You are on page 1of 205

SINGLE

Technical
Data Book
SINGLE for South East Asia
(R410A, Cooling Only)

Model : AC***TN**KC/EA (Indoor Unit), AC***TXAD*C/EA (Outdoor Unit)


 istory
H

Version Modification Date Remark


Ver.1.0 Released Single for South East Asia (R410A, Cooling Only) TDB 20.06.15

Features & Benefits
CAC

1. Top Level of EER 2. Wide Temperature Performance

Improve EER level : average 13~15% higher than Even cooling For spacious space
conventional models.

3. Universal Outdoor Unit 4. NASA communication

Universal outdoor unit makes more efficient More compatibility with new controllers.
stock management.
Nomenclature
Indoor Unit

Model Name

AC 052 T N 4 D K C EA
(1) (2) (3) (4) (5) (6) (7) (8) Buyer

(1) Classification (5) Product Notation

AC CAC 1 Way Cassette


1
Wind-Free 1Way Cassette
4 Way Cassette (600x600)
N
Wind-Free 4 Way Cassette (600x600)
(2) Capacity 4 Way Cassette, 360 Cassette
4
x 1/10 kW (3 digits) Wind-Free 4 Way Cassette
L LSP Duct
M MSP Duct
C Ceiling
J Console
(3) Version
A A3050 (Wall Mounted)
N 2018 T MAX (Wall Mounted)
R 2019 X Wind-Free™ (Wall Mounted)
T 2020

(6) Feature

(4) Product Type F Flagship


S Standard
N Indoor Unit
D Deluxe
X Outdoor Unit
P Premium

(7) Rating Voltage

K 1Ф, 220~240V, 50Hz

(8) Mode

C Cooling Only (R410A)


Nomenclature
Outdoor Unit

Model Name

AC 052 T X A D K C EA
(1) (2) (3) (4) (5) (6) (7) (8) Buyer

(1) Classification (5) Product Notation

AC CAC A, 1 Inv+Side+General Temp

(6) Feature
(2) Capacity
F Flagship
X 1/10 kW (3 digits) S Standard
D Deluxe
P Premium

(3) Version

T 2020
(7) Rating Voltage

K 1Ф, 220~240V, 50Hz


N 3Ф, 380~415V, 50Hz

(4) Product Type

N Indoor Unit
X Outdoor Unit (8) Mode

C Cooling Only (R410A)


Line-up
Indoor unit

Capacity (kW)
Model
3.5 5.2 7.1 10.0 12.0 14.0 16.0
Wind-
Free 1Way
Cassette

Wind-
Free 4Way
Cassett

360 Cassette

Duct

Ceiling
Line-up
Outdoor Unit

Capacity (kW)
Model
3.5 5.2 7.1 10.0 12.0 / 14.0 16.0

1Phase

3Phase
Contents

Wind-Free 1Way Cassette 9


Wind-Free 4Way Cassette 22
360 Cassette 44
73
Ceiling 110
Outdoor Units 141
Installation 170
 ind-Free 1Way Cassette
W

1. Specification 11
2. Summary Table 14
3. Capacity Table 15
4. Dimensional Drawing 16
5. Center of Gravity 18
6. Electrical Wiring Diagram 19
7. Sound Data 20
8. Temperature and airflow distribution 21

Features & Benefits
Wind-Free 1Way Cassette

1. Wind-Free cooling 3. Even cooling

Comfort wind implementation by Wind-Free cooling Even cooling For spacious space

Kitchen

Micro hole

Living room

※ Wind-Free implementation : Still air by the velocity of


flow below 0.15m/s.
※ Expand the blade angle from 30˚ to 80˚
Conventional product (Samsung) : 40~80 ˚
2. Big blade

Max. 5.5m Horizontal reach

Conventional

68 mm

Wind-Free

100 mm
5.5m

0.6m

※ Reach : 5.5m (Height 0.6m, Wind speed 0.3m/s)


Conventional product (Samsung) : 3m
※ Based on Wind-Free 1Way 3.5kW
1. Specification
Wind-Free 1Way Cassette

System Indoor Unit AC035TN1DKC/EA AC052TN1DKC/EA AC071TN1DKC/EA


Model Name
Outdoor Unit AC035TXADKC/EA AC052TXADKC/EA AC071TXADKC/EA
Mode - Cooling only Cooling only Cooling only
kW 1.0 / 3.5 / 4.1 1.5 / 5.0 / 6.0 1.8 / 6.1 / 7.8
Cooling
Capacity Btu/h 3,410/12,000/13,990 5,120/17,000/20,470 6,140/21,000/26,610
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.24/1.045/1.5 0.3/1.47/2.1 0.4/1.97/3.6
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 1.6/5.4/7.5 1.7/7.1/9.5 2.3/9.3/16.0
Power
(Min/Std/Max) Heating A - - -
MCA A 11.5 21.5 21.5
Current
MFA A 12.7 25.0 25.0
EER Cooling - 3.35 3.40 3.10
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 9.52 (3/8) 12.7 (1/2) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 20 30 50
(ODU-IDU) Elevation m 15 20 30
Chargeless m 20 5 5
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 1.05 1.30 2.00
1. Specification
Wind-Free 1Way Cassette

Indoor Indoor Unit AC035TN1DKC/EA AC052TN1DKC/EA AC071TN1DKC/EA


Unit Model Name
Outdoor Unit AC035TXADKC/EA AC052TXADKC/EA AC071TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Type - Crossflow Fan Crossflow Fan Crossflow Fan
Quantity EA 1 1 1
m³/min 9.0/8.2/7.2 14.0/13.0/12.0 15.0/14.0/12.5
Fan Air Flow Rate H/M/L
l/s 150/140/120 230/220/200 250/230/210
External mmAq - - -
Min/Std/Max
Static Pressure Pa - - -
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 27 x 1 62 x 1 62 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L/Silent dB(A) 38/35/32/27 41/38/35/29 46/42/38/30
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 9.2 13.4 13.4
External Shipping Weight kg 12 16.5 16.5
Dimension Net Dimensions (WxHxD) ㎜ 970 x 135 x 410 1,200 x 138 x 450 1,200 x 138 x 450
Shipping Dimensions (WxHxD) ㎜ 1,173 x 231 x 487 1,435 x 224 x 525 1,435 x 224 x 525
Casing Material - ABS ABS ABS
Model Name - PC1NWFMAN PC1BWFMAN PC1BWFMAN
Type - Wind-Free Type Wind-Free Type Wind-Free Type
Material - HIPS HIPS HIPS
Color - White White White
Panel (1)
Net Weight kg 4.3 5.0 5.0
Shipping Weight kg 6.3 7.0 7.0
Net Dimensions (WxHxD) ㎜ 1,198 x 35 x 500 1,410 x 35 x 500 1,410 x 35 x 500
Shipping Dimensions (WxHxD) ㎜ 1,262 x 122 x 566 1,474 x 122 x 566 1,474 x 122 x 566
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - Included Included Included
Drain Pump Max. lifting Height
㎜ / Liter/h 750/24 750/24 750/24
/ Displacement
External
- - - -
Model
Internal
- - - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - - -
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - - - -
1. Specification
Wind-Free 1Way Cassette

Outdoor Indoor Unit AC035TN1DKC/EA AC052TN1DKC/EA AC071TN1DKC/EA


Unit Model Name
Outdoor Unit AC035TXADKC/EA AC052TXADKC/EA AC071TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophille Anti-Corrosion Anti-Corrosion
Model Name UG9AJ3090FER UG9TK3150FE4 UG8T265FXAEW
Type - Single BLDC Twin BLDC Twin BLDC
Compressor Output kW 0.83 1.42 2.32
Type - POE POE POE
Oil
Initial charge cc 320 500 700
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 1 1
m³/min 40 50 60
Air Flow Rate
l/s 670 840 1,000
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 40 x 1 125 x 1 125 x 1
Sound Pressure
Cooling dB(A) 48 50 50
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 30.0 40.5 52.5
External Shipping Weight kg 32.5 43.5 56.5
Dimension Net Dimensions (WxHxD) ㎜ 790 x 548 x 285 880 x 638 x 310 880 x 798 x 310
Shipping Dimensions (WxHxD) ㎜ 913 x 622 x 371 1,023 x 730 x 413 1,023 x 881 x 413
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
Wind-Free 1Way Cassette

Performance Characteristics

Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 4.1 - High 9.0 38
AC035TN1DKC/EA 9.2 Std. 3.5 - Mid 8.2 35
Min. 1.0 - Low 7.2 32
Max. 6.0 - High 14.0 41
AC052TN1DKC/EA 13.4 Std. 5.0 - Mid 13.0 38
Min. 1.5 - Low 12.0 35
Max. 7.8 - High 15.0 46
AC071TN1DKC/EA 13.4 Std. 6.1 - Mid 14.0 42
Min. 1.8 - Low 12.5 38

NOTE
•• Sound data is based on cooling operation.

