Professional Documents
Culture Documents
ith the introduction of the smart quency and voltage support, active and reactive power con-
W
grid, there is an intense interest in the inte- trol, and better energy management through storage tech-
gration of intelligent and flexible microgrids nologies. The proximity of power generation to microgrid
in large-scale power systems. Microgrids consumptions could result in improved power quality,
would be operated locally in grid-connected lower power losses, better voltage stability, and higher reli-
and island modes and can provide black start operation, fre- ability (fewer customer outages) by engaging fewer compo-
nents and eliminating additional transmission services.
Distributed energy resources (DERs), which include distrib-
uted generation (DG), distributed storage, and adjustable
Digital Object Identifier 10.1109/MELE.2013.2273994
Date of publication: 23 October 2013 load, are a key component in microgrid operations.
Tertiary
Control Unit Islanding
Economical Commitment and Emergency Primary
Self-
Demand and Resynchronization Demand Secondary Control
Economical Healing
Response Response Control
Dispatch
Microgrid Components
Meters Coupling
Wind PV Gas Building HRDS Gas
and Switch
Turbine Arrays Turbines Controllers Switches Turbines
PMUs at PCC Set Point Values
Control Commands
Battery Battery Monitoring Signals Battery
Storage Storage Storage
Figure 1. The objectives and functions for the control and operation of the IIT microgrid.
Cu
n
PMU
TX
TRI
nin
Law
AEP
g
Parking
Flower
Farr IPS
East
Lewis
ha
Gunsaulus Gas Generator
m
Graduate
Charging Station
PKS
Chapel
Solar PV
North
South
PKP
SPE
DTD
Loop 4
ASP
Carmen
Bailey Loop 2 MTCC
Keating (Gymnasium) MC Parking Parking
KH
Commons
Parking
Parking
Parking
Parking Parking
Downtown State Street
Perlstein
E1 PH
AM
TS
Siegel
Alumni
Crown
LS
SB
Engineering 1 WH SH
CR
TN
TC
Stuart
Life Science
Loop 5
IIT Tower
HH GL
AAR 3
Loop 1
Loop 3
Parking
Parking South Substation IITRI
Chemistry
Wind Turbine AAR 2 VanderCook North Substation CO-GEN Power Plant
Machinery
43
May 2013. Here, the wind turbine unit would spin when the
wind speed is higher than 10 mi/h (4.47 m/s).
Battery Storage
The IIT microgrid is equipped with a 500-kWh battery
storage system (including ten 50-kWh battery cells)
with 250-kW power capacity, which is connected to
Loop 1. Figure 9 shows a stack of the flow battery and
the battery inverter, which can regulate the real and
reactive power output.
HRDS Switches
The HRDS at IIT uses underground closed-loop fault-
clearing Vista switchgear with SEL-351 directional over-
Figure 3. The full-scale model of the natural-gas turbine at IIT.
current protection relays. The fault isolation takes place in
a quarter of a cycle by automatic breakers. The communi-
cation via fiber-optic cables facilitates the coordination
between Vista switches. Figure 10 shows the underground
installation of a HRDS switch at IIT. In HRDS, at least two
simultaneous failures in the cable segments feeding a
building from both paths will lead to a complete outage in
the building. As the chances of two coincident failures is
far less than single failures in cables feeding, the interrup-
tion indices of the buildings are improved significantly by
the installation of HRDS. Figure 11 shows a loop configura-
tion in distribution system at IIT. Here, in Loop 1, any cable
Figure 4. The solar panel in IIT’s charging station.
failure between Vista switches 1C and 1D will be cleared,
and the Stuart and Life Sciences Buildings fed by the
uses a Viryd wind turbine unit. The wind turbine features switches will not face any interruptions.
