iii)(C)(1)
Using the best available ground to minimize the time the lines
remain energized,
(p)(4)(iii)(C)(2)
(p)(4)(iii)(C)(3)
(p)(4)(iii)(C)(4)
(q)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 62 of 107
(q)(1)
"General."
(q)(1)(i)
(q)(1)(ii)
..1910.269(q)(1)(iii)
(q)(1)(iii)
(q)(1)(iv)
To protect employees from falling into holes into which poles are to
be placed, the holes shall be attended by employees or physically
guarded whenever anyone is working nearby.
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 63 of 107
(q)(2)
(q)(2)(i)
(q)(2)(ii)
(q)(2)(ii)(A)
..1910.269(q)(2)(ii)(B)
(q)(2)(ii)(B)
(q)(2)(ii)(C)
(q)(2)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 64 of 107
(q)(2)(iv)
(q)(2)(iv)(A)
(q)(2)(iv)(B)
..1910.269(q)(2)(iv)(C)
(q)(2)(iv)(C)
(q)(2)(iv)(D)
(q)(2)(iv)(E)
(q)(2)(v)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 65 of 107
(q)(2)(vi)
(q)(2)(vii)
(q)(2)(viii)
Conductor grips may not be used on wire rope, unless the grip is
specifically designed for this application.
..1910.269(q)(2)(ix)
(q)(2)(ix)
(q)(2)(x)
(q)(2)(xi)
While the conductor or pulling line is being pulled (in motion) with a
power-driven device, employees are not permitted directly under
overhead operations or on the cross arm, except as necessary to
guide the stringing sock or board over or through the stringing
sheave.
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 66 of 107
(q)(3)
(q)(3)(i)
(q)(3)(ii)
..1910.269(q)(3)(ii)(A)
(q)(3)(ii)(A)
(q)(3)(ii)(B)
(q)(3)(ii)(C)
(q)(3)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 67 of 107
(q)(3)(iv)
(q)(3)(v)
..1910.269(q)(3)(vi)
(q)(3)(vi)
(q)(3)(vi)(A)
(q)(3)(vi)(B)
(q)(3)(vii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 68 of 107
(q)(3)(viii)
Aerial lifts to be used for live-line bare-hand work shall have dual
controls (lower and upper) as follows:
(q)(3)(viii)(A)
..1910.269(q)(3)(viii)(B)
(q)(3)(viii)(B)
The lower set of controls shall be located near the base of the
boom, and they shall be so designed that they can override
operation of the equipment at any time.
(q)(3)(ix)
(q)(3)(x)
Before employees are elevated into the work position, all controls
(ground level and bucket) shall be checked to determine that they
are in proper working condition.
(q)(3)(xi)
Before the boom of an aerial lift is elevated, the body of the truck
shall be grounded, or the body of the truck shall be barricaded and
treated as energized.
(q)(3)(xii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 69 of 107
A boom -current test shall be made before work is started each day,
each time during the day when higher voltage is encountered, and
when changed conditions indicate a need for an additional test. This
test shall consist of placing the bucket in contact with an energized
source equal to the voltage to be encountered for a minimum of 3
minutes. The leakage current may not exceed 1 microampere per
kilovolt of nominal phase-to-ground voltage. Work from the aerial
lift shall be immediately suspended upon indication of a malfunction
in the equipment.
..1910.269(q)(3)(xiii)
(q)(3)(xiii)
(q)(3)(xiv)
(q)(3)(xv)
(q)(3)(xvi)
Hand lines may not be used between the bucket and the boom or
between the bucket and the ground. However, non-conductive-type
hand lines may be used from conductor to ground if not supported
from the bucket. Ropes used for live-line bare-hand work may not
be used for other purposes.
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 70 of 107
(q)(3)(xvii)
..1910.269(q)(3)(xviii)
(q)(3)(xviii)
(q)(3)(xix)
(q)(4)
(q)(4)(i)
(q)(4)(ii)
(q)(4)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 71 of 107
(q)(4)(iv)
..1910.269(r)
(r)
(r)(1)
(r)(1)(i)
(r)(1)(ii)
(r)(1)(ii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 72 of 107
(r)(1)(ii)(B)
(r)(1)(ii)(C)
..1910.269(r)(1)(iii)
(r)(1)(iii)
(r)(1)(iv)
(r)(1)(v)
(r)(1)(vi)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 73 of 107
(r)(2)
"Brush chippers."
(r)(2)(i)
(r)(2)(ii)
..1910.269(r)(2)(iii)
(r)(2)(iii)
(r)(2)(iv)
(r)(2)(v)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 74 of 107
(r)(3)
(r)(3)(i)
(r)(3)(ii)
(r)(4)
"Stump cutters."
(r)(4)(i)
..1910.269(r)(4)(ii)
(r)(4)(ii)
(r)(5)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 75 of 107
(r)(5)(i)
(r)(5)(ii)
Each power saw shall be equipped with a control that will return the
saw to idling speed when released.
(r)(5)(iii)
(r)(5)(iv)
..1910.269(r)(5)(v)
(r)(5)(v)
A power saw engine may be started and operated only when all
employees other than the operator are clear of the saw.
(r)(5)(vi)
A power saw may not be running when the saw is being carried up
into a tree by an employee.
(r)(5)(vii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 76 of 107
(r)(6)
(r)(6)(i)
(r)(6)(ii)
(r)(6)(iii)
..1910.269(r)(7)
(r)(7)
"Rope."
(r)(7)(i)
(r)(7)(ii)
(r)(7)(iii)
Rope shall be stored away from cutting edges and sharp tools.
Rope contact with corrosive chemicals, gas, and oil shall be
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 77 of 107
avoided.
(r)(7)(iv)
(r)(7)(v)
(r)(7)(vi)
(r)(7)(vii)
(r)(8)
..1910.269(s)
(s)
"Communication facilities."
(s)(1)
"Microwave transmission."
(s)(1)(i)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 78 of 107
(s)(1)(ii)
(s)(1)(iii)
(s)(2)
(t)
..1910.269(t)(1)
(t)(1)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 79 of 107
(t)(2)
(t)(3)
(t)(3)(i)
(t)(3)(ii)
(t)(3)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 80 of 107
..1910.269(t)(3)(iv)
(t)(3)(iv)
(t)(4)
"Duct rods." If duct rods are used, they shall be installed in the
direction presenting the least hazard to employees. An employee
shall be stationed at the far end of the duct line being rodded to
ensure that the required minimum approach distances are
maintained.
(t)(5)
(t)(6)
(t)(7)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 81 of 107
..1910.269(t)(8)
(t)(8)
(u)
(u)(1)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 82 of 107
(u)(2)
(u)(3)
(u)(4)
(u)(4)(i)
..1910.269(u)(4)(i)(A)
(u)(4)(i)(A)
(u)(4)(i)(B)
If live parts operating at 151 to 600 volts and located within 8 feet
of the ground or other working surface inside the room or space are
guarded only by location, as permitted under paragraph (u)(5)(i) of
this section, or
(u)(4)(i)(C)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 83 of 107
If live parts operating at more than 600 volts are located within the
room or space, unless:
(u)(4)(i)(C)(1)
(u)(4)(i)(C)(2)
The live parts are installed at a height above ground and any other
working surface that provides protection at the voltage to which
they are energized corresponding to the protection provided by an
8-foot height at 50 volts.
(u)(4)(ii)
(u)(4)(iii)
..1910.269(u)(4)(iv)
(u)(4)(iv)
Entrances to rooms and spaces that are not under the observation
of an attendant shall be kept locked.
(u)(4)(v)
Unqualified persons may not enter the rooms or spaces while the
electric supply lines or equipment are energized.
(u)(5)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 84 of 107
(u)(5)(i)
(u)(5)(ii)
(u)(5)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 85 of 107
..1910.269(u)(6)
(u)(6)
"Substation entry."
(u)(6)(i)
(u)(6)(ii)
(v)
(v)(1)
(v)(1)(i)
(v)(1)(ii)
(v)(2)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 86 of 107
(v)(3)
..1910.269(v)(4)
(v)(4)
(v)(4)(i)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 87 of 107
(v)(4)(i)(A)
(v)(4)(i)(B)
If live parts operating at 151 to 600 volts and located within 8 feet
of the ground or other working surface inside the room or space are
guarded only by location, as permitted under paragraph (v)(5)(i) of
this section, or
(v)(4)(i)(C)
If live parts operating at more than 600 volts are located within the
room or space, unless:
(v)(4)(i)(C)(1)
(v)(4)(i)(C)(2)
The live parts are installed at a height above ground and any other
working surface that provides protection at the voltage to which
they are energized corresponding to the protection provided by an
8-foot height at 50 volts.
..1910.269(v)(4)(ii)
(v)(4)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 88 of 107
(v)(4)(iii)
(v)(4)(iv)
Entrances to rooms and spaces that are not under the observation
of an attendant shall be kept locked.
(v)(4)(v)
Unqualified persons may not enter the rooms or spaces while the
electric supply lines or equipment are energized.