Electric Characteristics

Model Outdoor Unit Maximum Input Current [A] Power Supply


Rated Voltage range Outdoor Unit Indoor
Indoor Unit Outdoor Unit Total MCA MFA
Hz Volts Min. Max. Cooling Heating Unit
AC035TN1DKC/EA AC035TXADKC/EA 50 220 to 240 198 264 10.0 - 1.5 11.5 11.5 12.7
AC052TN1DKC/EA AC052TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC071TN1DKC/EA AC071TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0

NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
Wind-Free 1Way Cassette

(1) AC035TN1DKC/EA+AC035TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 3.4 2.5 0.78 3.6 2.6 0.80 3.7 2.7 0.81 3.9 2.7 0.83 3.9 2.7 0.84 4.1 2.7 0.84 4.3 2.6 0.86
21 3.3 2.4 0.82 3.4 2.5 0.84 3.6 2.5 0.85 3.7 2.6 0.87 3.7 2.6 0.88 3.9 2.6 0.89 4.1 2.5 0.91
35 3.1 2.4 0.98 3.3 2.5 1.00 3.4 2.5 1.02 3.5 2.6 1.05 3.6 2.6 1.06 3.7 2.6 1.07 3.9 2.5 1.09
46 2.6 2.1 0.92 2.8 2.2 0.94 2.9 2.3 0.96 3.0 2.3 0.98 3.0 2.3 0.99 3.2 2.3 1.00 3.3 2.2 1.02
48 2.3 1.9 0.87 2.4 2.0 0.89 2.5 2.0 0.91 2.8 2.2 0.93 2.7 2.1 0.94 2.8 2.0 0.95 3.0 2.0 0.96
50 2.0 1.7 0.82 2.1 1.7 0.84 2.2 1.8 0.85 2.6 2.1 0.87 2.3 1.8 0.88 2.4 1.8 0.89 2.6 1.8 0.91

(2) AC052TN1DKC/EA+AC052TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 4.7 3.5 1.35 4.9 3.7 1.37 5.2 3.8 1.40 5.3 3.9 1.43 5.4 3.8 1.44 5.7 3.8 1.46 6.0 3.7 1.49
21 5.3 3.8 1.16 5.6 3.9 1.19 5.8 4.0 1.21 6.0 4.2 1.23 6.1 4.1 1.25 6.4 4.1 1.26 6.7 4.0 1.28
35 4.4 3.6 1.38 4.7 3.7 1.41 4.9 3.8 1.44 5.0 3.9 1.47 5.1 3.9 1.48 5.4 3.8 1.50 5.6 3.7 1.53
46 4.8 3.6 2.36 5.0 3.7 2.41 5.2 3.8 2.45 5.4 3.9 2.50 5.5 3.9 2.53 5.8 3.8 2.55 6.1 3.7 2.61
48 4.5 3.4 2.37 4.7 3.5 2.42 4.9 3.6 2.47 5.1 3.7 2.52 5.2 3.7 2.54 5.4 3.7 2.57 5.7 3.6 2.62
50 4.2 3.3 2.38 4.4 3.4 2.43 4.6 3.5 2.48 4.7 3.6 2.53 4.8 3.6 2.56 5.0 3.5 2.58 5.3 3.4 2.64

(3) AC071TN1DKC/EA+AC071TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 6.0 4.1 2.23 6.3 4.3 2.28 6.6 4.4 2.32 6.8 4.5 2.37 6.9 4.5 2.40 7.3 4.5 2.42 7.6 4.4 2.47
21 6.6 4.5 1.90 6.9 4.6 1.94 7.2 4.8 1.98 7.4 4.9 2.02 7.6 4.9 2.04 8.0 4.8 2.06 8.4 4.7 2.10
35 5.4 4.1 1.85 5.7 4.2 1.89 5.9 4.3 1.93 6.1 4.5 1.97 6.2 4.4 1.99 6.5 4.4 2.01 6.9 4.3 2.05
46 5.1 3.8 2.68 5.4 3.9 2.74 5.6 4.0 2.79 5.8 4.2 2.85 5.9 4.1 2.88 6.2 4.1 2.91 6.5 4.0 2.96
48 4.8 3.7 2.64 5.1 3.8 2.69 5.3 3.9 2.75 5.5 4.0 2.80 5.6 4.0 2.83 5.9 3.9 2.86 6.1 3.9 2.92
50 4.5 3.5 2.59 4.8 3.7 2.65 5.0 3.8 2.70 5.1 3.9 2.76 5.2 3.8 2.78 5.5 3.8 2.81 5.8 3.7 2.87

NOTE
•• The performance table shows the average value of each conditions.
4. Dimensional Drawing
Wind-Free 1Way Cassette

AC035TN1DKC/EA
Units : mm [inches]

No. Name Description


1 Gas pipe connection Φ 9.52 (3/8)
2 Liquid pipe connection Φ 6.35 (1/4)
3 Drain pipe connection VP-20 (OD26, ID20)
4 Power supply & Communication wiring conduit -
5 Air outlet louver -
6 Air inlet grille -

NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
4. Dimensional Dra
Drawing
Wind-Free 1Way Cassette

AC052TN1DKC/EA, AC071TN1DKC/EA
Units : mm [inches]

Description
No. Name
AC052TN1DKC/EA AC071TN1DKC/EA
1 Gas pipe connection Ø12.7 (1/2) 15.88 (5/8)
2 Liquid pipe connection Ø6.35 (1/4)
3 Drain pipe connection VP25 (OD 32,ID 25)
4 Power supply & Communication wiring conduit -
5 Air outlet louver -
6 Air inlet grille -

NOTE
• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
5. Center of Gravity
Wind-Free 1Way Cassette

Units : mm [inches]

Model A B C D E
1,198 500 108 555 200
AC035TN1DKC/EA
[47-3/16] [19-11/16] [4-1/2] [21-7/8] [7-7/8]
AC052TN1DKC/EA 1,410 500 108 755 200
AC071TN1DKC/EA [55-1/2] [19-11/16] [4-1/2] [29-3/8] [7-7/8]
6. Electrical Wiring Diagram
Wind-Free 1Way Cassette

SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
FLOAT SWITCH Check the FLOATING S/W EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)

NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
Wind-Free 1Way Cassette

Sound Pressure level


Unit: dB(A)
Model HIGH MID LOW Silent
AC035TN1DKC/EA 38 35 32 27
AC052TN1DKC/EA 41 38 35 29
AC071TN1DKC/EA 46 42 38 30

• NC Curve
1) AC035TN1DKC/EA 2) AC052TN1DKC/EA

2) AC071TN1DKC/EA

NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
8. Temperature and airflow distribution
Wind-Free 1Way Cassette

AC035TN1DKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)

AC052TN1DKC/EA
• •Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)

AC071TN1DKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
Wind-Free 4Way Cassette

1. Specification 24
2. Summary Table 33
3. Capacity Table 34
4. Dimensional Drawing 36
5. Center of Gravity 38
6. Electrical Wiring Diagram 39
7. Sound Data 40
8. Temperature and air flow distribution 42
F
 eatures & Benefits
Wind-Free 4Way Cassette

Stage a beautiful yet comfortable environment The Samsung Wind-Free 4Way Cassette indoor air
conditioning system delivers polish, comfort and
With its newly improved design, Wind-Free 4Way Cassette efficiency with features such as:
supports a clean, aesthetically appealing atmosphere and
adds a sense of sophistication to work and living spaces. • Stylishly clean design. Add panache to interior
Not only is this unit attractively designed, but it also spaces with a choice of clean, streamlined panel
uses advanced technologies to optimize comfort in any patterns in a lightweight build.
environment. • Robust operation. Control the atmosphere perfectly
with an advanced design for superior air flow and
cooling/heating performance.
• Low maintenance and simple installation. Ease
installation and minimize maintenance with a
detachable, no-drip design.

Wind-Free 4Way Cassette - Stylishly clean design

Aesthetic panel and display Neat and clean design


Wind-Free 4Way Cassette offers two different pattern The indoor Wind-Free 4Way Cassette boasts a smart
designs forthe panel. The simple display design with design that promotes a neat and clean look. The
rounded corners adds a chic sophistication to the interior. completely hermetic blade structure keeps the
indoor unit clean by preventing dust or other foreign
substances from entering it. The internal parts of the
indoor unit are also out of sight when the blade is shut,
thus improving the unit’s appearance.