continuous variable transmission (CVT) technology, which
provides automatic and continuous variable ratio change Meters and PMUs
that maintains stable rotor speed for the generator as wind The IIT microgrid is equipped with building meters and
speed changes. This would enable the generator to main- PMUs, which report building electricity consumptions to
tain high efficiency at all wind speeds. The CVT can also the master controller. The master controller will receive an
precisely slow the rotor in high wind speed, curtailing the energy consumption update every 15 min. The load data
excess wind power. Figure 7 shows the structure of the recorded on 17 July 2012 at the McCormick Tribune Campus
CVT-based wind turbine unit. The role of the variable gear Center (MTCC) at the IIT microgrid are shown in Figure 12.
ratio is to regulate the power output close to the rated value Approximately 30% of building consumptions at IIT are
when the wind speed is within the acceptable range. The shiftable loads, which can be served when the electricity
cut-in and cut-off wind speeds for this turbine are 4.5 and price is lower. The IIT microgrid is equipped with 12 PMUs
25 m/s, respectively, and the turbine has an 8-m diameter that monitor and record the real and reactive generation
and 50-m2 sweep area. Figure 8 shows the hourly power and consumption in real time and provide the information
output and the wind speed for the wind turbine unit on 20 on instantaneous voltage and current of DER units (includ-
ing the magnitude and phase angle)
at a sampling rate of one signal per
cycle to the master controller.
Angle Magnitude Figure 13 shows a PMU installed at
Control Control
MPPT the North Substation. Figure 14
ang mag
VPV, IPV Qout shows the real and reactive power of
Vdc PWM
critical loads and DER units, which
are calculated by master controller
Microgrid
ac Filter
based on the instantaneous values.
Vo
Capacitor
Building Controllers
Building controllers facilitate the
Figure 5. The equivalent circuit and power output characteristics of a solar PV cell. building consumption manage-
Microgrid
tional DGs and PE coupled DGs. Wind
Table 1 shows that the DER control
schemes are categorized into grid-
Induction
following and grid-forming control. Turbine CVT Generator
In grid-forming control, DER
units maintain the microgrid volt-
age and frequency, while in the Figure 7. A CVT-based wind turbine unit with a fixed-speed induction generator.
grid-following control, the units
maintain their individual real and
reactive power dispatch. In other Wind Generation Power Output (kW)
words, DER units with grid-forming 8 Wind Speed (mi/h) 25
7
control would act as the swing bus 20
Wind Speed (mi/h)
6
Dispatch (kW)
12.47 kV
PCC
North South
Substation Substation
4.16 kV 4.16 kV
VanderCook
Engineering 1
Vista lE
Vista lA
=
Gas-Turbine
S
= Synchronous
= Machinery Generators
Loop 1
Loop 2
Loop 3
Loop 7
CTA 1
S
PV =
Vista lD
Vista lB
=
Life Sciences =
S
=
S
= Vista lC
CTA 2 =
Battery = PV
S
=
Stuart =
= PV
Wind
PV
Figure 11. The DER units and HRDS in the IIT microgrid.
dispatch signals are sent to dispatchable DER units on master controller indicate the status of DER and distribution
campus, and the load signals are sent to the building components, while the master controller signals provide set
controllers. points for DER units and building controllers. Building con-
xxThe building controllers are responsible for setting the trollers will communicate with sub-building controllers
building loads according to the dispatch signal through a ZigBee wireless control and monitoring system to
received from the master controller. achieve a device-level rapid load management.
xxThe sub-building controllers
preform device-level load man-
380
agement by controlling the opera-
360
tion status of devices located in 340
Dispatch (kW)
buildings. 320
The hierarchical tertiary control 300
approach would receive the informa- 280
tion from loads and power supply 260
entities on campus as well as the 240
information on the status of campus 220
distribution network and procure the 200
12:14:33 a.m.
12:59:33 a.m.
1:44:33 a.m.
2:29:33 a.m.
3:14:33 a.m.
3:59:33 a.m.
4:44:33 a.m.
5:29:33 a.m.
6:14:33 a.m.
6:59:33 a.m.
