Product Bulletin 135-D Linear Bar & Floor Grilles


Pleasant .. Serene..
YOU & DASCO...

Since 1964

Partners for good health


www.dasco.com.kw
INTRODUCTION

DASCO Linear Bar Grilles and Registers covers a wide range


for supply and return air distribution of HVAC systems and

www.dasco.com.kw
are suitable for ceiling, floor, sill and sidewall applications.
T hey are selected for their pleasing continuous, line
architectural appearance and are designed for fan tops,
grilles of swimming pools, ventilation outlets and many other
applications.

Introduction
LINEAR BAR GRILLES & REGISTERS

GENERAL
DASCO Linear Bar Grilles and Registers
DLB (G,R) covers a wide range for supply
and return air distribution of HVAC systems
and are suitable for ceiling, floor, sill and
sidewall applications. They are selected for
their pleasing continuous line architectural
appearance and are designed for fan tops,
grilles of swimming pools, ventilation outlets Bar Grille DLBG - 30˚ - 2W

and many other applications.

DESCRIPTION
DASCO Linear Bar Grilles & Registers are
multiparallel fixed bar type in continuous
modular section up to 5 meters long to form
linear type grilles. They are available in one Mitered Corner (90˚ angle)
way airflow pattern for zero degree bar
deflection and in one or two way air flow
pattern for (15˚) & (30˚) bar deflection. DLB
(G,R) standard widths ranges from 3”to 12”
(76mm-305mm). For quiet airflow, bars are
equally spaced at 12.5mm (1/2”) distance
Flat frames are standard but curved frames
on request can be supplied for all models.
Mullion bars a cr o s s th e b l a d es p r ov i d e
additional strength. Mitered corners available Mitered Corner (135˚ angle)
in various arrangements to suit different
installations.

Linear Bar Grilles


MATERIAL & FINISH:
High quality extruded aluminium sections in matt silver anodized finish. White colour in electrostatic
polyester powder coating finish available as standard. Other colours as per RAL standards are also
available upon request.

www.dasco.com.kw
PRODUCT CODE (ORDERING KEY) :

DASCO LINEAR BAR GRILLES & REGISTERS


DLBX D A W L

X : TYPE
G : Grille
R : Grille with V.C.D. (Register)
D : Deflection Angle
O : Zero degree deflection
Oy : Zero degree deflection
(Special blade)
15 : 15 degree deflection
30 : 30 degree deflection
A : Air pattern
1W : One-way deflection
2W : Two-way deflection

W : Width of neck (inch or mm)


L : Length (inch or mm)

Linear Bar Grilles


Complete dimensional details for DASCO Linear Bar Grille DLBG-15˚-1W.

LISTED WIDTHS:

Table No (1) – Listed Widths


Note
Sizes other than listed are also available upon request.

AREA FACTORS
Below is the area factor per foot for DASCO Linear Bar Grilles (Ak)

Table No (2) – Area Factor (AK)

Note
For use with alnor velometer with Tip No.2220 or 2220A
CFM = Ak x L x Vk, where
Ak = Area Factor in Ft2/Ft Run
L = Active Length of Linear Bar Grille in feet.
Vk = Average velocity as measured by Alnor Velometer with Tip No.2220 or 2220A.

Linear Bar Grilles


DIMENSIONAL DATA (Linear Bar Grilles)

LISTED WIDTH + 58 mm

12.5 mm(1/2”) 32 mm

LISTED + 58 mm

32 mm
6mm 12.5mm(1/2”)
51.5 mm

3 mm(1/8”)

www.dasco.com.kw
51.5 mm
3 mm(1/8”)

LISTED WIDTH

DLBG – 0˚ DLBG – 0˚Y


DASCO Linear Bar Grille with fixed bar 0˚ deflection DASCO Linear Bar Grille with fixed bar (special blade)
0˚ deflection