(v)(5)
(v)(5)(i)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 89 of 107
(v)(5)(ii)
..1910.269(v)(5)(iii)
(v)(5)(iii)
(v)(6)
(v)(6)(i)
(v)(6)(ii)
(v)(7)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 90 of 107
vessels:
(v)(7)(i)
(v)(7)(i)(A)
The area shall be posted with signs restricting entry and warning of
the hazards of fire and explosion; and
..1910.269(v)(7)(i)(B)
(v)(7)(i)(B)
(v)(7)(ii)
(v)(7)(iii)
Note: See 1910.141 of this Part for requirements that apply to the
water supply and to washing facilities.
(v)(7)(iv)
(v)(8)
"Chlorine systems."
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 91 of 107
(v)(8)(i)
(v)(8)(ii)
(v)(8)(iii)
..1910.269(v)(8)(iv)
(v)(8)(iv)
(v)(8)(v)
The employer shall ensure that chlorine is not mixed with materials
that would react with the chlorine in a dangerously exothermic or
other hazardous manner.
(v)(9)
"Boilers."
(v)(9)(i)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 92 of 107
(v)(9)(ii)
(v)(10)
"Turbine generators."
(v)(10)(i)
(v)(10)(ii)
..1910.269(v)(10)(iii)
(v)(10)(iii)
(v)(11)
(v)(11)(i)
(v)(11)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 93 of 107
(v)(11)(iii)
(v)(11)(iv)
(v)(11)(v)
(v)(11)(vi)
(v)(11)(vii)
..1910.269(v)(11)(viii)
(v)(11)(viii)
(v)(11)(ix)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 94 of 107
(v)(11)(x)
..1910.269(v)(11)(xi)
(v)(11)(xi)
(v)(11)(xi)(A)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 95 of 107
(v)(11)(xi)(B)
(v)(11)(xi)(C)
(v)(11)(xii)
(v)(11)(xiii)
..1910.269(v)(11)(xiv)
(v)(11)(xiv)
(v)(12)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 96 of 107
(w)
"Special conditions."
(w)(1)
Note: See paragraphs (m) and (n) of this section for requirements
pertaining to the deenergizing and grounding of capacitor
installations.
(w)(1)(i)
(w)(1)(ii)
(w)(1)(iii)
..1910.269(w)(2)
(w)(2)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 97 of 107
(w)(3)
"Series streetlighting."
(w)(3)(i)
(w)(3)(ii)
(w)(4)
(w)(5)
(w)(5)(i)
(w)(5)(ii)
..1910.269(w)(5)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 98 of 107
(w)(5)(iii)
(w)(6)
(w)(6)(i)
Traffic control signs and traffic control devices used for the
protection of employees shall meet the requirements of 1926.200
(g)(2) of this Chapter.
(w)(6)(ii)
(w)(6)(iii)
(w)(6)(iv)
(w)(6)(v)
..1910.269(w)(7)
(w)(7)
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 99 of 107
(w)(8)
(w)(9)
(x)
"Definitions."
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 100 of 107
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 101 of 107
Note: Spaces that are enclosed but not designed for employee
entry under normal operating conditions are not considered to be
enclosed spaces for the purposes of this section. Similarly, spaces
that are enclosed and that are expected to contain a hazardous
atmosphere are not considered to be enclosed spaces for the
purposes of this section. Such spaces meet the definition of permit
spaces in 1910.146 of this Part, and entry into them must be
performed in accordance with that standard.
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 102 of 107
Note: Wires which are insulated, but not otherwise protected, are
not considered as guarded.
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 103 of 107
(x)(1)
(x)(2)
(x)(3)
(x)(4)
..1910.269(x)(5)
(x)(5)
Note: For air contaminants for which OSHA has not determined a
dose or permissible exposure limit, other sources of information,
such as Material Safety Data Sheets that comply with the Hazard
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 104 of 107
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 105 of 107
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 106 of 107
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Electric Power Generation, Transmission, and Distribution. - 1910.269 Page 107 of 107
duties safely at his or her level of training and who is under the
direct supervision of a qualified person is considered to be a
qualified person for the performance of those duties.
"Vented vault." A vault that has provision for air changes using
exhaust flue stacks and low level air intakes operating on
differentials of pressure and temperature providing for airflow
which precludes a hazardous atmosphere from developing.
http://www.osha-slc.gov/OshStd_data/1910_0269.html 11/9/2001
Flow Charts. - 1910.269AppA Page 1 of 7
Text version
Regulations (Standards - 29
CFR)
Flow Charts. - 1910.269AppA
OSHA Regulations (Standards - 29 CFR) - Table of Contents
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_A.html 11/9/2001
Flow Charts. - 1910.269AppA Page 2 of 7
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_A.html 11/9/2001
Flow Charts. - 1910.269AppA Page 3 of 7
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_A.html 11/9/2001
Flow Charts. - 1910.269AppA Page 4 of 7
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_A.html 11/9/2001
Flow Charts. - 1910.269AppA Page 5 of 7
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_A.html 11/9/2001
Flow Charts. - 1910.269AppA Page 6 of 7
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_A.html 11/9/2001
Flow Charts. - 1910.269AppA Page 7 of 7
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_A.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 1 of 19
Text version
Regulations (Standards - 29
CFR)
Working on Exposed Energized Parts. -
1910.269AppB
OSHA Regulations (Standards - 29 CFR) - Table of Contents
I. Introduction
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 2 of 19
II. General
A. Definitions
NOTE: Wires which are insulated, but not otherwise protected, are not
considered as guarded.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 3 of 19
does not compare to that required for high voltage systems. The
employee must avoid contact with the exposed parts, and the protective
equipment used (such as rubber insulating gloves) must provide
insulation for the voltages involved.
Table R -6, Table R-7, and Table R -8 of 1910.269 provide safe approach
and working distances in the vicinity of energized electric apparatus so
that work can be done safely without risk of electrical flashover.
Where:
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 4 of 19
NOTE: The distances given (in feet) are for air as the insulating
medium and provide no additional clearance for inadvertent movement.
D = (C + a)pu V(MAX)
Where:
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 5 of 19
____________________________________________________________________
|
Maximum anticipated | Phase to phase voltage
per-unit |____________________________________________
transient overvoltage | | |
| 362,000 | 552,000 | 800,000
_______________________|_______________|______________|_____________
| | |
1.5................... | ............. | 4.97 | 8.66
1.6................... | ............. | 5.46 | 9.60
1.7................... | ............. | 5.98 | 10.60
1.8................... | ............. | 6.51 | 11.64
1.9................... | ............. | 7.08 | 12.73
2.0................... | 4.20 | 7.68 | 13.86
2.1................... | 4.41 | 8.27 | ..........
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 6 of 19
NOTE: The distances given (in feet) are for air as the insulating
medium and provide no additional clearance for inadvertent movement.
In the case of live-line work, the employee must first perceive that he or
she is approaching the danger zone. Then, the worker responds to the
danger and must decelerate and stop all motion toward the energized
part. During the time it takes to stop, a distance will have been traversed.
It is this distance that must be added to the electrical component of the
minimum approach distance to obtain the total safe minimum approach
distance.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 7 of 19
for all the worker's unexpected movements. The usual live-line work
method for these voltages is the use of rubber insulating equipment,
frequently rubber gloves. The energized object needs to be far enough
away to provide the worker's face with a safe approach distance, as his or
her hands and arms are insulated. In this case, 2 feet has been accepted
as a sufficient and practical value.
For voltages between 72.6 and 800 kV, there is a change in the work
practices employed during energized line work. Generally, live-line tools
(hot sticks) are employed to perform work while equipment is energized.
These tools, by design, keep the energized part at a constant distance
from the employee and thus maintain the appropriate minimum approach
distance automatically.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 8 of 19
Where:
For each voltage involved, the distance in Table 4 in this appendix has
been added to the distance in Table 1, Table 2 or Table 3 in this appendix
to determine the resulting minimum approach distances in Table R-6,
Table R -7, and Table R -8 in 1910.269.
The strength of an air gap is influenced by the changes in the air medium
that forms the insulation. A brief discussion of each factor follows, with a
summary at the end.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 9 of 19
The combination of temperature and air pressure that gives the lowest
gap flashover voltage is high temperature and low pressure. These are
conditions not likely to occur simultaneously. Low air pressure is generally
associated with high humidity, and this causes increased electrical
strength. An average air pressure is more likely to be associated with low
humidity. Hot and dry working conditions are thus normally associated
with reduced electrical strength.
Summary. After taking all these correction factors into account and after
considering their interrelationships relative to the air gap insulation
strength and the conditions under which live work is performed, one finds
that only a correction for altitude need be made. An elevation of 900
meters is established as the base elevation, and the values of the
electrical component of the minimum approach distances has been
derived with this correction factor in mind. Thus, the values used for
elevations below 900 meters are conservative without any change;
corrections have to be made only above this base elevation.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 10 of 19
4. Standard deviation -- air -gap withstand. For each air gap length,
and under the same atmospheric conditions, there is a statistical variation
in the breakdown voltage. The probability of the breakdown voltage is
assumed to have a normal (Gaussian) distribution. The standard
deviation of this distribution varies with the wave shape, gap geometry,
and atmospheric conditions. The withstand voltage of the air gap used in
calculating the electrical component of the minimum approach distance
has been set at three standard deviations (3 sigma (1) ) below the critical
flashover voltage. (The critical flashover voltage is the crest value of the
impulse wave that, under specified conditions, causes flashover on 50
percent of the applications. An impulse wave of three standard deviations
below this value, that is, the withstand voltage, has a probability of
flashover of approximately 1 in 1000.)