7:44:33 a.m.
8:29:33 a.m.
9:14:33 a.m.
9:59:33 a.m.
10:44:33 a.m.
11:29:33 a.m.
12:14:33 p.m.
12:59:33 p.m.
1:44:33 p.m.
2:29:33 p.m.
3:14:33 p.m.
3:59:33 p.m.
4:44:33 p.m.
5:29:33 p.m.
6:14:33 p.m.
6:59:33 p.m.
7:44:33 p.m.
8:29:33 p.m.
9:14:33 p.m.
9:59:33 p.m.
10:44:33 p.m.
11:29:33 p.m.
Primary Control
The primary control, shown in Figure 1, is the lowest level
of control in the IIT microgrid. The primary control is
mainly used for load sharing among controllable and dis-
Figure 13. The PMU at the North Substation. patchable fast-response DER units, which have adequate
capacity to serve the microgrid load. The most widely used
primary control strategy is droop control, which is shown
Secondary Control in Figure 18. DER units equipped with droop control, which
Secondary control in Figure 1 is the middle level control at are connected in parallel, would not need to communicate
the IIT microgrid. Secondary control is used to eliminate with each other to perform load sharing; instead, individu-
frequency and voltage deviations caused by lower control al dispatch levels are calculated based on predefined droop
level (primary control). As illustrated in the Figure 17, once characteristics and microgrid frequency and voltage. In
PMU Information
Figure 14. Real and reactive power based on PMUs on DER units.
LS.AH08.CURT LS8SYS
Curtailment Descriptor
NONE Priority
OFF Value N/A Units
Figure 15. The building controllers showing the status of controllable loads in three buildings in Loop 1 at IIT.
Figure 18, the DER dispatch P is at its rated value Prated at the turbine and exciter, respectively, to regulate the real
the rated frequency frated , which are determined by the and reactive power output and maintain the microgrid
master controller through tertiary control level. As the fre- frequency and voltage at the rated values. At steady state,
quency increases, there will be a slight decrease in power if the generator dispatch is deviated from the rated value
dispatch to compensate the frequency deviation. Similarly, through primary droop control, the secondary control will
as the microgrid voltage increases, the injected reactive generate a nonzero adjustment signal shown in (1) to
power decreases to compensate the voltage drop. In Figure restore the frequency or voltage back to the rated value.
18(a) and (b), m p and m q , respectively, represent the slopes Thus, the natural-gas turbine synchronous generator
of the f - P and v - Q curves. The DER units at the IIT would serve the campus load while maintaining the
microgrid, which are equipped with primary and sec- microgrid frequency and voltage at the rated value.
ondary control, are the natural-gas turbine synchro-
nous generator and the battery storage unit. ~ 2nd = m p $ ^P - Prated h
V2nd = m q $ ^Q - Q rated h. (1)
Natural-Gas Turbine Synchronous Generator
Figure 19 shows the control diagram for the natural-gas Battery Storage Unit
turbine synchronous generator. Here, ~ , ~ rated , V , and The control structure of the battery storage system is
Vrated are the measured speed, rated speed, measured volt- shown in Figure 20, where the battery storage is connect-
age, and rated voltage of the synchronous generator, ed to the microgrid through a bidirectional dc/ac inverter,
respectively; P, Prated , Q , and Q rated are the measured real an ac filter, and a transformer. Here, the output real and
power, rated real power, measured reactive power, and reactive power denoted by P and Q is calculated by
rated reactive power of the generator, respectively; ~ 2nd measuring the terminal voltage and current Vo and I o .
