Professional Documents
Culture Documents
Transmission line should be made by a conductive material (Ag, Au, Cu, Al). Aluminum is preferred over
other material for construction of Transmission Lines due to the following reasons:
Significance of ‘L’
● It is used to represent reactive power Q absorbed by the line.
● It represents flux linkages in a conductor. There are two types of flux linkages in conductors
○ Internal magnetic flux linkages
○ External magnetic flux linkages
● For Inductance calculation we neglect skin effect.
Internal Inductance of a Conductor
External Inductance of a Conductor
GMD
Let us assume two composite conductors used in Transmission Line as shown in figure below.
For getting the GMD, first we need to calculate the distance between the strands of Go and Return
conductors.
Let,
● D11 = Distance between the 1ststrand of Go and Return conductor
● D12 = Distance between the 1ststrand of Go and 2nd strand of Return conductor
● D21 = Distance between the 2nd strand of Go and 1st strand of Return conductor
● Dmn = Distance between the mthstrand of Go and nth strand of Return conductor
GMR
Let us assume two composite conductors used in Transmission Line as shown in figure below.
For calculating GMR, first we find the distance between the individual strands. Thus if there are n strands in a
composite conductor then obviously there will be n2 distances between the strands.
Flux Linkage
Transposition of Transmission Lines
● Transmission Lines are transposed to reduce radio interference on communication lines. Transposition
makes the GMD of all the conductors equal.
● In transposition the position of conductors will be changed such that all 3 conductors have to
experience all 3 positional GMDs.
● Since, each conductor experiences all the positional GMDs the inductance of each conductor is given
by,
Inductance in Single Phase two wire line
Inductance of Stranded Conductors
For Stranded Conductors we calculate GMR in same way as Self GMD.
GMR of stranded conductors is less than Solid Conductors so, GMR < 0.7788r.
Three Phase Single Conductor System
Three Phase Bundled Conductor System
Calculation of Capacitance for Power Line
● The capacitance of a Power Line can be calculated as,
Significance of Capacitance
● It represents reactive power (Q) supplied by line.
● It represents changing current carried by line.
Calculation of Capacitance for Power Line
Capacitance in Single Phase two wire line
Effect of earth on Capacitance Calculation
Three phase Single Conductor System
Three phase bundle conductor system
Steady State Performance of Transmission
Line
● To know whether the equipment is working properly, we need to study the steady state behavior of
Transmission Line. Generally the performance indices that are studied are:
Efficiency
● Power efficiency
● Energy Efficiency or All Day Efficiency
● ABCD parameters of Nominal T & Nominal 𝝅 model are different but parameters of
Equivalent T and equivalent 𝝅 model are same.
● Thus, equivalent T-model and equivalent 𝝅 model can be obtained from each other by Star-
Delta Conversion.
Approximate ABCD parameters of long power
line
Per Unit ABCD Parameters
● A, B, C, D are always per-phase & these are complex numbers. In per unit
Complex Representation of ABCD Parameters
Static Power Transfer Equation
Condition for Maximum Power Transfer (P max)
Power Angle Characteristics of Power Line
Power Angle Characteristics of Power Line
Surge Impedance / Characteristic Impedance
/ Natural Impedance
Zc = impedance offered by an apparatus for surges, travelling waves / Transients. It is the voltage to current
ratio on Power line during wave propagation
Surge Impedance / Characteristic Impedance
/ Natural Impedance
Surge Impedance Loading (SIL)
Surge Impedance Loading (SIL)
● Note: When Loading = SIL, flat voltage profile is obtained on Transmission Line and hence SIL is called
as ideal loading capability of the line.
Characteristics of Transmission Lines
● The equivalent circuit of a Long Transmission Line is shown below. Here each section of the line is replaced by
equivalent circuit, so each parameter is per unit length.
● Here, each section of the line is assumed to have different length and thus the value of their lumped parameters is
different.
● The value of distributed parameters is R/km, L/km, C/km, G/km.
