Publication version: P3TDS17006en
Protection functions
Parameters and recorded values
Trace back information:
Workspace Main version a186
Checked in 2019-03-21
Skribenta version 5.3.023
Table of Contents
Table of Contents
P3TDS17006en 3
Table of Contents
4 P3TDS17006en
1 Distance protection Z< (ANSI 21)
P3TDS17006en 5
2 Underimpedance (ANSI 21G)
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 2.2: Recorded values of the underimpedance stages Z<, Z<< (21G)
6 P3TDS17006en
3 Volts/hertz over-excitation stage
(ANSI 24)
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 3.2: Recorded values of the volts/hertz over-excitation stage Uf>, Uf>>
(24)
U % Un Fault voltage
f Hz Fault frequency
P3TDS17006en 7
4 Synchrocheck (ANSI 25)
Side U12/U12y; - U12/U12z Voltage selection. The stage 1 has fixed voltages
U12/U12z; U12/U12y.
U12y/U12z
CBObj Obj1 – Obj6 - Obj1 The selected object for circuit breaker (CB) con-
trol. The synchrocheck closing command will use
the closing command of the selected object.
CBObj2 Obj1 – Obj6 - Obj2 The selected object for CB control. The syn-
chrocheck closing command uses the closing
command of the selected object.
ObjSel Digital inputs - - Input for selecting between CBObj1 and CBObj2.
When active CBObj2 is in use
Dibypass Digital inputs - - Bypass input. If the input is active, the function is
bypassed.
SGrpDI Digital inputs - - The input for changing the setting group.
8 P3TDS17006en
4 Synchrocheck (ANSI 25)
P3TDS17006en 9
5 Undervoltage (ANSI 27)
- None
Fx Function key
U<, U<<, U<<< %UN Start value scaled to primary value Set
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 5.2: Recorded values of the undervoltage stages (8 last faults) U<,
U<<, U<<< (27)
10 P3TDS17006en
6 Positive sequence under voltage
(ANSI 27P)
Force Off Force flag for status forcing for test purposes. This is a com- Set
On mon flag for all stages and digital outputs, too. Automatically
reset by a 5-minute timeout.
U1 %
The supervised positive sequence voltage of Un/
LVBlk %UN Low limit for selfblocking. This is a common setting for both Set
stages.
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 6.2: Recorded values of the positive sequence under voltages (8 last
faults) U1<, U1<< (27P)
P3TDS17006en 11
7 Directional power (ANSI 32)
P<, P<< -200.0 – +200.0 %Sn -4.0 (P<), -20.0(P<<) P<, P<< start setting
Table 7.2: Measured and recorded values of P< and P<< stages (32)
12 P3TDS17006en
8 Phase undercurrent (ANSI 37)
- None
Fx Function key
ILmin A Min. value of phase currents IL1, IL2, IL3 in primary value
Flt xIN or xIMOT Min. value of fault current as per times Imot
Edly % Elapsed time as compared to the set operate time, 100% = tripping
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
P3TDS17006en 13
9 Loss of field (ANSI 40)
Force Off Force flag for status forcing for test purposes. This is a common flag Set
On for all stages and output relays, too. Automatically reset by a 5-
minute timeout.
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
14 P3TDS17006en
10 Under-reactance (21/40)
10 Under-reactance (21/40)
Table 10.1: Parameters of the under-reactance stages X<, X<< (40)
Ros ohm Resistive offset for trip area origin in primary ohms
Xos xZN Reactive offset for trip area origin in primary ohms
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
P3TDS17006en 15
10 Under-reactance (21/40)
Table 10.2: Recorded values of the under-reactance stages X<, X<< (40)
16 P3TDS17006en
11 Negative sequence overcurrent
(ANSI 46)
- None
Fx Function key
Equation 11.1:
K1
T= 2
I2
− K 22
I MOT
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
P3TDS17006en 17
11 Negative sequence overcurrent
(ANSI 46)
Table 11.2: Recorded values of the negative sequence overcurrent I2> (46)
18 P3TDS17006en
12 Broken conductor (ANSI 46BC)
Table 12.2: Measured and recorded values of the broken conductor (46BC)
in feeder mode
P3TDS17006en 19
13 Incorrect phase sequence (ANSI
47)
EDly % Elapsed time as compared to the set operate time, 100% = tripping
20 P3TDS17006en
14 Negative sequence overvoltage
protection (ANSI 47)
Force Off Force flag for status forcing for test purposes. This set is a common
On flag for all stages and output relays, too.
Automatically reset by a 5-minute timeout.
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when
force flag is on.
Table 14.2: Recorded values of the negative sequence protection U2>, U2>>,
U2>>>
P3TDS17006en 21
15 Motor start-up supervision (ANSI
48)
Ist> A Motor start detection current scaled to primary value, calculated by relay
Ist> xIMOT Motor start detection current. Must be less than initial motor starting current.