LISTED WIDTH + 58 mm LISTED WIDTH + 58 mm

12.5mm(1/2”) 12.5mm(1/2”) 32 mm
15˚ 32 mm 15˚
51.5 mm

51.5 mm

3 mm(1/8”) 3 mm(1/8”)

LISTED WIDTH LISTED WIDTH

DLBG –15˚W DLBG – 15˚-2W


DASCO Linear Bar Grille with fixed bar 15˚ one-way DASCO Linear Bar Grille with fixed bar 15˚ two-way
deflection deflection

LISTED WIDTH + 58 mm LISTED WIDTH + 58 mm

12.5mm(1/2”) 32 mm
30˚ 12.5mm(1/2”) 32 mm
30˚
51.5 mm
51.5 mm

3 mm(1/8”) 3 mm(1/8”)

LISTED WIDTH
LISTED WIDTH

DLBG –30˚-1W DLBG – 30˚-2W


DASCO Linear Bar Grille with fixed bar 30˚ one-way DASCO Linear Bar Grille with fixed bar 30˚ two-way
deflection deflection

Dimensional Data
DIMENSIONAL DATA (Linear Bar Registers)

LISTED WIDTH + 58 mm

12.5 mm(1/2”) 32 mm

LISTED + 58 mm

32 mm
6mm 12.5mm(1/2”)
51.5 mm

3 mm(1/8”)

51.5 mm
3 mm(1/8”)

LISTED WIDTH

DLBR – 0˚ DLBR – 0˚Y


DASCO Linear Bar Register with fixed bar 0˚ DASCO Linear Bar Register with fixed bar (special blade)
deflection with opposed blade lever operated damper 0˚ deflection with opposed blade lever operated damper

LISTED WIDTH + 58 mm LISTED WIDTH + 58 mm

12.5mm(1/2”) 12.5mm(1/2”) 32 mm
15˚ 32 mm 15˚
51.5 mm

51.5 mm

3 mm(1/8”) 3 mm(1/8”)

LISTED WIDTH LISTED WIDTH

DLBR-15˚-1W DLBR-15˚-2W
DASCO Linear Bar Register with fixed bar 15˚ one way DASCO Linear Bar Register with fixed bar 15˚ two-way
deflection with opposed blade lever operated damper deflection with opposed blade lever operated damper

LISTED WIDTH + 58 mm LISTED WIDTH + 58 mm

12.5mm(1/2”) 32 mm
30˚ 12.5mm(1/2”) 32 mm
30˚
51.5 mm
51.5 mm

3 mm(1/8”) 3 mm(1/8”)

LISTED WIDTH
LISTED WIDTH

DLBR-30˚-1W DLBR-30˚-2W
DASCO Linear Bar Register with fixed bar 30˚ one way DASCO Linear Bar Register with fixed bar 30˚ two-way
deflection with opposed blade lever operated damper deflection with opposed blade lever operated damper

Dimensional Data
ACCESSORIES

A complete variety of accessories and options are available for DLB (G,R) series liner Bar Grilles
and Registers.
1. Opposed blade Volume Control Damper for supply grilles.
2. Equalized grid.
3. Lining strips for continuous sections.

www.dasco.com.kw
4. Mitered corner sections.
(Available in both horizontal and vertical settings )
Opposed Blade volume control damper.

DIFFERENT SETTINGS OF MITERED CORNERS


1. STANDARD 90˚ HORIZONTAL MITERED
CORNER SECTION
Suitable for floor, sill or ceiling application.
This standard corner section is available in 0˚,
15º and 30º deflection settings with angle of
90º. When specifying a corner section with 15º
or 30º deflection settings, it is important
to specify the direction of its throw either
towards the insideor outside of the corner.
Corner sections are not provided with dampers.

2. S P E C I A L H O R I Z O N TA L M I T E R E D
CORNER SECTION
Suitable for floor, sill or ceiling applications.
This special corner section includes an angle
greater than 90º and less than 180º and is
available in 0º, 15º and 30º deflection settings.
When specifying a corner section with a 15º or
30º deflection settings, it is important to specify
the direction of its throw either towards the
inside or outside of the corner . Corner
sections are not provided with dampers.

