STRUCTURAL AND MISCELLANEOUS STEEL: FABRICATION:

(REF: TECH. SPEC. 143256-ES-C-1008, 1011 & 1012) ALL FABRICATION SHALL COMPLY WITH THE SUPPLY OF STEEL, STEEL DECK AND MISCELLANEOUS
STRUCTURES TECHNICAL SPECIFICATION 143256-ES-C-1011.
MATERIALS:
1. ALL MATERIALS SHALL COMPLY WITH THE SUPPLY OF STEEL, STEEL DECK AND MISCELLANEOUS
PAINTING:
STRUCTURES TECHNICAL SPECIFICATION 143256-ES-C-1011.
ALL PAINTING SHALL COMPLY WITH THE SHOP PAINTING AND PAINTING GENERAL SPECIFICATION
2. STEEL SHAPES (IN AND HN, CHANNELS (C), ANGLES (L), TEES (T), PLATES AND BARS) SHALL CONFORM 143256-ES-C-1009.
TO ASTM A36 MATERIAL WITH A MINIMUM YIELD STRESS
fy = 36 ksi = 250 MPa.
ERECTION:
3. STEEL PIPE SHALL COMFORM TO ASTM A53 GRADE B WITH A MINIMUM YIELD STRESS
fy = 35 ksi = 245 MPa 1. ALL ERECTION WORK INCLUDING GROUTING UNDER BASE PLATES SHALL COMPLY WITH THE
STRUCTURAL STEEL, STEEL DECK AND MISCELLANEOUS STRUCTURES ERECTION TECHNICAL
4. STEEL TUBING (HSS) SHALL CONFORM TO ASTM A500 GRADE C. SPECIFICATION 143256-ES-C-1012.

5. HIGH STRENGTH BOLTS, NUTS AND WASHERS SHALL CONFORM TO ASTM F3125 GRADE A325. 2. EXAMINE ALL SURFACES AND CONDITIONS TO ENSURE THAT THEY ARE SUITABLE FOR STEEL WORK
ERECTION. VERIFY LOCATIONS AND ELEVATIONS OF ALL ANCHOR RODS (BOLTS) AND THAT THEY ARE
6. CHECKER PLATE SHALL CONFORM TO ASTM A36. IN GOOD CONDITION TO RECEIVE THE BASE PLATES. COMMENCEMENT OF ERECTION WILL MEAN
ACCEPTANCE OF THESE CONDITIONS.
7. WELDING MATERIALS SHALL CONFORM TO AWS USING E480XX (E70XX) ELECTRODES.
3. SET BASE PLATES TO PROPER ELEVATIONS USING STEEL SHIMS. INSTALL ALL CONCRETE ANCHORS
8. ANCHOR RODS (BOLTS) SHALL CONFORM TO ASTM F1554 GR.36 U.N.O. AS REQUIRED.

9. RAIL SHALL CONFORM TO ASTM A1 AND A759. 4. ERECT STEEL WORK TRUE AND PLUMB; USE TEMPORARY BRACING WHERE NECESSARY TO RESIST
ALL LOADS TO WHICH THE STRUCTURE MAY BE SUBJECTED TO, DURING ERECTION.

5. THE CONTRACTOR IS RESPONSIBLE FOR LATERAL STABILITY AND TEMPORARY BRACING WHICH SHALL
REMAIN IN PLACE UNTIL THE STRUCTURE IS COMPLETE. WHERE LATERAL STABILITY OF THE STEEL
CONNECTION DESIGNS AND DETAILING : STRUCTURE IS DEPENDENT ON OTHER STRUCTURAL ITEMS SUCH AS SLABS, DECKING, CONCRETE
WALLS, OR OTHER ELEMENTS, THE TEMPORARY BRACING IS TO BE LEFT IN PLACE UNTIL ITEMS
1. ALL DETAILING SHALL BE TO THE STRUCTURAL STEEL DETAILING WORK, PROCESS, TECHNICAL PROVIDING PERMANENT LATERAL STABILITY ARE COMPLETED AND THE STRUCTURE HAS BECOME
SPECIFICATION 143256-ES-C-1008. SAFE.

2. STRUCTURES SHALL BE DETAILED AND FABRICATED TO MINIMIZE FIELD WORK. 6. MAKE PROPER PROVISIONS THROUGH-OUT THE COURSE OF ERECTION FOR SAFE SUPPORT OF
REFER TO SITE INFORMATION DESIGN CRITERIA 143256-DC-G-0001 FOR TRANSPORT ENVELOPE. MATERIALS, ERECTION EQUIPMENT OR OTHER LOADS AS NECESSARY.