ImotSt A Nominal motor starting current scaled to primary value, calculated by relay
22 P3TDS17006en
15 Motor start-up supervision (ANSI
48)
Status Stopped
Starting
Running
P3TDS17006en 23
16 Thermal overload (ANSI
49F/49M)
ctau xtau Coefficient for cooling time constant. Default = 1.0 Set
Imax40 %IN or %IMOT Allowed load at Tamb +40 °C. Default = 100 %. Set
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
24 P3TDS17006en
17 Phase overcurrent (ANSI 50/51)
- None
Fx Function key
P3TDS17006en 25
17 Phase overcurrent (ANSI 50/51)
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 17.2: Parameters of the phase overcurrent stages I>>, I>>> (50/51)
- None
Fx Function key
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
26 P3TDS17006en
17 Phase overcurrent (ANSI 50/51)
Table 17.3: Recorded values of the overcurrent stages (8 last faults) I>, I>>,
I>>> (50/51)
P3TDS17006en 27
18 Earth fault overcurrent (ANSI
50N/51N)
- None
Fx Function key
Io, IoCalc, IoPeak pu The supervised value according the parameter "Input" below.
Io> pu Start setting relative to the parameter "Input" and the corres- Set
ponding CT value
28 P3TDS17006en
18 Earth fault overcurrent (ANSI
50N/51N)
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
- None
Fx Function key
Io>>, Io>>>, Io>>>>, pu Start setting relative to the parameter "Input" and the corres- Set
Io>>>>> ponding CT value
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
P3TDS17006en 29
18 Earth fault overcurrent (ANSI
50N/51N)
Table 18.3: Recorded values of the undirectional earth fault stages (8 last
faults) I0>>, I0>>>, I0>>>>, I0>>>>> (50N/51N)
30 P3TDS17006en
19 Breaker failure (ANSI 50BF)
1 Relay T1
2 Relay T2
Table 19.2: Recorded values of the breaker failure stage (8 last faults) (50BF)
P3TDS17006en 31
20 Switch-onto-fault (ANSI 50HS)
SOTF active after CB closure s 1.00s SOTF active time after CB closure
32 P3TDS17006en
21 Capacitor bank unbalance (ANSI
51C)
P3TDS17006en 33
21 Capacitor bank unbalance (ANSI
51C)
34 P3TDS17006en
22 Locked rotor (ANSI 51LR)
P3TDS17006en 35
23 Voltage-dependent overcurrent
(ANSI 51V)
23 Voltage-dependent overcurrent
(ANSI 51V)
Table 23.1: Parameters of the voltage-dependent overcurrent stage IV> (51V)
Y1 %IV> Multiplier for start setting at the 1st knee point Set
Y2 %IV> Multiplier for start setting at the 1st knee point Set
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
36 P3TDS17006en
23 Voltage-dependent overcurrent
(ANSI 51V)
P3TDS17006en 37
24 Overvoltage (ANSI 59)
- None
Fx Function key
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 24.2: Recorded values of the overvoltage stages (8 last faults) U>, U>>,
U>>> (59)
38 P3TDS17006en
25 Capacitor overvoltage (ANSI
59C)
Status - -
Blocked -
Start F
Trip F
SCntr Clr
TCntr Clr
SetGrp 1, 2, 3, 4 Set
- None
Fx Function key
15
XC In
UC =
U CLN
∑n
n =1
Equation 25.2:
Q N = 2πf N U CLN
2
C SET
P3TDS17006en 39
25 Capacitor overvoltage (ANSI
59C)
UcLL V
x UcLN
40 P3TDS17006en
26 Neutral voltage displacement
(ANSI 59N)
- None
Fx Function key
Uo %
The supervised value relative to Un/
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 26.2: Recorded values of the neutral voltage displacement stages U0>,
U0>>, U0>>> (59N), U0>>>
Flt %
Fault voltage relative to Un/
P3TDS17006en 41
27 Stator earth-fault (ANSI 64S)
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 27.2: Recorded values of the 100 % stator earth fault stage U0F3< (64S)
Flt %
3rd harmonic value relative to Un/ during fault
42 P3TDS17006en
28 Motor restart inhibition (ANSI 66)
Default t 0 min or 120 min Default elapsed time from motor start
P3TDS17006en 43
29 Directional phase overcurrent
(ANSI 67)
- None
Fx Function key
44 P3TDS17006en
29 Directional phase overcurrent
(ANSI 67)
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
- None
Fx Function key
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
P3TDS17006en 45
29 Directional phase overcurrent
(ANSI 67)
46 P3TDS17006en
30 Directional earth fault overcurrent
(ANSI 67N)
- None
Fx Function key
Ioφ> pu Start setting relative to the parameter “Input” and the corres- Set
ponding CT value
Uo % Measured U0
P3TDS17006en 47
30 Directional earth fault overcurrent
(ANSI 67N)
Offset ° Angle offset (MTA) for RecCap and Sector modes Set
Sector Default = 88 ±° Half sector size of the trip area on both sides of the offset Set
angle
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 30.2: Recorded values of the directional earth fault overcurrent stages
(8 last faults) I0φ>, I0φ>>, I0φ>>> (67N)
48 P3TDS17006en
31 Transient intermittent earth fault
(ANSI 67NI)
- None
Fx Function key
Direction mode Forward Setting between direction towards line or bus Set
Reverse
Intrmt s Intermittent time. When the next fault occurs within this time, Set
the delay counting continues from the previous value.