Accessories
3. VERTICAL OUTSIDE MITERED CORNER
SECTION
Designed for sidewall applications at the
junctions of two outside walls. This type of
corner section has a standard angle of 90º
and is available in 0º, 15º and 30º deflection
settings . Corner sections are not provided
with dampers.

4. VERTICAL INSIDE MITERED CORNER


SECTION
Designed for sidewall applications at the
junction of two inside walls. This type of
corner section has a standard angle of 90º and
is available in 0º, 15º and 30º deflection settings.
Corner sections are not provided with dampers.

Curved Bar Grille (Convex Shape) Curved Bar Grille (Concave Shape)

Accessories
BALANCING DATA AND SELECTION PROCEDURE

HOW TO DETERMINE ( CFM ) ?

www.dasco.com.kw
1. Use an Alnor Velometer with tip No. 2220 or 2220A .
2. For outlets less than 3” wide , position tip over center bar and take velocity readings at various
points along the length of the liner bar grilles . For outlets greater than 2 1/2” wide, take
velocity readings near the outer and center or near center bar at various points along the
length of the linear bar grilles.
3. Take a minimum of four equally spaced readings .
4. Average the velocity readings .
5. Select appropriate Ak from table (2).
6. Determine CFM by the following equation :
CFM = Ak x Active Length x Average Velocity .

SAMPLE PROBLEM :
Determine air flow rate through a 5” wide ( 15º ) – 14 feet long supply liner bar grille. The active
length is a total of 7 feet .

SOLUTION
1. The average of 14 velocity readings taken at various points along the active length of the
linear bar grille centered over the next to outer bar and middle bar is 525 fpm.
2. From table (2) the Ak for 5» wide 15º on supply air is 0.19
3. CFM=Ak x Active Length x Average Velocity
=0.19 x 7 x 525
=700 CFM

Balancing and Selection


BASIC PERFORMANCE DATA

DASCO Linear Bar Grille Model : DLBG - 0˚


WIDTH Area Factor Velocity (fpm) 400 500 600 700 800 1000 1200 1400 1600
AK
Total Pressure
(inch) ( Ft2 /Ft) (Inch W.G.) 0.009 0.014 0.021 0.028 0.036 0.056 0.08 0.11 0.146

CFM/Ft 40 50 60 70 80 100 120 140 160


3” 0.1
Throw (Ft) 8-14 11-17 13-20 14-22 16-26 20-33 24-39 27-42 30-45
NC <20 <20 <20 <20 <20 25 28 31 34

CFM/Ft 60 75 90 105 120 150 180 210 240


4” 0.15
Throw (Ft) 10-16 12-19 14-24 18-28 20-31 25-40 30-47 33-50 37-54
NC <20 <20 <20 <20 <20 26 29 33 36

CFM/Ft 76 95 114 133 152 190 228 266 304


5” 0.19
Throw (Ft) 12-20 15-25 18-29 22-35 25-39 31-48 37-56 40-60 43-64
NC <20 <20 <20 <20 <20 26 29 34 37

CFM/Ft 92 115 138 161 184 230 276 322 368


6” 0.23
Throw (Ft) 14-21 16-26 20-31 24-37 26-41 32-52 39-62 43-66 46-69
NC <20 <20 <20 <20 20 26 30 35 38

CFM/Ft 124 155 186 217 248 310 372 434 496
8” 0.31
Throw (Ft) 16-24 18-29 22-33 26-39 27-43 35-55 41-65 46-69 50-73
NC <20 <20 <20 <20 21 27 31 35 39

CFM/Ft 160 200 240 280 320 400 480 560 640
10” 0.4
Throw (Ft) 18-28 20-32 24-36 28-42 29-45 37-58 43-68 48-74 51-76
NC <20 <20 <20 <20 22 28 32 36 40

CFM/Ft 192 240 288 336 384 480 576 672 768
12” 0.48
Throw (Ft) 20-30 22-35 26-39 30-45 31-48 39-61 45-69 50-78 55-80
NC <20 <20 <20 20 23 29 33 37 41

Table No. 3 ( 0˚ Deflection Liner Bar Grille )

VELOCITY : Is discharge velocity measured at face of grille in FPM .