Power Defrost Time Clean

11kg 17kg
1. Specification
Wind-Free 4Way Cassette

System Indoor Unit AC052TN4DKC/EA AC071TN4DKC/EA AC100TN4DKC/EA


Model Name
Outdoor Unit AC052TXADKC/EA AC071TXADKC/EA AC100TXADKC/EA
Mode - Cooling only Cooling only Cooling only
kW 1.0 / 5.0 / 6.0 2.2 / 7.1 / 8.5 3.0 / 10.0 / 12.0
Cooling
Capacity Btu/h 3,410/17,000/20,470 7,510/24,000/29,000 10,240/34,000/40,940
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.33/1.41/2.1 0.35/2.185/3.6 0.6/3.125/4.7
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 1.5/6.7/9.5 2.0/10.1/16.0 3.0/14.8/20.4
Power
(Min/Std/Max) Heating A - - -
MCA A 21.5 21.5 26.0
Current
MFA A 25.0 25.0 30.0
EER Cooling - 3.55 3.25 3.20
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 6.35 (1/4) 6.35 (1/4) 9.52 (3/8)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 12.7 (1/2) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 30 50 50
(ODU-IDU) Elevation m 20 30 30
Chargeless m 5 5 30
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 1.30 2.00 3.00
1. Specification
Wind-Free 4Way Cassette

Indoor Indoor Unit AC052TN4DKC/EA AC071TN4DKC/EA AC100TN4DKC/EA


Unit Model Name
Outdoor Unit AC052TXADKC/EA AC071TXADKC/EA AC100TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Type - Turbo Fan Turbo Fan Sirocco
Quantity EA 1 1 1
m³/min 16.9/15.9/14.9 20.8/17.8/14.8 30.3/24.3/19.4
Fan Air Flow Rate H/M/L
l/s 280/270/250 350/300/250 510/410/320
External mmAq - - -
Min/Std/Max
Static Pressure Pa - - -
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 65 x 1 65 x 1 97 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 35/33/31 40/36/32 43/38/33
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 14.5 14.5 20
External Shipping Weight kg 17.5 17.5 23.5
Dimension Net Dimensions (WxHxD) ㎜ 840 x 204 x 840 840 x 204 x 840 840 x 288 x 840
Shipping Dimensions (WxHxD) ㎜ 898 x 275 x 898 898 x 275 x 898 898 x 357 x 898
Casing Material - Polypropylene Polypropylene Polypropylene
Model Name - PC4NUFMAN PC4NUFMAN PC4NUFMAN
Type - Wind-Free Type Wind-Free Type Wind-Free Type
Material - HIPS HIPS HIPS
Color - DA White DA White DA White
Panel (1)
Net Weight kg 6.3 6.3 6.3
Shipping Weight kg 8.7 8.7 8.7
Net Dimensions (WxHxD) ㎜ 950 x 48 x 950 950 x 48 x 950 950 x 48 x 950
Shipping Dimensions (WxHxD) ㎜ 1,010 x 117 x 1,000 1,010 x 117 x 1,000 1,010 x 117 x 1,000
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - Included Included Included
Drain Pump Max. lifting Height
㎜ / Liter/h 750/24 750/24 750/24
/ Displacement
External
- - - -
Model
Internal
- - - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - - -
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - Optional Optional Optional
1. Specification
Wind-Free 4Way Cassette

Outdoor Indoor Unit AC052TN4DKC/EA AC071TN4DKC/EA AC100TN4DKC/EA


Unit Model Name
Outdoor Unit AC052TXADKC/EA AC071TXADKC/EA AC100TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG9TK3150FE4 UG8T265FXAEW UG8T300FUBJU
Type - Twin BLDC Twin BLDC Twin BLDC
Compressor Output kW 1.42 2.32 2.82
Type - POE POE POE
Oil
Initial charge cc 500 700 1200
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 1 1
m³/min 50 60 76
Air Flow Rate
l/s 840 1,000 1,270
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 125 x 1 125 x 1 125 x 1
Sound Pressure
Cooling dB(A) 50 50 53
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 40.5 52.5 71.0
External Shipping Weight kg 43.5 56.5 76.0
Dimension Net Dimensions (WxHxD) ㎜ 880 x 638 x 310 880 x 798 x 310 940 x 998 x 330
Shipping Dimensions (WxHxD) ㎜ 1,023 x 730 x 413 1,023 x 881 x 413 995 x 1,096 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Wind-Free 4Way Cassette

System Indoor Unit AC100TN4DKC/EA AC120TN4DKC/EA AC120TN4DKC/EA


Model Name
Outdoor Unit AC100TXADNC/EA AC120TXADKC/EA AC120TXADNC/EA
Mode - Cooling only Cooling only Cooling only
kW 3.0 / 10.0 / 12.0 3.5 / 12.1 / 14.0 3.5 / 12.1 / 14.0
Cooling
Capacity Btu/h 10,240/34,000/40,940 11,940/41,500/47,770 11,940/41,500/47,770
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.6/3.125/4.7 0.8/3.67/5.3 0.8/3.67/5.5
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 1.5/5.2/7.1 3.7/16.7/23.0 2.1/5.9/8.8
Power
(Min/Std/Max) Heating A - - -
MCA A 18.1 34.0 18.1
Current
MFA A 18.1 40.0 18.1
EER Cooling - 3.20 3.30 3.30
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 50 75 75
(ODU-IDU) Elevation m 30 30 30
Chargeless m 30 30 30
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 3.00 3.40 3.40
1. Specification
Wind-Free 4Way Cassette

Indoor Indoor Unit AC100TN4DKC/EA AC120TN4DKC/EA AC120TN4DKC/EA


Unit Model Name
Outdoor Unit AC100TXADNC/EA AC120TXADKC/EA AC120TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Type - Sirocco Sirocco Sirocco
Quantity EA 1 1 1
m³/min 30.3/24.3/19.4 31.5/25.5/20.5 31.5/25.5/20.5
Fan Air Flow Rate H/M/L
l/s 510/410/320 530/430/340 530/430/340
External mmAq - - -
Min/Std/Max
Static Pressure Pa - - -
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 97 x 1 97 x 1 97 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 43/38/33 44/40/35 44/40/35
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 20 20 20
External Shipping Weight kg 23.5 23.5 23.5
Dimension Net Dimensions (WxHxD) ㎜ 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840
Shipping Dimensions (WxHxD) ㎜ 898 x 357 x 898 898 x 357 x 898 898 x 357 x 898
Casing Material - Polypropylene Polypropylene Polypropylene
Model Name - PC4NUFMAN PC4NUFMAN PC4NUFMAN
Type - Wind-Free Type Wind-Free Type Wind-Free Type
Material - HIPS HIPS HIPS
Color - DA White DA White DA White
Panel (1)
Net Weight kg 6.3 6.3 6.3
Shipping Weight kg 8.7 8.7 8.7
Net Dimensions (WxHxD) ㎜ 950 x 48 x 950 950 x 48 x 950 950 x 48 x 950
Shipping Dimensions (WxHxD) ㎜ 1,010 x 117 x 1,000 1,010 x 117 x 1,000 1,010 x 117 x 1,000
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - Included Included Included
Drain Pump Max. lifting Height
㎜ / Liter/h 750/24 750/24 750/24
/ Displacement
External
- - - -
Model
Internal
- - - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - - -
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - Optional Optional Optional
1. Specification
Wind-Free 4Way Cassette

Outdoor Indoor Unit AC100TN4DKC/EA AC120TN4DKC/EA AC120TN4DKC/EA


Unit Model Name
Outdoor Unit AC100TXADNC/EA AC120TXADKC/EA AC120TXADNC/EA
Power Supply Ø, #, V, Hz 3,4,380-415,50 1,2,220-240,50 3,4,380-415,50
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG8T300FUCJU UG5TK1450FJX UG5TK1450FJX
Type - Twin BLDC Twin BLDC Twin BLDC
Compressor Output kW 2.82 4.19 4.19
Type - POE POE POE
Oil
Initial charge cc 1200 1700 1700
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 2 2
m³/min 76 110 110
Air Flow Rate
l/s 1,270 1,840 1,840
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 125 x 1 125 x 2 125 x 2
Sound Pressure
Cooling dB(A) 53 53 53
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 71.0 86.5 86.5
External Shipping Weight kg 76.0 96.5 96.5
Dimension Net Dimensions (WxHxD) ㎜ 940 x 998 x 330 940 x 1,210 x 330 940 x 1,210 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,096 x 426 995 x 1,388 x 426 995 x 1,388 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Wind-Free 4Way Cassette