___________________________________________________________________
|
Cause | Magnitude (per unit)
_________________________________________|_________________________
|
Energized 200 mile line without |
closing resistors......................| 3.5
Energized 200 mile line with one step |
closing resistor.......................| 2.1
Energized 200 mile line with multi-step |
resistor...............................| 2.5
Reclosed with trapped charge one step |
resistor...............................| 2.2
Opening surge with single restrike.......| 3.0
Fault initiation unfaulted phase.........| 2.1
Fault initiation adjacent circuit........| 2.5
Fault clearing...........................| 1.7 - 1.9
_________________________________________|_________________________
SOURCE: ANSI/IEEE Standard No. 516, 1987.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 11 of 19
Step 4. Specify in detail the control technique to be used, and direct its
implementation during the course of the work.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 12 of 19
Step 5. Using the new value of transient overvoltage in per unit (p.u.),
determine the required phase-to-ground minimum approach distance
from Table R-7 or Table R -8 of 1910.269.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 13 of 19
Step 1. Select the appropriate withstand voltage for the protective gap
based on system requirements and an acceptable probability of actual
gap flashover.
Step 2. Using this distance, calculate the air gap withstand voltage from
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 14 of 19
Step 4. Calculate the withstand voltage of the protective gap (85 percent
of the critical flashover voltage) to ensure that it provides an acceptable
risk of flashover during the time the gap is installed.
NOTE: The air gap is based on the 60-Hz rod-gap withstand distance.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 15 of 19
Step 2. Using test data for a particular protective gap, select a gap that
has a critical flashover voltage greater than or equal to:
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 16 of 19
_ _
| (8.00 - 7.57) |
900 kV + | 50 X ------------------ | = 933 kV.
| (8.23 - 7.57) |
|_ _|
The crest withstand voltage of the protective gap in per unit is thus.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 17 of 19
3. If protective gaps are used at the work site, the work site impulse
insulation strength is established by the gap setting. Lightning strikes as
much as 6 miles away from the worksite may cause a voltage surge
greater than the insulation withstand voltage, and a gap flashover may
occur. The flashover will not occur between the employee and the line,
but across the protective gap instead.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 18 of 19
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Working on Exposed Energized Parts. - 1910.269AppB Page 19 of 19
Std. 516, 1987. This graph could also be used to determine the
appropriate withstand voltage for the minimum approach distance
involved. (Back to Text)
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_B.html 11/9/2001
Protection from Step and Touch Potentials. - 1910.269AppC Page 1 of 3
Text version
Regulations (Standards - 29
CFR)
Protection from Step and Touch Potentials.
- 1910.269AppC
OSHA Regulations (Standards - 29 CFR) - Table of Contents
I. Introduction
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_C.html 11/9/2001
Protection from Step and Touch Potentials. - 1910.269AppC Page 2 of 3
"Step potential" is the voltage between the feet of a person standing near
an energized grounded object. It is equal to the difference in voltage,
given by the voltage distribution curve, between two points at different
distances from the "electrode". A person could be at risk of injury during
a fault simply by standing near the grounding point.
"Touch potential" is the voltage between the energized object and the
feet of a person in contact with the object. It is equal to the difference in
voltage between the object (which is at a distance of 0 feet) and a point
some distance away. It should be noted that the touch potential could be
nearly the full voltage across the grounded object if that object is
grounded at a point remote from the place where the person is in contact
with it. For example, a crane that was grounded to the system neutral
and that contacted an energized line would expose any person in contact
with the crane or its uninsulated load line to a touch potential nearly
equal to the full fault voltage.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_C.html 11/9/2001
Protection from Step and Touch Potentials. - 1910.269AppC Page 3 of 3
zone can be produced through the use of a metal mat connected to the
grounded object. In some cases, a grounding grid can be used to equalize
the voltage within the grid. Equipotential zones will not, however, protect
employees who are either wholly or partially outside the protected area.
Bonding conductive objects in the immediate work area can also be used
to minimize the potential between the objects and between each object
and ground. (Bonding an object outside the work area can increase the
touch potential to that object in some cases, however.)
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_C.html 11/9/2001
Methods of Inspecting and Testing Wood Poles. - 1910.269AppD Page 1 of 3
Text version
Regulations (Standards - 29
CFR)
Methods of Inspecting and Testing Wood
Poles. - 1910.269AppD
OSHA Regulations (Standards - 29 CFR) - Table of Contents
I. "Introduction"
__________
Footnote(1) A properly guyed pole in good condition should, at a
minimum, be able to handle the weight of an employee climbing it.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_D.html 11/9/2001
Methods of Inspecting and Testing Wood Poles. - 1910.269AppD Page 2 of 3
__________
Footnote(2) The presence of any of these conditions is an
indication that the pole may not be safe to climb or to work from.
The employee performing the inspection must be qualified to make a
determination as to whether or not it is safe to perform the work
without taking additional precautions.
A. General Condition
The pole should be inspected for buckling at the ground line and for
an unusual angle with respect to the ground. Buckling and odd
angles may indicate that the pole has rotted or is broken.
B. Cracks
C. Holes
Rotting and decay are cutout hazards and are possible indications
of the age and internal condition of the pole.
E. Knots
One large knot or several smaller ones at the same height on the
pole may be evidence of a weak point on the pole.
F. Depth of Setting
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_D.html 11/9/2001
Methods of Inspecting and Testing Wood Poles. - 1910.269AppD Page 3 of 3
G. Soil Conditions
Soft, wet, or loose soil may not support any changes of stress on
the pole.
H. Burn Marks
A. Hammer Test
B. Rocking Test
Apply a horizontal force to the pole and attempt to rock it back and
forth in a direction perpendicular to the line. Caution must be
exercised to avoid causing power lines to swing together. The force
may be applied either by pushing with a pike pole or pulling with a
rope. If the pole cracks during the test, it shall be considered
unsafe.
http://www.osha-slc.gov/OshStd_data/1910_0269_APP_D.html 11/9/2001
Introduction. - 1910.301 Page 1 of 2
Text version
Regulations (Standards - 29
CFR)
Introduction. - 1910.301
OSHA Regulations (Standards - 29 CFR) - Table of Contents
(a)
(b)
(c)
http://www.osha-slc.gov/OshStd_data/1910_0301.html 11/9/2001
Introduction. - 1910.301 Page 2 of 2
(d)
(e)
http://www.osha-slc.gov/OshStd_data/1910_0301.html 11/9/2001
Electric utilization systems. - 1910.302 Page 1 of 5
Text version
Regulations (Standards - 29
CFR)
Electric utilization systems. - 1910.302
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
Scope -
(a)(1)
(a)(1)(i)
Yards,
(a)(1)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0302.html 11/9/2001
Electric utilization systems. - 1910.302 Page 2 of 5
Carnivals,
(a)(1)(iii)
(a)(1)(iv)
Mobile homes,
(a)(1)(v)
Recreational vehicles,
(a)(1)(vi)
Industrial substations,
(a)(1)(vii)
(a)(1)(viii)
..1910.302(a)(2)
(a)(2)
(a)(2)(i)
(a)(2)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0302.html 11/9/2001
Electric utilization systems. - 1910.302 Page 3 of 5
(a)(2)(iii)
(a)(2)(iv)
(a)(2)(v)
..1910.302(b)
(b)
Extent of application.
(b)(1)
Sections:
http://www.osha-slc.gov/OshStd_data/1910_0302.html 11/9/2001
Electric utilization systems. - 1910.302 Page 4 of 5
(b)(2)
(b)(3)
http://www.osha-slc.gov/OshStd_data/1910_0302.html 11/9/2001
Electric utilization systems. - 1910.302 Page 5 of 5
escalators.
1910.306(i)................... Electrically controlled irrigation
machines.
1910.306(j)(5)................ Ground-fault circuit interrupters
for fountains.
1910.308(a)(1)(ii)............ Physical protection of conductors
over 600 volts.
1910.308(c)(2)................ Marking of Class 2 and Class 3 power
supplies.
1910.308(d)................... Fire protective signaling circuits.
http://www.osha-slc.gov/OshStd_data/1910_0302.html 11/9/2001
General requirements. - 1910.303 Page 1 of 10
Text version
Regulations (Standards - 29
CFR)
General requirements. - 1910.303
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
Approval. The conductors and equipment required or permitted by
this subpart shall be acceptable only if approved.