NC : Is for supply without damper and room effect of 8 dB.
TOTAL PRESSURE : Is in inch W.G. for supply grille without damper .
THROW : Is for 8’ long supply grille without damper , for 100 and 50 FPM terminal
velocities respectively.
Ak : Is area factor in Ft2/Ft Run

10

Basic Performance Data


DASCO Linear Bar Grille Model : DLBG - 0˚ Y
WIDTH Area Factor Velocity (fpm) 400 500 600 700 800 1000 1200 1400 1600
AK
Total Pressure
(inch) ( Ft 2 /Ft) (Inch W.G.) 0.010 0.018 0.025 0.032 0.044 0.064 0.088 0.120 0.157

CFM/Ft 35 44 53 62 71 88 106 124 142


3” 0.97

www.dasco.com.kw
Throw (Ft) 6-11 9-14 10-16 11-18 13-22 17-27 20-31 23-35 26-39
NC <20 <20 <20 <20 <20 23 27 31 35

CFM/Ft 51 64 77 90 103 129 155 181 206


4” 0.145
Throw (Ft) 7-13 9-16 11-20 14-23 16-26 20-32 24-40 27-43 30-47
NC <20 <20 <20 <20 20 24 28 32 36

CFM/Ft 67 84 101 118 135 169 202 236 271


5” 0.186
Throw (Ft) 9-16 11-20 14-25 18-30 21-33 25-40 30-45 34-49 38-54
NC <20 <20 <20 <20 21 25 29 33 37

CFM/Ft 83 104 125 146 167 209 251 292 335


6” 0.225
Throw (Ft) 11-17 13-22 16-27 20-33 22-37 27-44 30-48 34-53 38-57
NC <20 <20 <20 20 22 26 31 34 38

CFM/Ft 119 149 179 208 239 298 359 419 478
8” 0.30
Throw (Ft) 13-19 14-24 18-28 22-34 24-38 27-44 31-49 35-52 39-58
NC <20 <20 <20 21 23 27 32 36 40

CFM/Ft 151 189 227 265 303 379 455 530 607
10” 0.398
Throw (Ft) 15-22 16-22 19-29 22-35 25-38 30-45 33-49 37-54 40-59
NC <20 <20 20 22 25 29 33 37 41

CFM/Ft 183 229 275 321 367 459 551 643 735
12” 0.478
Throw (Ft) 17-24 19-27 20-30 24-35 37-39 31-45 35-50 39-55 43-62
NC <20 <20 21 23 26 31 34 38 42

Table No. 4 ( 0˚ Deflection Liner Bar Grille - Special Blade )

VELOCITY : Is discharge velocity measured at face of grille in FPM .


NC : Is for supply without damper and room effect of 8 dB.
TOTAL PRESSURE : Is in inch W.G. for supply grille without damper .
THROW : Is for 8’ long supply grille without damper , for 100 and 50 FPM terminal
velocities respectively.
Ak : Is area factor in Ft2/Ft Run

11

Basic Performance Data


DASCO Linear Bar Grille Model : DLBG - 15˚
WIDTH Area Factor Velocity (fpm) 400 500 600 700 800 1000 1200 1400 1600
AK
Total Pressure
(inch) ( Ft2 /Ft) (Inch W.G.) 0.009 0.014 0.021 0.028 0.036 0.056 0.08 0.11 0.146

CFM/Ft 38 47 57 67 77 96 115 134 153


3” 0.095
Throw (Ft) 8-13 11-16 12-18 13-20 15-25 19-31 23-36 26-40 29-43
NC <20 <20 <20 <20 <20 25 28 31 35

