You are on page 1of 13

The Eighth Jordan International Chemical Engineering Conference (JIChEC 2017)

November 7-9, 2017

Experimental study and mathematical modeling of a


vapor compression refrigeration system
Dr. Shurooq Talib Remedhan Al-Hemeri *

Abstract
Vapor compression refrigeration systems are regularly refrigerants because evaporation and condensation
utilized to give a cool atmosphere to space thermal processes in refrigeration systems are achieved in
condition control purposes in commercial and consider a result of the energy transfer from
industrial applications, especially in dehydration of refrigerants and change its phase from the vapor into
gases, and application of refrigeration in the petroleum
the liquid [1].
industry including lubricating-oil purification in
addition to the separation of volatile hydrocarbons. Due to the amount of energy required by the
Keeping in mind to outline good-performance that can refrigeration sector, which is estimated to be around
be implemented for a wide range of operation, 15% of total energy consumption in the world, the
mathematical modeling which allows the simulation of scientific community is working hard to optimize
its behavior for changing input conditions, necessary to the operation of refrigeration plants. To do so,
be developed. In this work we changed the volumetric mathematical models constitute one of the best tools
flow rate of secondary fluid (water) in the condenser in both for analyzing and for controlling systems.
the range of (16-40) liter/hr, to study the experimental [2].There are two types of mathematical models
and mathematical analysis of condenser and
slated to the behavior of vapor compression
evaporator of the cycle. Experimental analysis was
conducted using a test rig for a vapor compression refrigeration system: empirical or statistical models
refrigeration system with R-134a as a refrigerant. The and physical models. Empirical models are based on
theoretical model is based on the mathematical mathematical routines which obtain the formulation
formulation of the refrigerant side and water side in of the system from experimental data, but these were
the condenser and air side of the evaporator, and the only valid for a particular system or specific
simulation program is based on the steady state conditions. The physical models were based on
mathematical model of vapor compression detailed data of parts in the system and their
refrigeration cycle components solved using Mat-lab modeling using equation derived from the physics
program that is used to solve the algebraic equations.
laws [3].
The model requires input parameters of mass flow rate
of the secondary fluid (water) to obtain the model Vapor compression refrigeration systems, which are
prediction of the outlet temperature of the secondary frequently utilized to give chilled media to space
fluids at the condenser and evaporator, the condenser warm condition control purposes in domestics,
and evaporator thermal capacities, the power commercial and industrial applications, mainly
consumed by the compressor and the coefficient of comprise a compressor, a fixed-orifice expansion
performance. The experimental validation of the model device, two of heat exchangers such as (condenser
has been carried out using R-134a as a working fluid, and evaporator), and the light secondary fluid known
concluding that the model can predict the performance as (refrigerant) which evaporates and condenses
of the cycle with an error lower than ±10%.
readily. And the one since for the system was closed
Keyword: Refrigeration, COP, heat exchanger, R134a, to never the refrigerant leaves the system [4].
refrigerant. The ratio of the cooling heat capacity of the
compression work called as a coefficient of
I. Introduction performance for refrigeration system; therefore COP
can be increased by increasing the refrigerating
Refrigeration processes are important in a variety of effect or by decreasing the compression work. For a
applications; where the refrigeration is used in large vapor compression refrigeration cycle, it is
scale industries, especially in the manufacture of ice, important to study how much heat is extracted and
dehydration of gases, domestic, commercial how little energy is spent. The ratio of heat absorbed
refrigerators and other commercial industrial to the work input is called the coefficient of
services. The applications of refrigerants in the oil performance. The ratio should be as high as possible
industry include the separation of Light components, [5].
in the reactions required low temperature and for the COP= = (1)
purification of lubricating-oil. The refrigeration −
system design depends on the properties of the Theoretical COP is the ratio of (theoretical
refrigerating effect) to (the theoretical compressor
* E-mail: 80024@uotechnology.edu.iq , work or isentropic compressor work). Theoretical
salhemeri2004@yahoo.com refrigerating effect, calculated from enthalpies about
Chemical engineering department, University of Technology, evaporator is found from the pressure-enthalpy
Baghdad, Iraq diagram or the temperature-enthalpy diagram and