(b)
Examination, installation, and use of equipment --
(b)(1)
Examination. Electrical equipment shall be free from recognized
hazards that are likely to cause death or serious physical harm to
employees. Safety of equipment shall be determined using the
following considerations:
(b)(1)(i)
Suitability for installation and use in conformity with the provisions
of this subpart. Suitability of equipment for an identified purpose
may be evidenced by listing or labeling for that identified purpose.
(b)(1)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
General requirements. - 1910.303 Page 2 of 10
..1910.303(b)(1)(v)
(b)(1)(v)
Arcing effects.
(b)(1)(vi)
Classification by type, size, voltage, current capacity, specific use.
(b)(1)(vii)
Other factors which contribute to the practical safeguarding of
employees using or likely to come in contact with the equipment.
(b)(2)
Installation and use. Listed or labeled equipment shall be used or
installed in accordance with any instructions included in the listing
or labeling.
(c)
Splices. Conductors shall be spliced or joined with splicing devices
suitable for the use or by brazing, welding, or soldering with a
fusible metal or alloy. Soldered splices shall first be so spliced or
joined as to be mechanically and electrically secure without solder
and then soldered. All splices and joints and the free ends of
conductors shall be covered with an insulation equivalent to that of
the conductors or with an insulating device suitable for the
purpose.
(d)
Arcing parts. Parts of electric equipment which in ordinary
operation produce arcs, sparks, flames, or molten metal shall be
enclosed or separated and isolated from all combustible material.
..1910.303(e)
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
General requirements. - 1910.303 Page 3 of 10
(e)
Marking. Electrical equipment may not be used unless the
manufacturer's name, trademark, or other descriptive marking by
which the organization responsible for the product may be
identified is placed on the equipment. Other markings shall be
provided giving voltage, current, wattage, or other ratings as
necessary. The marking shall be of sufficient durability to withstand
the environment involved.
(f)
Identification of disconnecting means and circuits. Each
disconnecting means required by this subpart for motors and
appliances shall be legibly marked to indicate its purpose, unless
located and arranged so the purpose is evident. Each service,
feeder, and branch circuit, at its disconnecting means or
overcurrent device, shall be legibly marked to indicate its purpose,
unless located and arranged so the purpose is evident. These
markings shall be of sufficient durability to withstand the
environment involved.
(g)
600 Volts, nominal, or less --
(g)(1)
Working space about electric equipment. Sufficient access and
working space shall be provided and maintained about all electric
equipment to permit ready and safe operation and maintenance of
such equipment.
..1910.303(g)(1)(i)
(g)(1)(i)
Working clearances. Except as required or permitted elsewhere
in this subpart, the dimension of the working space in the direction
of access to live parts operating at 600 volts or less and likely to
require examination, adjustment, servicing, or maintenance while
alive may not be less than indicated in Table S-1. In addition to the
dimensions shown in Table S-1, workspace may not be less than 30
inches wide in front of the electric equipment. Distances shall be
measured from the live parts if they are exposed, or from the
enclosure front or opening if the live parts are enclosed. Concrete,
brick, or tile walls are considered to be grounded. Working space is
not required in back of assemblies such as dead-front switchboards
or motor control centers where there are no renewable or
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
General requirements. - 1910.303 Page 4 of 10
Nominal voltage to
(a) (b) (c)
ground
(g)(1)(ii)
Clear spaces. Working space required by this subpart may not be
used for storage. When normally enclosed live parts are exposed
for inspection or servicing, the working space, if in a passageway or
general open space, shall be suitably guarded.
(g)(1)(iii)
Access and entrance to working space. At least one entrance of
sufficient area shall be provided to give access to the working space
about electric equipment.
..1910.303(g)(1)(iv)
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
General requirements. - 1910.303 Page 5 of 10
(g)(1)(iv)
Front working space. Where there are live parts normally
exposed on the front of switchboards or motor control centers, the
working space in front of such equipment may not be less than 3
feet.
(g)(1)(v)
Illumination. Illumination shall be provided for all working spaces
about service equipment, switchboards, panelboards, and motor
control centers installed indoors.
(g)(1)(vi)
Headroom. The minimum headroom of working spaces about
service equipment, switchboards, panel-boards, or motor control
centers shall be 6 feet 3 inches.
NOTE: As used in this section a motor control center is an assembly
of one or more enclosed sections having a common power bus and
principally containing motor control units.
(g)(2)
Guarding of live parts.
(g)(2)(i)
Except as required or permitted elsewhere in this subpart, live
parts of electric equipment operating at 50 volts or more shall be
guarded against accidental contact by approved cabinets or other
forms of approved enclosures, or by any of the following means:
(g)(2)(i)(A)
By location in a room, vault, or similar enclosure that is accessible
only to qualified persons.
..1910.303(g)(2)(i)(B)
(g)(2)(i)(B)
By suitable permanent, substantial partitions or screens so
arranged that only qualified persons will have access to the space
within reach of the live parts. Any openings in such partitions or
screens shall be so sized and located that persons are not likely to
come into accidental contact with the live parts or to bring
conducting objects into contact with them.
(g)(2)(i)(C)
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
General requirements. - 1910.303 Page 6 of 10
..1910.303(h)(2)
(h)(2)
Enclosure for electrical installations. Electrical installations in a
vault, room, closet or in an area surrounded by a wall, screen, or
fence, access to which is controlled by lock and key or other
approved means, are considered to be accessible to qualified
persons only. A wall, screen, or fence less than 8 feet in height is
not considered to prevent access unless it has other features that
provide a degree of isolation equivalent to an 8 foot fence. The
entrances to all buildings, rooms, or enclosures containing exposed
live parts or exposed conductors operating at over 600 volts,
nominal, shall be kept locked or shall be under the observation of a
qualified person at all times.
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
General requirements. - 1910.303 Page 7 of 10
(h)(2)(i)
Installations accessible to qualified persons only. Electrical
installations having exposed live parts shall be accessible to
qualified persons only and shall comply with the applicable
provisions of paragraph (h)(3) of this section.
(h)(2)(ii)
Installations accessible to unqualified persons. Electrical
installations that are open to unqualified persons shall be made
with metal-enclosed equipment or shall be enclosed in a vault or in
an area, access to which is controlled by a lock. If metal-enclosed
equipment is installed so that the bottom of the enclosure is less
than 8 feet above the floor, the door or cover shall be kept locked.
Metal-enclosed switchgear, unit substations, transformers, pull
boxes, connection boxes, and other similar associated equipment
shall be marked with appropriate caution signs. If equipment is
exposed to physical damage from vehicular traffic, suitable guards
shall be provided to prevent such damage. Ventilating or similar
openings in metal-enclosed equipment shall be designed so that
foreign objects inserted through these openings will be deflected
from energized parts.
..1910.303(h)(3)
(h)(3)
Workspace about equipment. Sufficient space shall be provided
and maintained about electric equipment to permit ready and safe
operation and maintenance of such equipment. Where energized
parts are exposed, the minimum clear workspace may not be less
than 6 feet 6 inches high (measured vertically from the floor or
platform), or less than 3 feet wide (measured parallel to the
equipment). The depth shall be as required in Table S-2. The
workspace shall be adequate to permit at least a 90-degree
opening of doors or hinged panels.
(h)(3)(i)
Working space. The minimum clear working space in front of
electric equipment such as switchboards, control panels, switches,
circuit breakers, motor controllers, relays, and similar equipment
may not be less than specified in Table S-2 unless otherwise
specified in this subpart. Distances shall be measured from the live
parts if they are exposed, or from the enclosure front or opening if
the live parts are enclosed. However, working space is not required
in back of equipment such as deadfront switchboards or control
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
General requirements. - 1910.303 Page 8 of 10
601 to 2,500 3 4 5
2,501 to 9,000 4 5 6
9,001 to 25,000 5 6 9
25,001 to 75kV (1a) 6 8 10
Above 75kV(1a) 8 10 12
(1a) Minimum depth of clear working space in
front of electric equipment with a nominal
voltage to ground above 25,000 volts may be
the same as for 25,000 volts under Conditions
(a), (b), and (c) for installations built prior to
April 16, 1981.
..1910.303(h)(3)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
General requirements. - 1910.303 Page 9 of 10
(h)(3)(ii)
Illumination. Adequate illumination shall be provided for all
working spaces about electric equipment. The lighting outlets shall
be so arranged that persons changing lamps or making repairs on
the lighting system will not be endangered by live parts or other
equipment. The points of control shall be so located that persons
are not likely to come in contact with any live part or moving part
of the equipment while turning on the lights.
(h)(3)(iii)
Elevation of unguarded live parts. Unguarded live parts above
working space shall be maintained at elevations not less than
specified in Table S -3.
Nominal voltage be -
Minimum elevation
tween phases
601 to 7,500 *8 feet 6 inches.
7,501 to 35,000 9 feet.
Over 35kV 9 feet + 0.37 inches
kV above
35kV.
*Note. -- Minimum elevation may be 8 feet 0
inches for installations built prior to April 16,
1981 if the nominal voltage between phases is
in the range of 601-6600 volts.
(h)(4)
Entrance and access to workspace. (See §1910.302(b)(3).)