CFM/Ft 56 70 84 98 112 140 168 196 224


4” 0.14
Throw (Ft) 9-15 11-18 13-22 16-26 19-29 23-37 28-45 31-48 35-51
NC <20 <20 <20 <20 20 25 29 32 37

CFM/Ft 72 90 108 126 144 180 216 252 288


5” 0.18
Throw (Ft) 11-19 14-23 19-28 21-33 24-38 30-46 35-53 38-57 41-61
NC <20 <20 <20 <20 21 26 30 34 38

CFM/Ft 88 110 132 154 176 220 264 308 352


6” 0.22
Throw (Ft) 13-20 15-25 19-30 23-36 25-40 31-50 37-58 40-61 43-65
NC <20 <20 <20 <20 22 27 31 35 39

CFM/Ft 122 153 184 214 244 304 364 425 486
8” 0.3
Throw (Ft) 15-22 17-28 21-32 25-38 26-42 33-53 38-60 42-64 46-68
NC <20 <20 <20 20 23 28 32 36 40

CFM/Ft 156 195 234 273 312 390 468 546 624
10” 0.39
Throw (Ft) 17-26 19-30 22-34 27-40 28-43 35-55 40-63 44-66 48-70
NC <20 <20 <20 21 24 29 33 37 41

CFM/Ft 188 235 282 329 376 470 564 658 752
12” 0.47
Throw (Ft) 19-28 21-32 24-36 29-42 30-46 37-56 42-63 46-69 50-75
NC <20 <20 20 22 25 30 35 38 42

Table No. 5 ( 15˚ Deflection Liner Bar Grille )

VELOCITY : Is discharge velocity measured at face of grille in FPM .


NC : Is for supply without damper and room effect of 8 dB.
TOTAL PRESSURE : Is in inch W.G. for supply grille without damper .
THROW : Is for 8’ long supply grille without damper , for 100 and 50 FPM terminal
velocities respectively.
Ak : Is area factor in Ft2/Ft Run

12

Basic Performance Data


DASCO Linear Bar Grille Model : DLBG - 30˚
WIDTH Area Factor Velocity (fpm) 400 500 600 700 800 1000 1200 1400 1600
AK
Total Pressure
(inch) ( Ft 2 /Ft) (Inch W.G.) 0.009 0.014 0.021 0.028 0.036 0.056 0.08 0.11 0.146

CFM/Ft 36 45 54 63 72 90 108 126 144


3” 0.09

www.dasco.com.kw
Throw (Ft) 7-12 10-15 11-17 12-19 14-23 18-29 22-23 25-37 28-41
NC <20 <20 <20 <20 20 24 28 32 37

CFM/Ft 52 65 78 91 104 130 156 182 208


4” 0.13
Throw (Ft) 8-14 10-17 12-21 15-24 17-27 22-35 26-42 29-46 32-49
NC <20 <20 <20 <20 20 25 29 33 38

CFM/Ft 68 85 102 119 136 170 204 238 272


5” 0.17
Throw (Ft) 10-18 13-22 16-27 21-33 23-36 29-45 34-50 37-54 40-58
NC <20 <20 <20 <20 21 26 30 34 39

CFM/Ft 84 105 126 147 168 210 252 294 336


6” 0.21
Throw (Ft) 12-19 14-24 18-29 22-35 24-39 30-47 34-52 38-57 41-60
NC <20 <20 <20 20 22 28 32 35 40

CFM/Ft 120 150 180 210 240 300 360 420 480
8” 0.29
Throw (Ft) 14-21 16-26 20-30 24-36 25-40 31-49 35-53 39-58 42-61
NC <20 <20 <20 21 24 29 33 37 41

CFM/Ft 152 190 228 266 304 380 456 532 608
10” 0.38
Throw (Ft) 16-24 18-27 21-31 25-38 27-41 33-50 36-54 40-59 43-62
NC <20 <20 20 22 26 30 34 38 42

CFM/Ft 184 230 276 322 368 460 552 644 736
12” 0.46
Throw (Ft) 18-26 20-29 22-33 27-39 29-43 35-51 38-56 42-61 46-67
NC <20 <20 21 24 27 32 36 39 43

Table No.6 ( 30˚ Deflection Liner Bar Grille )

VELOCITY : Is discharge velocity measured at face of grille in FPM .