Flat Line or Infinite Line
If the voltage magnitude and current magnitude remains same at all points on the Transmission Line but the
phase may be different, then it is termed as Flat Line or Infinite Line. A Transmission Line terminated in
Characteristic Impedance is termed as Flat Line or Infinite Line.
Distortion Less Line
If the wave in the Transmission Line does not suffer any distortion in the wave shape as wave propagates in
the
Transmission Line, it is called as Distortion Less Line. The condition of Distortion less line is,
Time constant of series part = Time constant of shunt part
As shown in the figure above that due to resistance and conductance of the line the wave may be attenuated
i.e.
amplitude may change but wave shape should remain constant.
Lossless Transmission Line
● If R=G, G=0, in each section of Transmission Line then the wave amplitude remains same and does not
decrease as the wave propagates forward in a Transmission Line.
● If R≠ 0, or G ≠ 0, then it is called as lossy line or attenuated line.
● If RC=LG, R ≠ 0, G ≠ 0 then wave magnitude decreases without any distortion.
Propagation Constant ( 𝛾 )
Wavelength of Transmission Line ( 𝜆 )
Wave Propagation Phenomenon
● When a DC voltage is impressed on a Transmission Line in the form of Surge or
● a Lightning Discharge it propagates as a surge in Transmission Line.
Wave Propagation Phenomenon
(lossless Transmission Line)
So, as the time progresses the right shift in the function increases
and thus we can say that wave travels forward.
Wave Propagation Phenomenon
(lossless Transmission Line)
Time variation for f2
So, as the time progresses the left shift in the function increases
and thus we can say that wave travels backward
Wave Propagation Phenomenon
(lossless Transmission Line)
Wave Propagation Phenomenon
(lossless Transmission Line)
Current Equation
● The forward and backward travelling current and voltage waves are related as,
● Thus, forward current and voltage are in same phase whereas backward voltage and current are in opposite
phase.
Open Circuited Transmission Line
The surge voltage is induced almost instantaneously and thus is modelled as a step voltage source.
Since, receiving end is open circuit,
Transmitted Current, I2 = 0
At sending end side, due to constant voltage source
Open Circuited Transmission Line
Surge Voltage and Surge Currents are impressed on the Transmission Line as shown below,
Open Circuited Transmission Line
Open Circuited Transmission Line
● Current Coefficients
● Voltage Coefficients
Open Circuited Transmission Line
Steady state Open circuit of the line
● Voltage Coefficients
Short Circuited Transmission Line
Steady state Open circuit of the line
Thevenin Equivalent
To draw the Thevenin Equivalent of the Transmission Line for the surges at the time of first reflection, we
need to determine the Open Circuit Voltage and Short Circuit Current.
Reflection and Refraction Coefficients
Important Points
● If surge voltage enters from high surge impedance, medium (OH) line to low surge impedance medium
(cable) then surge voltage magnitude reduces.
● If surge voltage travels from low surge impedance medium to high surge impedance medium then
surge voltage magnitude increases.
● Hence, if a shunt capacitor is employed it will bypass the surge by providing a low impedance path and
thus protecting the other devices in the system.
Bifurcated / Parallel lines
Voltage Control
Voltage Control
Types of loads in our system
Voltage Control
Voltage control methods
Voltage Control
Voltage control devices
● Shunt Capacitor
● Shunt Reactor / inductor
● Series Capacitor
● Synchronous Condenser
● Synchronous coil / inductor
● Synchronous phase modifier / advancer
Voltage Control
The reactive power consumer or delivered by various apparatus under different conditions is tabulated
below,
Relation between receiving end voltage (Vr)
& net reactive power Qs or Qshunt
QL
𝜃2
Series Capacitor
Series Capacitor
● Impact on Stability
Series Capacitor
● Impact on Fault Current
Series Capacitor Vs Shunt Capacitor
Series Capacitor Vs Shunt Capacitor
Voltage Profile
The voltage drop in a line is approximately,
Series Capacitor Vs Shunt Capacitor
Surge Impedance and Surge Impedance Loading
Surge Impedance and Surge Impedance Loading
Dynamic Voltage Control
The use of Synchronous Motor for Voltage Control is called as Dynamic Voltage Control as it has rotor which
is
rotating part. Based on excitation of Synchronous Motor we can control the reactive power of the motor.