(h)(4)(i)
At least one entrance not less than 24 inches wide and 6 feet 6
inches high shall be provided to give access to the working space
about electric equipment. On switchboard and control panels
exceeding 48 inches in width, there shall be one entrance at each
end of such board where practicable. Where bare energized parts at
any voltage or insulated energized parts above 600 volts are
located adjacent to such entrance, they shall be suitably guarded.
(h)(4)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
General requirements. - 1910.303 Page 10 of 10
http://www.osha-slc.gov/OshStd_data/1910_0303.html 11/9/2001
Wiring design and protection. - 1910.304 Page 1 of 16
Text version
Regulations (Standards - 29
CFR)
Wiring design and protection. - 1910.304
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
(a)(1)
(a)(2)
(a)(3)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 2 of 16
(b)
Branch circuits -
(b)(1)
[Reserved]
(b)(2)
Outlet devices. Outlet devices shall have an ampere rating not less
than the load to be served.
..1910.304(c)
(c)
(c)(1)
(c)(1)(i)
(c)(1)(ii)
(c)(1)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 3 of 16
(c)(2)
(c)(2)(i)
(c)(2)(ii)
(c)(2)(iii)
..1910.304(c)(2)(iv)
(c)(2)(iv)
(c)(3)
(c)(4)
(c)(4)(i)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 4 of 16
Where the voltage between conductors is 300 volts or less and the
roof has a slope of not less than 4 inches in 12, the clearance from
roofs shall be at least 3 feet, or
(c)(4)(ii)
Where the voltage between conductors is 300 volts or less and the
conductors do not pass over more than 4 feet of the overhang
portion of the roof and they are terminated at a through-the-roof
raceway or approved support, the clearance from roofs shall be at
least 18 inches.
..1910.304(c)(5)
(c)(5)
(d)
Services -
(d)(1)
Disconnecting means -
(d)(1)(i)
(d)(1)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 5 of 16
(d)(2)
(d)(2)(i)
(d)(2)(ii)
(e)
Overcurrent protection.
(e)(1)
..1910.304(e)(1)(i)
(e)(1)(i)
(e)(1)(ii)
(e)(1)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 6 of 16
(e)(1)(iv)
(e)(1)(v)
..1910.304(e)(1)(vi)
(e)(1)(vi)
Circuit breakers.
(e)(1)(vi)(A)
Circuit breakers shall clearly indicate whether they are in the open
(off) or closed (on) position.
(e)(1)(vi)(B)
(e)(1)(vi)(C)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 7 of 16
(e)(2)
Over 600 volts, nominal. Feeders and branch circuits over 600
volts, nominal, shall have short -circuit protection.
(f)
(f)(1)
(f)(1)(i)
(f)(1)(ii)
..1910.304(f)(1)(ii)(A)
(f)(1)(ii)(A)
(f)(1)(ii)(B)
(f)(1)(ii)(C)
(f)(1)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 8 of 16
(f)(1)(iv)
(f)(1)(iv)(A)
(f)(1)(iv)(B)
(f)(1)(iv)(C)
..1910.304(f)(1)(iv)(D)
(f)(1)(iv)(D)
(f)(1)(v)
(f)(1)(v)(A)
(f)(1)(v)(B)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 9 of 16
(f)(1)(v)(C)
(f)(1)(v)(C)(1)
(f)(1)(v)(C)(2)
(f)(1)(v)(C)(3)
(f)(1)(v)(C)(4)
..1910.304(f)(1)(v)(D)
(f)(1)(v)(D)
(f)(2)
(f)(3)
Grounding connections.
(f)(3)(i)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 10 of 16
(f)(3)(ii)
(f)(3)(iii)
..1910.304(f)(4)
(f)(4)
(f)(5)
(f)(5)(i)
(f)(5)(i)(A)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 11 of 16
(f)(5)(i)(B)
(f)(5)(i)(B)(1)
(f)(5)(i)(B)(2)
(f)(5)(i)(B)(3)
(f)(5)(ii)
..1910.304(f)(5)(iii)
(f)(5)(iii)
(f)(5)(iv)
(f)(5)(iv)(A)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 12 of 16
(f)(5)(iv)(B)
(f)(5)(iv)(C)
(f)(5)(iv)(D)
(f)(5)(iv)(E)
(f)(5)(iv)(F)
(f)(5)(iv)(F)(1)
..1910.304(f)(5)(iv)(F)(2)
(f)(5)(iv)(F)(2)
(f)(5)(iv)(F)(3)
(f)(5)(v)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 13 of 16
(f)(5)(v)(A)
(f)(5)(v)(B)
(f)(5)(v)(C)
(f)(5)(v)(C)(1)
(f)(5)(v)(C)(2)
(f)(5)(v)(C)(3)
..1910.304(f)(5)(v)(C)(4)
(f)(5)(v)(C)(4)
(f)(5)(v)(C)(5)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 14 of 16
(f)(5)(v)(C)(6)
(f)(5)(v)(C)(7)
(f)(5)(v)(C)(8)
(f)(5)(vi)
..1910.304(f)(6)
(f)(6)
(f)(6)(i)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 15 of 16
(f)(6)(ii)
(f)(7)
(f)(7)(i)
(f)(7)(ii)
..1910.304(f)(7)(ii)(A)
(f)(7)(ii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring design and protection. - 1910.304 Page 16 of 16
(f)(7)(ii)(B)
(f)(7)(ii)(C)
(f)(7)(ii)(D)
(f)(7)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0304.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 1 of 21
Text version
Regulations (Standards - 29
CFR)
Wiring methods, components, and
equipment for general use. - 1910.305
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
(a)(1)
General requirements -
(a)(1)(i)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 2 of 21
(a)(1)(ii)
(a)(2)
..1910.305(a)(2)(i)
(a)(2)(i)
(a)(2)(i)(A)
(a)(2)(i)(B)
(a)(2)(i)(C)
(a)(2)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 3 of 21
(a)(2)(iii)
(a)(2)(iii)(A)
..1910.305(a)(2)(iii)(B)
(a)(2)(iii)(B)
(a)(2)(iii)(C)
(a)(2)(iii)(D)
No bare conductors nor earth returns may be used for the wiring of
any temporary circuit.
(a)(2)(iii)(E)
(a)(2)(iii)(F)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 4 of 21
(a)(2)(iii)(G)
..1910.305(a)(3)
(a)(3)
Cable trays.
(a)(3)(i)
Uses permitted.
(a)(3)(i)(A)
(a)(3)(i)(A)(1)
(a)(3)(i)(A)(2)
(a)(3)(i)(A)(3)
(a)(3)(i)(A)(4)
(a)(3)(i)(A)(5)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 5 of 21
(a)(3)(i)(A)(6)
(a)(3)(i)(A)(7)
(a)(3)(i)(A)(8)
(a)(3)(i)(A)(9)
(a)(3)(i)(A)(10)
..1910.305(a)(3)(i)(A)(11)
(a)(3)(i)(A)(11)
(a)(3)(i)(B)
(a)(3)(i)(B)(1)
Single conductor cables which are 250 MCM or larger and are Types
RHH, RHW, MV, USE, or THW, and other 250 MCM or larger single
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 6 of 21
(a)(3)(i)(B)(2)
(a)(3)(i)(C)
(a)(3)(ii)
(a)(4)
(a)(4)(i)
..1910.305(a)(4)(ii)
(a)(4)(ii)
(a)(4)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 7 of 21
(a)(4)(iv)
(a)(4)(v)
..1910.305(b)
(b)
(b)(1)
(b)(2)
Covers and canopies. All pull boxes, junction boxes, and fittings
shall be provided with covers approved for the purpose. If metal
covers are used they shall be grounded. In completed installations
each outlet box shall have a cover, faceplate, or fixture canopy.
Covers of outlet boxes having holes through which flexible cord
pendants pass shall be provided with bushings designed for the
purpose or shall have smooth, well-rounded surfaces on which the
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 8 of 21
(b)(3)
Pull and junction boxes for systems over 600 volts, nominal. In
addition to other requirements in this section for pull and junction
boxes, the following shall apply to these boxes for systems over
600 volts, nominal:
(b)(3)(i)
(b)(3)(ii)
..1910.305(c)
(c)
Switches -
(c)(1)
(c)(2)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 9 of 21
(d)
(e)
(e)(1)
(e)(2)
..1910.305(f)
(f)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 10 of 21
(g)
(g)(1)
(g)(1)(i)
(g)(1)(i)(A)
Pendants;
(g)(1)(i)(B)
Wiring of fixtures;
(g)(1)(i)(C)
(g)(1)(i)(D)
Elevator cables;
(g)(1)(i)(E)
(g)(1)(i)(F)
(g)(1)(i)(G)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 11 of 21
(g)(1)(i)(H)
..1910.305(g)(1)(i)(i)
(g)(1)(i)(i)
(g)(1)(ii)
(g)(1)(iii)
(g)(1)(iii)(A)
(g)(1)(iii)(B)
(g)(1)(iii)(C)
(g)(1)(iii)(D)
(g)(1)(iii)(E)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 12 of 21
(g)(1)(iv)
..1910.305(g)(2)
(g)(2)
(g)(2)(i)
(g)(2)(ii)
(g)(2)(iii)
(h)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 13 of 21
..1910.305(i)
(i)
Fixture wires -
(i)(1)
(i)(2)
(i)(2)(i)
(i)(2)(ii)
(i)(3)
(j)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 14 of 21
(j)(1)
(j)(1)(i)
(j)(1)(ii)
..1910.305(j)(1)(iii)
(j)(1)(iii)
(j)(1)(iv)
(j)(2)
(j)(2)(i)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 15 of 21
(j)(2)(ii)
(j)(3)
Appliances.