NC : Is for supply without damper and room effect of 8 dB.
TOTAL PRESSURE : Is in inch W.G. for supply grille without damper .
THROW : Is for 8’ long supply grille without damper , for 100 and 50 FPM terminal
velocities respectively.
Ak : Is area factor in Ft2/Ft Run

13

Basic Performance Data


PERFORMANCE NOTES

DEFINITIONS
VELOCITY : Is discharge velocity measured at face of grille in (FPM) .
NC : Noise criteria for the supply grille without damper with room effect of 8
dB and 8’ active length ( see NC correction values in table No. (7)).
TOTAL PRESSURE : Is in inches W.G. for supply grille without damper .
THROW : Is for 8’ active length supply grille without damper for 100 and 50 FPM
terminal velocities respectively .
( see throw correction value in table No. (8) ).
Ak : Is area factor in Ft2/Ft Run
For other non – listed widths, use the following formula :
W- 0.85
Ak = , W : width in inches
24

CORRECTIONS
NC ( Noise Criteria ) :
• Add 2 dB to the tabulated NC values in case of grille with damper .
• Add 4 dB to the tabulated NC values for return grilles .
• For other active lengths , use the following corrections :

Table No. 7 – NC correction factors

NC ( Noise Criteria ) :
• For grille with damper , multiply the tabulated value by 1.4
• For return grilles, multiply by 0.85

Throw :
• For other active lengths use the following corrections :

Active length (Ft) 1’ 2’ 4’ 6’ 8’ 10’ 12’


Multiply throw by 0.60 0.7 0.8 0.9 1.0 1.2 1.4
Table No. 8 – Throw correction factors

14

Performance Notes
INSTALLATION DETAILS

Here is the most commonly used methods of installing DASCO Linear Bar Grilles/Registers for
different site applications ( Ceiling/Side wall/Floor)

www.dasco.com.kw
Ceiling Installation

Floor Installation

Side wall Installation

15

Installation Details
FLOOR GRILLES & REGISTERS

GENERAL
DASCO Floor Grilles and Registers (DFG -21
H/V & DFR -21 H/V) are designed to be
installed on floors where air ducts are required
to be underneath the floor level, such as for
computer room s. T h ey a r e d es i g n ed to
withstand 450 kg. point load for heavy duty
applications.

Floor grille DFG – 21H

Description
DFG -21 H/V are multiparallel, horizontal
or vertical fixed Bars in continuous modular
sections. They are available in fixed pattern
of air flow (Zero deflection) for supplying
Floor grille DFGL – 21H vertical air flow. Bars are of heavy duty type
6mm wide, and are equally spaced at( 1 /4”)
distance.

Floor grille DFGL – 21H Floor grille DFG – 21H

Mullion bars across the blades provide additional strength and extra special reinforcement in
the structure of the grille to withstand loads up to 450 kg. Bars are fixed by a standard frame
(1.5mm thickness). Special type heavy duty frames with 7mm thickness are also available forming
an extra special heavy type of floor grilles.
Both horizontal and vertical bar models can be supplied with apposed blade dampers and are
called registers DFR-21 H/V.

16

Floor Grilles & Registers


MATERIAL & FINISH:
Frame blades and dampers are all of heavy gauge extruded aluminum sections in matt silver
anodized finish. Blades are 6mm thickness, and standard frames are flat type extruded aluminum
with 1.5 mm thickness sections. Special blades for heavy duty type floor grilles are available in

www.dasco.com.kw
7mm thickness. DASCO floor grilles can be supplied in white polyester powder coating finish or
any other specified RAL- standard colour upon your requirement .