Due to increase in Capacitance and reduction in Inductance, surge impedance of UG cable is reduced
as compared to Overhead Lines.
● Due to decrease in Surge Impedance, the Surge Impedance Loading of an UG cable is more as
compared to Overhead Line.
Due to this reason, the loading in case of UG cable is decided on the basis of Thermal Limit and thus
Loading < SIL.
Due to increase in capacitance, the line charging current is more in UG cable as compared to Overhead
Line so Ferranti Effect is more in case of UG cables.
● To reduce Ferranti effect in the cable, Ferranti surge absorber in used or series reactor will be used
whereas in Transmission line shunt reactor will be used.
Proximity Effect
The inductance and current distribution in a conductor is affected by presence of other conductors in its
vicinity,
this is called as Proximity Effect.
If conductors carry current is opposite direction, the magnetic fields tend to increase the current density in
adjacent portions of the conductor and thus current is concentrated in small regions causing an increase in
the
resistance of the conductor just like the case of Skin Effect.
In case of UG cables the conductors are more closely located as compared to Overhead Lines and hence
Proximity
effect is more pronounced in case of UG cables.
Insulation Resistance of cable
● The DC distributed model for a UG cable is shown below,
Insulation Resistance of cable
● The DC distributed model for a UG cable is shown below,
Electrostatic Stress Distribution in Cable Cross
Section
Electrostatic Stress Distribution in Cable Cross
Section
● Since, electric field is inversely proportional to distance so maximum electric field occurs on the surface
of conductor.
● The choice of Insulating material is based on Maximum electric Field as the dielectric strength of the
insulator must be higher than maximum electric field so that it does not breakdown. High Value of
Maximum Electric Field increases the dielectric strength requirement of insulator and thus cost of cable
increases.
Most economical radius of core
Grading of cables
● Potential Gradient is maximum at conductor surface and decreases towards inner surface of sheath. We
want to use different dielectric materials to decrease difference between minimum & maximum
gradient so that electric field is uniformly distributed and dielectric strength requirement of Insulator is
reduced.
● The most ideal condition is if the potential gradient is constant throughout the insulator width. Potential
Gradient at distance x is given by,
We try to obtain approximation of this condition by using 3 or 4 dielectric materials with varying permittivity.
● The other reason is flow of leakage current through the dielectric due to finite insulator
resistance. Ideally, Insulator resistance should be infinite so no leakage current shall flow.
This loss is present in case of AC as well as DC Transmission.
Dielectric Power Loss
Radial Distribution
● Distribution power is supplied from one substation. eg. The distributor after SS5 in the above
● figure is a Radial Distributor.
Ring Distribution
● It is a closed loop forming a complete distribution of all loads. e.g. the closed loop for
● substations SS1 to SS4 is an example of Ring Distribution.
Source fed from both ends
Ring Distribution
Uniform Distribution
Power
Generation
Types of Power
plants
✗ Base Load Plants
✗ Gas plant
✗ Wind turbines
✗ Diesel generators
Load
Characteristics
Load Characteristics
✗ To get minimum fuel cost decision for economic dispatch problem the product
of penalty factor & incremental cost of all the power plants should be same.
✗ The penalty factor of generator is increases, the incremental cost should
decreases to maintain the constant product between L & IC hence the
generator will supply less power into the system.
✗ If the distance between load center & generator station increases penalty
factor increases
✗ Penalty factor is physical parameter within depend on distance between
generating station & load center.
✗ Lmin , It is possible if the load center connected directly across the generator
terminal.
✗ L=1 represents there no penalty on the corresponding generator
✗ Incremental Transmission line loss increases penalty factor increases.
