Professional Documents
Culture Documents
QUICK GUIDE
Quarterly Newsletter of
Australia 's leading
supplier of low-voltage
motor control and
switchgear.
(
TO FAULT LEVELS
The Wiring Rules require
that protective devices
danger but to provide
ratings much higher than
The point of
shall be capable of that required can be a supply
interrupting any over- waste of money.
current up to and The calculation method At the point of supply two
including the prospective described in this fault levels can exist. The
short circuit current at the publication is intended to first is the actual fault
point where the protective provide a quick and level determined mainly
devices are installed. To simple means of by the impedance of the
provide equipment with determining the distribution transformer
lower ratings can create a approximate fault level. supplying the installation.
(continuedfrom page 1) To calculate the fault level at calculation very simple if the
the terminals of the distribution transformer impedance is
transformer, it is generally known. Typical values are
The second is that declared by sufficiently accurate to listed in Table 1.
the supply authority. This consider only the transformer
level may be higher than the impedance. The HV supply The calculation for maximum
actual as it may allow for usually has a far greater fault current is ;
flexibility in the future. capacity and can supply a I sc = k VA x 100
Changes to the distribution transformer shorted on its ·J3 x Vs x Z%
transformer or its location will output with little drop (5 % is a e.g. For a 500 kVA trans-
not cause an upgrading of the typical figure) in voltage. former with 4% impedance and
installation if it has already 415 volt secondary
been designed for worst case Neglecting the impedance of Isc = 500 x 100
conditions. the HV supply makes the .J3x415x4 (
= 17.4 kA
Table 1
Transformer X R z Impedance Fault prospective
kVA Q Q Q % kA
250 0.0 120 0.0200 0.0230 3.3 10.5
500 0.0052 0.0120 0.01 37 4.0 17.5
1000 0.0026 0.0081 0.0086 5.0 28.0
1500 0.0015 0.0053 0.0056 5.0 43.0
2000 0.00 12 0.0050 0.0052 6.0 46.5
Figure 1
50 II I I I I I II
Reducing
FAULT LEVEL AT SUPPLY factors
......._
<t
45
--..
r-- r-.
r....
ORIGIN (kA)
I
I
I
I
The fault level at the trans-
(
~ 40 46.5 former terminals may not
+-' represent the actual fault level
c
....
Q)
35
,\. at the switchboard. The
....
:::!
\.\ impedance of the connecting
u 43 ~
+-' 30 busbar or cables may make a
5
~
u
t:
25
- \ \.
~
~
significant reduction.
(continuer£from page 2)
Note: With the above phase centres the bar resistance is much
smaller than the reactance.
( For cable calculations please ask for your free copy of the
NHP Short Circuit Calculation Nomogram available from any
NHPoffice.