INTRODUCTION

Linear slot diffusers are always considered as the most


attractive air distribution devices. They are specially

www.dasco.com.kw
designed for ceiling mounting in a wide range of
applications in heating, ventilation and air conditionin
systems. At a perfect setting, linear slot diffusers provide a
stable pattern of diffusion to produce an optimum
performance for both supply and return air in addition to
their pleasant appearance.
To satisfy both architectural and engineering needs, curved
slot diffusers have been also developed and designed.
Whether it requires a continuous linear run, ellipse,
complete circle orserpentine curve,…. LINEAR/CURVED
SLOT DIFFUSERS CAN ALWAYS BE INCORPORATED
INTO ANY DESIGN.

Introduction
LINEAR SLOT DIFFUSERS

GENERAL
Dasco linear slot diffusers for both supply and
return applications DLD-C(S/R) are designed
to give unobstrusive continuous air diffusion
with a pleasing aesthetic appearance .
Hairline joints ensure clean continuous runs of
linear slot diffusers for both active and dummy
sections. They are normally connected to the
main ducting system by means of connection Linear Slot Diffuser ( 3 Slots)

boxes (Plenums), and are adjustable in height


for accurate lining-up with the ceiling.

Linear Slot Diffuser ( 2 Slots)

In general , DLD-C(S/R) linear slot diffuser


is considered as a unique type of an air
distribution device, dispenses proper air
quantities, controls air pattern for ultimate
human comfort and adapts to any design concept
perceived by architect / design engineer.

Mitered Corner ( 90º )

Linear Slot Diffusers


DESCRIPTION
Dasco linear slot diffusers DLD-C(S/R) are designed to give a comprehensive and full range
of air flow patterns and volumes. Their deflector blades and volume control dampers give a full
flexibility in air patternand volume control. These are fully adjustable from the face of the diffuser.

www.dasco.com.kw
Single or multiple slot arrangements can provide any combinations of horizontal, vertical or
any intermediate setting of air flow pattern over a full range of 180º adjustment, as each slot is
individually adjustable. Volume control dampers consist of two strips of extruded aluminium
profiles, one fixed and one movable. They can be also usedas equalizing grids.

Mitered Corners (Different angles)

SINGLE SLOT ADJUSTMENTS

Horizontal right Horizontal left Fully Vertical Dampered Horizontal Fully Closed

MULTIPLE SLOT ADJUSTMENTS (TWO TO EIGHT SLOTS )

Horizontal Horizontal Fully Vertical Horizontal two-way Vertical


one-way two-way Dampered(unequal flow) Horizontal

Linear Slot Diffusers


Two types of linear slot diffusers are available:
• Linear slot diffusers with 3/4” slot width.
• Linear slot diffusers with 1” slot width.
Both are manufactured in one up to eight slots with a maximum one–piece length of 6 meters as a standard,
permitting complete control of flow rate without disturbing the selected air pattern. Linear slot diffusers
with other lengths and /or number of slots can also be provided on request.

End caps on both sides are supplied on one piece linear slot diffusers, and on one side of end sections
of continuous units. Sections are connected by using alignment strips.

MATERIAL & FINISH


High quality and heavy gauge extruded aluminium profiles. They are available in white polyester powder
coated finish. However, any other RAL standard colours are also available upon customer’s request.
Deflector blades and dampers are also made from extruded aluminium profiles normally in black colour.
Plenum boxes are made from galvanized steel.

LINEAR DIFFUSER (3-SLOTS) WITH DAMPERS

Linear Slot Diffusers


www.dasco.com.kw
Linear Slot Diffuser
(Hexagonal Shape)

Linear Slot Diffuser


(T-Shape)

Vertical outside Mitered corner section


Linear Slot Diffusers (2Slots)
Special Geometric Shapes

2 Slots Diffuser
Circular Shape

Vertical inside Mitered corner section

Vertical inside Mitered corner section


Chamfered type

Linear Slot Diffusers


ACCESSORIES

A complete variety of accessories and options are always available for DLD-C(S/R)

1. MOUNTING BRACKETS
Are used normally for ceiling installations.
They are made from Z-27(gauge 20 ) galvanized
steel and are arranged with holes for easy
installations .
Mounting Brackets