and V2nd are the adjustment signals used for secondary The measured real and reactive power are used in the
control. As shown in Figure 19, the natural-gas turbine primary droop control to provide a reference voltage sig-
and exciter provide the input mechanical torque TM and nal V *o . The voltage loop is used to stabilize the inverter
excitation to the generator. The primary and secondary terminal voltage using the reference voltage signal and
control modules for ~ - P and v - Q generate signals to to ensure that the DER output impedance is inductive at
Economical Operation
Storage Control The cost of economical
System
operation includes the cost
of utility grid energy trans-
Battery Storage actions (in both directions),
Charging Station cost of microgrid energy
supply, and load curtail-
ment costs (value of lost
Figure 16. Architecture of master controller at IIT. load.) Microgrid outages
Q-V
V2nd Secondary
Vrated +
Prated +
Q-V
Tertiary Qrated Primary
Control
signals when the price of electricity is high, which would was recorded by ComEd. Here, the campus load is reduced
lower the cost of supplying the campus load. Here, the by 60% through curtailing building loads, shifting campus
building load is shifted from peak hours 16–18 to off-peak loads, and dispatching the natural-gas turbine at IIT.
hours 4–6. The set points shown in Figure 22 are sent to
DER units and building controllers to set the campus load Short-Term Reliability
and generation. The local microgrid generation is also The IIT microgrid connects to the utility grid through
used to supply the peak demand at the utility grid. four 12.47-kV feeders located at the North and South
Accordingly, the daily energy cost of the microgrid is Substations. The IIT microgrid can operate in both grid-
reduced from US$15,524 to US$13,715. Figure 23 shows the connected and island (autonomous) modes. In the grid-
economical load reduction at IIT on 19 August 2010, which connected mode, the microgrid frequency and voltage
Inverter
ac Filter
Microgrid
PWM
Ic Vo Vo Io
Primary
∗ Control
Current Voltage Vo P, Q Power
Loop Loop Calculation
Biloop
Secondary
Control
Tertiary
fMG, VMG
Control
Power (kW)
20
while solar PV and wind turbine units 7,000
serve portions of the campus load. 15
5,000
The short-term microgrid reliability is 10
3,000
enhanced by implementing three
1,000 5
major functions at IIT: islanding and
resynchronization, emergency −1,000 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 0
demand response, and self-healing, Time (h)
which are discussed in this section. Utility Grid Supply Total Demand
Battery Supply Price of Electricity
Microgrid Supply
Islanding and Resynchronization
The microgrid may increase its load
point reliability indices by setting up Figure 21. The day-ahead storage, microgrid, and utility grid supply on 17 July 2012.
its operation in island mode. Gener-
ally, there are two major reasons for
setting up a microgrid in island mode: 1) poor power nization signals to the campus DER units through sec-
quality at the utility grid, such as frequency or voltage ondary control for mitigating any possible transients.
deviations, and 2) major faults at the utility grid. PMUs The following criteria are to be satisfied for transition
and voltage/current meters at the point of common cou- from island to grid-connected mode:
pling (PCC) would report the utility grid malfunction to 1) The voltage magnitude difference at the PCC would be
the master controller, which will initiate the islanding small.
process at the tertiary control level. The master controller 2) The frequency difference would be small to match the
will monitor building meters for supplying the local gen- voltage phase angles at the switching instance.
eration dispatch. At islanding, the master controller may 3) The voltage angle with the lower frequency should lag
reduce the campus load through emergency demand behind that of the higher frequency. Figure 25 shows
response to match the load with the local generation dis- the voltage angle difference between the microgrid and
patch. The load reduction may entail shifting building the utility grid at resynchronization instance. Assuming
loads and reducing curtailable building loads. Matching that the microgrid frequency is slightly smaller than
the load with generation at islanding will reduce tran- that of the utility grid if VMG leads Vgrid , then the power
sients and ensure a feasible microgrid operation consid- flow will be from the microgrid to the utility grid and in
ering the ramping limits of DER unit g eneration. the reverse direction at steady state. The flow from the
Figure 24 shows the campus load restoration in island microgrid to the utility grid at resynchronization may
mode at the Engineering 1 and Stuart Buildings located result in the overloading of the microgrid DER units.
in Loop 1 on 19 July 2012. The load restoration started at The IIT microgrid resynchronization process is present-
6:19 a.m. on both buildings and was fully restored at 6:29 ed as follows. At first, the master controller will send the
a.m. Figure 24(b) shows the inrush
current of a switched-on transform-
er located in the Stuart Building. In 13,000 30
Electricity Price (cents/kWh)
20
by the battery storage through pri-
7,000
mary and secondary controls. Once 15
5,000
the normal operation at the utility 10
3,000
grid is restored, the microgrid will be
1,000 5
resynchronized with the utility grid.
