Instructions for F-15-683 Instructions for F-15-683

April, 2001 April, 2001

REGULATOR FLASH ARRESTORS REGULATOR FLASH ARRESTORS


P/N 0558002695 P/N 0558002695
Includes: Flash Arrestor, Oxygen - P/N-0558002693 Includes: Flash Arrestor, Oxygen - P/N-0558002693
Flash Arrestor Acetylene/Fuel Gas - P/N0558002694 Flash Arrestor Acetylene/Fuel Gas - P/N0558002694

SPECIFICATIONS SPECIFICATIONS

Welding Capacity ..................................................................................... 1-in. Welding Capacity ..................................................................................... 1-in.


Cutting Capacity .................................................................................... 12-in. Cutting Capacity .................................................................................... 12-in.
Maximum Inlet Pressure Maximum Inlet Pressure
Oxygen ....................................................................................... 150 psig Oxygen ....................................................................................... 150 psig
Acetylene ..................................................................................... 15 psig Acetylene ..................................................................................... 15 psig
Other Fuel Gases ......................................................................... 50 psig Other Fuel Gases ......................................................................... 50 psig
Connections (female inlet: male outlet) Connections (female inlet: male outlet)
Oxygen ............................................................... CGA-022 (9/16”-18 RH) Oxygen ............................................................... CGA-022 (9/16”-18 RH)
Acet/F.G .............................................................. CGA-023 (9/16”-18 LH) Acet/F.G .............................................................. CGA-023 (9/16”-18 LH)

Assembly and Fitting Instructions Assembly and Fitting Instructions


Designed to be fitted to oxygen and acet/fuel gas regulator outlets. Each con- Designed to be fitted to oxygen and acet/fuel gas regulator outlets. Each con-
tains a sintered steel flame barrier and a spring-loaded reverse flow check valve. tains a sintered steel flame barrier and a spring-loaded reverse flow check valve.
In the event of a flashback, the barrier will stop the flame from reaching the In the event of a flashback, the barrier will stop the flame from reaching the
check valve and regulator. The check valve will prevent one gas from flowing check valve and regulator. The check valve will prevent one gas from flowing
into the other regulator. A check valve alone will not stop a flashback. into the other regulator. A check valve alone will not stop a flashback.

INSTALLATION INSTALLATION

1. Assemble appropriate flash arrestor to each outlet connection of the regu- 1. Assemble appropriate flash arrestor to each outlet connection of the regu-
lator and tighten firmly with a wrench. DO NOT overtighten. lator and tighten firmly with a wrench. DO NOT overtighten.
2. Connect the proper hose to each flash arrestor with one wrench while tight- 2. Connect the proper hose to each flash arrestor with one wrench while tight-
ening the hose nut firmly with the other wrench. ening the hose nut firmly with the other wrench.
OPERATION OPERATION
Increase recommended operating pressure by 20% when using welding heads Increase recommended operating pressure by 20% when using welding heads
up through size No.70 and cutting tips to compensate for pressure drop through up through size No.70 and cutting tips to compensate for pressure drop through
the flash arrestor. the flash arrestor.
For No.100 welding heads, increase pressure by 40%. Do not use flash arres- For No.100 welding heads, increase pressure by 40%. Do not use flash arres-
tors when welding or heating larger than No.100. The combination of the arres- tors when welding or heating larger than No.100. The combination of the arres-
tor and large heads can cause severe overheating and possible damage to the tor and large heads can cause severe overheating and possible damage to the
equipment. equipment.
MAINTENANCE MAINTENANCE
Every six months or after 50 flashbacks, whichever occurs first, remove and Every six months or after 50 flashbacks, whichever occurs first, remove and
examine inside each flash arrestor If they appear clogged with carbon soot or examine inside each flash arrestor If they appear clogged with carbon soot or
discolored by heat, they should be replaced by new flash arrestors. Clogged discolored by heat, they should be replaced by new flash arrestors. Clogged
flash arrestors can cause excess pressure drop, overheating, and may not stop flash arrestors can cause excess pressure drop, overheating, and may not stop
a flashback resulting in damage to equipment. If they appear clean, reconnect a flashback resulting in damage to equipment. If they appear clean, reconnect
the arrestor to the regulator. the arrestor to the regulator.
F-15-683 4/01 F-15-683 4/01