The ICAR Group has several plants, all located in Europe. The Power Quality range is made entirely in Italy.
For details on the individual families, download the full catalogs on the website, www.icar.com. Here are all equipment and the
solutions ICAR proposes.
Automatic
Power electronics
Power Factor
capacitors
Correction Banks
LV voltage
EMI RFI filters
stabilizers
Capacitors for
Motor run
energy storage
capacitors
and discharge
1
Services
For many companies, the electricity is an important cost It is also important a proper maintenance and use of original
element, and a part of the amounts is due to the spare parts since capacitors, when worn or of poor quality,
consumption of reactive energy and poor Power Quality. are likely to burst causing damage to electrical equipment,
plant shutdowns due to protection tripping, or even real
All companies that distribute electricity are collecting fire.
penalties in the bill of consumption, if the user consumes
reactive power over the allowed limits, and few are starting Our services:
to set limits to harmonic pollution. • Site surveis to verify existing power factor correction
So today is particularly convenient to install a power factor systems.
correction and active filters systems effectively, correctly • Surveys on electrical systems, as analysis of PFC
sized, which saves a lot of money and to closely monitor • Start-up and commissioning of new LV power factor
the quality of the energy used within a plant. correction banks and Active Harmonic Filters
• Power Quality Analysis in LV installations
But we must not forget the PFC and AHF installed since • Scheduled maintenance on power factor correction
several years: we must monitor the proper functioning systems
because if you do not keep them in perfect working order, • Revamping solutions
they efficiency, and you are likely to pay penalties and have • Original spare parts
unexpected break downs. • Analysis of the Energy Authority Penalties
With proper maintenance you can avoid wasting money
and unnecessary power dissipation in the electric plant
cables and transformers that undergoes premature aging.
Check-up of existing
Local support
PFC systems
2
Quality
ICAR has always regarded product quality and effectiveness
of internal processes as key factors of corporate strategy.
In ICAR we believe that compliance with international
standards is a basic requirement to offer equipment that
can meet the needs of our customers.
Quality System
The ICAR Quality management system is certified
according to ISO 9001 since 1994.
We participate actively in international standards committees
that draft regulations applicable to our production
equipment, and in particular to industrial capacitors: this
guarantees to be always up with changes in legislation, or
rather pre-empt it.
Product quality
The equipment produced in ICAR are tested both in our
laboratories and in the most important internationally
recognized laboratories, in order to ensure compliance with
the highest standards.
3
ACTIVEmatic
FA30
In particular voltage and current harmonics, where the latter
is the more dangerous, generate a series of problems, like:
• Cable overheating.
• Undue tripping of circuit breakers.
• Blowing of fuses.
• Capacitor overloading and network resonance.
• Neutral cable overload.
• Transformer premature ageing.
• Electronic appliances disturbance.
4
Main features
ACTIVEmatic FA30 ACTIVE HARMONIC FILTER is a solid- Capacity ratings
state power converter which measures the harmonics current From 30A to 300A it may increase the maximum capacity
generated by the non-linear load. It generates opposite up to 1500A by using parallel technology. 3 and 4 wires
phase shifted harmonics current of the same amplitude, and versions are available and compensation capability ranges
so it cancels the loads harmonic current and then obtains a from 3rd till 50th harmonic order. Harmonic single activation
sinusoidal current in the utility, also improving power quality can be made by means of user communication software.
and compensating unbalanced currents.
5
Working principle
3 2
150 150
100 100
50 50
0 0
-50 -50
-100 -100
-150 -150
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08
Time (second) Time (second)
150
100
50
-50
-100
-150
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08
Time (second)
6
ACTIVEmatic
Application fields
As the Power Electronic operated loads are widely used The awareness of harmonic pollution consequences, is
in any filed of energy consumption, the need for Active leading Energy Authorities in many countries to rule the
Harmonic Filtration is spreading in Industrial as well as maximum and allowed harmonic pollution generated by
Private and Tertiary applications. Energy Users; consumers are then led to monitor, to keep
The flexibility of ACTIVEmatic compensation allows their under control, and ofter to take measures to respect limits
selection and implementation even at the design stage, and avoid penalties.
without knowing the actual load profiles. ACTIVEmatic is a valid remedy to improve power quality in
ACTIVEmatic can also efficiently compensate harmonic most of the critical parameters.