2. ALIGNMENT STRIPS
Are used for continuous sections and are made
from aluminium sheets.

Alignment strips

3. END CAPS Alignment strips


L-Shape flanges, manufactured from aluminium
extruded profiles and are available in different
lengths to match different number of slots
and widths.
They are usually fixed at the end of linear
slot diffusers and are very easy to install and
remove .
End caps

Without end caps End cap (left or right) End caps (both sides)

Accessories
4. DUMMY SECTIONS
With exactly the same construction of supply air linear slot diffusers but with blank off damper
sheets. Are used along with continuation sections of supply and /or return linear slot diffusers
for decoration purposes.

www.dasco.com.kw
Linear Diffuser (3 Slots) - Dummy Type

5. MITERED CORNERS
Are usually used when slot diffusers are designed to form closed loops. They are available in one
to eight slots and can have any combination of L1, L2 and angle ø.

Mitered Corners

Accessories
PLENUM BOXES

DESCRIPTION
It is designed to ensure even air distribution along the associated linear slot diffusers, and therefore
maintaining correct performance characteristics. Plenum boxes, are available with or without internal
lining of thermal and acoustic insulation and are available for single or continuous installations.
All joints are sealed for a perfect tightness and in most cases are “Lock formed”, which adds to
maintain rigidity.

INSULATION
Fiberglass 25 mm thick (16kg/m3) with black
tissue face for acoustic and thermal insulation
(Available as optional)

Plenum Box with insulation

MATERIAL
Galvanized sheet steel Z-27 (Gauge 24 )

Plenum Box without insulation

Plenum Boxes
SIZES
Available in various neck openings (5”to12”) suitable for fixing linear slot diffusers (1 to 8 slots).
Maximum plenum length is 240 cm per piece. Longer lengths are provided with special joints to
fit continuous shape.

www.dasco.com.kw
Insulated Plenum Plenum without Insulation

Single Installation DLD-C with


Plenum box DPB-C

Table 1. Dimensions of plenum boxes ( with /without ) insulation

Plenum Boxes
ORDERING CODE

Dasco Linear Slot Diffuser DLD-C a - b - c - d - e

a =Version S :Supply
R :Return
RD :Return with volume
control damper
D :Dummy
b =Number of slots
1,2,3,4,5,6,7,8
c =Slot width 1 :3/4” slot width
2 :1” slot width
d =Length ,cm (Maximum 600)
e =Number of end caps 0 : Without
1 : One end cap
2 : Two end caps

Dasco Plenum Box DPB-C a - b - c - d - e

a =Installation S :Single Unit


I :In - Line
b =Number of slots 1,2,3,4,5,6,7,8

c = Slot width 1 :3/4” slot width


2 :1” slot width
d =Length, cm (Maximum 240)
e =Thermal insulation 0 : Without thermal insulation
1 : With thermal insulation

10

Ordering Code
DIMENSIONAL DATA

www.dasco.com.kw
Linear slot diffuser with 3/4 “ slot width

Linear slot diffuser with 1” slot width

11

Dimensional Data
DIMENSIONS OF LISTED SIZES:

a) Linear slot diffusers with 3/4” slot width

Table 2. Dimensions of linear slot diffusers with 3/4” slot width

a) Linear slot diffusers with 1” slot width

Table 3. Dimensions of linear slot diffusers with 1 “ slot width

Woodall Colour

Curved Diffusers
Arched Shape

12

Dimensional Data
ENGINEERING DATA

DEFINITIONS
• Throw (T) : Throw of an outlet, in m (feet), is the distance from the center of the
outlet to a point in the mixed air stream where the highest sustained
velocity of the mixed air stream has been reduced to a specified level,

www.dasco.com.kw
i. e, 100 and 50 FPM.
• CFM : Is the air flow rate in cubic feet per minute.
• Velocity (Vk) : Discharge or intake velocity of an outlet or inlet , in m/s (FPM) measured
with an approved calibrated velometer at specified locations relative to
the face of the outlet or inlet. Sometimes referred to as jet velocity.
• Terminal velocity (Vt) : Terminal velocity from an outlet, in m/s (FPM), is the highest sustained
velocity in the mixed air stream arbitrarily specified and used to
determine throw.
• Area factor (Ak) : Is the area factor of an outlet or inlet which is also a flow factor
determined from the discharge or intake velocity ( V k ), and the volume
flow rate (CFM).
Ak = CFM
Vk
• Static Pressure (Ps) : The outward force within a duct measured in mm (inch) W.G.
• Velocity pressure (Pd) : The forward moving force of an air stream within a duct measured in
(Dynamic pressure) mm ( inch) W.G.
• Total pressure (Pt) : The sum of the velocity pressure and static pressure measured in mm
(inch) W.G.
The following table could be helpful before starting the selection of a linear slot diffuser.