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
P3TDS17006en 49
31 Transient intermittent earth fault
(ANSI 67NI)
Table 31.2: Recorded values of the transient intermittent earth fault stage (8
latest faults) I0INT> (67NI)
50 P3TDS17006en
32 Magnetishing inrush detection
(ANSI 68F2)
Measured values IL1H2. % 2. harmonic of IL1, proportional to the fundamental value of IL1
EDly % Elapsed time as compared to the set operate time; 100% = tripping
P3TDS17006en 51
33 Fifth harmonic detection (ANSI
68H5)
Table 33.2: Measured and recorded values of the fifth harmonic detection
(68H5)
52 P3TDS17006en
34 Pole slip protection (ANSI 78)
- None
Fx Function key
R setting forward xZn Pole slip detection area forward R limit Set
R setting reverse xZn Pole slip detection area reverse R limit Set
X setting forward xZn Pole slip detection area forward X limit Set
X setting reverse xZn Pole slip detection area reverse X limit Set
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
Table 34.2: Recorded values of the out-of-step (pole slip) stage (78)
P3TDS17006en 53
35 Auto-recloser function (ANSI 79)
ExtSync None, - - The digital input for blocking CB close. This can be used for
any digital input, Synchrocheck.
virtual input or virtu-
al output
AR_DI None, - - The digital input for toggling the enabling/disabling parameter
any digital input, (ARena)
virtual input or virtu-
al output
ReclT 0.02 – 300.00 s 10.00 Reclaim time setting. This is common for all the shots.
CB2Sel None, any digital - The digital input for selecting the CB2.
input, virtual input
or virtual output
Shot settings
DeadT 0.02 – 300.00 s 5.00 The dead time setting for this shot. This is a common setting
for all the AR lines in this shot
54 P3TDS17006en
35 Auto-recloser function (ANSI 79)
AR1 On; Off - Off Indicates if this AR signal starts this shot
AR2 On; Off - Off Indicates if this AR signal starts this shot
AR3 On; Off - Off Indicates if this AR signal starts this shot
AR4 On; Off - Off Indicates if this AR signal starts this shot
Start1 0.02 – 300.00 s 0.02 AR1 Start delay setting for this shot
Start2 0.02 – 300.00 s 0.02 AR2 Start delay setting for this shot
Start3 0.02 – 300.00 s 0.02 AR3 Start delay setting for this shot
Start4 0.02 – 300.00 s 0.02 AR4 Start delay setting for this shot
Discr1 0.02 – 300.00 s 0.02 AR1 Discrimination time setting for this shot
Discr2 0.02 – 300.00 s 0.02 AR2 Discrimination time setting for this shot
Discr3 0.02 – 300.00 s 0.02 AR3 Discrimination time setting for this shot
Discr4 0.02 – 300.00 s 0.02 AR4 Discrimination time setting for this shot
P3TDS17006en 55
35 Auto-recloser function (ANSI 79)
* There are 5 counters available for each one of the two AR signals.
56 P3TDS17006en
36 Overfrequency and
underfrequency (ANSI 81)
36 Overfrequency and
underfrequency (ANSI 81)
Table 36.1: Parameters of the overfrequency and underfrequency stages
(81)
- None
Fx Function key
LVblck % Un Low limit for self blocking. This is a common setting for all four Set
stages.
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
P3TDS17006en 57
36 Overfrequency and
underfrequency (ANSI 81)
58 P3TDS17006en
37 Rate of change of frequency
(ANSI 81R)
P3TDS17006en 59
38 Differential overcurrent protection
(ANSI 87M / 87L)
38 Differential overcurrent
protection (ANSI 87M / 87L)
Table 38.1: Parameters of the differential overcurrent stages ΔI> (87)
Type 1-N, 2-N, 3-N Fault type/single-phase fault e.g.: 1 – N = fault on phase L1
1-2, 2-3, 1-3 Fault type/two-phase fault e.g.: 2 – 3 = fault between L2 and L3
Recorded values Type 1-N, 2-N, 3-N Fault type/single-phase fault e.g.: 1-N = fault on phase L1
1-2, 2-3, 1-3 Fault type/two-phase fault e.g.: 2-3 = fault between L2 and L3
60 P3TDS17006en
39 Cold load start and magnetising
inrush
MaxTime s Set
Idle xIN or xIMOT Current limit setting for idle situation Set
Start xIN or xIMOT Start setting for minimum start current Set
Startf2 % Start value for relative amount of the second harmonic, If2/If1 Set
P3TDS17006en 61
40 Programmable stages (99)
- None
Fx Function key
Link See Table "Avail- Name for the supervised signal Set
able signals to be
supervised by the
programmable
stages" in the
product user
manual.
> Overprotection
< Underprotection
Diff Difference
Set = An editable parameter (password needed). C = Can be cleared to zero. F = Editable when force flag is on.
62 P3TDS17006en
40 Programmable stages (99)
P3TDS17006en 63
http://www.schneider-electric.com/CCC
Schneider Electric
www.schneider-electric.com 10/17
Publication version: P3TDS17006en