MAIN 70 AT 2P CB

PANEL 1 FEEDER 2-14 SQ MM THHN + 1-5.5Q MM TW


IN 25 MM DIAMETER RSC
PANEL 1 NO OF OUTLETS NO OF SW FACTOR WATTS VOLTS AMP CB RATING 2PCS (MM2) 1 PC (2MM) WIRE SIZE OF
CKT # DESCRIPTION CO 2W 3W OTHER V A AT AF POLE WIRE SIZE GND WIRE PCS CONDUIT (MM)
1 CONVENIENCE OUTLET 7 180 1260 230 5.48 20 50 2 3.50 3.50 THHN 20
2 CONVENIENCE OUTLET 8 180 1440 230 6.26 20 50 2 3.50 3.50 THHN 20
3 CONVENIENCE OUTLET 8 180 1440 230 6.26 20 50 2 3.50 3.50 THHN 20
4 LIGHT OUTLET 31 60 1860 230 8.09 20 50 2 2.00 2.00 THHN 20
5 INVERTER REF 1 720 720 230 3.13 20 50 2 3.50 3.50 THHN 20
6 SPARE /MOTOR 1HP 1 1840 1840 230 8.00 30 50 2 3.50 3.50 THHN 20
7 SPLIT TYPE AC 1HP 1 1840 1840 230 8.00 30 50 2 3.50 3.50 THHN 20
8 WINDOW AC 3/4 HP 1 1840 1380 230 6.00 20 50 2 3.50 3.50 THHN 20
9 SPARE 1000 1000 230 4.35 20 50 2 3.50 3.50 THHN 20
COMPUTATION
4,140.00 4,420.00 4,220.00 230
TOTAL CONNECTED LOAD
12,780.00 230 55.57
DEMAND FACTOR 80%
DEMAND LOAD 10,224.00 230 44.45
DEMAND LOAD PLUS 25% 13,419.00 230 58.34 70 14 5.5 THHN 25

118

MAIN 200 AT 2P CB
PANEL 2 FEEDER 2-80 SQ MM THHN + 1-38 SQ MM TW
IN 40 MM DIAMETER RSC
NO OF OUT NO OF SW VA/CKT TOTAL VA VOLTS AMP CB RATING 2PCS (MM2) 1 PC (2MM) WIRE SIZE OF
CKT # DESCRIPTION QTY 2W 3W OTHER CO LO OTHERS V A AT AF POLE WIRE SIZE GND WIRE PCS CONDUIT (MM)
1 CONVENIENCE OUTLET 7 180 1260 230 5.48 20 50 2 3.50 3.50 THHN 20
2 CONVENIENCE OUTLET 6 180 1080 230 4.70 20 50 2 3.50 3.50 THHN 20
3 CONVENIENCE OUTLET 7 180 1260 230 5.48 20 50 2 3.50 3.50 THHN 20
4 CONVENIENCE OUTLET 7 180 1260 230 5.48 20 50 2 3.50 3.50 THHN 20
5 LIGHT OUTLET 34 60 2040 230 8.87 20 50 2 2 2 THHN 20
6 LIGHT OUTLET 27 60 1620 230 7.04 20 50 2 2 2 THHN 20
7 LIGHT OUTLET 26 60 1560 230 6.78 20 50 2 2 2 THHN 20
8 INVERTER SPLIT TYPE AC 1HP 1 1840 1840 230 8.00 30 50 2 3.50 3.50 THHN 20
9 INVERTER SPLIT TYPE AC 2HP 1 1840 3680 230 16.00 30 50 2 5.5 5.5 THHN 25
10 INVERTER SPLIT TYPE AC 1HP 1 1840 1840 230 8.00 30 50 2 3.50 3.50 THHN 20
11 INVERTER SPLIT TYPE AC 1HP 1 1840 1840 230 8.00 30 50 2 3.50 3.50 THHN 20
12 WATER HEATER 1 5000 5000 230 21.74 30 50 2 5.5 5.5 THHN 25
13 WASHING MACHINE 1 5000 5000 230 21.74 30 50 2 5.5 5.5 THHN 25
14 WATER HEATER 1 5000 5000 230 21.74 30 50 2 5.5 5.5 THHN 25
15 WATER HEATER 1 5000 5000 230 21.74 30 50 2 5.5 5.5 THHN 25
16 SPARE /MOTOR 1HP 1 1840 1840 230 8.00 30 50 2 3.5 3.5 THHN 20
17 GATE CLOSER 1 400 400 230 1.74 15 50 2 3.5 3.5 THHN 20
COMPUTATION
4,860.00 5,220.00 31,440.00 230
TOTAL CONNECTED LOAD
41,520.00 230 Err:522
DEMAND FACTOR 80%
DEMAND LOAD 33,216.00 230 Err:522
DEMAND LOAD PLUS 25% OF MOTOR 43,596.00 230 189.55 200 80 38 THHN 32