(j)(3)(i)
(j)(3)(ii)
..1910.305(j)(3)(iii)
(j)(3)(iii)
Each appliance shall be marked with its rating in volts and amperes
or volts and watts.
(j)(4)
(j)(4)(i)
(j)(4)(ii)
Disconnecting means.
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 16 of 21
(j)(4)(ii)(A)
(j)(4)(ii)(B)
..1910.305(j)(4)(ii)(C)
(j)(4)(ii)(C)
If a motor and the driven machinery are not in sight from the
controller location, the installation shall comply with one of the
following conditions:
(j)(4)(ii)(C)(1)
(j)(4)(ii)(C)(2)
A manually operable switch that will disconnect the motor from its
source of supply shall be placed in sight from the motor location.
(j)(4)(ii)(D)
(j)(4)(ii)(E)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 17 of 21
(j)(4)(ii)(F)
(j)(4)(ii)(F)(1)
(j)(4)(ii)(F)(2)
..1910.305(j)(4)(ii)(F)(3)
(j)(4)(ii)(F)(3)
(j)(4)(iii)
(j)(4)(iv)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 18 of 21
(j)(4)(iv)(A)
(j)(4)(iv)(A)(1)
..1910.305(j)(4)(iv)(A)(2)
(j)(4)(iv)(A)(2)
(j)(4)(iv)(A)(3)
(j)(4)(iv)(B)
(j)(5)
Transformers.
(j)(5)(i)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 19 of 21
(j)(5)(i)(A)
Current transformers;
(j)(5)(i)(B)
(j)(5)(i)(C)
..1910.305(j)(5)(i)(D)
(j)(5)(i)(D)
(j)(5)(i)(E)
(j)(5)(ii)
(j)(5)(iii)
(j)(5)(iv)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 20 of 21
(j)(5)(v)
(j)(5)(vi)
..1910.305(j)(5)(vii)
(j)(5)(vii)
Any pipe or duct system foreign to the vault installation may not
enter or pass through a transformer vault.
(j)(5)(viii)
(j)(6)
Capacitors.
(j)(6)(i)
(j)(6)(ii)
Capacitors rated over 600 volts, nominal, shall comply with the
following additional requirements:
(j)(6)(ii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Wiring methods, components, and equipment for general use. - 1910.305 Page 21 of 21
(j)(6)(ii)(B)
(j)(6)(ii)(B)(1)
(j)(6)(ii)(B)(2)
Interlocks, or
..1910.305(j)(6)(ii)(B)(3)
(j)(6)(ii)(B)(3)
(j)(7)
http://www.osha-slc.gov/OshStd_data/1910_0305.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 1 of 15
Text version
Regulations (Standards - 29
CFR)
Specific purpose equipment and
installations. - 1910.306
OSHA Regulations (Standards - 29 CFR) - Table of Contents
(a)
(a)(1)
(a)(2)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 2 of 15
..1910.306(b)
(b)
(b)(1)
(b)(1)(i)
(b)(1)(ii)
(b)(1)(ii)(A)
(b)(1)(ii)(B)
(b)(1)(ii)(B)(1)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 3 of 15
(b)(1)(ii)(B)(2)
(b)(1)(ii)(B)(3)
No fixed work platform has been provided for servicing the unit.
..1910.306(b)(2)
(b)(2)
(b)(3)
(c)
(c)(1)
(c)(2)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 4 of 15
(c)(3)
Control panels. If control panels are not located in the same space
as the drive machine, they shall be located in cabinets with doors
or panels capable of being locked closed.
..1910.306(d)
(d)
(d)(1)
(d)(2)
(e)
(f)
(f)(1)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 5 of 15
Disconnecting means.
(f)(1)(i)
..1910.306(f)(1)(ii)
(f)(1)(ii)
(f)(2)
Control -
(f)(2)(i)
(f)(2)(ii)
(g)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 6 of 15
(g)(1)
(g)(2)
(g)(2)(i)
..1910.306(g)(2)(ii)
(g)(2)(ii)
(g)(2)(iii)
(g)(2)(iv)
(g)(2)(v)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 7 of 15
..1910.306(g)(2)(vi)
(g)(2)(vi)
(g)(3)
(h)
Electrolytic cells.
(h)(1)
(h)(2)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 8 of 15
Cell line working zone: The cell line working zone is the space
envelope wherein operation or maintenance is normally performed
on or in the vicinity of exposed energized surfaces of cell lines or
their attachments.
(h)(3)
..1910.306(h)(3)(i)
(h)(3)(i)
(h)(3)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 9 of 15
(h)(3)(iii)
Electrolytic cells, cell line conductors, cell line attachments, and the
wiring of auxiliary equipment and devices within the cell line
working zone need not comply with the provisions of 1910.303, and
1910.304 (b) and (c).
(h)(4)
Disconnecting means.
(h)(4)(i)
If more than one DC cell line process power supply serves the same
cell line, a disconnecting means shall be provided on the cell line
circuit side of each power supply to disconnect it from the cell line
circuit.
(h)(4)(ii)
..1910.306(h)(5)
(h)(5)
(h)(5)(i)
(h)(5)(ii)
(h)(6)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 10 of 15
(h)(6)(i)
(h)(6)(ii)
(h)(6)(iii)
..1910.306(h)(7)
(h)(7)
(h)(7)(i)
(h)(7)(ii)
(h)(7)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 11 of 15
(h)(7)(iii)(A)
(h)(7)(iii)(B)
(h)(7)(iii)(C)
(h)(7)(iv)
..1910.306(h)(8)
(h)(8)
(h)(9)
(h)(9)(i)
The conductive surfaces of cranes and hoists that enter the cell line
working zone need not be grounded. The portion of an overhead
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 12 of 15
(h)(9)(ii)
(h)(9)(ii)(A)
(h)(9)(ii)(B)
(h)(9)(ii)(C)
(h)(9)(ii)(D)
Radio.
(i)
..1910.306(i)(1)
(i)(1)
(i)(2)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 13 of 15
(j)
(j)(1)
(j)(2)
(j)(2)(i)
..1910.306(j)(2)(ii)
(j)(2)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 14 of 15
(j)(2)(ii)(A)
Unless they are 12 feet above the maximum water level, lighting
fixtures and lighting outlets may not be installed over a pool or
over the area extending 5 feet horizontally from the inside walls of
a pool. However, a lighting fixture or lighting outlet which has been
installed before April 16, 1981, may be located less than 5 feet
measured horizontally from the inside walls of a pool if it is at least
5 feet above the surface of the maximum water level and shall be
rigidly attached to the existing structure. It shall also be protected
by a ground-fault circuit interrupter installed in the branch circuit
supplying the fixture.
(j)(2)(ii)(B)
Unless installed 5 feet above the maximum water level and rigidly
attached to the structure adjacent to or enclosing the pool, lighting
fixtures and lighting outlets installed in the area extending between
5 feet and 10 feet horizontally from the inside walls of a pool shall
be protected by a ground-fault circuit interrupter.
(j)(3)
(j)(3)(i)
(j)(3)(ii)
(j)(4)
Underwater equipment.
(j)(4)(i)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Specific purpose equipment and installations. - 1910.306 Page 15 of 15
..1910.306(j)(4)(ii)
(j)(4)(ii)
(j)(5)
http://www.osha-slc.gov/OshStd_data/1910_0306.html 11/9/2001
Hazardous (classified) locations. - 1910.307 Page 1 of 4
Text version
Regulations (Standards - 29
CFR)
Hazardous (classified) locations. -
1910.307
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
http://www.osha-slc.gov/OshStd_data/1910_0307.html 11/9/2001
Hazardous (classified) locations. - 1910.307 Page 2 of 4
(b)
..1910.307(b)(1)
(b)(1)
(b)(2)
(b)(2)(i)
Equipment shall be approved not only for the class of location but
also for the ignitable or combustible properties of the specific gas,
vapor, dust, or fiber that will be present.
