BL 600 250 SUMP OR TRENCH WIDTH 250 600 3 ON LAYOUT DRAWING, SEE TABLE PANEL WIDTH = +100 GRATING - TYPE 1
VARIES, SEE DESIGN DWG'S SET ANGLE 30mm TRENCH WIDTH +65 GRATING - TYPE 2
BELOW TOP OF SLAB +45 GRATING - TYPE 3
ISLOATION JOINTS
PANEL LENGTH
DETAIL 1 0 A A
12
2400 MAX.
TRENCH SEE FLOOR TRENCH TRENCH ANGLE SIZE TO SUIT
30 GRATING, SEE TABLE SPAN
CONSTRUCTION
50
JOINT
COLUMN 30x6 FLAT BAR ANCHORS AT 300 o/c SUPPORTING BAR
INVERT (ALTERNATE AS SHOWN)
EL. VARIES
BL
450
EQUIPMENT PAD
DETAIL 1 TRENCH
250
WIDTH
CONSTRUCTION OR TABLE
ISLOATION JOINTS
CONTROL JOINTS,
PLAN
SEE NOTES SUMP OR TRENCH 900-1750 DEEP USE
L 65x65x6
1
NOTES:
B
A
L 45x45x6 SUPPORTING BARS
1. VARY JOINT SPACING TO SUIT SLAB THICKNESS AND CURING PROCEDURES. 2
B
2. CONSTRUCTION JOINTS: DETAIL 1
SEE FLOOR TRENCH 3 L 35x35x6
- INSTALL WHEN CONSTRUCTION IS INTERRUPTED FOR 30 MINUTES OR MORE.
A
GRATING DETAILS
- LOCATE AT LOCATIONS WHICH WOULD OTHERWISE BE PROVIDED WITH A 200 SUPPORTING BAR
CONTROL JOINT, AT HIGH POINTS OF FLOOR. TYP.
3. CONTROL JOINTS:
- LOCATE SO PANELS ARE AS SQUARE AS POSSIBLE. ENSURE LONG SIDES OF PANELS DO
ANGLE INTERSECTION
SEE DESIGN
NOT EXCEED 150% OF LENGTH OF SHORT SIDE.
DWGS.
- DO NOT EXCEED 7500 SPACING. INVERT
- LOCATE AT COLUMN LINES WHERE POSSIBLE. EL. VARIES
600
- DO NOT LOCATE JOINT INTERSECTIONS IN TRAFFIC AISLE. 12mm SUPPORTING BAR
- INSTALL WITHIN 24 HOURS OF PLACING CONCRETE. TRENCH ANGLE CONTINUOUS DEPTH TO MATCH GRATING
ACROSS OPENING
200
4.
DIAGONALLY AT CORNERS.
SLAB ON GRADE - JOINT LAYOUT SUMP OR FLOOR TRENCH DETAILS FLOOR TRENCH GRATING DETAILS FLOOR TRENCH - DETAILS AT CORNERS
CONTAINMENT WALL
FOR WALL/PEDESTAL
THICKNESS, DIMENSIONS
TOP OF WALL AND REINFORCING, SEE
PLANS AND DETAILS
EL. SEE DWG.
= =
T
1. FOR GENERAL NOTES SEE DWG'S 0500-C-111 TO 113.