Case1: The load center is directly
connected to G1 terminal
Case2: The load center is directly
connected to G2 terminal
Case-3: The load center is connected at a
same distance from both plants
To summarize
Power System Matrices
There are two power system
matrices
▹ Bus Admittance Matrix YBUS
▹ Bus Impedance Matrix ZBUS
Bus Admittance Matrix YBUS
Z3
Construction of YBUS
There are two methods for construction,
YBUS
▹ Direct inspection method
▹ Singular transformation method
Direct inspection method
Construction of ZBUS
The most common method for construction of Bus Impedance Matrix
would be Inversion of Bus Admittance Matrix.
ZBUS building algorithm
Modification of Bus Impedance Matrix for every small change in power system would
be difficult as we would have to convert to Bus Admittance Matrix and modify it and
then convert back to Bus Impedance Matrix.
So, we resort to another algorithm which makes it easier to modify Bus Impedance
Matrix.
ZBUS building algorithm
Case 1: Addition of a new bus to reference bus
ZBUS building algorithm
Case 2: Addition of new bus to existing bus through impedance
ZBUS building algorithm
Case-3: Adding an impedance to reference bus from existing bus
ZBUS building algorithm
Case 4 : Adding an impedance between existing bus
ZBUS Based Fault Analysis
There are two cases to be considered.
▹ Symmetrical Fault or Three Phase
Fault
▹ Change in System Bus Voltages
Symmetrical Fault or Three Phase Fault
Change in System Bus Voltages
▹ Assuming fault occurs at bus k. Before the fault the current injected into bus k is Ik and
due to fault the current that is delivered by bus to fault is If.
Load Flow Analysis
It is a steady state analysis of an interconnected power system during normal operation. Single
line diagram of power system contains hundreds of buses and branches with impedances
specified in per-unit on a common MVA base. Power flow studies, commonly referred to as load
flow, are essential of power system analysis and design.
Basic load flow equation
Basic load flow equation
It is taken as reference bus where the magnitude and phase angle of the voltage are
specified. This bus provide the additional real and reactive power to supply the
transmission losses, since these are unknown until the final solution is obtained.
▹ |V|, δ - known quantities
▹ P, Q - unknown quantities
Slack bus- generator having power capacity compared to all generators in the system.
During load flow solution, the real power generated by all generators will be kept as
constant, such that if there is any real power change in the system, it will be taken care
by slack bus. No practical existence for slack bus.
Generator Bus (or) PV Bus (voltage controlled Bus)
In these buses, the real power and voltage magnitude are specified. The phase angles
of the voltages and the reactive power are unknown until the final solution is obtained.
The limits on the value of reactive power are also specified.
▹ P,| V | - known quantities
▹ Q, δ - unknown quantities
Load Bus/PQ Bus
In these buses, the real and reactive powers are specified. The magnitude and phase
angle of the bus voltage are unknown until the final solution is obtained.
▹ P, Q - known quantities
▹ |V|, δ - unknown quantities
Voltage controlled buses
The Gauss-Seidel Method (GS) is an iterative algorithm for solving a set of non-linear
algebraic equations. To start with, a solution vector is assumed, based on guidance
from practical experience in a physical situation.
▹ One of the equations is then used to obtain the revised value of a particular
variable by substituting in it the present values of the remaining variables. The
solution vector is immediately updated in respect of this variable. The process is
then repeated for all the variables thereby completing one iteration.
▹ The iterative process is then repeated till the solution vector converges within
prescribed accuracy. The convergence is quite sensitive to the starting values
assumed. Fortunately, in a load flow study, a starting vector close to the final
solution can be easily identified with previous experience.
Newton- Raphson Method
▹ Its only drawback is the large requirement of computer memory which has been
overcome through a compact storage scheme. Convergence can be considerably
speeded up by performing the first iteration through the GS method and using the
values so obtained for starting the NR iterations.
The Jacobian matrix
▹ The increment in number of iteration with system size is less in case of N-R &
FDLF but not in case of GS.