isentropic compressor work is calculated from
enthalpies about compressor was also got from the
1
diagram. Whenever, define the actual coefficient of analysis for the two heat exchanger “condenser and
performance "COP”as a ratio of actual refrigeration the evaporator” used in the test rig of the vapor
effect to the actual work supplied to the compressor compression refrigeration system. A vapor
[6]. compression refrigeration system is simulated at
There are a many literature which deals with the steady state conditions. A Mat-lab programming
mathematical statements of the vapor compression version 2013a was used in analyzing the heat
refrigeration systems such as Arora and Kanshik [7] transfer for evaporator and condenser in addition to
who presented the theoretical analysis and the thermodynamic properties for the refrigerant. The
exergy analysis in detail to the real vapor simulation was performed with the eco-friendly
compression refrigeration cycle for highest 1,1,1,2-tetrafluoroethane or known as hydro-
condensing efficiency in a condenser. Viabhav et fluorocarbon (HFC) refrigerant R134a.
al.[8] studied the property of the refrigerant that
dependent a thermodynamic model for the simple II. Description of physical system:
vapor compression refrigeration system using A simple vapor compression refrigeration cycle is
various refrigerants that simulate the performance of shown in Figure 1 which comprises of the four
actual system used for a higher efficiency. Gustavo fundamental parts; evaporator, compressor,
[9] studied the theoretical and experimental analysis condenser and expansion valve. The refrigerant is
of the effect of condenser sub-cooling on the the primary working fluid in the cycle. In the
performance of vapor compression refrigeration evaporator, the refrigerant takes heat from the low-
system using various refrigerants. Belman et al.[10] temperature primary fluid by vaporization. The
the analyst of the refrigeration cycle such as vapor refrigerant in the evaporator is superheated and
compression refrigeration cycle by artificial neural vapor is then moved to compressor. To get on the
network using a mathematical model which highest level of energy done by adding the
depended on the operation of a biological neural mechanical work. On the discharge side of the
networks, where the analysis and experimental compressor, the vapor at higher pressure and
results provided ideas to clarify the linkage between temperature is condensed in the condenser.
the input and output parameters in vapor In the condenser, the refrigerant vapor gives the heat
compression refrigeration cycle, and at the end of to the secondary fluid and then it condenses. The
the model actually predicted the performance of the condensation is done in horizontal tubes which
cycle. Maruthi et al. [11] performed the involves total condensation of the vapor. Close to
experimental analysis of vapor compression the outlet of the horizontal level tubes, the vapor
refrigeration system by using R134a and R404a lessens to zero and the flow in the tube becomes
which also evaluated the performance of the cycle. liquid stream.
Mitesh et al.[12] predicated a theoretical The condensed refrigerant then passed through an
performance of vapor compression refrigeration expansion valve which is lowering the pressure and
system and refrigerating effect with alternative control of the mass-flow rate of the refrigerant. The
hydrocarbon refrigerants such as refrigerant leaving the extension gadget enters the
R290,R600a,R1270 as well as their blend mixtures evaporator; in which the refrigerant absorbs heat and
in various ratios. Kedarnath and Patil [13] studied boils. The refrigerant at that point comes back to the
the performance enhancement of vapor compression compressor and the cycle is returned again. The
refrigeration system using nano-fluids which ideal vapor compression refrigeration cycle is shown
increased the area available for exchanging heat and on the pressure – enthalpy and temperature-entropy
efficiency. diagrams in Figures 2,3 also the refrigeration cycle
The experimental study of any refrigeration of vapor compression at actual state is shown in
framework generally is considered complicated, Figure 4 [14,18,19].
essentially because of the cost and the vast number
of factors included. The utilization of numerical
models can lessen the costs and furthermore
encourage understanding the phenomena related to
the issue. Refrigeration systems models are
partitioned into two wide classes: steady –state
models and dynamic models [14].
There is a large number of researchers who studied a
steady state condition for refrigeration system type
of vapor compression ,for example Koury et
al.[15],Jong et al.[16] and Sivak and Hroncova[17]
suggested a refrigeration system model related to
parameters for condenser and evaporator and
simulated the compressor and expansion device Fig. 1: Schematic diagram of simple vapor
using the refrigerant R134a. compression refrigeration system [14]
The main objective of this work is to study the
experimental data and present the mathematical
2
Fig. 2: P-h diagram of ideal vapor compression refrigeration cycle [19].

