Professional Documents
Culture Documents
2 Protection systems
2 Sensitivity
Protection should be as sensitive as possible in order to
detect faults at the lowest possible current level. At the
same time, however, it should remain stable under all R1A R 2A R 3A
3 permissible load, overload and through-fault conditions. A R
For more information: www.siemens.com / systemplanning.
The Siemens engineering programs SINCAL and SIGRADE
4 are especially designed for selective protection grading of
protection relay systems. They provide short-circuit calcula-
tions as well as international standard characteristics of
relays, fuses and circuit-breakers for easy protection Fig. 6.2-57: Operating characteristics of Siemens distance relays
5 grading with respect to motor starting, inrush phenomena,
and equipment damage curves.
1 Background: 0.1
Even in the case where the 3 conductors are centrally 0.01
bundled, when passing through the cable type CT, an error
0.001
2 current "I error" will arise in the secondary circuit. This error 0 1 2 3 4 5 6 7 8 9 10
current is generally proportional to load current flowing Current in multiplies of full-load amps
through the CT.
Motor starting current High set instantaneous O/C stage
8
Numerical relays are able to filter out the asymmetrical Fig. 6.2-60: Coordination of inverse-time relays
current component very rapidly so that the setting of an
additional time delay is no longer applicable.
9 If the same characteristic is used for all relays, or if when
The overload protection characteristic should follow the the upstream relay has a steeper characteristic (e.g., very
thermal motor characteristic as closely as possible. The much over normal inverse), then selectivity is automatically
10 adaptation is made by setting the pickup value and the fulfilled at lower currents.
thermal time constant, using the data supplied by the
motor manufacturer. Furthermore, the locked-rotor protec- Differential relay
tion timer has to be set according to the characteristic Transformer differential relays are normally set to pickup
11 motor value. values between 20 and 30 % of the rated current. The
higher value has to be chosen when the transformer is
Time grading of overcurrent relays (51) fitted with a tap changer.
12 The selectivity of overcurrent protection is based on time
grading of the relay operating characteristics. The relay Restricted earth-fault relays and high-resistance
closer to the infeed (upstream relay) is time-delayed motor / generator differential relays are, as a rule, set to
against the relay further away from the infeed (down- about 10 % of the rated current.
stream relay). The calculation of necessary grading times is
shown in fig. 6.2-59 by an example for definite-time over- lnstantaneous overcurrent protection
current relays. This is typically applied on the final supply load or on any
protection relay with sufficient circuit impedance between
Inverse-time relays itself and the next downstream protection relay. The set-
For the time grading of inverse-time relays, in principle the ting at transformers, for example, must be chosen about
same rules apply as for the definite-time relays. The time 20 to 30 % higher than the maximum through-fault current.
grading is first calculated for the maximum fault level and The relay must remain stable during energization of the
then checked for lower current levels (fig. 6.2-60). transformer.
The Ip / IN settings shown in fig. 6.2-61 have been chosen to A 300 4,500 400 / 5 1.0 400 11.25
2
get pickup values safely above maximum load current. B 170 2,690 200 / 5 1.1 220 12.23
C 50 1,395 100 / 5 0.7 70 19.93
This current setting should be lowest for the relay farthest D – 523 – – – –
3 downstream. The relays further upstream should each have 1 ISCC. max = Maximum short-circuit current
equal or higher current settings. 2 I / I = Relay current multiplier setting
p N
3I
prim = Primary setting current corresponding to Ip / IN
Station C:
5 • For coordination with the fuses, the fault in location F1 is
considered.
The short-circuit current Iscc. max. related to 13.8 kV is
6 523 A.
This results in 7.47 for I / Ip at the overcurrent relay in
location C.
• With this value and Tp = 0.05, an operating time of tA =
7 0.17 s can be derived from fig. 6.2-60.
Station B:
10 The relay in B has a primary protection function for line B-C
and a backup function for the relay in C. The maximum
through-fault current of 1.395 A becomes effective for a
fault in location F2. For the relay in C, an operating time
11 time of 0.11 s (I / Ip = 19.93) is obtained.
• W
ith this value and the set value of Tp = 0.11, an
100
operating time of 0.3 s is obtained again (fig. 6.2-62).
Station A: t
50
• Adding the time grading interval of 0.3 s, the desired 40
operating itme is tA = 0.3 + 0.3 = 0.6 s. 30
the following values are obtained for the relay in station A: Tp [s]
• Pickup current: Ip / IN = 1.0 10
0.1 0.05
Note:
To simplify calculations, only inverse-time characteristics
7 have been used for this example. About 0.1 s shorter 0.05
operating times could have been reached for high-current 2 4 6 8 10 20
faults by additionally applying the instantaneous zones I>>
[A]
8 of the 7SJ60 relays. p
12 52 7SJ80
Ip = 0.7 IN
Bus-C
Tp = 0.05 s
I>> = ∞
100/5 A Ip = 0.10 – 4.00 IN
Tp = 0.05 – 3.2 s
52 7SJ80 I>> = 0.1 – 25 IN
13.8/0.4 kV
TR 625 kVA
5.0%
4 Normalinverse
0.14 MV bus
t = ―――――― · Tp(s)
(I / Ip)0.02 – 1 Inverse-time relay
Time 51
5 Strong inverse characteristics may be used with expulsion-
type fuses (fuse cutouts), while extremely inverse versions Other Fuse
adapt better to current limiting fuses. consumers
6
In any case, the final decision should be made by plotting
n
the curves in the log-log coordination diagram. a
LV bus
7 Electronic trip devices of LV breakers have long-delay, Fuse 0.2 s
short-delay and instantaneous zones. Numerical overcur-
rent relays with one inverse-time and two definite-time Current
8 zones can closely be adapted to this (fig. 6.2-65b). a) Maximum fault available at HV bus
9 MV bus
50/51
10
11 a
n
LV bus
12
• T
ypical settings of the ratio R / X are: Mechanical relays tOS = 0.15 s
–– Short lines and cables (≤ 10 km): R / X =2 to 6 Safety margin for
11 –– Medium line lengths < 25 km: R / X =2 measuring errors, etc. tM = 0.15 s
–– Longer lines 25 to 50 km: R / X =1. Example 2 tTG = 0.08 + 0.02 + 0.10 = 0.20 s
Vacuum circuit-breaker t52F = 0.08 s
12 Shortest feeder protectable by distance relays Numerical relays tOS = 0.02 s
The shortest feeder that can be protected by underreaching
Safety margin tM = 0.10 s
distance zones without the need for signaling links depends
on the shortest settable relay reactance. Fig. 6.2-67: Time grading of overcurrent-time relays
VTratio
XPrim Min = XRelay Min · ———
CTratio
XPrim Min
lmin = ————
X’Line
10
11
12
10
11
12