System Indoor Unit AC140TN4DKC/EA AC140TN4DKC/EA


Model Name
Outdoor Unit AC140TXADKC/EA AC140TXADNC/EA
Mode - Cooling only Cooling only
kW 3.5 / 13.4 / 15.5 3.5 / 13.4 / 15.5
Cooling
Capacity Btu/h 11,940/45,500/52,890 11,940/45,500/52,890
Performance
(Min/Std/Max) kW - -
Heating
Btu/h - -
Power Input Cooling kW 0.8/4.42/6.4 0.8/4.42/6.4
(Min/Std/Max) Heating kW - -
Current Input Cooling A 3.7/20.4/28.0 2.1/7.1/9.5
Power
(Min/Std/Max) Heating A - -
MCA A 34.0 18.1
Current
MFA A 40.0 18.1
EER Cooling - 3.03 3.03
Efficiency
COP Heating - - -
Type Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5
Piping length Max. m 75 75
(ODU-IDU) Elevation m 30 30
Chargeless m 30 30
Wiring Min. ㎟ 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2
Type - R410A R410A
Refrigerant
Factory Charging kg 3.40 3.40
1. Specification
Wind-Free 4Way Cassette

Indoor Indoor Unit AC140TN4DKC/EA AC140TN4DKC/EA


Unit Model Name
Outdoor Unit AC140TXADKC/EA AC140TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile
Type - Sirocco Sirocco
Quantity EA 1 1
m³/min 31.5/26.7/21.8 31.5/26.7/21.8
Fan Air Flow Rate H/M/L
l/s 530/450/360 530/450/360
External mmAq - -
Min/Std/Max
Static Pressure Pa - -
Type - BLDC BLDC
Fan Motor
Output Wxn 97 x 1 97 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 44/41/37 44/41/37
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 20 20
External Shipping Weight kg 23.5 23.5
Dimension Net Dimensions (WxHxD) ㎜ 840 x 288 x 840 840 x 288 x 840
Shipping Dimensions (WxHxD) ㎜ 898 x 357 x 898 898 x 357 x 898
Casing Material - Polypropylene Polypropylene
Model Name - PC4NUFMAN PC4NUFMAN
Type - Wind-Free Type Wind-Free Type
Material - HIPS HIPS
Color - DA White DA White
Panel (1)
Net Weight kg 6.3 6.3
Shipping Weight kg 8.7 8.7
Net Dimensions (WxHxD) ㎜ 950 x 48 x 950 950 x 48 x 950
Shipping Dimensions (WxHxD) ㎜ 1,010 x 117 x 1,000 1,010 x 117 x 1,000
Control Infrared remote control - AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N
Drain Pump - Included Included
Drain Pump Max. lifting Height
㎜ / Liter/h 750/24 750/24
/ Displacement
External
- - -
Model
Internal
- - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - -
Displacement
Air Filter - Removable / Washable Removable / Washable
Virus Doctor - Optional Optional
1. Specification
Wind-Free 4Way Cassette

Outdoor Indoor Unit AC140TN4DKC/EA AC140TN4DKC/EA


Unit Model Name
Outdoor Unit AC140TXADKC/EA AC140TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 3,4,380-415,50
Type - Fin & Tube Fin & Tube
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion
Model Name UG5TK1450FJX UG5TK1450FJX
Type - Twin BLDC Twin BLDC
Compressor Output kW 4.19 4.19
Type - POE POE
Oil
Initial charge cc 1700 1700
Type - Propeller Propeller
Discharge direction - Front Front
Fan Quantity EA 2 2
m³/min 110 110
Air Flow Rate
l/s 1,840 1,840
Type - BLDC BLDC
Fan Motor
Output Wxn 125 x 2 125 x 2
Sound Pressure
Cooling dB(A) 54 54
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 86.5 86.5
External Shipping Weight kg 96.5 96.5
Dimension Net Dimensions (WxHxD) ㎜ 940 x 1,210 x 330 940 x 1,210 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,388 x 426 995 x 1,388 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50
Temp. Range Heating ℃ - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
Wind-Free 4Way Cassette

Performance Characteristics
Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 6.0 - High 16.9 35
AC052TN4DKC/EA 14.5 Std. 5.0 - Mid 15.9 33
Min. 1.0 - Low 14.9 31
Max. 8.5 - High 20.8 40
AC071TN4DKC/EA 14.5 Std. 7.1 - Mid 17.8 36
Min. 2.2 - Low 14.8 32
Max. 12.0 - High 30.3 43
AC100TN4DKC/EA 20.0 Std. 10.0 - Mid 24.3 38
Min. 3.0 - Low 19.4 33
Max. 14.0 - High 31.5 44
AC120TN4DKC/EA 20.0 Std. 12.1 - Mid 25.5 40
Min. 3.5 - Low 20.5 35
Max. 15.5 - High 31.5 44
AC140TN4DKC/EA 20.0 Std. 13.4 - Mid 26.7 41
Min. 3.5 - Low 21.8 37

NOTE
•• Sound data is based on cooling operation.

Electric Characteristics
Model Outdoor Unit Maximum Input Current [A] Power Supply
Rated Voltage range Outdoor Unit Indoor
Indoor Unit Outdoor Unit Total MCA MFA
Hz Volts Min. Max. Cooling Heating Unit
AC052TN4DKC/EA AC052TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC071TN4DKC/EA AC071TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC100TN4DKC/EA AC100TXADKC/EA 50 220 to 240 198 264 24.0 - 2.0 26.0 26.0 30.0
AC100TN4DKC/EA AC100TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
AC120TN4DKC/EA AC120TXADKC/EA 50 220 to 240 198 264 32.0 - 2.0 34.0 34.0 40.0
AC120TN4DKC/EA AC120TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
AC140TN4DKC/EA AC140TXADKC/EA 50 220 to 240 198 264 32.0 - 2.0 34.0 34.0 40.0
AC140TN4DKC/EA AC140TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1

NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
Wind-Free 4Way Cassette

(1) AC052TN4DKC/EA+AC052TXADKC/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 5.1 4.3 1.18 5.4 4.4 1.20 5.6 4.5 1.23 5.8 4.7 1.25 5.9 4.6 1.27 6.2 4.6 1.28 6.5 4.5 1.30
21 5.4 4.4 1.12 5.7 4.5 1.15 5.9 4.7 1.17 6.1 4.8 1.19 6.2 4.7 1.20 6.5 4.7 1.22 6.8 4.6 1.24
35 4.4 3.9 1.33 4.7 4.1 1.35 4.9 4.2 1.38 5.0 4.2 1.41 5.1 4.3 1.42 5.4 4.2 1.44 5.6 4.1 1.47
46 5.0 4.2 2.37 5.3 4.3 2.42 5.5 4.5 2.47 5.7 4.6 2.52 5.8 4.6 2.55 6.1 4.5 2.57 6.4 4.4 2.62
48 4.7 4.1 2.43 5.0 4.2 2.48 5.2 4.3 2.53 5.4 4.5 2.58 5.5 4.4 2.60 5.7 4.4 2.63 6.0 4.3 2.68
50 4.5 4.0 2.48 4.7 4.1 2.53 4.9 4.2 2.58 5.0 4.4 2.63 5.2 4.3 2.66 5.4 4.3 2.69 5.7 4.2 2.74

(2) AC071TN4DKC/EA+AC071TXADKC/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 6.9 5.2 2.19 7.3 5.4 2.23 7.6 5.6 2.28 7.8 5.7 2.33 8.0 5.7 2.35 8.4 5.6 2.37 8.8 5.5 2.42
21 8.1 5.9 2.14 8.6 6.1 2.19 8.9 6.2 2.23 9.2 6.4 2.28 9.4 6.4 2.30 9.9 6.3 2.32 10.4 6.2 2.37
35 6.3 5.1 2.06 6.6 5.2 2.10 6.9 5.4 2.14 7.1 5.6 2.19 7.2 5.5 2.21 7.6 5.5 2.23 8.0 5.3 2.27
46 6.0 4.9 2.71 6.3 5.0 2.77 6.6 5.2 2.82 6.8 5.4 2.88 7.0 5.3 2.91 7.3 5.3 2.94 7.7 5.2 3.00
48 5.6 4.7 2.64 5.9 4.9 2.70 6.2 5.0 2.75 6.4 5.2 2.81 6.5 5.1 2.84 6.8 5.1 2.87 7.2 5.0 2.92
50 5.3 4.6 2.58 5.5 4.7 2.63 5.8 4.8 2.68 5.9 5.0 2.74 6.1 4.9 2.76 6.4 4.9 2.79 6.7 4.8 2.85