In island mode, the microgrid could −1,000 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 0
be operated at a frequency and a Time (h)
voltage magnitude that are different
than those of the utility grid, which Utility Grid Supply
Total Demand
could cause transients during the Utility Grid Supply with Building Controllers
resynchronization process and dam- Price of Electricity
age the substation equipment. The
master controller will send synchro- Figure 22. The day-ahead economical demand response by building controllers on 17 July 2012.
(°F)
5,000 50
40 the emergency demand response will
4,000
3,000 IIT Load 30 match the load with the generation
2,000 Temperature 20 (e.g., dispatch the battery storage or
1,000 10
curtail building loads), while in grid-
0 0
0:00 4:00 8:00 12:00 16:00 20:00 24:00 connected mode, the microgrid
Time (h) would curtail loads as required. The
master controller will communicate
Figure 23. The load reduction test at the IIT microgrid on 19 August 2010. with building controllers to curtail or
shift loads and monitor the updated
frequency adjustment signal to the natural-gas turbine and load level through building meters.
the battery storage unit to adjust the microgrid frequency Once the campus load is reduced, DER units on campus
to less than nominal frequency (59.9 Hz). The secondary will be redispatched through primary and secondary con-
control will maintain a lower microgrid frequency than that trols to maintain the nominal voltage and frequency. After
of the utility grid before resynchronization. When the the completion of emergency demand response, the ter-
microgrid voltage angle lags behind that of the utility grid tiary control provided by master controller will procure
slightly (fewer than 10), the PCC switch will be closed, and the steady-state optimal generation dispatch of dispatch-
the IIT microgrid will be resynchronized with the utility. able DER units.
200
Current (A)
150
100
50
0
0 20 40 60 80 100 120 140 160 180
6:18 a.m. Time (s) 6:21 a.m.
(a)
Current (A)
20 120
15 100
80
10
60
5
40
0 20
0 20 40 60 80 100 120 140 160 180 0 50 100 150 200 250 300
6:19 a.m. Time (s) 6:22 a.m. 6:28 a.m. Time (s) 6:33 a.m.
(b)
Figure 24. The load restoration at the (a) Engineering 1 and (b) Stuart Buildings in Loop 1 in island mode on 19 July 2012.
Conclusions Vgrid
This article discusses the hierarchical control of
VM
microgrids and the role of primary, secondary, and ter- G Lags
Vg
rid
tiary controls in enhancing the microgrid reliability VMG
and economics and introduced the control applica-
tions to a functional microgrid at IIT. The IIT microgrid Figure 25. The voltages at the microgrid and the utility grid.
is analyzed as a test bed, and the functions for imple-
menting microgrid objectives are
discussed. The functions include
unit commitment and economi- Motor 1 Motor 2
cal dispatch, economical demand
response, islanding and resyn- Generator
chronization, emergency demand
response, and self-healing. The
MV Breaker
master controller applies tertiary
(a)
and secondary control to ensure
Motor 1 Motor 2
the economical and reliable oper-
ation of the microgrid. Primary
control is applied at the DER unit Generator
level to respond to disturbances
i n a s h o r t t i m e, w h i l e t h e Vista Switch 1 Vista Switch 2
s econdary and tertiary control
signals eliminate errors intro- (b)
duced by primary control to regu-
late the voltage and frequency Figure 26. Distribution networks (a) with and (b) without HRDS switches.