Saturated
liquid 2

me
ter
3
𝐐𝐇 𝐖𝐢𝐧

1
4’ 4 𝐐𝐋
' Saturated
vapor

Process 1 – 2: Isentropic compression in the compressor.


Process 2 –3: Constant pressure heat rejection in the condenser. Fig. 4: P-h diagram for the actual vapor
Process 3 – 4: Isenthalpic expansion in the expansion device.
Process 4 –1: Constant pressure heat absorption in the evaporator. compression refrigeration cycle [18]

Fig. 3: T-S diagram for the ideal vapor


compression refrigeration cycle [19].

3
Table 1: Accuracy for the experimental refrigeration cycle model (10C- R134a), with a
measurements. range of (0.03 – 0.3) L/min. The second flow meter
was used to measure the volumetric flow rate of the
inlet water to the condenser model (Z-3002-liquid
Uncertainty water) with a range of (14 –40) L/hr.
Independent variables
interval
± 0.2 % ( bar ) Experimental procedure:
Pressure gauge
Temperature readers ± 1 ( ºC ) The main object of this work is to estimate and
analyze the performance of the vapor compression
Thermometer ± 1 ( ºC ) refrigeration system with R134a as a refrigerant by
using refrigeration rig that is shown in Figure 5.
Flow meter ± 0.014 %( kg/sec )
1- The test rig system was turned on and
operated without a thermal load in the
III. Experimental work: evaporator for 5 min. to ensure a proper
operation.
Experimental rig
2- Set the float in the water volumetric rot meter
Test rig of refrigeration system was used to perform to any flow in the range (16-40) L / hr.
the experimental tests as shown in Figure 5 which 3- Turn on the compressor and the fan.
consist of the following components: compressor, 4- Check the system has reached to steady state
condenser, capillary tube, evaporator, and by selecting the temperature and pressure
accessories like :( Pressure gages, thermocouples measurements every minute until no further
and readers, flow meters and sight glasses). change is observed should be (10 to 15 )min.
Compressor: A single 370W capacity hermetic 5- At steady state, take the readings of the
compressor (Panasonic model QB77C16GAX5) was refrigerant flow rate, four pressures and eight
selected in the current work. The compressor was temperatures .This step was repeated for each
designed to work at a speed 2990rpm and R134a thermal load applied to the evaporator.
was used as a refrigerant. 6- For shutdown, stop the compressor, wait for 5
Condenser: The water condenser used in this cycle minutes, then close the water valve .Then
is wire and tube type with exchange surface area switch off the main power supply and thermo-
equal to 600 m2. couple device (to save batteries).
Expansion Device: In this cycle the capillary tube
consists of a single copper tube with (2800 mm) IV. Thermodynamic model for vapor
length and (1.5 mm) diameter is located before the
compression refrigeration performance:
evaporator to make a pressure drop and control on
the mass flow rate of refrigerant that enters the The mathematical models of the parts for the
evaporator. refrigeration circuit including the compressor, heat
Evaporator: In order to get variable load on the exchangers, expansion valve at steady state was
evaporator, a shell and coil evaporator has been include it in simulation program. To simulate a
used, where the flow of refrigerant in the tube and refrigeration system, we ought to be joined the parts
air in a shell with exchange surface area equal to 600 models into a general model as indicated by the
m2. relationship for ingredients parameters. Figure 6 is a
Sight Glass: Sight glasses are used for viewing the simplified flow chart for the vapor compression
phase of refrigerant through the refrigeration system, refrigeration system with assuming the pressure
and to view the liquid refrigerant level through tubes losses in condenser and evaporator are ignored.
and other vessels in the system. It is used also as Considering the operation of the cyclic system at
refrigerant moisture indicator to ensure that the steady-state using refrigerant R134a vapor outlet
refrigerant contains less moisture. from evaporator at point 1 and compression through
Pressure Gauges: Pressure gaugesare used to the compressor to point 2.The sub-cooled refrigerant
measure the pressures at different locations in the exits the condenser at point 3 then flows through the
cycle. Pressure gauge with a range of (0 to 20) bars expansion valve to the evaporator inlet at point 4.
is used to measure the low side pressure, and the The analysis of the cycle in Figure 6 in terms of:
high side pressure. 1) Cooling capacity
Temperature Sensors: Temperatures at different 2) Condenser heat capacity
points in the test rig were measured by 3) Compressor power consumption
thermocouples connected to the temperature readers. 4) Mass flow rate of refrigerant
Temperatures were measured by K-type 5) Coefficient of performance
thermocouple operating in the range of (-200 to 6) Efficiency of vapor compression refrigeration
1250 ºC). cycle
Flow Meters: Two flow meters were used in the
present work, the first one was used for measure the
volumetric flow rate of the liquid refrigerant in the
4
Fig. 5: Refrigeration Unit