Table 4. CFM range for supply linear slot diffusers (1 to 8 slots).

13

Engineering Data
NOISE CRITERIA

• Noise criteria : The sound pressure level of 8 octave bands acceptable to human ears
and are estimated from table 5.

The sound caused by an air outlet is directly proportional to the velocity


of the air passing through it.

Ambient sounds a) ENVIRONMENTAL SOUND – Existing within the space with air
conditioning Equipment off
b) EXTERNAL SOUND – Entering a space from outdoors.
c) INTRUDING SOUND – Entering from adjacent spaces.
Prior to selection of NC level from table 5, the three ambient sounds above must be considered.

• The room effect : Is the difference between the sound power level of a terminal and the
sound pressure level sensed by human ears in the room, and is affected
by room size, sound absorption characteristic of the room surfaces,
ceiling height, space volume, distance of listener to terminal, terminal
location and number of terminals.

Curved Slot Diffuser Concave Shape

Curved Slot Diffusers


Convex Shape

14

Noise Criteria
RECOMMENDED NOISE CRITERIA FOR ROOMS

www.dasco.com.kw

Table 5. Recommended range of noise criteria from ASHRAE GUIDE.

15

Noise Criteria
BASIC PERFORMANCE DATA FOR DLD-CS

A. Supply linear slot diffusers with 3/4” slot width


Number of slots
1 2 3 4 5 6 7 8
CFM/Ft 10 20 30 40 50 60 70 80
Throw (Ft) 4-8 7-12 7-14 8-16 9-18 11-20 11-22 12-23
NC <20 <20 < 20 <20 <20 <20 < 20 <20
CFM/Ft 15 30 45 60 75 90 105 120
Throw (Ft) 6-10 9-15 11-19 12-21 14-24 15-27 17-29 18-31
NC <20 <20 < 20 20 22 23 25 27
CFM/Ft 20 40 60 80 100 120 140 160
Throw (Ft) 8-12 10-19 14-24 16-27 18-30 20-33 22-36 24-38
NC 20 22 24 26 27 28 29 30
CFM/Ft 25 50 75 100 125 150 175 200
Throw (Ft) 10-14 13-22 17-26 20-30 22-32 25-36 28-39 30-42
NC 25 26 28 30 31 32 33 34
CFM/Ft 30 60 90 120 150 180 210 240
Throw (Ft) 12-17 15-24 20-29 24-33 25-34 29-40 31-42 33-45
NC 30 32 33 34 35 36 37 38
CFM/Ft 35 70 105 140 175 210 245 280
Throw (Ft) 13-18 17-26 22-33 25-36 27-38 31-44 33-47 34-49
NC 33 35 37 38 39 40 41 42

CFM/Ft 40 80 120 160 200 240 280 320


Throw (Ft) 14-20 19-28 24-35 26-38 29-41 33-47 35-51 36-54
NC 36 38 40 42 43 44 45 46
CFM/Ft 45 90 135 180 225 270 315 360
Throw (Ft) 15-22 21-30 26-38 27-40 32-45 35-50 37-54 38-58
NC 39 42 44 46 47 48 49 50
CFM/Ft 50 100 150 200 250 300 350 400
Throw (Ft) 17-24 24-33 29-40 28-44 35-50 37-54 39-58 40-62
NC 42 44 46 48 50 52 54 56
Table 6. Performance data for supply linear slot diffusers with 3/4” Slot width
Note • Throw data (Ft) is based on terminal velocities of 100 & 50 FPM for horizontal discharge.
• NC values are for horizontal discharge. For vertical discharge subtract(5) from NC values.
• NC values are for 4 Ft long unit and assume room attenuation 10 db.