Per Unit
System
Per unit System
The quantities involved in Power System are Voltages, Currents, Power and Impedances.
These quantities are sometimes expressed in per-unit of their base or reference values
to simplify the calculations.
Thus,
Representation of Power System in
pu
✖ A universal MVA base is chosen for entire Power System.
✖ Voltage base of one section is assumed and other voltage bases are determined based on
Transformation Ratio of different Transformers.
✖ All impedances are expressed in pu based on the base value defined in their particular
section.
Representation of Power System
✖ Single Line Diagram
Power System can be represented in terms of Single Line Diagram which makes it
more readable. An example of such a Power System is given below,
Up till now what we can do..
The equivalent circuit for Power System shown
Symmetrical
Components
Balanced System
✖ Magnitude of quantities are equal
✖ Phase difference between them are also equal
Unbalanced System
✖ Different magnitudes or phase
differences of phasor quantity(V,I)
in a system.
Reactance
where Nph is the number of turns per phase of where Nph is the number of turns
armature winding. per phase of armature winding.
Thus d-axis synchronous reactance Thus q-axis synchronous
reactance
Xd = ωLd = 2πfLd
Xq = ωLq = 2πfLq
d-axis and q-axis Reactance
✖ In case of salient pole synchronous machine, the air gap is non-uniform.
Therefore, Xd > Xq. But due to uniform air gap in cylindrical pole synchronous
machine, both direct and quadrature axis synchronous reactance are equal i.e. Xd
= Xq. In fact due to presence of rotor slots along q-axis, the Xq is slightly less than
Xd for cylindrical pole synchronous machine.
Star Connected Alternator
✖ Positive ✖ Negative ✖ Zero Sequence
Sequence Sequence
Delta Connected Alternator
✖ For delta connected alternator we have to convert it to star connection before
drawing the sequence networks.
Delta Connected Alternator
✖ Positive ✖ Negative ✖ Zero Sequence
Sequence Sequence
Transmission Line
✖ In a Transmission Line, the voltage drop in any phase depends on the current in
that phase as well as the current in the other two phases.
Transmission Lines
✖ Positive ✖ Negative ✖ Zero sequence
sequence sequence
Delta connected Load
Negative Sequence
Star connected Load
For Solid
Grounding
Zn=0
Peterson Coil
Solid Grounding Resistance Grounding Reactance Grounding /suppresser coil
grounding
Power System
Stability
6
Dynamics of Synchronous Machine
Dynamics of Synchronous Machine
Swing Equation
9
Swing Equation
Te 𝜔𝑠 Te
Tm
𝜔𝑠 Tm
Swing Equation
Two alternators connected in parallel and swinging together
▧ If 𝛿1 = 𝛿2 , then both alternator are swinging together
Two machine system where machine are not swinging together
▧ If 𝛿1 ≠ 𝛿2 . There is a real power exchange between machines, the
equivalent single machine will be constructed w.r.t 𝛿1 − 𝛿2 or 𝛿2 −
𝛿1 because stability of both the machine will be determined by this
angle.
Steady State Stability
▧ It is ability of a synchronous machine or power system to maintain synchronism with
respect to external connected network or external circuit connected to line for small
disturbances.
▧ In steady state stability, generator will be represented as a constant voltage source
behind its steady state x- axis reactance (Xd or Xs).
Steady State Stability
Methods to improve Steady State Stability
▧ Operating alternator at over excitation such that |E| is high value
▧ Reducing transfer reactance
By placing series compensation
By using double circuit line
By using bundled conductors
By using parallel line system
▧ By using SVC (static VAR compensation) at mid point of transmission line.
SVC (static VAR compensation)
▧ SVC is assumed to be ideal
▧ No real power injected into system, only reactive power.
Steady State Stability
▧ The power angle curves before and after the connection of SVC have been shown below,
Transient Stability Analysis
It is the ability of power network or synchronous machine to remain in synchronous with
respect to external connected tie line even after experiencing a large disturbance.