(b)(2)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0307.html 11/9/2001
Hazardous (classified) locations. - 1910.307 Page 3 of 4
(b)(2)(ii)(A)
(b)(2)(ii)(B)
..1910.307(b)(2)(ii)(C)
(b)(2)(ii)(C)
(b)(2)(ii)(D)
(b)(3)
Note: The National Electrical Code, NFPA 70, contains guidelines for
determining the type and design of equipment and installations
which will meet this requirement. The guidelines of this document
address electric wiring, equipment, and systems installed in
http://www.osha-slc.gov/OshStd_data/1910_0307.html 11/9/2001
Hazardous (classified) locations. - 1910.307 Page 4 of 4
(c)
(d)
http://www.osha-slc.gov/OshStd_data/1910_0307.html 11/9/2001
Special systems. - 1910.308 Page 1 of 11
Text version
Regulations (Standards - 29
CFR)
Special systems. - 1910.308
OSHA Regulations (Standards - 29 CFR) - Table of Contents
(a)
Systems over 600 volts, nominal. Paragraphs (a) (1) through (4) of
this section cover the general requirements for all circuits and
equipment operated at over 600 volts.
(a)(1)
(a)(1)(i)
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 2 of 11
(a)(1)(ii)
..1910.308(a)(2)
(a)(2)
(a)(2)(i)
(a)(2)(ii)
(a)(2)(iii)
(a)(3)
(a)(3)(i)
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 3 of 11
..1910.308(a)(3)(ii)
(a)(3)(ii)
Guarding live parts. All energized switching and control parts shall
be enclosed in effectively grounded metal cabinets or enclosures.
Circuit breakers and protective equipment shall have the operating
means projecting through the metal cabinet or enclosure so these
units can be reset without locked doors being opened. Enclosures
and metal cabinets shall be locked so that only authorized qualified
persons have access and shall be marked with a sign warning of
the presence of energized parts. Collector ring assemblies on
revolving-type machines (shovels, draglines, etc.) shall be guarded.
(a)(4)
Tunnel installation -
(a)(4)(i)
(a)(4)(ii)
(a)(4)(ii)(A)
(a)(4)(ii)(B)
Type MC cable, or
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 4 of 11
(a)(4)(ii)(C)
(a)(4)(iii)
..1910.308(a)(4)(iv)
(a)(4)(iv)
(a)(4)(v)
(b)
(b)(1)
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 5 of 11
(b)(2)
(b)(3)
..1910.308(c)
(c)
(c)(1)
(c)(1)(i)
Class 1 circuits.
(c)(1)(i)(A)
(c)(1)(i)(B)
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 6 of 11
(c)(1)(ii)
(c)(1)(ii)(A)
Power for Class 2 and Class 3 circuits is limited either inherently (in
which no overcurrent protection is required) or by a combination of
a power source and overcurrent protection.
(c)(1)(ii)(B)
(c)(1)(ii)(C)
..1910.308(c)(1)(iii)
(c)(1)(iii)
(c)(2)
(d)
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 7 of 11
(d)(1)
(d)(2)
Power sources. The power sources for use with fire protective
signaling circuits shall be either power limited or nonlimited as
follows:
(d)(2)(i)
(d)(2)(ii)
..1910.308(d)(3)
(d)(3)
(d)(4)
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 8 of 11
(d)(5)
..1910.308(e)
(e)
Communications systems -
(e)(1)
(e)(2)
Protective devices.
(e)(2)(i)
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 9 of 11
(e)(2)(ii)
(e)(3)
Conductor location -
(e)(3)(i)
Outside of buildings.
(e)(3)(i)(a)
(e)(3)(i)(b)
..1910.308(e)(3)(ii)
(e)(3)(ii)
(e)(3)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 10 of 11
(e)(4)
(e)(5)
Grounding -
(e)(5)(i)
..1910.308(e)(5)(ii)
(e)(5)(ii)
(e)(5)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Special systems. - 1910.308 Page 11 of 11
http://www.osha-slc.gov/OshStd_data/1910_0308.html 11/9/2001
Scope - 1910.331 Page 1 of 4
Text version
Regulations (Standards - 29
CFR)
Scope - 1910.331
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
(a)(1)
(a)(2)
http://www.osha-slc.gov/OshStd_data/1910_0331.html 11/9/2001
Scope - 1910.331 Page 2 of 4
(a)(3)
(a)(4)
..1910.331(b)
(b)
(c)
(c)(1)
http://www.osha-slc.gov/OshStd_data/1910_0331.html 11/9/2001
Scope - 1910.331 Page 3 of 4
(c)(2)
(c)(3)
http://www.osha-slc.gov/OshStd_data/1910_0331.html 11/9/2001
Scope - 1910.331 Page 4 of 4
(c)(4)
http://www.osha-slc.gov/OshStd_data/1910_0331.html 11/9/2001
Training - 1910.332 Page 1 of 3
Text version
Regulations (Standards - 29
CFR)
Training - 1910.332
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
(b)
Content of training.
(b)(1)
http://www.osha-slc.gov/OshStd_data/1910_0332.html 11/9/2001
Training - 1910.332 Page 2 of 3
assignments.
(b)(2)
(b)(3)
..1910.332(b)(3)(i)
(b)(3)(i)
(b)(3)(ii)
(b)(3)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0332.html 11/9/2001
Training - 1910.332 Page 3 of 3
(c)
Occupation
_________________________________________________________________________
http://www.osha-slc.gov/OshStd_data/1910_0332.html 11/9/2001
Selection and use of work practices - 1910.333 Page 1 of 13
Text version
Regulations (Standards - 29
CFR)
Selection and use of work practices -
1910.333
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
(a)(1)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 2 of 13
..1910.333(a)(2)
(a)(2)
(b)
(b)(1)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 3 of 13
(b)(2)
(b)(2)(i)
..1910.333(b)(2)(ii)
(b)(2)(ii)
"Deenergizing equipment."
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 4 of 13
(b)(2)(ii)(A)
(b)(2)(ii)(B)
(b)(2)(ii)(C)
(b)(2)(ii)(D)
(b)(2)(iii)
(b)(2)(iii)(A)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 5 of 13
..1910.333(b)(2)(iii)(B)
(b)(2)(iii)(B)
(b)(2)(iii)(C)
(b)(2)(iii)(D)
(b)(2)(iii)(E)
(b)(2)(iii)(E)(1)
(b)(2)(iii)(E)(2)
The lockout period does not extend beyond the work shift, and
(b)(2)(iii)(E)(3)
..1910.333(b)(2)(iv)
(b)(2)(iv)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 6 of 13
(b)(2)(iv)(A)
(b)(2)(iv)(B)
(b)(2)(v)
(b)(2)(v)(A)
..1910.333(b)(2)(v)(B)
(b)(2)(v)(B)
(b)(2)(v)(C)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 7 of 13
Each lock and tag shall be removed by the employee who applied it
or under his or her direct supervision. However, if this employee is
absent from the workplace, then the lock or tag may be removed
by a qualified person designated to perform this task provided that:
(b)(2)(v)(C)(1)
The employer ensures that the employee who applied the lock or
tag is not available at the workplace, and
(b)(2)(v)(C)(2)
The employer ensures that the employee is aware that the lock or
tag has been removed before he or she resumes work at that
workplace.
(b)(2)(v)(D)
(c)
(c)(1)
..1910.333(c)(2)
(c)(2)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 8 of 13
(c)(3)
(c)(3)(i)
"Unqualified persons."
(c)(3)(i)(A)
(c)(3)(i)(A)(1)
(c)(3)(i)(A)(2)
For voltages to ground over 50kV - 10 feet (305 cm) plus 4 inches
(10 cm) for every 10kV over 50kV.
..1910.333(c)(3)(i)(B)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 9 of 13
(c)(3)(i)(B)
(c)(3)(ii)
(c)(3)(ii)(A)
(c)(3)(ii)(B)
(c)(3)(ii)(C)
______________________________________________________________
|
Voltage range (phase to phase) | Minimum approach distance
__________________________________|___________________________
|
300V and less ....................| Avoid Contact
Over 300V, not over 750V .........| 1 ft. 0 in. (30.5 cm).
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 10 of 13
Over 750V, not over 2kV ..........| 1 ft. 6 in. (46 cm).
Over 2kV, not over 15kV ..........| 2 ft. 0 in. (61 cm).
Over 15kV, not over 37kV .........| 3 ft. 0 in. (91 cm).
Over 37kV, not over 87.5kV .......| 3 ft. 6 in. (107 cm).
Over 87.5kV, not over 121kV ......| 4 ft. 0 in. (122 cm).
Over 121kV, not over 140kV .......| 4 ft. 6 in. (137 cm).
__________________________________|___________________________
..1910.333(c)(3)(iii)
(c)(3)(iii)
(c)(3)(iii)(A)
(c)(3)(iii)(A)(1)
(c)(3)(iii)(A)(2)
(c)(3)(iii)(A)(3)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 11 of 13
(c)(3)(iii)(B)
(c)(3)(iii)(B)(1)
..1910.333(c)(3)(iii)(B)(2)
(c)(3)(iii)(B)(2)
(c)(3)(iii)(C)
(c)(4)
"Illumination."
(c)(4)(i)
(c)(4)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 12 of 13
..1910.333(c)(5)
(c)(5)
(c)(6)
(c)(7)
(c)(8)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Selection and use of work practices - 1910.333 Page 13 of 13
..1910.333(c)(9)
(c)(9)
(c)(10)
http://www.osha-slc.gov/OshStd_data/1910_0333.html 11/9/2001
Use of equipment. - 1910.334 Page 1 of 5
Text version
Regulations (Standards - 29
CFR)
Use of equipment. - 1910.334
OSHA Regulations (Standards - 29 CFR) - Table of Contents
(a)
(a)(1)
(a)(2)
"Visual inspection."