currents along with other Power Quality devices, such as
Power Factor Correction Banks and Voltage Stabilizers, The following standards applies for harmonics limits in
that ICAR makes and offer as a comprehensive package. electric networks:
EN 61000-2-2, EN 61000-2-4, EN 61000-3-2, EN 61000-
• Variable Speed Drives 3-12, EN 61000-3-3
• (UPSs) Uninterrupted Power Supplies
• Building automation
• Welding
• Tunnel ventilation
• Data centers
• Marine propulsion
• Large elevators and cranes
• Oil and gas
• Wind turbines
• Paper mills
• Steel industry
• Cement industry
• Automotive industry
• Water treatment
7
Technical Characteristics FA30
TECHNICAL CHARACTERISTICS:
Mains frequency: 50/60 Hz ± 3 Hz
Harmonic range: Up to 50th ord
Parallel units: Up to 5
Response time: 300 µs
Orload capability: 2 * In
Cooling Type: Forced air, Forced air + liquid for
200/250/300A
Ambient temperature: 0 – 40°C, derating up to 55°C
0 – 30°C, derating up to 55°C for
FA34 200V and FA34/33 60A
and 120A
For temperature derating refer to
page 12
Ambient conditions: Pollution degree: 2;
Relative humidity: <95%, non-condensing, 3K3;
Interfaces: Modbus RTU (RS485), Modbus
TCP/IP (Ethernet)
Altitude: 1,000 m
Switching frequency: 16 KHz
Controller topology: Digital with FFT analysis
Current limitation: Nominal current
Current transformer: 50/5 A to 50000/5 A
Protection degree: IP20 for 30/50/60/100/120A
(optional IP 54)
IP54 200/250/300A
Cabinet color RAL 7047
GENERALITIES:
• Response time: FA30 reacts to any disturbance within
300μs and it automatically cleans supply line in order to
avoid consequences on other loads and users
• Compact: the best performaces in a very small space
• Easy maintenance,
• Flexible: the continuous generation of out of phase harmonic currents, allows a perfect compensation of load generated harmonic
currents at any time.
All used parts and components are in full compliance with health and safety regulations.
ACTIVEMATIC FA34 200V 30A 50/60HZ - 4 wires 30 90 200/240 ±10% 200/240 ±10% <900 63 70
ACTIVEMATIC FA34 200V 60A 50/60HZ - 4 wires 90 180 200/240 ±10% 200/240 ±10% <1600 63 70
ACTIVEMATIC FA33 480V 30A 50/60HZ - 3 wires 30 380 ±15%, 480 ±10% 380 ±15%, 480 ±10% <900 65 47
ACTIVEMATIC FA33 480V 50A 50/60HZ - 3 wires 50 380 ±15%, 480 ±10% 380 ±15%, 480 ±10% <1300 65 47
ACTIVEMATIC FA33 480V 100A 50/60HZ - 3 wires 100 380 ±15%, 480 ±10% 380 ±15%, 480 ±10% <2200 68 105
ACTIVEMATIC FA33 480V 120A 50/60HZ - 3 wires 120 380 ±15%, 480 ±10% 380 ±15%, 480 ±10% <2500 68 105
ACTIVEMATIC FA33 480V 200A 50/60HZ - 3 wires 200 380 ±15%, 415 ±10% 480 ±10% <5000 70 440
ACTIVEMATIC FA33 480V 250A 50/60HZ - 3 wires 250 380 ±15%, 415 ±10% 480 ±10% <6000 70 440
ACTIVEMATIC FA33 480V 300A 50/60HZ - 3 wires 300 380 ±15%, 415 ±10% 480 ±10% <7500 70 440
ACTIVEMATIC FA34 400V 30A 50/60HZ - 4 wires 30 90 380 ±15%, 415 ±10% 380 ±15%, 415 ±10% <950 63 70
ACTIVEMATIC FA34 400V 60A 50/60HZ - 4 wires 60 180 380 ±15%, 415 ±10% 380 ±15%, 415 ±10% <1800 63 70
ACTIVEMATIC FA34 400V 100A 50/60HZ - 4 wires 100 300 380 ±15%, 415 ±10% 380 ±15%, 415 ±10% <3000 69 145
ACTIVEMATIC FA34 400V 120A 50/60HZ - 4 wires 120 300 380 ±15%, 415 ±10% 380 ±15%, 415 ±10% <3000 69 145
ACTIVEMATIC FA34 400V 200A 50/60HZ - 4 wires 200 60 380 ±15%, 415 ±10% - <5500 70 525
ACTIVEMATIC FA34 400V 250A 50/60HZ - 4 wires 250 750 380 ±15%, 415 ±10% - <6300 70 525
ACTIVEMATIC FA34 400V 300A 50/60HZ - 4 wires 300 750 380 ±15%, 415 ±10% - <8500 70 525
358 415
296
288
296
ACTIVEmatic 30/50A
288
842
615
176
182
240
246
469
358 415
412
296
288
296
412
288
ACTIVEmatic 30/60A
842
615
972
176
182
240
246
253
364
Mechanical data
10 ECOsineTM Active 100/120A (3-wire)
246
Mechanical data
ECOsineTM Active 100/120A (3-wire)
412 469
412
ACTIVEmatic 100/120A (3 phases)
972
ECOsin
253
Mechanical data
364
ECOsineTM Active 100/120A (4-wire)
469
412
412
239
1460
253
364
11
253
364
808
Mechanical data
604
60
2105
ACTIVEmatic 200/250/300A
155
All models - 2% / °C
12
COLTADV.IT
ICCA06A0314E
ICAR S.p.A.
Via Isonzo, 10
20900 Monza (MB) - Italy
tel. +39 039 83.951
fax +39 039 83.32.27 TECHNICAL FEATURES AND DIMENSIONS OF THIS CATALOGUE CAN BE
CHANGED WITHOUT ICAR PRIOR NOTICE.
www.icar.com ICAR DECLINES ANY RESPONSIBILITY FOR DAMAGES TO HUMANS OR
sales@icar.com OBJECTS FROM WRONG SELECTION OR USE OF ICAR MADE PRODUCTS.