3. CONNECTIONS SHALL BE DESIGNED IN ACCORDANCE WITH THE CHILEAN SEISMIC CODE FOR 7. FIELD MODIFICATION OF ANY STEEL WORK MUST BE APPROVED BY THE ENGINEER PRIOR TO
INDUSTRIAL STRUCTURES NCh 2369 AND THE FOLLOWING REQUIREMENTS: COMMENCEMENT OF THE WORK.

a. STRUCTURAL STEEL MEMBER AND CONNECTION DESIGN SHALL USE THE ALLOWABLE STRESS 8. AFTER ERECTION AND COMPLETION OF CONNECTIONS, REPAIR ALL DAMAGED COATINGS.
DESIGN (ASD) METHOD. LOADS GIVEN ON THE DESIGN DRAWINGS ARE UNFACTORED.

b. FABRICATION SHOP CONNECTIONS SHALL BE WELDED. FIELD CONNECTIONS SHALL BE BOLTED


FRP GRATING: (REF: TECH. SPEC. 143256-ES-C-1021)
U.N.O.
1. GRATING SHALL BE MOLDED FRP GRATING UNLESS OTHERWISE APPROVED OR NOTED ON THE
c. IN GENERAL, CONNECTIONS ARE TO BE AS SHOWN ON THE PROJECT'S DESIGN DRAWINGS AND DESIGN DRAWINGS.
THE PROJECT'S STEEL DETAIL DRAWINGS 25800-220-S0-0000-00003 TO 00019. IN THE CASE OF
CONFLICT, THE DESIGN DRAWINGS SHALL GOVERN. 2. GRATING TO HAVE BEARING AND CROSS BARS, 40mm DEEP x 6mm THICK AT 40mm SPACES.

d. BRACING MEMBER CONNECTIONS (VERTICAL AND HORIZONTAL) SHALL BE DESIGNED FOR 110% 3. STAIR TREADS SHALL BE 40mm DEEP.
OF THE TENSION CAPACITY OF THE MEMBER USING THE GROSS SECTION.
4. STAIR TREADS AND LANDINGS SHALL HAVE A "D" OR "BOX" SHAPED INTEGRAL NOSING AT THE
e. BRACING MEMBERS SHALL BE CONNECTED WITH A MINIMUM OF 2 BOLTS FOR L65, 3 BOLTS FOR LEADING EDGE OF TREADS OR LANDINGS.
L75 AND 4 BOLTS FOR L100 AND TEES.
5. TOP SURFACES SHALL HAVE A BONDED, ANGULAR, QUARTZ GRIT SURFACE FOR SKID RESISTANCE.
f. BRACING MEMBERS SHALL BE CONNECTED AT THEIR CROSS-OVER POINTS.
6. AFTER FABRICATION ALL CUT ENDS, HOLES AND ABRASIONS SHALL BE SEALED WITH RESIN IN
g. CONNECT HORIZONTAL BRACING TO UNDERSIDE OF BEAMS AND PURLINS TO ELIMINATE SAG. ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATION.

h. BEAM END CONNECTIONS SHALL BE "DOUBLE ANGLE" TYPE CONNECTIONS UNLESS PERMITTED 7. GRATING PANEL ATTACHMENTS SHALL BE MINIMUM 1.5mm (16 GAUGE), 316 STAINLESS STEEL SADDLE
OTHERWISE. END PLATE CONNECTIONS WILL BE PERMITTED ONLY IN THE FOLLOWING AND INSERT CLIPS, COMPLETE WITH STAINLESS STEEL BOLTS AND SCREWS.
LOCATIONS:
WHERE THEY ARE DESIGNED TO TRANSMIT PASS-THOUGH FORCES OR TO MAKE IT EASIER 8. PROVIDE A MINIMUM 4 ATTACHMENTS FOR EACH GRATING PANEL AND STAIR TREAD.
TO CONNECT BRACING.
FOR LIGHT MEMBERS SUCH AS BEAMS AND PURLINS WHICH DO NOT EXCEED 360mm DEEP.
DO NOT USE SINGLE ANGLE BEAM CONNECTIONS EXCEPT FOR CHANNEL SECTIONS
SUPPORTING WALKWAYS AND GRATING.

i. BEAM END CONNECTIONS SHALL BE DESIGNED FOR 75% OF THE SHEAR CAPACITY OF MEMBER
USING THE FULL SECTION OR THE LOADS GIVEN ON THE DESIGN DRAWINGS.

j. COLUMN SPLICES SHALL BE DESIGNED FOR THE MOST STRINGENT OF FULL COMPRESSION OR
TENSION CAPACITY (UPLIFT COLUMNS ONLY) AND 100% OF THE MOMENT CAPACITY OF THE
SMALLER MEMBER SPLICED..

k. COLUMN TO BASE PLATE CONNECTIONS SHALL BE A MINIMUM 5mm CONTINUOUS FILLET WELD
OR DESIGNED TO THE LOADS GIVEN ON THE DESIGN DRAWINGS.

l. MOMENT CONNECTIONS SHALL BE DESIGNED FOR 100% OF THE MEMBERS MOMENT CAPACITY.

m. USE 3 4" DIAMETER BOLTS OR LARGER IF REQUIRED FOR STRUCTURAL MEMBER CONNECTIONS.
USE ONE BOLT SIZE THROUGH-OUT.

n. USE BEARING TYPE BOLTED CONNECTIONS UNLESS NOTED OTHERWISE WITH THREADS
INCLUDED IN THE SHEAR PLANE. SLIP CRITICAL CONNECTIONS WHERE REQUIRED WILL BE
NOTED ON THE DESIGN DRAWINGS.

o. MINIMUM THICKNESS OF STIFFENER PLATES TO BE 8mm.


MINIMUM THICKNESS OF GUSSET PLATES TO BE 10mm.
MINIMUM THICKNESS OF CONNECTION ANGLES TO BE 6mm.

p. MINIMUM SIZE OF FILLET WELD TO BE 5mm FOR SHOP WELDING AND 6mm FOR FIELD WELDING
(WHERE FIELD WELDING HAS BEEN APPROVED)

4. ALL HSS SECTIONS TO HAVE SEALED CAPPED ENDS.