In the present work, developed assumptions to Where, Cp is the heat capacity for the external fluid
specify thermodynamic analysis in the refrigeration (air) (kJ/kg.K),T7 is the external fluid (air) inlet
system: temperature (K), T8 is the external fluid (air) outlet
temperature (K), m.ref is the mass flow rate of
 Pressure losses in the pipelines are neglected. refrigerant (kg/s) and h is the specific enthalpy of the
 Kinetic and potential energy are not considered. refrigerant at state point (kJ/kg).
 Heat transfer from the system or to the system is As the same, the heat-transfer rate between the
not considered. refrigeration cycle and the sink in the condenser i.e,
By applying the first law of thermodynamics with condenser heat capacity is:
the change in internal energy for a cyclic process is Q.cond = m.ref (h2 – h3) = (m. .Cp)w (T5– T6) (4)
zero, we get [8]:
(Q.cond–Q.evap)–W.=0 (2) Where, T5 is the external fluid (water) inlet
Where, Q.cond is the rate of heat rejection in the temperature (K) and T6 is the external fluid (water)
condenser (kW),Q.evap is the rate of heat absorbed by outlet temperature (K).
the evaporator (kW), W. is the power input to the
compressor (kW). And the power required by the compressor at
The heat absorbed through the evaporator and isentropic efficiency, is given by:
exothermic from the condenser occurs by the W. = m.ref (h1 – h2) (5)
working fluid “refrigerant” streams with mass flow We then calculate the circulation rate of refrigerant
rates and specific heats. Therefore, the heat-transfer m·ref which is determined from the rate of heat
rate to the cycle in the heat exchanger (evaporator) absorption in the evaporator by the equation:
i.e, cooling capacity becomes: Q.evap
m·ref = h1 − h4
(6)
Q.evap = m.ref (h4 – h1) = (m. .Cp)air (T7– T8) The COP is defined as the refrigerating effect over
(3) the net work input, i.e.
(h1 – h4)
COP”actual” = Q.evap / W. = (h2 – h1)
(7)

5
Performance of coefficient for Carnot ideal cycle: Efficiency of vapor compression cycle ( ɳ ) :
𝑇𝑐
ω =COPcarnot = 𝑇ℎ−𝑇𝑐
(8) ɳ=COP”actual”/ω (9)
Requirements for calculation the
Where, Tc = T1sat is the saturated temperature of thermodynamic properties of R134a
refrigerant in (K) at evaporator pressure, and Th= refrigerant in simulation of the refrigeration
T3sat is the refrigerant saturated temperature in (K) at
condenser pressure.
cycle:
To analysis the refrigeration system, the following
requirements must be availability to calculate the
Cooling refrigerant
Mode thermodynamic properties [20-21]:

Diagram
Throttling
T4 Device
Evaporator Water Condenser
Water
Fan flow
meter Out
𝐓𝟔
𝐓𝟕 𝐓𝟖
𝐓𝟒

Water
In
𝐓𝟓 𝐓𝟑

Refrigerant
turbine
flow

𝐓𝟏 𝐓𝟐
Compressor

Temperature Symbols Define

T1 Refrigerant inlet compressor temperature


T2 Refrigerant discharge compressor
temperature
T3 Refrigerant outlet condenser temperature
T4 Refrigerant inlet evaporator temperature
T5 Water inlet condenser temperature
T6 Water outlet condenser temperature
T7 Air inlet evaporator temperature
T8 Air outlet evaporator temperature

Fig. 6: Schematic diagram of the vapor compression refrigeration system.

