DATE MACHINE ID WORK COMPLETED COMMENTS AND

RECOMMENDATION
08/09/21 CAMPESE 500 KVA Did walk around inspection  All the filter housings are
GENERATOR PERKINS Cleaned machine. Removed Filters and drained damaged at the bottom
2800 SERIES ENGINE Oil. Replaced with new filters and topped up where you loosen them to
with fresh oil. change the cartridges. Had
The Generator room was cleaned. to remove the three
Primed the engine fuel system. complete housings from
the Engine and take them
to the Workshop to loosen
with a wrench.
 The outlet of the drain
pump for oil needs to be
plugged to prevent dust
ingress and the pump
handle must not be kept
on the machine because
someone can pump all the
oil out of the Engine sump.
09/09/202 CAMPESE 500 KVA Added Electrolyte to the batteries and started  There is grass growing
1 GENERATOR PERKINS the machine. Running well. No fuel and engine inside the perimeter of the
2800 SERIES ENGINE oil leaks. pump room that needs to
Replaced all Covers. be removed.
09/09/202 PERKINS 350 KVA Did walk around inspection  Signs of overheating on the
1 GENERATOR NO 1 Cleaned machine. Removed all filters and radiator. History given is
drained oil. that every start up the
Replaced with new filters and added fresh oil. machine is topped with 5
Started ma litres.
 The machine cooling
compartment is filled with
tap water. Recommend use
of coolant.
 The radiator for No 2
Generator can be given to
us we have it pressure
tested and flushed out and
fit on No 1 since No 2 does
not have an Engine.
 The Priming pump on the
injector pump is leaking
and needs replacement.