16

Performance Data
Number of Slots
Supply 1 2 3 4 5 6 7 8
P.D.” W.G.
0.3

www.dasco.com.kw
0.2

0.1

0.05

0.03

0.02
10 20 30 50 70 100 200 300

Curve 1. Static pressure drop Vs. Air flow for DLD-CS (3/4” Slot width)

Note • Static pressure drop in inch W.G. for horizontal discharge. For vertical discharge multiply by 0.6

EFFECTIVE FREE AREA (Ak)

Table 7. Effective free area Ak (Ft2 /Ft run) for DLC-CS (3/4” Slot width)

17

Performance Data
BASIC PERFORMANCE DATA FOR DLD-CS

B. Supply linear slot diffusers with 1 ” slot width


Number of slots
1 2 3 4 5 6 7 8
CFM/Ft 10 20 30 40 50 60 70 80
Throw (Ft) 4-7 7-11 7-13 8-15 9-17 11-19 11-21 12-22
NC <20 <20 < 20 <20 <20 <20 < 20 <20
CFM/Ft 15 30 45 60 75 90 105 120
Throw (Ft) 5-9 8-14 10-18 11-20 1 3 -2 3 14-26 1 6 -2 7 17-30
NC < 20 < 20 < 20 <20 21 22 24 26
CFM/Ft 20 40 60 80 100 120 140 160
Throw (Ft) 8-12 9-19 13-23 15-26 1 7 -2 9 19-32 21-34 23-36
NC <20 21 23 25 26 27 28 30
CFM/Ft 25 50 75 100 125 150 175 200
Throw (Ft) 9-14 12-21 16-25 20-30 21-31 24-36 27-38 29-40
NC 24 25 26 28 30 31 32 33
CFM/Ft 30 60 90 120 150 180 210 240
Throw (Ft) 11-17 14-23 18-28 23-32 24-34 27-39 30-40 32-44
NC 27 29 30 32 34 35 36 37
CFM/Ft 35 70 105 140 175 210 245 280
Throw (Ft) 12-18 16-25 21-32 24-36 26-38 30-43 32-46 33-48
NC 30 32 34 36 38 39 40 41
CFM/Ft 40 80 120 160 200 240 280 320
Throw (Ft) 14-20 18-28 23-34 25-38 28-42 31-46 34-50 36-52
NC 33 35 37 39 40 41 43 45
CFM/Ft 45 90 135 180 225 270 315 360
Throw (Ft) 15-22 20-30 25-38 26-40 30-44 34-49 36-52 37-56
NC 35 38 40 43 45 46 47 49
CFM/Ft 50 100 150 200 250 300 350 400
Throw (Ft) 16-24 24-32 27-39 29-43 34-49 36-53 38-56 39-60
NC 39 41 44 46 48 50 52 54
Table 8. Performance data for supply linear slot diffusers with 1˝ slot width
Note • Throw data (Ft) is based on terminal velocities of 100 & 50 FPM for horizontal discharge.
• NC values are for horizontal discharge. For vertical discharge subtract(5) from NC values.
• NC values are for 4 Ft long unit and assume room attenuation 10 db.

18

Performance Data
Supply
Number of Slots
P.D.” W.G. 1 2 3 4 5 6 7 8

0.15

www.dasco.com.kw
0.1

0.05

0.025

0.015

0.01
10 20 30 50 70 100 200 300

Curve 2. Static pressure drop Vs. Air flow for DLD-CS ( 1˝ slot width)

Note • Static pressure drop in inch W.G. for horizontal discharge. For vertical discharge multiply by 0.6

EFFECTIVE FREE AREA (Ak)

Table 9. Effective free area Ak (Ft2 /Ft run) for DLC-CS (1” Slot width)

19

Performance Data
BASIC PERFORMANCE DATA FOR DLD-CR

A. Return linear slot diffusers with 3/4 ” slot width

Number of slots
1 2 3 4 5 6 7 8
Static Pressure
0.007 0.030 0.062 0.117 0.173 0.236 0.335 0.452
Drop W.G
CFM/Ft 10 20 30 40 50 60 70 80
NC < 20 < 20 <20 <20 < 20 < 20 < 20 <20
CFM/Ft 15 30 45 60 75 90 105 120
NC <20 <20 20 21 23 24 26 27
CFM/Ft 20 40 60 80 100 120 140 160
NC 21 22 24 26 28 29 30 31
CFM/Ft 25 50 75 100 125 150 175 200
NC 25 27 29 31 32 33 34 35
CFM/Ft 30 60 90 120 150 180 210 240
NC 31 33 34 35 36 37 38 39
CFM/Ft 35 70 105 140 175 210 245 280
NC 34 36 38 39 40 41 42 43
CFM/Ft 40 80 120 160 200 240 280 320
NC 37 39 41 43 44 45 46 47
CFM/Ft 45 90 135 180 225 270 315 360
NC 40 43 45 47 48 49 50 51
CFM/Ft 50 100 150 200 250 300 350 400
NC 43 45 47 49 51 53 55 57
Table 10. Performance data for return linear slot diffusers with 3/4˝ slot width