6
 The quick calculation: Because occur many h4=hL3 (13)
calculations that related to the simulation field of h4: enthalpy of refrigerant at outlet from throttling
thermodynamic properties for refrigerant, valve (kJ/kg)b ~> 0, then: b ~> 0, then: Provided AT
therefore, the quick calculation of refrigerant At point (1) outlet from evaporator: if vapor
thermodynamic properties consider an important superheat that is given by:
factor for simulation, and it has an effect on the ∆Ts=Tsup – T1sat (14)
selection of component model in the system. Where, Tsup= T1 and T1sat is calculated from
 Higher stability: Since there are many attempts eq.(10) at low pressure ”Pevap.” .
for the calculation of refrigerant thermodynamic
hv =249455+606.163 T1sat -1.05644 T21sat -
properties, the dissimilarity in calculation has
happened regardless of the possibility that 1.82426*10-2T31sat (15)
likelihood is low in a solitary estimation , so the hv :enthalpy of saturated vapor at ∆Ts=0 in(kJ/kg) .
requirement on the stability must be achieved h1= hv (1+3.48186*10-3 ∆Ts +1.6886*10-6 ∆T2s
 The reversibility: There are a large number of +9.2642*10-6∆Ts T1sat -7.698*10-8 ∆T2s T1sat +
refrigerant thermodynamic properties in the 1.7070*10-7∆TsT21sat-1.2130*10-9∆T2sT21sat (16)
simulation of refrigeration systems which need to h1: enthalpy of superheated vapor at ∆Ts >0 that
be converted to each other. In spite of the inlet to compressor (kJ/kg).
deviation is almost very little in a solitary At point (2) outlet from compressor: the vapor is
conversion process however will lead to a large superheat, therefore, we need another parameter to
difference in the last figured outcomes due to a
determine h2 ,that is the specific volume of saturated
numerous iterations that required.
 The continuity and simplify: The result of vapor (ῦv ) in (m3/kg):
2669
convergence is achieved only when there is ῦv=exp(-12.4539+ 273.15+Tsat
)(1.01357+
1
iteration for continuous functions. And because
1.06736*10-3T1sat-9.2532*10-6 T21sat -3.2192
of some refrigerant thermodynamic properties
are used the differential coefficients, therefore *10-7 T31sat ) (17)
the differential coefficients must be also then convert ῦv to superheated specific volume
continuous and its function curve should be V1sup at point (1) in (m3/kg):
smooth. V1sup= ῦv (1+4.7881*10-3∆Ts -3.965*10-6∆T2s
Cleland [22] and Wang etal. [23], presented a quick +8.5739*10-7∆Ts T21sat -5.401*10-9∆T2s T21sat)
method to calculate the refrigerant thermodynamic (18)
properties in addition they gave the correlations for ∆Tc= T3sat – T1sat (19)
R134a for the saturation temperature of _40 to70 oC . C1=1.06469-1.6907*10-3 T1sat -8.560*10-6 T21sat
For a reversible calculation the formula of saturation
-2.135*10-5 T1sat∆Tc -6.1730*10-7 T21sat∆Tc
pressure and temperature is presented in a simple
and practical model, consumes less computation +2.0740*10-7 T1sat∆T2c +7.720*10-9 T21sat∆T2c -
time. The estimations of polynomial curve- fit 6.103*10-4∆Tc (20)
equations for thermodynamic properties of C=C1(1+1.1757*10-3∆Ts-1.814*10-5∆T2s+
refrigerant R134a are easy, and computationally
quick; for usually refrigeration conditions
4.121*10-5∆TsT1sat-8.093*10-7∆T2sT1sat) (21)
anticipated properties generally a large concur with Where, C is the curve fit equation.
the source information to about ±0.4%. Calculate ∆h¯ enthalpy change in isentropic
For the saturated temperature of the saturated compression for R134a:
pressure relationship, Antoine equation was adopted: 𝐶 𝑃 𝐶−1
𝟐𝟐𝟎𝟎.𝟗𝟖𝟎
∆h¯ = 𝐶−1 P1 V1sup({𝑃2 } 𝐶 - 1) (22)
1
Tsat = (𝟐𝟏.𝟓𝟏𝟐−𝐋𝐧𝐏 ) -246.61 (10) ∆𝐡¯
𝐬𝐚𝐭 ∆h𝒂𝒄𝒕 . = ɳ (23)
comp.
Where, temperature in (0C) and the pressure in(KPa) ɳcomp.: actual efficiency of compressor and equal
At point (3) outlet from condenser: The extend of 80%
liquid sub-cooling found by: h2 = ∆hact + h1 (24)
∆Tb = T3sat –TL (11) From the previous equations, the procedure of flow
chart for the saving simulation is shown in Figure 7.
Where: TL= T3 and T3sat is calculated from
eq.(10) at high pressure “Pcond.”.

hL3 =50952+1335.29 T3 +1.70650T23 +7.6741


*10-3T33 (12)
hL3:enthalpy of sub-cooled liquid (kJ/kg) at ∆Tb > 0
and is enthalpy of saturated liquid at ∆T b= 0.
At point (4) since the expansion is the throttling
valve:
7
Start

Input: (m.water)

Read:{ Ph“Pcond”., PL”Pevap.”,T1, T2, T3, T4, T5, T6, T7, T8,m.ref }
measured from experimental work

Calculation at point 3:
 Calculate Tsat3 from eq.(10)
 Calculate ∆Tb from eq.(11)
 Calculate hL3 from eq.(12):