(3) AC100TN4DKC/EA+AC100TXAD*C/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 9.7 7.8 2.46 10.2 8.1 2.51 10.7 8.3 2.56 11.0 8.6 2.61 11.2 8.5 2.64 11.8 8.4 2.66 12.4 8.2 2.71
21 10.5 8.1 2.44 11.0 8.3 2.49 11.5 8.6 2.54 11.8 8.8 2.59 12.1 8.8 2.61 12.7 8.7 2.64 13.3 8.5 2.69
35 8.8 7.3 2.94 9.3 7.5 3.00 9.7 7.8 3.06 10.0 8.0 3.13 10.2 7.9 3.16 10.7 7.9 3.19 11.2 7.7 3.25
46 7.6 6.6 3.45 8.0 6.8 3.52 8.3 7.0 3.59 8.6 7.2 3.66 8.8 7.2 3.70 9.2 7.1 3.74 9.7 7.0 3.81
48 7.1 6.5 3.20 7.5 6.7 3.26 7.8 6.9 3.33 8.1 7.1 3.40 8.2 7.0 3.43 8.6 7.0 3.47 9.1 6.8 3.54
50 6.7 6.4 2.95 7.0 6.6 3.01 7.3 6.8 3.07 7.6 7.0 3.13 7.7 6.9 3.16 8.1 6.9 3.20 8.5 6.7 3.26

NOTE
•• The performance table shows the average value of each conditions.
3. Capacity Table
Wind-Free 4Way Cassette

(4) AC120TN4DKC/EA+AC120TXAD*C/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 11.8 8.9 2.64 12.4 9.2 2.70 12.9 9.4 2.75 13.3 9.7 2.81 13.6 9.6 2.84 14.3 9.5 2.86 15.0 9.4 2.92
21 11.2 8.5 2.78 11.8 8.7 2.84 12.3 9.0 2.90 12.7 9.3 2.96 13.0 9.2 2.99 13.6 9.1 3.01 14.3 8.9 3.08
35 10.7 8.2 3.45 11.3 8.5 3.52 11.7 8.7 3.60 12.1 9.0 3.67 12.3 8.9 3.71 13.0 8.8 3.74 13.6 8.7 3.82
46 9.3 8.1 3.13 9.8 8.3 3.19 10.2 8.6 3.26 10.5 8.8 3.33 10.7 8.8 3.36 11.3 8.7 3.39 11.8 8.5 3.46
48 8.3 7.3 2.96 8.7 7.6 3.02 9.1 7.8 3.08 9.4 8.0 3.14 9.6 8.0 3.17 10.0 7.9 3.20 10.5 7.7 3.27
50 7.3 6.6 2.78 7.7 6.8 2.84 8.0 7.0 2.90 8.2 7.2 2.96 8.4 7.2 2.99 8.8 7.1 3.01 9.3 7.0 3.08

(5) AC140TN4DKC/EA+AC140TXAD*C/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 13.1 9.8 3.18 13.8 10.1 3.25 14.3 10.5 3.31 14.8 10.8 3.38 15.1 10.7 3.42 15.8 10.6 3.45 16.6 10.4 3.52
21 12.4 9.4 3.35 13.1 9.7 3.42 13.6 10.0 3.49 14.1 10.3 3.56 14.4 10.2 3.60 15.1 10.1 3.63 15.8 9.9 3.70
35 11.9 8.8 4.16 12.5 9.1 4.24 13.0 9.3 4.33 13.4 9.6 4.42 13.7 9.5 4.46 14.4 9.4 4.51 15.1 9.3 4.60
46 10.1 8.7 3.77 10.6 9.0 3.85 11.0 9.3 3.92 11.4 9.6 4.01 11.6 9.5 4.05 12.2 9.4 4.09 12.8 9.2 4.17
48 8.9 7.9 3.56 9.4 8.1 3.63 9.7 8.4 3.71 10.1 8.6 3.78 10.3 8.5 3.82 10.8 8.4 3.86 11.3 8.3 3.94
50 7.7 7.0 3.35 8.1 7.2 3.42 8.4 7.4 3.49 8.7 7.7 3.56 8.9 7.6 3.60 9.3 7.5 3.63 9.8 7.4 3.70

NOTE
• The performance table shows the average value of each conditions.
4. Dimensional Drawing
Wind-Free 4Way Cassette

AC052TN4DKC/EA, AC071TN4DKC/EA
Units : mm [inches]

890~910 [35-1/16 ~ 35-13/16]


(Ceiling opening)
735 [28-15/18]
(Suspension position)

890~910 [35*1/16 ~ 35-13/16]


(Suspension position)

(Ceiling opening)
735 [28-15/18]
840 [33-1/16]

840 [33-1/16] 55 [2-3/16] 370


[14-9/16]
185

80 [3-1/8]
40 [1-9/16]

133 [5-1/4]
185 [7-1/4]

239 [9-3/8]
70 [2-3/4]

61 [7-1/4] 101
[2-3/8] 80 [3-1/8]
93 [3-11/16] [4]
[4-3/4]
120
[8-7/16]
[7-11/16]

[8-1/8]
215

206
196

[6]
[4-1/8]

153
105

3 330 237 5 195


[9-5/16] 2 166
[13] 4 1 [7-11/16]
302 [6-1/2]
[11-7/8] 351
[13-13/16]

950
[37-3/8]
48 [1-7/8]
[8-1/16]
204

[37-3/8]
[5-3/16]

950
132
[2-1/2]
64

Description
No. Name
AC052TN4DKC/EA AC071TN4DKC/EA
1 Liquid pipe connection Φ6.35(1/4)
2 Gas pipe connection Φ12.7(1/2) Φ15.88(5/8)
3 Drain pipe connection VP-25(OD32, ID25)
4 Power supply & Communication wiring conduit
5 Fresh air intake knockout hole Φ10[4] , Use M4 Screw

NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
4. Dimensional Drawing
Wind-Free 4Way Cassette

AC100TN4DKC/EA, AC120TN4DKC/EA, AC140TN4DKC/EA


Units : mm [inches]

890~910 [35-1/16 ~ 35-13/16]


(Ceiling opening)
735 [28-15/16]
(Suspension position)
416 [16-3/8]
200 or less
[7-7/8 or less]

890~910 [35-1/16 ~ 35-13/16]


(Suspension position)

(Ceiling opening)
735 [28-15/16]
417 [16-7/16]
Adjustable (until 550mm)
Adjustable (until 21-5/16 inches)

427 [16-13/16]

840 Ø101
239 61 55 55
[33-1/16] [ Ø4] 80 [3-1/8]
40 [1-9/16]

133 [5-1/4]
185 [7-1/4]
70 [2-3/4]

[9-3/8] [2-3/8] [2-3/16] [2-3/16]

80 [3-1/8]
222 [8-3/4]

[11-5/16]

48 [1-7/8]
288

[6-3/4]
[5-3/16]

172
330 237 132 195
[13] [9-5/16] 8
[7-11/16]
3 302 4 1 2
185 [11-7/8]
[7-5/16] 5
176 950
[6-15/16] [37-3/8]
238
[9]

370 (4 x 92.5)
127
[5]

A
[14-9/16 (4 x 3-5/8)]
A
[37-3/8]
[4-3/4 (2 x 2-3/8)]

950
[98-7/16 or more]

7
120 (2 x 60)

2500 or more
101 [4]

166 [6-1/2]

351 [13-13/16]
DETAIL A
6
SCALE 1:3

No. Name Description


1 Liquid pipe connection Ø9.52 (3/8)
2 Gas pipe connection Ø15.88 (5/8)
3 Drain pipi connection VP25(OD32, ID25)
4 Conduit for power supply & communication wiring
5 Air inlet grille
6 Air outlet louver
7 Sub-duct * The sub duct is not applicable to the Wind-Free Panel.
8 Fresh air intake

NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
5. Center of Gravity
Wind-Free 4Way Cassette

Units : mm [inches]

890~910 [35-1/16 ~ 35-13/16]

445 [17-1/2]

890~910 [35-1/16 ~ 35-13/16]


445 [17-1/2]
B
A

A B
AC052/071TN4DKC/EA 221 [8-11/16] 70 [2-3/4]
AC100/120/140TN4DKC/EA 305 [12] 130 [5-1/8]
6. Electrical Wiring Diagram
Wind-Free 4Way Cassette

SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
FLOAT SWITCH Switch of the float of Drain EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)

NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
Wind-Free 4Way Cassette

Sound Pressure level


Unit: dB(A)
Model HIGH MID LOW
AC052TN4DKC/EA 35 33 31
AC071TN4DKC/EA 40 36 32
1.5m AC100TN4DKC/EA 43 38 33
AC120TN4DKC/EA 44 40 35

Microphone

• NC Curve
1) AC052TN4DKC/EA 2) AC071TN4DKC/EA

3) AC100TN4DKC/EA 4) AC120TN4DKC/EA

NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
7. Sound Data
Wind-Free 4Way Cassette

Sound Pressure level


Unit: dB(A)
Model HIGH MID LOW
AC140TN4DKC/EA 44 41 37

1.5m

Microphone

• NC Curve
1) AC140TN4DKC/EA

NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
8. Temperature and air flow distribution
Wind-Free 4Way Cassette

AC052TN4DKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)

AC071TN4DKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)

AC100TN4DKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)
8. Temperature and air flow distribution
Wind-Free 4Way Cassette

AC120TN4DKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)

AC140TN4DKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)
360 Cassette

1. Specification 46
2. Summary Table 56
3. Capacity Table 57
4. Dimensional Drawing 59
5. Center of Gravity 67
6. Electrical Wiring Diagram 68
7. Sound Data 69
8. Temperature and air flow distribution 71
Features
 & Benefits
360 Cassette

All round cooling and comfort


The Samsung 360 Cassette air conditioner offers a brand
new way of staying comfortably cool in every corner of
the room. Its innovative circular design not only means
it perfectly fits in everywhere, adding a sophisticated
look to many different sites, but it also blows cool air
in all directions, so that the whole room is the same
temperature*. And its bladeless outlet ensures that cool
air is gently dispersed, without creating a cold draft**,
and doesn’t block the air flow, even at low angles, so it Conventional 360 Cassette
expels 25% more air* and spreads it farther.

EVENLY CIRCULATES & COOLS EVERY CORNER


Unike 4-way, cassette type air conditioners that create
areas of uneven airflow where cool air can't reach*, a
circular outlet blows cool air in all directions, so every
corner of a room is the same temperature**.
* Samsung testing compared to a general 4 way cassette type air
conditioner. * Within an 9.3m radius the temperature difference is less than 0.6°C.
** Within an 9.3m radius the temperature difference is less than 0.6°C.

Comfortably cool, not cold Spreads more air in more ways

A bladeless design softly disperses cool air across the An innovative Booster Fan enables cool air to be
room, making you comfortably cool without feeling a expelled at much lower angles. It creates a low pressure
cold draft**. With no blades to block the air flow, it also area around the outlet, so that cool air comes out
expels 25% more air* and spreads it farther. parallel to the ceiling and disperses across a wider area.

* Within a 5m radius, no cold draft between 0~1.5m in height (with 14.0kw).

Circular to perfectly fit in everywhere All round simpler & intuitive control

Its innovative circular design can match a multitude of Intuitively control its performance and see where the
interior designs, so it perfectly fits in everywhere. Its air is going. The Wireless Remote Controller's* Jog
minimalist modern styling creates a sophisticated look shuttle and button offer a fun way to adjust the air flow
and its circular shape stands out beautifully. and a Circular LED Display shows its direction.

*Optional
1. Specification
360 Cassette

System Indoor Unit AC052TN4PKC/EA AC071TN4PKC/EA AC100TN4PKC/EA


Model Name
Outdoor Unit AC052TXADKC/EA AC071TXADKC/EA AC100TXADKC/EA
Mode - Cooling only Cooling only Cooling only
kW 1.0 / 5.0 / 6.0 2.2 / 7.1 / 8.5 3.0 / 10.0 / 12.0
Cooling
Capacity Btu/h 3,410/17,000/20,470 7,510/24,000/29,000 10,240/34,000/40,940
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.33/1.41/2.1 0.35/2.185/3.6 0.6/3.125/4.7
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 1.5/6.7/9.5 2.0/10.1/16.0 3.0/14.8/20.4
Power
(Min/Std/Max) Heating A - - -
MCA A 21.5 21.5 26.0
Current
MFA A 25.0 25.0 30.0
EER Cooling - 3.55 3.25 3.20
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 6.35 (1/4) 6.35 (1/4) 9.52 (3/8)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 12.7 (1/2) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 30 50 50
(ODU-IDU) Elevation m 20 30 30
Chargeless m 5 5 30
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 1.30 2.00 3.00
Indoor Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Unit Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Type - Turbo Fan Turbo Fan Turbo Fan
Quantity EA 1 1 1
m³/min 17.7/15.6/14.1 21.3/16.8/13.2 31.2/25.5/19.8
Fan Air Flow Rate H/M/L
l/s 300/260/240 360/280/220 520/430/330
External mmAq - - -
Min/Std/Max
Static Pressure Pa - - -
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 65 x 1 65 x 1 97 x 1
1. Specification
360 Cassette

Indoor Indoor Unit AC052TN4PKC/EA AC071TN4PKC/EA AC100TN4PKC/EA


Unit Model Name
Outdoor Unit AC052TXADKC/EA AC071TXADKC/EA AC100TXADKC/EA
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 36/34/32 41/37/33 44/39/33
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 20.2 20.2 25.5
External Shipping Weight kg 24.5 24.5 30.3
Dimension Net Dimensions (WxHxD) ㎜ 947 x 281 x 947 947 x 281 x 947 947 x 365 x 947
Shipping Dimensions (WxHxD) ㎜ 990 x 330 x 990 990 x 330 x 990 990 x 414 x 990
Casing Material - HIPS HIPS HIPS
Model Name - PC4NUDMAN PC4NUDMAN PC4NUDMAN
Type - Ceiling Type(Sqare) Ceiling Type(Sqare) Ceiling Type(Sqare)
Material - HIPS HIPS HIPS
Color - White White White
Panel (1)
Net Weight kg 3.6 3.6 3.6
Shipping Weight kg 6.3 6.3 6.3
Net Dimensions (WxHxD) ㎜ 1,000 x 66 x 1,000 1,000 x 66 x 1,000 1,000 x 66 x 1,000
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083 1,093 x 85 x 1,083
Model Name - PC4NBDMAN PC4NBDMAN PC4NBDMAN
Type - Ceiling Type(Sqare) Ceiling Type(Sqare) Ceiling Type(Sqare)
Material - HIPS HIPS HIPS
Color - Black Black Black
Panel (2)
Net Weight kg 3.6 3.6 3.6
Shipping Weight kg 6.3 6.3 6.3
Net Dimensions (WxHxD) ㎜ 1,000 x 66 x 1,000 1,000 x 66 x 1,000 1,000 x 66 x 1,000
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083 1,093 x 85 x 1,083
Model Name - PC4NUNMAN PC4NUNMAN PC4NUNMAN
Type - Open Type(Circle) Open Type(Circle) Open Type(Circle)
Material - HIPS HIPS HIPS
Color - White White White
Panel (3)
Net Weight kg 2.7 2.7 2.7
Shipping Weight kg 5.3 5.3 5.3
Net Dimensions (WxHxD) ㎜ 1,050 x 66 x 1,050 1,050 x 66 x 1,050 1,050 x 66 x 1,050
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083 1,093 x 85 x 1,083
Model Name - PC4NBNMAN PC4NBNMAN PC4NBNMAN
Type - Open Type(Circle) Open Type(Circle) Open Type(Circle)
Material - HIPS HIPS HIPS
Color - Black Black Black
Panel (4)
Net Weight kg 2.7 2.7 2.7
Shipping Weight kg 5.3 5.3 5.3
Net Dimensions (WxHxD) ㎜ 1,050 x 66 x 1,050 1,050 x 66 x 1,050 1,050 x 66 x 1,050
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083 1,093 x 85 x 1,083
1. Specification
360 Cassette