▧ Due to SC faults
▧ Contingencies (removal of any apparatus)
Steady State Stability
Assumptions
▧ Generator will be modeled as constant voltage source behind transient reactance Xd.
▧ Saturation & saliency in alternator are neglected. Saliency tends to make machine more
stable by increasing maximum power and thus it is neglected.
▧ No damping force as damping force will reduce the oscillations to improve the stability of
the system.
▧ Resistance & shunt elements like Shunt Capacitance are neglected
▧ Speed variations & frequency variations are neglected.
▧ Speed governing action will be de-activated such that mechanical input will be
maintained as constant.
▧ AVR (Automatic Voltage Regulator) will be de-activated such that generated emf E is
maintained as constant.
Power Transfer
In Transient Stability Analysis, we generally consider three cases,
▧ Before the Fault Occurrence
▧ During the Fault
▧ After the Fault Clearance
Power Transfer
▧ Before fault ▧ During the fault ▧ After clearing the
occurrence fault
X2 = transfer reactance
X1 = transfer reactance during fault
between Generator & infinite X3 = transfer reactance
bus after fault clears
Maximum Power Transfer Maximum Power Transfer
capability is given by, capability is given by, Maximum Power Transfer
capability is given by,
30
Equal Area Criterion
▧ This is a special case of solution of swing equation which is only applicable for single
machine system. In case of two machines, we must first convert it to single machine
system and then apply this criteria.
Equal Area Criterion
▧ The system will be stable if the amplitude of oscillations of rotor angle remains constant
in an un-damped system.
▧ In a practical system such a system will be stable as due to losses and damping the
oscillations will be damped out and rotor angle will settle to a steady state value.
33
Increasing steam input of alternator
Increasing steam input of alternator
Fault occurs on Transmission Line very near to bus
Fault occurs on Transmission Line very near to bus
Fault occurs in middle of one of the Parallel Lines
▧ In this case the reactance to ground is comparable to reactance between source and
load.
▧ Thus, power transfer during fault is non-zero.
Fault occurs in middle of one of the Parallel Lines
▧ During Fault
The circuit during the fault looks like as shown below,
Critical Clearing Angle and Time
Fault occurs on one of parallel lines very close to bus
▧ Before Fault
▧ During Fault
Since, the fault is close to bus we will assume that during fault no power is transferred from
generator to infinite bus.
Fault occurs on one of parallel lines very close to bus
Removal of one of parallel lines (Contingency Analysis)
Stability in
synchronous motor
44
Swing Equation of synchronous motor
Methods to improve Transient Stability
Swing Equation for Alternator is,
ⅆ𝛿 2
𝑀 = 𝑃𝑎 = 𝑃𝑠 − 𝑃𝑚𝑎𝑥 sin 𝛿
ⅆ𝑡
By improving Transient Stability we mean to reduce the rotor acceleration. This can be
done by following methods
▧ Design alternator with high capability rating with large inertia (J).
▧ By connecting a flywheel to the shaft of rotor we can reduce the variation in
speed and thus improve Transient Stability.
Methods to improve Transient Stability
▧ The original swing equation with damping included is
ⅆ𝜔
𝑀 + 𝐷𝜔 = 𝑃𝑎
ⅆ𝑡
Thus, the rotor acceleration is,
ⅆ𝜔 𝑃𝑎 − 𝐷𝜔
=
ⅆ𝑡 𝑀
Thus, acceleration reduces with introduction of damping term.
This can be introduced by means of damper winding in the
alternator
▧ If steam input is reduced when the fault occurs then the accelerating
power is reduced which reduces the acceleration of the machine. This
can be done by use of Speed Governing Mechanism.
▧ By using AVR if we increase excitation, then 𝑃𝑒 increases and
accelerating power reduces which reduces the acceleration of the
machine.
Methods to improve Transient Stability
▧ Reducing reactance of system by using larger air gap between stator &
rotor increases 𝑃𝑒 and reduces acceleration of the machine.