Calculation at point 4:
h4=hL3

Calculation at point 1:
 Calculate T1sat from eq.(10)
 Calculate ∆TS from eq.(14)
 Calculate hv from eq.(15)
 Calculate h1from eq.(16)

Calculation at point 2:
 Calculate ῦv from eq.(17)
 Calculate V1sup from eq.(18)
 Calculate ∆Tc from eq.(19), C1from eq.(20) and C from eq.(21)
 Calculate ∆h¯ from eq.(22)
 Calculate ∆h𝒂𝒄𝒕 from eq.(23)
 Calculate h2from eq.(24)

Outputs:
 cooling capacity eq.(3)
 condenser heat capacity eq.(4)
 compressor power consumption eq.(5)
 COP eq.(7)
 ω eq.(8)
 Efficiency of vapor compression refrigeration cycle eq.(9)

End

Fig. 7: Schematic diagram describing the overall model for simple


vapor compression refrigeration system with R134a
8
V. Results and Discussion condenser heat capacity increases, COP increases
too. But cooling capacity is nearly the same at
In this area, thermodynamic performance parameters
obtained increased in COP as studied by
are computed from the experimental data using
Yeunyongkul et al.[28] .Therefore, in this case,
refrigerant R134a by utilizing the different equations
when consider in (equation 7), it was found that the
(2-24) and discussed. The outcomes acquired from
compressor work decreases, resulting in the increase
this research may vary slightly relying on the
in COP with remaining the cooling capacity nearly
refrigerant charge, experimental and the
constant.
environmental conditions. Performance parameters
of the vapor compression refrigeration system, for
example, genuine work of compressor, coefficient 24.5
of performance, cooling capacity and condenser
capacity were analysis for various volumetric flow 24
rate of water inlet to the condenser that using R134a.
Many investigations are executed into performance 23.5
analysis of the vapor compression refrigeration 23
system. But a limited research is implemented for

Q˙cond (kW)
effect of volumetric or mass flow rate of the 22.5
secondary fluid in condenser on the refrigeration
system. Some researchers such as Dalkilic and 22
Wongwises [24] and Elsayed and Hariri [25]
21.5
studied the effect of air mass flow rate in shell
evaporator on the heat pump system. 21
The numerical results of the obtained simulation are
presented in a graphical form, as shown in Figures 20.5
8-14.
It was seen that for the same inlet temperature 20
(Tin,cond.) of water which the condenser secondary 0 0.005 0.01 0.015
fluid, as the water mass flow rate (m.w) increases, the m˙water(kg/sec)
condenser heat capacity (Q.cond.) increased due to
increase water mass flow rate as seen from Figure 8.
Figure 9 shows the COP (coefficient of
performance) variation with respect to the condenser Fig. 8: Variation of condenser heat capacity at
heat capacity. As the cooling capacity (Q.evap) was different water mass flow rate
the constant. It was observed that as, the condenser
heat capacity increases, coefficient of performance
increased as studied by Maruthi et al. [11] , Bhatkar
et al.[18]and Saidur et al.[26] . Figure 10 and
Figure 11 show the effect of variation of condenser 8
heat capacity on system temperatures. Tin,cond.(T5),
Tin,evap.(T7), Tout,cond.(T6) and Tout,evap.(T8) data are 7.5
independent of refrigerant temperature in two heat
exchangers. The temperature (T6) gradient outlet 7
from condenser increases with increases in
condenser heat capacity as shown in Figure 10. But 6.5
there is a slight change in temperature of air outlet
COP

from evaporator (T8 ) with variation for condenser 6


heat capacity as shown in Figure 11. Variation of
condenser pressure (Ph) and evaporator pressure (PL) 5.5
with condenser heat capacity is shown in Figure
12.The condenser pressure decreases whereas 5
evaporator pressure increases with increase in
condenser heat capacity. The results show the same 4.5
trend as obtained by Akintunde et al.[27]. Figure 13
pointed out that as the pressure drop between 4
condenser and evaporator increases for same cooling 20 21 22 23 24 25
capacity (Q.evap) of the system , the work of Q·cond (KW)
compression increases due to decreased condenser
heat capacity (refer Figure 12). Figure 14 shows the
COP variation with respect to the rate of heat
transfer in (kW).As the compressor work
consumption reduced thus COP increases. And when Fig. 9: Variation of coefficient of performance
at different condenser heat capacity
9
50 20 evap.press.(bar)
T in (0C)
45 18
cond.press.(bar)
T cond.(0C)
16
40
14
35 12

