A 2 B C FOR OFFICIAL USE ONLY

3947 968 4196 586 2044 1716 1812


171

347
513
GENERAL NOTES:

3473
T20 @ 100 C/C (T) 1. DIMENSIONS TO BE READ ONLY.

2436
2. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED OTHERWISE.
3. CHANGE IN DIMENSION TO BE NOTIFIED TO THE CONSULTANCY IMMEDIATELY.
4. ALL DRAWINGS AND SPECIFICATIONS REMAIN THE PROPERTY OF THE CONSULTANT.
4 4
5. THE STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH
ARCHITECTURAL DRAWINGS. DISCREPANCIES, IF ANY, SHALL BE REPORTED TO
SITE ENGINEER.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING FIELD DIMENSIONS AND
SITE CONDITIONS.
7. GRADE OF CONCRETE MIX SHALL BE M20 FOR FOOTING, M25 FOR BEAM AND SLAB M30 FOR COLUMNS CONFIRMING TO NBC 110 : 1994.
8. REINFORCEMENT SHALL BE THERMO MECHANICALLY TREATED OF GRADE
4696

4696
Fe : 500 CONFORMING TO NBC 101 : 1994 / NS 191.
1 1 9. CLEAR COVER TO REINFORCEMENT SHALL BE AS FOLLOWS :
FOOTING : 50 mm
COLUMN :40 mm
BEAM : 25 mm
SLAB : 15 mm
3 3
STAIR SLAB : 15 mm

T20 @ 150 C/C (T)


1000

10. LAP LENGTH SHALL BE 60 TIMES THE DIAMETER OF THE BAR.


11. DEVELOPMENT LENGTH SHALL BE 60 TIMES THE DIAMETER OF THE BAR.
12. NOT MORE THAN HALF THE COLUMN BARS SHALL BE LAPPED AT A SECTION.
13. LAP SPLICES SHALL BE PROVIDED ONLY IN THE MIDDLE HALF OF THE COLUMN.
14. LAPPING OF BOTTOM BARS IN THE BEAM SHOULD BE RESTRICTED TO A REGION
AT LEAST '2Z' AWAY FROM COLUMN FACE WHERE 'z' IS THE BEAM DEPTH BUT

4900
EXCLUDING MIDDLE QUARTER LENGTH OF THE BEAM WHILE LAPPING OF TOP
3900

BARS SHOULD BE RESTRICTED TO ONE - THIRD LENGTH OF THE BEAM.

T20 @ 90 C/C (B)


15. CONFINING STIRRUP IN BEAM - COLUMN JUNCTION SHALL BE PROVIDED IN 'z'
PORTION AT THE SPACING INDICATED WHERE 'z' IS THE BEAM DEPTH. HOWEVER
IF BEAMS ARE CONNECTED ON ALL THE FOUR DIRECTIONS OF THE COLUMNS
THE SPACING SHOULD BE DOUBLED. IN CASE OF DIFFICULTY IN PROVIDING
2 2
CLOSED STIRRUPS, U - TYPE STIRRUPS MAY BE PROVIDED.
16. AT BEAM - COLUMN JUNCTIONS, BEAM BARS IF IN CONFLICT WITH COLUMN BARS
SHOULD BE GRADUALLY BENT AND PLACED CLEAR OFF COLUMN BARS. UNDER
NO CIRCUMSTANCES COLUMN VERTICAL BARS SHALL BE BENT TO ACCOMMODATE
BEAM BARS.
17. UNLESS OTHERWISE INDICATED ALL CONSTRUCTION JOINTS SHALL BE
4400

4400
ROUGHENED JOINTS WITH MINIMUM AMPLITUDE OF 5 mm.
18. PLUMBING SLOTS,HOLES AROUND PIPES,DUCTS OR OTHER ITEMS WHICH PASS
THROUGH CONCRETE SLAB OR WALL SHALL BE FILLED AND PATCHED TO THE
SAME DEPTH AS THE SLAB OR WALL.
19. IN DRAWINGS 'TH'&'EX' DENOTES FOR THROUGH& EXTRA RESPECTIVELY
20. DISTANCE OF END TIES 'Z1' FROM FACE OF COLUMN SHALL BE 600mm.
1 1
T20 @ 150 C/C (B)

1704

194
1138 2616 5750 3760

A B C
2

FOUNDATION LAYOUT PLAN


(SCALE 1:100)

1851 2824 1855 850

800 600 700


350 350

T20@150 C/C (T)


T20@150 C/C (B)

EL. 4.35m
1200

BOF

150 THK PCC


T20@150 C/C (T)
T20@150 C/C (B)
15112

SECTION 1-1
DETAIL OF RAFT FOOTING
(SCALE 1:50)
1553 2375 2525 2867
OWNER: SIGNATURE:
700 700 700
350 350 BARSHA SHRESTHA
T20@150 C/C (T)
T20@150 C/C (B)
BUILDING TYPE: LOCATION:

RESIDENTIAL DILLIBAZAR,KATHMANDU

EL. 4.35m PLOT NO.: AREA:


1200

BOF 655
0 - 9 - 3 - 0.97 R-A-P-D
311.9409 SQ. M.

DETAILS:
150 THK PCC FOOTING DETAILS
T20@150 C/C (T)
T20@150 C/C (B) DRAWN BY: CHECKED BY:
Saroj Bhattarai ..
18989

SECTION 2-2
DATE: 2022.06.12 SCALE: AS SHOWN
NEC Reg No: 573 'A' SHEET NO:
DETAIL OF RAFT FOOTING KMC Reg No: 1994
ST-01