Indoor Indoor Unit AC052TN4PKC/EA AC071TN4PKC/EA AC100TN4PKC/EA


Unit Model Name
Outdoor Unit AC052TXADKC/EA AC071TXADKC/EA AC100TXADKC/EA
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - Included Included Included
Drain Pump Max. lifting Height
㎜ / Liter/h 750/24 750/24 750/24
/ Displacement
External
- - - -
Model
Internal
- - - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - - -
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - Optional Optional Optional
Outdoor Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Unit Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG9TK3150FE4 UG8T265FXAEW UG8T300FUBJU
Type - Twin BLDC Twin BLDC Twin BLDC
Compressor Output kW 1.42 2.32 2.82
Type - POE POE POE
Oil
Initial charge cc 500 700 1,200
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 1 1
m³/min 50 60 76
Air Flow Rate
l/s 840 1,000 1,270
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 125 x 1 125 x 1 125 x 1
Sound Pressure
Cooling dB(A) 50 50 53
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 40.5 52.5 71.0
External Shipping Weight kg 43.5 56.5 76.0
Dimension Net Dimensions (WxHxD) ㎜ 880 x 638 x 310 880 x 798 x 310 940 x 998 x 330
Shipping Dimensions (WxHxD) ㎜ 1,023 x 730 x 413 1,023 x 881 x 413 995 x 1,096 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -
1. Specification
360 Cassette

System Indoor Unit AC100TN4PKC/EA AC120TN4PKC/EA AC120TN4PKC/EA


Model Name
Outdoor Unit AC100TXADNC/EA AC120TXADKC/EA AC120TXADNC/EA
Mode - Cooling only Cooling only Cooling only
kW 3.0 / 10.0 / 12.0 3.5 / 12.1 / 14.0 3.5 / 12.1 / 14.0
Cooling
Capacity Btu/h 10,240/34,000/40,940 11,940/41,500/47,770 11,940/41,500/47,770
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.6/3.125/4.7 0.8/3.67/5.3 0.8/3.67/5.5
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 1.5/5.2/7.1 3.7/16.7/23.0 2.1/5.9/8.8
Power
(Min/Std/Max) Heating A - - -
MCA A 18.1 34.0 18.1
Current
MFA A 18.1 40.0 18.1
EER Cooling - 3.20 3.30 3.30
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 50 75 75
(ODU-IDU) Elevation m 30 30 30
Chargeless m 30 30 30
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 3.00 3.40 3.40
Indoor Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Unit Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Type - Turbo Fan Turbo Fan Turbo Fan
Quantity EA 1 1 1
m³/min 31.2/25.5/19.8 32.0/26.0/19.5 32.0/26.0/19.5
Fan Air Flow Rate H/M/L
l/s 520/430/330 530/430/330 530/430/330
External mmAq - - -
Min/Std/Max
Static Pressure Pa - - -
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 97 x 1 97 x 1 97 x 1
1. Specification
360 Cassette

Indoor Indoor Unit AC100TN4PKC/EA AC120TN4PKC/EA AC120TN4PKC/EA


Unit Model Name
Outdoor Unit AC100TXADNC/EA AC120TXADKC/EA AC120TXADNC/EA
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 44/39/33 45/41/36 45/41/36
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 25.5 25.5 25.5
External Shipping Weight kg 30.3 30.3 30.3
Dimension Net Dimensions (WxHxD) ㎜ 947 x 365 x 947 947 x 365 x 947 947 x 365 x 947
Shipping Dimensions (WxHxD) ㎜ 990 x 414 x 990 990 x 414 x 990 990 x 414 x 990
Casing Material - HIPS HIPS HIPS
Model Name - PC4NUDMAN PC4NUDMAN PC4NUDMAN
Type - Ceiling Type(Sqare) Ceiling Type(Sqare) Ceiling Type(Sqare)
Material - HIPS HIPS HIPS
Color - White White White
Panel (1)
Net Weight kg 3.6 3.6 3.6
Shipping Weight kg 6.3 6.3 6.3
Net Dimensions (WxHxD) ㎜ 1,000 x 66 x 1,000 1,000 x 66 x 1,000 1,000 x 66 x 1,000
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083 1,093 x 85 x 1,083
Model Name - PC4NBDMAN PC4NBDMAN PC4NBDMAN
Type - Ceiling Type(Sqare) Ceiling Type(Sqare) Ceiling Type(Sqare)
Material - HIPS HIPS HIPS
Color - Black Black Black
Panel (2)
Net Weight kg 3.6 3.6 3.6
Shipping Weight kg 6.3 6.3 6.3
Net Dimensions (WxHxD) ㎜ 1,000 x 66 x 1,000 1,000 x 66 x 1,000 1,000 x 66 x 1,000
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083 1,093 x 85 x 1,083
Model Name - PC4NUNMAN PC4NUNMAN PC4NUNMAN
Type - Open Type(Circle) Open Type(Circle) Open Type(Circle)
Material - HIPS HIPS HIPS
Color - White White White
Panel (3)
Net Weight kg 2.7 2.7 2.7
Shipping Weight kg 5.3 5.3 5.3
Net Dimensions (WxHxD) ㎜ 1,050 x 66 x 1,050 1,050 x 66 x 1,050 1,050 x 66 x 1,050
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083 1,093 x 85 x 1,083
Model Name - PC4NBNMAN PC4NBNMAN PC4NBNMAN
Type - Open Type(Circle) Open Type(Circle) Open Type(Circle)
Material - HIPS HIPS HIPS
Color - Black Black Black
Panel (4)
Net Weight kg 2.7 2.7 2.7
Shipping Weight kg 5.3 5.3 5.3
Net Dimensions (WxHxD) ㎜ 1,050 x 66 x 1,050 1,050 x 66 x 1,050 1,050 x 66 x 1,050
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083 1,093 x 85 x 1,083
1. Specification
360 Cassette

Indoor Indoor Unit AC100TN4PKC/EA AC120TN4PKC/EA AC120TN4PKC/EA


Unit Model Name
Outdoor Unit AC100TXADNC/EA AC120TXADKC/EA AC120TXADNC/EA
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - Included Included Included
Drain Pump Max. lifting Height
㎜ / Liter/h 750/24 750/24 750/24
/ Displacement
External
- - - -
Model
Internal
- - - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - - -
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - Optional Optional Optional
Outdoor Power Supply Ø, #, V, Hz 3,4,380-415,50 1,2,220-240,50 3,4,380-415,50
Unit Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG8T300FUCJU UG5TK1450FJX UG5TK1450FJX
Type - Twin BLDC Twin BLDC Twin BLDC
Compressor Output kW 2.82 4.19 4.19
Type - POE POE POE
Oil
Initial charge cc 1,200 1,700 1,700
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 2 2
m³/min 76 110 110
Air Flow Rate
l/s 1,270 1,840 1,840
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 125 x 1 125 x 2 125 x 2
Sound Pressure
Cooling dB(A) 53 53 53
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 71.0 86.5 86.5
External Shipping Weight kg 76.0 96.5 96.5
Dimension Net Dimensions (WxHxD) ㎜ 940 x 998 x 330 940 x 1,210 x 330 940 x 1,210 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,096 x 426 995 x 1,388 x 426 995 x 1,388 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -
1. Specification
360 Cassette

System Indoor Unit AC140TN4PKC/EA AC140TN4PKC/EA


Model Name
Outdoor Unit AC140TXADKC/EA AC140TXADNC/EA
Mode - Cooling only Cooling only
kW 3.5 / 13.4 / 15.5 3.5 / 13.4 / 15.5
Cooling
Capacity Btu/h 11,940/45,500/52,890 11,940/45,500/52,890
Performance
(Min/Std/Max) kW - -
Heating
Btu/h - -
Power Input Cooling kW 0.8/4.42/6.4 0.8/4.42/6.4
(Min/Std/Max) Heating kW - -
Current Input Cooling A 3.7/20.4/28.0 2.1/7.1/9.5
Power
(Min/Std/Max) Heating A - -
MCA A 34.0 18.1
Current
MFA A 40.0 18.1
EER Cooling - 3.03 3.03
Efficiency
COP Heating - - -
Type Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5
Piping length Max. m 75 75
(ODU-IDU) Elevation m 30 30
Chargeless m 30 30
Wiring Min. ㎟ 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2
Type - R410A R410A
Refrigerant
Factory Charging kg 3.40 3.40
Indoor Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50
Unit Type - F&T F&T
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile
Type - Turbo Fan Turbo Fan
Quantity EA 1 1
m³/min 33.3/27.0/21.7 33.3/27.0/21.7
Fan Air Flow Rate H/M/L
l/s 560/450/360 560/450/360
External mmAq - -
Min/Std/Max
Static Pressure Pa - -
Type - BLDC BLDC
Fan Motor
Output Wxn 97 x 1 97 x 1
1. Specification
360 Cassette