P (bar)
T(°C)

10
30
8
25 6
4
20
2
15 0
20 21 22 23 24 25 20 21 22 23 24 25
Q·cond (kW) Q· cond (kW)

Fig.10: Variation of water inlet &outlet Fig.12: Variation of condenser pressure &
temperatures about condenser vs. condenser evaporator pressure vs. condenser heat
heat capacity capacity

25
6

23
5.5

21
5
T in evap(0C)
W·comp (kW)
T ( °C)

19
Tevap(0C) 4.5

17
4
15
3.5
13
20 21 22 23 24 25 3
Q·cond (kW) 5 10 15 20
∆P (bar)

Fig.11: Variation of air inlet &outlet Fig.13: Variation of compressor power


temperatures about evaporator vs. condenser consumption with pressure drop between
heat capacity condenser & evaporator

10
value of the range that used to improve the
30 condenser heat capacity and coefficient of
performance of the system.
25 5) A validation of the model was carried out
by a comparison between experimental
20 information and model yields. The
Q.EVAP outcomes were demonstrating a comparison
between measured mass flow rate values of
Q· (kW)

15 Q.COND refrigerant R134a and those obtained with


the circulation rate of refrigerant that
WCOMP determined from the rate of heat absorption
10 in the evaporator. It is observed that a good
fit with relative error estimations that differ
within±10%.
5

0 Acknowledgments
5 6 7 8
COP Dr. Shurooq T. Al-Hemeri thankful to the
department of chemical engineering /University of
Technology for providing Laboratory of
thermodynamic and Dr. Zaidoon Mohsen Shakor
Fig.14: Comparison of different power Q.evap.
their help during this study.
, Q.cond. , W.comp. vs. coefficient of
performance References:

1] Calm,J.,” The next generation of refrigerants-


VI. Conclusions
This experimental study and the mathematical review and considerations”, International journal of
model investigated the effect of the changing the refrigeration 2008,31,pp.1123-1133.
water volumetric flow rate (16-40 )L/hr or by the 2]Liopis R., Cabello R., Torrella E.,”A dynamic
mass flow rate (15.8 to 39.6 )kg/hr.The working model of a shell and tube condenser operating in a
fluid in the refrigeration system is R134a. From this vapor compression refrigeration plant”,
study the following conclusion is deduced:-
International journal of thermal sciences 2008 ,47,
1) The present study is allocated to develop a pp. 926-934.
physical model that permits clarification the 3]Ye Y.,Weiwei W.,Mengwei H.,”A state-space
energy conduct of a vapor compression dynamic model for vapor compression refrigeration
system utilizing input parameters that can system based on moving-boundary formulation”,
be easily acquired from experimental work. International journal of refrigeration 2015,60,pp.1-
2) Based on the simulation of the refrigeration 16.
system, it can be said that the refrigeration
4] Suresh B. and Satyanarayana V., ”Improving and
system performance is improved by
bringing down the power consumption for comparing the coefficient of performance of
compressor, increasing the rejection of domestic refrigerator by using refrigerants R134a
condenser heat capacity or decreasing the and R600a”, International journal of scientific
pressure difference amongst condenser and research and management studies2014,8,pp.267-
evaporator. 277.
3) The mass flow rate of water, which is the 5]Mishra R., ”Thermodynamic performance
secondary fluid in condenser are need to be
evaluation of multi-evaporators single compressor
considered in selecting the condenser, since
it effect on the condenser heat capacity for in vapor compression refrigeration systems for
vapor compression refrigeration system. reducing ozone depletion”, International journal of
4) Given the requirement for energy advance research and innovation 2014,2,pp.325-
preservation, it is desirable to enhance the 332.
execution of vapor compression system 6]Neeraj U., ”To study the effect of sub-cooling and
presenting new parameter designs and
diffuser on the coefficient of performance of vapor
additionally applying a proficient operation.
In this way, a mass flow rate of water of the compression refrigeration system”, International
refrigeration system can be used at higher