ORDERING CODE :
1. DASCO FLOOR AIR GRILLES & REGISTERS DFXL – 21a - WxH
( Ordinary – Light duty – Type )

X : TYPE
G : Grille
R : Register (Grille with damper)
a : Blade setting
H : Horizontal
V : Vertical
WXH : Neck size, (inch)

2. DASCO FLOOR AIR GRILLES & REGISTERS DFX – 21a - WxH


( Heavy duty Type )

X : TYPE
G : Grille
R : Register (Grille with damper)
a : Blade setting
H : Horizontal
V : Vertical
WXH : Neck size, (inch)

17

Floor Grilles & Registers


BASIC PERFORMANCE DATA

SIZE Area Factor Velocity (fpm) 400 500 600 700 800 1000 1200 1400 1600
WxH
(inch)
2
( Ft ) St. Pressure 0.01 0.016 0.025 0.039 0.052 0.093 0.134 0.178 0.218
(Inch W.G)

CFM 104 132 160 188 216 272 328 384 440
12x6 0.25
NC <20 <20 <20 <20 <20 20 25 28 31

12x8 CFM 142 178 214 250 286 358 430 502 574
0.34
16x6 NC <20 <20 <20 <20 20 23 26 29 33

12x10 CFM 180 228 276 324 372 468 564 660 756
0.43
20x6 NC <20 <20 <20 <20 21 24 27 31 35

12x12 CFM 217 269 321 373 425 529 633 737 841
18x8 0.52
24x6 NC <20 <20 <20 <20 22 25 29 33 37

12x12 CFM 305 362 420 478 536 652 770 890 1051
20x10 0.73
24x8 NC <20 <20 <20 20 23 26 30 34 38

16x14 CFM 335 415 476 559 650 796 944 1090 1237
18x12 0.84
32x6 NC <20 <20 <20 21 24 27 31 35 39

20x12 CFM 378 453 540 631 736 904 1073 1241 1409
0.90
24x10 NC <20 <20 <20 22 26 29 32 36 40

24x12 CFM 450 567 648 756 881 1089 1296 1504 1712
1.10
24x10 NC <20 <20 <20 23 27 31 34 37 41

20x18 CFM 574 697 819 946 1104 1360 1615 1871 2127
30x12 1.45
36x10 NC <20 <20 <20 24 28 32 35 39 42

CFM 929 1107 1324 1521 1771 2195 2618 3040 3469
24x24 2.37
NC <20 <20 21 25 29 33 36 40 44

CFM 1180 1370 1656 1895 2194 2729 3228 3758 4288
30x24 3.21
NC <20 <20 22 26 30 34 38 41 45

CFM 1381 1631 1987 2265 2595 3230 3866 4500 5136
36x24 4.03
NC <20 <20 23 27 31 35 39 43 47

Table No. 9 - Floor Grille DFGL - 21H

18

Basic Performance Data


SIZE Area Factor Velocity (fpm) 400 500 600 700 800 1000 1200 1400 1600
WxH
(inch)
2
( Ft ) St. Pressure 0.01 0.016 0.025 0.039 0.052 0.093 0.134 0.178 0.218
(Inch W.G)

CFM 126 162 180 216 252 306 360 414 468
12x6 0.26

www.dasco.com.kw
NC <20 <20 <20 <20 20 23 26 29 32

12x8 CFM 168 216 240 288 335 408 481 554 627
0.35
16x6 NC <20 <20 <20 <20 21 24 27 30 33

12x10 CFM 210 270 300 358 417 508 599 690 781
0.44
20x6 NC <20 <20 <20 <20 22 26 30 34 37

12x12 CFM 252 296 340 428 498 610 722 834 946
18x8 0.53
24x6 NC <20 <20 <20 20 23 27 31 35 38

16x12 CFM 351 442 510 590 686 840 994 1148 1302
20x10 0.75
24x8 NC <20 <20 <20 21 24 28 32 36 40

16x14 CFM 378 477 540 635 738 905 1072 1239 1406
18x12 0.86
32x6 NC <20 <20 <20 22 25 29 33 37 41