Note •Performance data are for return linear slot diffusers with deflection blades.
•NC values are for 4 Ft long unit and assume room attenuation 10 db.
•Static pressure values are in inches W.G.
EFFECTIVE FREE AREA (Ak)

Table 11. Effective free area Ak (Ft2 /Ft run) for DLC-CR (3/4˝ Slot width)

20

Performance Data
BASIC PERFORMANCE DATA FOR DLD-CR

B. Return linear slot diffusers with 1 ” slot width


Number of slots
1 2 3 4 5 6 7 8
Static Pressure
0.005 0.020 0.044 0.078 0.115 0.164 0.231 0.310
Drop W.G

www.dasco.com.kw
CFM/Ft 10 20 30 40 50 60 70 80
NC < 20 < 20 < 20 <20 < 20 < 20 < 20 20
CFM/Ft 15 30 45 60 75 90 105 120
NC <20 <20 <20 20 22 23 25 26
CFM/Ft 20 40 60 80 100 120 140 160
NC <20 22 24 26 27 28 29 30
CFM/Ft 25 50 75 100 125 150 175 200
NC 24 26 27 29 31 32 33 34
CFM/Ft 30 60 90 120 150 180 210 240
NC 28 29 31 33 35 36 37 38
CFM/Ft 35 70 105 140 175 210 245 280
NC 31 33 35 37 39 40 41 42
CFM/Ft 40 80 120 160 200 240 280 320
NC 34 36 38 40 41 42 44 46
CFM/Ft 45 90 135 180 225 270 315 360
NC 36 39 41 44 46 47 49 50
CFM/Ft 50 100 150 200 250 300 350 400
NC 40 42 45 47 49 51 52 55
Table 12. Performance data for return linear slot diffusers with 1 ˝ slot width

Note •Performance data are for return linear slot diffusers with deflection blades.
•NC values are for 4 Ft long unit and assume room attenuation 10 db.
•Static pressure values are in inches W.G.
EFFECTIVE FREE AREA (Ak)

Table 13. Effective free area Ak (Ft2 /Ft run) for DLC-CR (1 ˝ slot width)

21

Performance Data
CORRECTION FACTORS

A) Supply Linear slot diffusers


• Throw and NC values in performance tables are based on supply linear slot diffusers with active
length of 4 Ft. To determine throw and NC values for other lengths, use the correction factors in
the following table :

Table 14. Correction factors for throw and NC values at different active lengths of supply linear slot diffusers

• Static pressure drop and NC values in performance table/curves are based on 100% damper
opening . Use the following correction factors for different damper adjustments.

Table 15. Correction factors for static pressure drop and NC values at different damper adjustments

B) Return linear slot diffusers


• NC values in performance tables are based on return linear slot diffusers with active length of 4 Ft.
To determine NC values for other lengths, use the correction factors in the following table:

Table 16. Correction factors for NC values at different active lengths of return linear slot diffusers.

22

Correction Factors
AIR BALANCING ADJUSTMENT

To determine the CFM, follow up the following procedure:


1) Use measuring tools for air velocity like ALNOR 2220 A or 2220 probe, or anemotherm air
meter model 60.

www.dasco.com.kw
2) Take number of measuring points ( should be not less than 4)based on 4 Ft long linear diff-
fuser, and probe should be located and adjusted as to measure the maximum air velocity by
facing the probe to the air flow direction on the face of the linear slot diffuser as shown.
3) Take the arithmetic average of velocity readings to obtain the V k (average) as follows:

Vk ( average) = ( V1+V2+.....+Vk)
K

4) Determine the area factor (Ak) from previous tables considering the linear diffuser length
and number of slots.
5) Calculate the air volume ( CFM ) with the following formula :

CFM = Vk (average) x Ak

Right Flow Left Flow Vertical Flow Return

Note If the air volume calculated from above procedure is not satisfactory, repeat the same proced-
dure after adjusting the deflector angle.