(a)(2)(i)
Portable cord and plug connected equipment and flexible cord sets
(extension cords) shall be visually inspected before use on any shift
for external defects (such as loose parts, deformed and missing
http://www.osha-slc.gov/OshStd_data/1910_0334.html 11/9/2001
Use of equipment. - 1910.334 Page 2 of 5
..1910.334(a)(2)(ii)
(a)(2)(ii)
(a)(2)(iii)
(a)(3)
(a)(3)(i)
(a)(3)(ii)
(a)(3)(iii)
http://www.osha-slc.gov/OshStd_data/1910_0334.html 11/9/2001
Use of equipment. - 1910.334 Page 3 of 5
..1910.334(a)(4)
(a)(4)
(a)(5)
(a)(5)(i)
(a)(5)(ii)
(a)(5)(iii)
(b)
(b)(1)
http://www.osha-slc.gov/OshStd_data/1910_0334.html 11/9/2001
Use of equipment. - 1910.334 Page 4 of 5
the load break type, fuses, terminal lugs, and cable splice
connections may not be used for such purposes, except in an
emergency.
..1910.334(b)(2)
(b)(2)
Note: When it can be determined from the design of the circuit and
the overcurrent devices involved that the automatic operation of a
device was caused by an overload rather than a fault condition, no
examination of the circuit or connected equipment is needed before
the circuit is reenergized.
(b)(3)
(c)
(c)(1)
(c)(2)
http://www.osha-slc.gov/OshStd_data/1910_0334.html 11/9/2001
Use of equipment. - 1910.334 Page 5 of 5
(c)(3)
..1910.334(d)
(d)
http://www.osha-slc.gov/OshStd_data/1910_0334.html 11/9/2001
Safeguards for personnel protection. - 1910.335 Page 1 of 4
Text version
Regulations (Standards - 29
CFR)
Safeguards for personnel protection. -
1910.335
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
(a)
(a)(1)
(a)(1)(i)
(a)(1)(ii)
http://www.osha-slc.gov/OshStd_data/1910_0335.html 11/9/2001
Safeguards for personnel protection. - 1910.335 Page 2 of 4
(a)(1)(iii)
(a)(1)(iv)
..1910.335(a)(1)(v)
(a)(1)(v)
(a)(2)
(a)(2)(i)
(a)(2)(i)(A)
http://www.osha-slc.gov/OshStd_data/1910_0335.html 11/9/2001
Safeguards for personnel protection. - 1910.335 Page 3 of 4
(a)(2)(i)(B)
(a)(2)(ii)
..1910.335(b)
(b)
(b)(1)
(b)(2)
(b)(3)
http://www.osha-slc.gov/OshStd_data/1910_0335.html 11/9/2001
Safeguards for personnel protection. - 1910.335 Page 4 of 4
http://www.osha-slc.gov/OshStd_data/1910_0335.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 1 of 19
Text version
Regulations (Standards - 29
CFR)
Definitions applicable to this subpart. -
1910.399
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 2 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 3 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 4 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 5 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 6 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 7 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 8 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 9 of 19
physical damage.
Equipment. A general term including material, fittings, devices,
appliances, fixtures, apparatus, and the like, used as a part of, or in
connection with, an electrical installation.
Equipment grounding conductor. See Grounding conductor,
equipment.
Explosion-proof apparatus. Apparatus enclosed in a case that is
capable of withstanding an explosion of a specified gas or vapor
which may occur within it and of preventing the ignition of a
specified gas or vapor surrounding the enclosure by sparks, flashes,
or explosion of the gas or vapor within, and which operates at such
an external temperature that it will not ignite a surrounding
flammable atmosphere.
Exposed. (As applied to live parts.) Capable of being inadvertently
touched or approached nearer than a safe distance by a person. It
is applied to parts not suitably guarded, isolated, or insulated. (See
Accessible. and Concealed.)
Exposed. (As applied to wiring methods.) On or attached to the
surface or behind panels designed to allow access. [See
Accessible. (As applied to wiring methods.)]
Exposed. (For the purposes of 1910.308(e), Communications
systems.) Where the circuit is in such a position that in case of
failure of supports or insulation, contact with another circuit may
result.
Externally operable. Capable of being operated without exposing
the operator to contact with live parts.
Feeder. All circuit conductors between the service equipment, or
the generator switchboard of an isolated plant, and the final
branch-circuit overcurrent device.
Fitting. An accessory such as a locknut, bushing, or other part of a
wiring system that is intended primarily to perform a mechanical
rather than an electrical function.
Fuse. (Over 600 volts, nominal.) An overcurrent protective device
with a circuit opening fusible part that is heated and severed by the
passage of overcurrent through it. A fuse comprises all the parts
that form a unit capable of performing the prescribed functions. It
may or may not be the complete device necessary to connect it into
an electrical circuit.
Ground. A conducting connection, whether intentional or
accidental, between an electrical circuit or equipment and the
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 10 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 11 of 19
operate.
Identified. Identified, as used in reference to a conductor or its
terminal, means that such conductor or terminal can be readily
recognized as grounded.
Induction heating. Induction heating is the heating of a nominally
conductive material due to its own I 2 R losses when the material is
placed in a varying electromagnetic field.
Insulated conductor. See Conductor.
Interrupter switch. (Over 600 volts, nominal.) A switch capable
of making, carrying, and interrupting specified currents.
Irrigation machine. An irrigation machine is an electrically driven
or controlled machine, with one or more motors, not hand portable,
and used primarily to transport and distribute water for agricultural
purposes.
Isolated. Not readily accessible to persons unless special means
for access are used.
Isolated power system. A system comprising an isolating
transformer or it equivalent, a line isolation monitor, and its
ungrounded circuit conductors.
Labeled. Equipment is "labeled" if there is attached to it a label,
symbol, or other identifying mark of a nationally recognized testing
laboratory which, (a) makes periodic inspections of the production
of such equipment, and (b) whose labeling indicates compliance
with nationally recognized standards or tests to determine safe use
in a specified manner.
Lighting outlet. An outlet intended for the direct connection of a
lampholder, a lighting fixture, or a pendant cord terminating in a
lampholder.
Line-clearance tree trimming. The pruning, trimming, repairing,
maintaining, removing, or clearing of trees or cutting of brush that
is within 10 feet (305 cm) of electric supply lines and equipment.
Listed. Equipment is "listed" if it is of a kind mentioned in a list
which, (a) is published by a nationally recognized laboratory which
makes periodic inspection of the production of such equipment, and
(b) states such equipment meets nationally recognized standards
or has been tested and found safe for use in a specified manner.
Location - (i) Damp location. Partially protected locations under
canopies, marquees, roofed open porches, and like locations, and
interior locations subject to moderate degrees of moisture, such as
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 12 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 13 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 14 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 15 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 16 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 17 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 18 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Definitions applicable to this subpart. - 1910.399 Page 19 of 19
http://www.osha-slc.gov/OshStd_data/1910_0399.html 11/9/2001
Authority for 1910 Subpart S - 1910SubpartS Page 1 of 1
Text version
Regulations (Standards - 29
CFR)
Authority for 1910 Subpart S -
1910SubpartS
OSHA Regulations (Standards - 29 CFR) - Table of Contents
Interpretation(s)
http://www.osha-slc.gov/OshStd_data/1910_SUBPART_S.html 11/9/2001
Reference Documents - 1910SubpartSAppA Page 1 of 3
Text version
Regulations (Standards - 29
CFR)
Reference Documents - 1910SubpartSAppA
OSHA Regulations (Standards - 29 CFR) - Table of Contents
http://www.osha-slc.gov/OshStd_data/1910_SUBPART_S_APP_A.html 11/9/2001
Reference Documents - 1910SubpartSAppA Page 2 of 3
http://www.osha-slc.gov/OshStd_data/1910_SUBPART_S_APP_A.html 11/9/2001
Reference Documents - 1910SubpartSAppA Page 3 of 3
http://www.osha-slc.gov/OshStd_data/1910_SUBPART_S_APP_A.html 11/9/2001
Explanatory Data - 1910SubpartSAppB Page 1 of 1
Text version
Regulations (Standards - 29
CFR)
Explanatory Data - 1910SubpartSAppB
OSHA Regulations (Standards - 29 CFR) - Table of Contents
[Reserved]
http://www.osha-slc.gov/OshStd_data/1910_SUBPART_S_APP_B.html 11/9/2001
Tables, Notes, and Charts - 1910SubpartSAppC Page 1 of 1
Text version
Regulations (Standards - 29
CFR)
Tables, Notes, and Charts -
1910SubpartSAppC
OSHA Regulations (Standards - 29 CFR) - Table of Contents
[Reserved]
http://www.osha-slc.gov/OshStd_data/1910_SUBPART_S_APP_C.html 11/9/2001