▧ By using Resistance Grounding, Net Electrical Output becomes,
𝑃𝑒 + 𝐼𝑓2 𝑅𝑛
This is taken for faults where zero sequence currents exist so that
current flows through the neutral resistance. Thus, electrical output
increases and acceleration of machine reduces.
Methods to improve Transient Stability
▧ If we use 3-pole CB then all lines are isolated in case of an LG fault on a single
line so 𝑃𝑒 = 0 & 𝑃𝑎 is high.
But is we use single pole circuit breaker then supply can be maintained
through other two lines and electrical output increases due to which
acceleration of machine decreases and stability is improved.
Types of protective switches
Types of protective switches
✖ Fuse
✖ Load Interrupter
✖ Line Isolator
✖ Circuit Breaker (CB)
✖ Relay
Fuse
✖ Heat energy (Q) = I2rt
✖ If heat energy is greater than thermal limit of fuse, then fuse will melt down & circuit will be
opened.
✖ The length of fuse will be designed based on operation voltage such that after the fuse melt
down there should not be any ionization.
✖ Materials: Al, Sn, Cu, Ag etc., else alloys
Load Interrupter
✖ Operators only at FL condition
✖ Used for Load shredding or load curtailment or energy management.
✖ It will be used to avoid over loads
✖ Braking capacity of load interrupter is full load capacity
Line Isolator
✖ It will be operated only at No-load operating condition.
✖ Purpose is to provide more clearance between two points in the network or to increase safety
of power syrstem network.
✖ Line isolator provides more gaps such that there is a perfect disconnection between two
areas.
✖ First load interrupte operated
✖ Then line isolator opened
✖ Breaking capacity of isolator is zero as it operates at zero current.
Circuit Breaker
(CB)
Circuit Breaker
CB is a protective switch which can make the circuit and break the circuit during normal and abnormal conditions
respectively by taking trip command or signal from the relay and operates under all conditions (abnormal, full
load, no-load).
Arc Phenomenon
When a SC occurs, heavy current flows & when contacts separate, contact area decreases & so
current density increases & temperature rises which ionize the air. The ionized air acts as
conductor between the contacts and an arc is struck between the contacts. The current between
the contacts during the arcing period depends on arc resistance which depends on:
○ The resistance increases with decreases in number of ionized particles.
○ Arc resistance increases with increase in length of arc
○ Resistance of arc decreases with increases in area of cross-section of arc.
Arc Phenomenon
✖ Properties of Arc
Arc Interruption Method
✖ High Resistance Method
○ Arc lengthening process
○ Reducing area of cross area of arc
○ Cooling the arc
✖ Current zero arc interruption method
Terms Regarding CB Arc
Phenomenon
✖ Recovery Voltage
It is the steady state power frequency RMS voltage appearing across breaker contacts after
final extinction of arc.
✖ Active Recovery Voltage (ARV)
It is the instantaneous value of recovery voltage across CB contacts as the instant of arc
interruption
ARV depends on power factor of the system
○ If Pf=unity
Voltage=0 when I = 0 (arc extinction)
○ If pf= lag
0 < ARV < Vmax when I = 0
Active Recovery Voltage (ARV)
Restriking Voltage (Vr)
✖ It is the instantaneous voltage appearing across CB contacts at the instant of arc interruption.
If resistance is neglected
Restriking Voltage (Vr)
Resistance Switching
✖ A resistance ‘r’ is connected across CB contacts to damp out frequency of oscillations made
by restriking voltage.
✖ The connection of resistor or disconnection will be done on basis of sphere gap which is
connected in series with ‘r’
✖ At the instant of arc interruption VCB is restricting voltage (very high value), sphere gap will
experience high voltage & gap will be ionized.
Resistance Switching
✖ After final extinction of arc, resistor is disconnected from the circuit as voltage across sphere
gap is normal recovery voltage. To make fosc=0
✖ Rated Current
Carried by CB under normal operating conditions (Continuous RMS current
rating).