DEFLECTOR SETTING
The deflector blades of the supply linear slot diffusers can be fully adjusted to give either a horiz-
zontal / vertical air pattern, or any combination of them.
The horizontal air flow adjustment may be set for either left or right hand throw.

23

Air Balancing
STANDARD FIXING METHOD

Linear Diffuser (2 slots)


with end cap from one side

Linear Diffuser (2 slots)


without end caps

24

Fixing Method
CONVERSION TABLE

Quantity Imperial Unit Metric Unit From Imperial To From Metric To


Metric Multiply By Imperial Multiply By

www.dasco.com.kw
Area Square foot Square meter (m2 ) 0.0929 10.764
2
Square inch Square millimeter (mm ) 645.16 0.00155

Density Pounds per cubic foot Kilograms per cubic 16.018 0.624
3
meter (kg/m )

Length inch millimeter (mm) 25.4 0.0394


foot millimeter (mm) 304 .8 0.00328
foot meter (m) 0.3048 3.2808
ya rd meter (m) 0.9144 1.0938

Pressure inch of wa ter column K ilopa sca l (kPa ) 0.2486 4.0219


foot of wa ter column K ilopa sca l (kPa ) 2.9837 0.3252
inch of mercury column K ilopa sca l (kPa ) 3.3741 0.2964
ounces per squa re inch K ilopa sca l (kPa ) 0.4309 2.3206
pounds per squa re inch K ilopa sca l (kPa ) 6.8948 0.145

Temperature fa hrenheit celcius (º C ) 5 / 9 (º F- 3 2 ) (9 / 5 º C ) + 3 2

Velocity feet per second meters per second (m/s) 0.3048 3.2808
feet per minute ( fpm) meters per second (m/s) 0.00508 196.85
miles per hour meters per second (m/s) 0.44704 2.2369

Volume Flow Cubic feet per minute (cfm) Liters per second (L/s) 0.4719 2.119
3
Cubic feet per minute (cfm) Cubic meters per second (m /s) 0.0004719 2119.0
Cubic feet per hour ( cfh) Milliliters per second( ml/s) 7.8658 0.127133
Gallons per minute(U.S.) Liters per second( L/s) 0.6309 15.850
Gallons per minute(imperial) Liters per second( L/s) 0.7577 13.198

Table 17. Metric guide conversion factors.

25

Conversion Table
TESTING AND APPROVAL

Different samples from DASCO air terminal devices (Linear Slot Diffusers) were
tested at ITS (Intertek Testing Services) labs in accordance with:
• Air diffusion council test code for grilles, registers and diffusers No. ADC 1062:
GRD-84.
• ISO 5219 “Air distribution and air diffusion laboratory aerodynamic testing and
rating of air terminal devices”.
• ANSI/ASHRAE 70-1991, “Method of testing for rating the performance of air
outlets and inlets”.

LINEAR SLOT DIFFUSERS WERE TESTED FOR:

a. Sound (NC Noise Criteria).


b. Static pressure in inches W.G.
c. Throw, feet.
d. Ak (Area factor).

26

Testing & Approval


COATING WITH POWDER

NOW YOU CAN ACHIEVE OPTIMAL COATING PERFORMANCE


ON ALL PRODUCTS YOU PAINT!

www.dasco.com.kw
DASCO offers a first class service by introducing a wide range of perfect polyester
powder coating on all of its aluminium products of air terminal devices.
The best quality of polyester powder Corro-Coat are used in according to the intern-
national standards (BS,ISO,DIN,ASTM). PE-F architectural grade polyester powders
are used perfectly with pre-treatment, electrostatic spray and curing in accordance
with the above standards recommendations. A complete range of RAL-Standard
colours are always available in addition to a vast range of special compound colours
as per our customers request.
RAL Standard Colour Chart Swatch

27
28

www.dasco.com.kw
www.dasco.com.kw

29

www.dasco.com.kw
Since 1962
Product Bulletin 133-D

P.O. Box: 6192 Hawalli 32036 Kuwait.


Tel: +965 4839911 Fax: +965 4815498
www.dasco.com.kw

You might also like