You are on page 1of 1

A B C D E F G H I J K

1 1

3100 3100 3100 3100 3100 3100

2 2

3
PLAN FOR PV TABLE

3
3 3

4 4

NOTES : -

B B 1. ALL DIMENSIONS ARE IN MM UNLESS OTHERWISE SPECIFIED.


NO DIMENSIONS ARE TO BE SCALED FROM DRAWING.
2. CONTRACTOR MUST VERIFY ALL DIMENSIONS ON SITE BEFORE COMMENCING THE WORK.
3. ALIGNMENT AND CENTERING OF FOUNDATION PILE SHALL BE CHECKED BEFORE
POURING CONCRETE.
4. CONCRETING OF PILE SHALL BE UNIFORM.
5. PILES ARE DESIGNED AS PER IS 456: 2000 AND IS 2911: 2010
5 (PART1 - SEC 2) USING LIMIT STATE METHOD. 5
6. THE GRADE OF CONCRETE SHALL BE OF 25 MPA .
7. MAXIMUM NOMINAL SIZE OF AGGREGATES SHOULD BE 20 MM .
3 8. AFTER MIXING , CONCRETE TO BE TRANSPORTED TO THE FORMWORK AS RAPIDLY AS
POSSIBLE BY METHODS WHICH WILL PREVENT THE SEGREGATION OF LOSS OF ANY OF THE
INGREDIENTS OR INGRESS OF FOREIGN MATTER OR WATER AND MAINTAINING THE REQUIRED
WORKABILITY.
9. THE CONCRETE TO BE DEPOSITED AS NEARLY AS PRACTICABLE IN ITS FINAL POSITION TO
FOR DETAIL REFER 10.
AVOID RE HANDLING.
THE CONCRETE TO BE PLACED AND COMPACTED BEFORE INITIAL SETTING OF CONCRETE
SECTION A-A COMMENCES AND SHOULD NOT BE SUBSEQUENTLY DISTURBED .

6 6
REFER DRAWING NO : -
1. MODULE MOUNTING STRUCTURE GENERAL ARRANGEMENT DRAWING -- JEL-S029-CE-001-DRG-005_R04
2. MODULE MOUNTING STRUCTURE- FABRICATION DRAWINGS --JEL-S029-CE-001-DRG-005A_R04 (Sh.01 TO 10)
3. OVERALL MODULE LAYOUT ---------------------------------------------------JEL-S029-CE-001-DRG-001_R02
TYP. VIEW OF MODULE 4. OVERALL PLANT PILE FOUNDATION MARKING-------------------------JEL-S029-CE-001-DRG-007A_R02
STRUCTURE FOUNDATION

03 REVISED AS PER CUSTOMER COMMENT 3 A.A V.K K.P M.A 02.03.17


02 REVISED AS PER CUSTOMER COMMENT M.H V.K K.P M.A 03.02.17
7
SECTION A-A 01 REVISED AS PER CUSTOMER COMMENT M.H V.K K.P M.A 12.01.17
7

00 RELEASED FOR APPROVAL M.H V.K K.P M.A 15.12.16


Rev DETAILS OF REVISION AND DESCRIPTION Drawn Design Checked Approved Date

PROJECT
A

7.5MW SOLAR POWER PLANT AT INDIAN OIL SANAND


BOTTLING PLANT DIST.-AHMEDABAD,GUJARAT

OWNER INDIAN OIL CORPORATION


LIMITED,AHMEDABAD
8 8
EPC
CONTRACTOR JAKSON ENGINEERS LIMITED (JEL)

SECTION B-B 3
TITLE
DETAIL OF PILE FOUNDATION FOR
Scale NTS
(MAIN VERTICAL COLUMN CONNECTION MODULE MOUNTING STRUCTURE
A

Sheet 01 of 01
WITH SHORT COLUMN)
JEL Dwg. No.
PILE FOUNDATION PLAN JEL-S029-CE-001-DRG-007 Date 15.12.16

9 NOTE: THE DRAWINGS OF THIS DRAWING SET IS THE PROPERTY OF JAKSON ENGINEERS 9
LIMITED. COPYING OR REUSE OF THIS DRAWING WITHOUT PERMISSION IS PROHIBITED. Rev 03