Professional Documents
Culture Documents
Range Overview
KEY FEATURES Chloride® FP20R is supplied with a single-
phase input and offers a wide choice of
Power factor corrector to limit output voltages, from 12 Vdc to 220 Vdc.
perturbations on the upstream network. The range of available ratings is from 6 to
Low voltage ripple to optimize battery 180 A, according to the chosen output
life. voltage.
Fuse or circuit breaker on the output Chloride® FP20R combines high frequency
and on the battery line. switch-mode technology with
microprocessor control to bring a high
Up to IP41 ingress protection to meet
Example of Chloride® FP20R-CK
Design Flexibility which allows paralleling To further ensure reliability of the connected
of the internal rectifier modules to load, Chloride® FP20R is provided with
increase the available power or to ensure natural convection cooling, thus eliminating
N+1 redundancy. the need to replace worn mechanical parts.
CHLORIDE® FP20R CABINET
Rectifier - Charger - DC power pack
6-180 A ( 1-ph input)
Available Ratings
AVAILABLE ACCEPTABLE
OUTPUT CHARGER BATTERY AVAILABLE POWER ON BATTERY
ITEM CODE POWER PEAKS CABINET
VOLTAGE CURRENT CAPACITY(1) (W)
(MAINS)(2) (A)
(2) Output power value given with mains input available and battery in recharge at 0.1C10
CHLORIDE® FP20R CABINET
Rectifier - Charger - DC power pack
6-180 A ( 1-ph input)
Available Ratings
AVAILABLE ACCEPTABLE
OUTPUT CHARGER BATTERY AVAILABLE POWER ON BATTERY
ITEM CODE POWER PEAKS CABINET
VOLTAGE CURRENT CAPACITY(1) (W)
(MAINS)(2) (A)
(2) Output power value given with mains input available and battery in recharge at 0.1C10
Technical Data
INPUT OPTIONS
Main supply 230 Vac 1 ph Charger / Load 400 Single-phase 400 Vac input voltage
Input voltage tolerance -20 % / +15 % Q Position contact on AC input circuit breaker
Power factor > 0.95
D Paralleling diode
Input frequency 50 / 60 Hz
Frequency range From 47 to 63 Hz I DC earth fault alarm
F Integrated distribution board, up to 12 feeders (fuses)
OUTPUT Battery FB Battery protection (fuse 32 A)
Nominal voltage See selection table A Low-voltage battery cut-off
Output voltage range ±15 % B Battery test
Static regulation ±1 %
C C13-100 automatic control system - programmable
Voltage ripple < 0.1 % RMS
0.5 to 24 h (in compliance with French standards)
BATTERY T Temperature probe for battery charge compensation
Type Valve regulated lead acid Mechanical External ingress protection IP41
RC Space heater with hygrostat and/or
MONITORING thermostat
Type of display Alphanumerical, 2 lines of 8 characters Internal lighting
Monitoring of the DC voltage
Lifting rings
Main functions LED test Feet 100 mm or 200 mm
Battery recharge current limitation
Communication RS Modbus RS485
Measurements Output voltage
FR / EN Display Language French or English
Output current
Remote signaling Up to 4 dry contacts
SPECIAL REQUEST
GENERAL DATA Battery Other types of batteries, lead-acid or nickel-cadmium,
vented or recombination
Rectifier efficiency From 83 % to 91 %
JB / HB Battery protection (circuit breaker with or without
Operating temperature From 0 to 40 °C
contact)
Storage temperature From -5 to 45 °C
Relative humidity < 95 % non condensing at 20 °C Load J/H Integrated distribution board, up to 6 feeders (circuit
breakers with or without contact)
Operating altitude 1000 m (without system derating)
Cooling Natural convection cooling
External protection IP 21
Noise (at 1 m in front of the ≤ 60 dBA
unit)
Input / output insulation 2500 Vac / 1 minute
Frame colour RAL 7035
Dimensions CK type: H 850 mm x W 500 mm x D 420 mm
CR type: H 1200 mm or 1800 mm x W 800 mm x
D 600 mm - Height to be confirmed based on options.
Compliance
STANDARDS EUROPEAN DIRECTIVES
IEC/NF EN 60146-1-1: 2009 Semiconductor converters - Part 1-1: Specification of Low voltage directive: 2006/95/EC (before April 2016)
basic requirements
2014/35/EU (after April 2016)
IEC/NF EN 61000-6-2: 2006 Electromagnetic compatibility (EMC) - Part 6-2:
Generic standards - Immunity for industrial EMC directive: 2004/108/EC (before April 2016)
environments
2014/30/EU (after April 2016)
IEC/NF EN 61000-6-4: 2007 Electromagnetic compatibility (EMC) - Part 6-4:
AMD1:2011 Generic standards - Emission standards for industrial
environments
IEC/NF EN 61439-1: 2012 Low voltage switchgear and controlgear assemblies -
Part1: General rules
IEC/NF EN 60950-1: 2013 Information technology equipment - Safety - Part 1:
AMD2:2014 General requirements
NF C58-311: 1990 Procedure for type tests for rectifier-battery charger
and batteries
© 2017 Vertiv Co. All rights reserved. Vertiv, the Vertiv logo and Chloride are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every
precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.
Chloride-FP20R-DS-EN-gl-rev2-0617