You are on page 1of 1

2 Overview

Protection Coordination Phase-fault o/c relays


The pickup values of phase o/c relays are normally
set 30 % above the maximum load current, provided
that sufficient short-circuit current is available.
This practice is recommended in particular for
Peak value of inrush current mechanical relays with reset ratios of 0.8 to 0.85.
2 Numerical relays have high reset ratios near 0.95
and allow therefore about 10 % lower setting.
Feeders with high transformer and/or motor load
require special consideration.

Transformer feeders
The energizing of transformers causes inrush cur-
rents that may last for seconds, depending on their
size (Fig. 2/81).
Selection of the pickup current and assigned time
delay have to be coordinated so that the inrush
current decreases below the relay o/c reset value
before the set operating time has elapsed.
The inrush current typically contains only about
50 % fundamental frequency component.
Numerical relays that filter out harmonics and the
DC component of the inrush current can there-
fore be set more sensitive. The inrush current peak
Time constant of inrush current values of Fig. 2/81 will be reduced more than to
Nominal power 0.5 … 1.0 1.0 … 10 > 10
one half in this case.
(MVA) Some digital relay types have an inrush detection
Time constant 0.16 … 0.2 0.2 … 1.2 1.2 … 720 function which may block the trip of the over-
(s) current protection resulting from inrush currents.
Fig. 2/81
Earth-fault protection relays
Earth-current relays enable a much more sensitive
Typical applications and functions
setting, as load currents do not have to be considered
Relay operating characteristics and their setting (except 4-wire circuits with single-phase load). In
must be carefully coordinated in order to achieve solidly and low-resistance earthed systems a setting
selectivity. The aim is basically to switch off only of 10 to 20 % rated load current can generally be ap-
the faulted component and to leave the rest of the plied. High-resistance earthing requires much more
power system in service in order to minimize sup- sensitive setting in the order of some amperes pri-
ply interruptions and to assure stability. mary. The earth-fault current of motors and gen-
erators, for example, should be limited to values
Sensitivity below 10 A in order to avoid iron burning.
Protection should be as sensitive as possible to Residual-current relays in the star point connec-
detect faults at the lowest possible current level. tion of CTs can in this case not be used, in partic-
At the same time, however, it should remain ular with rated CT primary currents higher than
stable under all permissible load, overload and 200 A. The pickup value of the zero-sequence re-
through-fault conditions. For further information lay would in this case be in the order of the error
see: http://www.siemens.com/systemplanning. currents of the CTs.
The Siemens engineering programs SINCAL and A special core-balance CT is therefore used in this
SIGRADE are especially designed for selective case as earth-current sensor. The core-balance CT
protection grading of protection relay systems. 7XR96 is designed for a ratio of 60/1 A. The detec-
They provide short-circuit calculations, interna- tion of 6 A primary would then require a relay
tional standard characteristics of relays, fuses and pickup setting of 0.1 A secondary. An even more sen-
circuit-breakers for easy protection grading with sitive setting is applied in isolated or Peterson-
respect to motor starting, inrush phenomena and coil-earthed networks where very low earth currents
equipment damage curves. occur with single-phase-to-earth faults. Settings of
20 mA and less may then be required depending on
the minimum earth-fault current. Sensitive direc-
tional earth-fault relays (integrated in the relays
7SJ62, 63 and 7SA6) allow settings as low as 5 mA.
2/44 Siemens SIP · 2004

You might also like