11
journal of research in aeronautical and mechanical 18]Bhatkar V., Kriplani V., Awari G.,
engineering 2015,6,pp.14-44. ”Experimental performance of R134a and R152a
7]Arora A. and Kanshik S., ”Theoretical analysis of using microchannel condenser”, Journal of thermal
vapor compression refrigeration system with engineering 2015,7,pp.575-582.
R502,R404a and R507a”, International journal of 19] Sandip P., Chavhan S., Mahajan D.,”
refrigeration 2008,31,pp.998-1005. Experimental performance evaluation of R152a to
8]Vaibhav J., Kachhwaha S., Mishra R., replace R134a in vapour compression refrigeration
system”, International journal of modern
”Comparative performance study of of vapor
engineering research 2015, 5 ,pp. 37-47.
compression refrigeration system with 20]Guo L., ”Recent developments in simulation
R22/R134a/R410a/R407c/M20”, International techniques for vapor compression refrigeration
journal of energy and environment 2011,2,pp.297- systems”, International journal of refrigeration
310. 2007,30,pp.1119-1133.
9]Gustavo P., ”Effect of condenser sub-cooling on 21] Lima R.and Seixlack A., "Modeling of wire-on-
the performance of vapor compression refrigeration tube condensers for domestic refrigerators ", 13 th
systems: experimental and numerical investigation”, Brazilian congress of thermal sciences and
International refrigeration and air conditioning engineering 2010.
conference at Puradue,July16-19,2012. 22]Cleland A., ”Polynomial curve-fit for refrigerant
10]Belman J., Ledesma S., Garcia J., ”Analysis of a thermodynamic properties: extension to include
variable speed vapor compression system using R134a”, International journal of refrigeration
artificial neural networks”, Expert systems with 2000,17,pp.245-249.
applications2013,40,4362-4369. 23]Wang K., Ding G., Fukaya M., ”Extension of the
11]Maruthi G., Rajendra P., Veeresh G.," applicable range of the implicit curve-fitting method
Experimental analysis of vapor compression for refrigerant thermodynamic properties to critical
refrigeration system with liquid line suction heat pressure”, International journal of refrigeration
exchanger by using R134a and R404a”, 2007,3,pp.418-432.
International journal of scientific research and 24]Dalkilic A., Wongwises S.,”A performance
management studies2014,12,pp.382-395. comparison of vapor compression refrigeration
12]Mitesh M., Deshmukh K., Mali V.,” system using various alternative refrigerants”,
Performance comparison of R22 refrigerant with International communication in heat and mass
alternative hydrocarbon refrigerants” International transfer 2013,37,pp.1340-1349.
journal on theoretical and applied research in 25]Elsayed A., Hariri A., ”Effect of condenser air
mechanical engineering 2015,2,pp.17-21. flow on the performance of split air
13]Kedarnath B. and Patil U.,” Performance conditioner”,World renewable energy congress,
enhancement of vapor compression refrigeration Sweden 2011,pp.2134-2141.
system using nano-fluids: a review”, International 26]Saidur H., Ahmed J., Masjuk H.,
journal of research in aeronautical and mechanical ”Thermodynamic performance analysis of R-600
engineering 2016,1,pp.56-63. and R-600a as refrigerant”, Engineering e-
14]Santa R. and Garbai L.,” The mathematical transaction,1,2015.
model and numerical simulation of the heat pump 27]Akintunde M., Falade T., Bolaji
system”, International journal of engineering-annals B.,”Comparative analysis of performance of three
of faculty engineering hunedoara 2013,4,pp.271- ozone friendly refrigerants in vapor compression
280. refrigerator”, Journal of sustainable energy and
15]Koury R., Machado L., Ismail K., ”Numerical environment 2015,2,pp.61-64.
simulation of a variable speed refrigeration system”, 28] Yeunyongkul P., Sakulchangsatjatai P.,
International journal of refrigeration Terdtoon P., ”Mathematical model of the optimum
2010,24,pp.192-200. heat pipe heat exchanger for a condenser of vapor
16]Jong w., Gilbong L., Min S.,”Numerical study compression refrigeration cycle”, Energy research
on the steady state and transient performance of a Journal 2012,2,pp.104-110.
multi-type heat pump system”, International journal
of refrigeration 2014,34,pp.1157-1172.
17]Sivak P. and Hroncova D., ”State-space model of
a mechanical system in MATLAB/ Simulink”,
Procedia engineering 2015,48,pp.629-635.

12
Sh.T.Al-Hemeri: Shurooq.
Talib Remedhan Al-Hemeri, PhD in
Chemical Engineering - University of
Technology-Baghdad-Iraq. Assist professor
“lecture “ in University of Technology,
chemical engineering department..Her interests
in Thermodynamic engineering ”Refrigeration
system”, Phase change of materials”, Extraction
of organic compounds, Two-phase in bubble
column and Renewable energy.

13

You might also like