20x12 CFM 420 530 600 704 818 1005 1192 1379 1566
0.93
24x10 NC <20 <20 <20 23 26 30 34 38 42

24x12 CFM 504 630 720 840 979 1210 1441 1672 1903
1.12
36x8 NC <20 <20 20 24 28 32 36 39 43

20x18 CFM 630 766 900 1040 1213 1494 1775 2056 2337
30x12 1.48
36x10 NC <20 <20 21 25 29 33 37 40 45

CFM 1010 1203 1440 1654 1925 2385 2845 3305 3765
24x24 2.41
NC <20 <20 22 26 30 34 38 41 46

CFM 1283 1490 1800 2060 2384 2966 3548 4130 4712
30x24 3.25
NC <20 <20 23 27 31 35 39 42 47

CFM 1502 1773 2160 2462 2852 3550 4248 4946 5644
36x24 4.09
NC <20 <20 24 28 32 36 40 44 48

Table No. 10 - Floor Grille DFG - 21H

19

Basic Performance Data


PERFORMANCE NOTES

DEFINITIONS
VELOCITY : Is discharge velocity measured at face of grille in (FPM) .
NC : Noise criteria for the supply grille without damper with room effect of 8 dB.
STATIC PRESSURE : Is in inches W.G. for supply grill without damper .
Ak : Is area factor in Ft2

CORRECTIONS
NC ( Noise Criteria ) :
• Add 2 dB to the tabulated NC value in case of grille with damper .
• Add 4 dB to the tabulated NC value for return grilles .

Static Pressure :
• For grille with damper, multiply the tabulated value by 1.4
• For return grilles, multiply by 0.8

Floor Register DFRL – 21H

20
CONVERSION TABLE

www.dasco.com.kw
Table No. 11 - Metric Guide Conversion Factors.

Bar Grille DLBG – 0º

21

Conversion Table
TESTING AND APPROVAL

Different samples from DASCO air terminal devices (Linear Bar Grilles and Registers)
were tested at ITS (Intertek Testing Services) labs in accordance with:
• Air diffusion council test code for grilles, registers and diffusers
No. ADC 1062: GRD-84.
• ISO 5219 “Air distribution and air diffusion laboratory aerodynamic
testing and rating of air terminal devices”.
• ANSI/ASHRAE 70-1991, “Method of testing for rating the performance
of air outlets and inlets”.

LINEAR BAR GRILLES AND REGISTERS WERE TESTED FOR

a. Sound (NC Noise Criteria).


b. Static pressure in inches W.G.
c. Throw, feet.
d. Ak (Area factor).

22

Testing & Approval


COATING WITH POWDER

NOW YOU CAN ACHIEVE OPTIMAL COATING PERFORMANCE


ON ALL PRODUCTS YOU PAINT!

www.dasco.com.kw
DASCO offers a first class service by introducing a wide range of perfect polyester
powder coating on all of its aluminium products of air terminal devices.
The best quality of polyester powder Corro-Coat are used in according to the intern-
national standards (BS,ISO,DIN,ASTM). PE-F architectural grade polyester powders
are used perfectly with pre-treatment, electrostatic spray and curing in accordance
with the above standards recommendations. A complete range of RAL-Standard
colours are always available in addition to a vast range of special compound colours
as per our customers request.
RAL Standard Colour Chart Swatch

23
Now producing relief knots as in natural wood

New Technology Excellence


1. Resistance to high radiation and extreme climatic conditions.
2. It can be used in painting elaborate geometrical shapes producing perfect
quality and aesthetic results.
3. It is the only technology that can replace wood in traditional areas.

New Mahogany - 21

New Mahogany - 22

24
www.dasco.com.kw

25

www.dasco.com.kw
Since 1962
Product Bulletin 135-D

P.O. Box: 6192 Hawalli 32036 Kuwait.


Tel: +965 4839911 Fax: +965 4815498
www.dasco.com.kw

You might also like