Indoor Indoor Unit AC140TN4PKC/EA AC140TN4PKC/EA


Unit Model Name
Outdoor Unit AC140TXADKC/EA AC140TXADNC/EA
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 45/42/38 45/42/38
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 25.5 25.5
External Shipping Weight kg 30.3 30.3
Dimension Net Dimensions (WxHxD) ㎜ 947 x 365 x 947 947 x 365 x 947
Shipping Dimensions (WxHxD) ㎜ 990 x 414 x 990 990 x 414 x 990
Casing Material - HIPS HIPS
Model Name - PC4NUDMAN PC4NUDMAN
Type - Ceiling Type(Sqare) Ceiling Type(Sqare)
Material - HIPS HIPS
Color - White White
Panel (1)
Net Weight kg 3.6 3.6
Shipping Weight kg 6.3 6.3
Net Dimensions (WxHxD) ㎜ 1,000 x 66 x 1,000 1,000 x 66 x 1,000
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083
Model Name - PC4NBDMAN PC4NBDMAN
Type - Ceiling Type(Sqare) Ceiling Type(Sqare)
Material - HIPS HIPS
Color - Black Black
Panel (2)
Net Weight kg 3.6 3.6
Shipping Weight kg 6.3 6.3
Net Dimensions (WxHxD) ㎜ 1,000 x 66 x 1,000 1,000 x 66 x 1,000
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083
Model Name - PC4NUNMAN PC4NUNMAN
Type - Open Type(Circle) Open Type(Circle)
Material - HIPS HIPS
Color - White White
Panel (3)
Net Weight kg 2.7 2.7
Shipping Weight kg 5.3 5.3
Net Dimensions (WxHxD) ㎜ 1,050 x 66 x 1,050 1,050 x 66 x 1,050
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083
Model Name - PC4NBNMAN PC4NBNMAN
Type - Open Type(Circle) Open Type(Circle)
Material - HIPS HIPS
Color - Black Black
Panel (4)
Net Weight kg 2.7 2.7
Shipping Weight kg 5.3 5.3
Net Dimensions (WxHxD) ㎜ 1,050 x 66 x 1,050 1,050 x 66 x 1,050
Shipping Dimensions (WxHxD) ㎜ 1,093 x 85 x 1,083 1,093 x 85 x 1,083
1. Specification
360 Cassette

Indoor Indoor Unit AC140TN4PKC/EA AC140TN4PKC/EA


Unit Model Name
Outdoor Unit AC140TXADKC/EA AC140TXADNC/EA
Control Infrared remote control - AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N
Drain Pump - Included Included
Drain Pump Max. lifting Height
㎜ / Liter/h 750/24 750/24
/ Displacement
External
- - -
Model
Internal
- - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - -
Displacement
Air Filter - Removable / Washable Removable / Washable
Virus Doctor - Optional Optional
Outdoor Power Supply Ø, #, V, Hz 1,2,220-240,50 3,4,380-415,50
Unit Type - Fin & Tube Fin & Tube
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion
Model Name UG5TK1450FJX UG5TK1450FJX
Type - Twin BLDC Twin BLDC
Compressor Output kW 4.19 4.19
Type - POE POE
Oil
Initial charge cc 1,700 1,700
Type - Propeller Propeller
Discharge direction - Front Front
Fan Quantity EA 2 2
m³/min 110 110
Air Flow Rate
l/s 1,840 1,840
Type - BLDC BLDC
Fan Motor
Output Wxn 125 x 2 125 x 2
Sound Pressure
Cooling dB(A) 54 54
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 86.5 86.5
External Shipping Weight kg 96.5 96.5
Dimension Net Dimensions (WxHxD) ㎜ 940 x 1,210 x 330 940 x 1,210 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,388 x 426 995 x 1,388 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50
Temp. Range Heating ℃ - -
1. Specification
360 Cassette

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
360 Cassette

Performance Characteristics
Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 6.0 - High 17.7 36
AC052TN4PKC/EA 20.2 Std. 5.0 - Mid 15.6 34
Min. 1.0 - Low 14.1 32
Max. 8.5 - High 21.3 41
AC071TN4PKC/EA 20.2 Std. 7.1 - Mid 16.8 37
Min. 2.2 - Low 13.2 33
Max. 12.0 - High 31.2 44
AC100TN4PKC/EA 25.5 Std. 10.0 - Mid 25.5 39
Min. 3.0 - Low 19.8 33
Max. 14.0 - High 32.0 45
AC120TN4PKC/EA 25.5 Std. 12.1 - Mid 26.0 41
Min. 3.5 - Low 19.5 36
Max. 15.5 - High 33.3 45
AC140TN4PKC/EA 25.5 Std. 13.4 - Mid 27.0 42
Min. 3.5 - Low 21.7 38

NOTE
•• Sound data is based on cooling operation.

Electric Characteristics
Model Outdoor Unit Maximum Input Current [A] Power Supply
Rated Voltage range Outdoor Unit Indoor
Indoor Unit Outdoor Unit Total MCA MFA
Hz Volts Min. Max. Cooling Heating Unit
AC052TN4PKC/EA AC052TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC071TN4PKC/EA AC071TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC100TN4PKC/EA AC100TXADKC/EA 50 220 to 240 198 264 24.0 - 2.0 26.0 26.0 30.0
AC100TN4PKC/EA AC100TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
AC120TN4PKC/EA AC120TXADKC/EA 50 220 to 240 198 264 32.0 - 2.0 34.0 34.0 40.0
AC120TN4PKC/EA AC120TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
AC140TN4PKC/EA AC140TXADKC/EA 50 220 to 240 198 264 32.0 - 2.0 34.0 34.0 40.0
AC140TN4PKC/EA AC140TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1

NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
360 Cassette

(1) AC052TN4PKC/EA+AC052TXADKC/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 5.1 4.3 1.18 5.4 4.4 1.20 5.6 4.5 1.23 5.8 4.7 1.25 5.9 4.6 1.27 6.2 4.6 1.28 6.5 4.5 1.30
21 5.4 4.4 1.12 5.7 4.5 1.15 5.9 4.7 1.17 6.1 4.8 1.19 6.2 4.7 1.20 6.5 4.7 1.22 6.8 4.6 1.24
35 4.4 3.9 1.33 4.7 4.1 1.35 4.9 4.2 1.38 5.0 4.3 1.41 5.1 4.3 1.42 5.4 4.2 1.44 5.6 4.1 1.47
46 5.0 4.2 2.37 5.3 4.3 2.42 5.5 4.5 2.47 5.7 4.6 2.52 5.8 4.6 2.55 6.1 4.5 2.57 6.4 4.4 2.62
48 4.7 4.1 2.43 5.0 4.2 2.48 5.2 4.3 2.53 5.4 4.5 2.58 5.5 4.4 2.60 5.7 4.4 2.63 6.0 4.3 2.68
50 4.5 4.0 2.48 4.7 4.1 2.53 4.9 4.2 2.58 5.0 4.4 2.63 5.2 4.3 2.66 5.4 4.3 2.69 5.7 4.2 2.74

(2) AC071TN4PKC/EA+AC071TXADKC/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 6.9 5.2 2.19 7.3 5.4 2.23 7.6 5.6 2.28 7.8 5.7 2.33 8.0 5.7 2.35 8.4 5.6 2.37 8.8 5.5 2.42
21 8.1 5.9 2.14 8.6 6.1 2.19 8.9 6.2 2.23 9.2 6.4 2.28 9.4 6.4 2.30 9.9 6.3 2.32 10.4 6.2 2.37
35 6.3 5.0 2.06 6.6 5.2 2.10 6.9 5.3 2.14 7.1 5.5 2.19 7.2 5.4 2.21 7.6 5.4 2.23 8.0 5.3 2.27
46 6.0 4.9 2.71 6.3 5.0 2.77 6.6 5.2 2.82 6.8 5.4 2.88 7.0 5.3 2.91 7.3 5.3 2.94 7.7 5.2 3.00
48 5.6 4.7 2.64 5.9 4.9 2.70 6.2 5.0 2.75 6.4 5.2 2.81 6.5 5.1 2.84 6.8 5.1 2.87 7.2 5.0 2.92
50 5.3 4.6 2.58 5.5 4.7 2.63 5.8 4.8 2.68 5.9 5.0 2.74 6.1 4.9 2.76 6.4 4.9 2.79 6.7 4.8 2.85

(3) AC100TN4PKC/EA+AC100TXAD*C/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 9.7 7.8 2.46 10.2 8.1 2.51 10.7 8.3 2.56 11.0 8.6 2.61 11.2 8.5 2.64 11.8 8.4 2.66 12.4 8.2 2.71
21 10.5 8.1 2.44 11.0 8.3 2.49 11.5 8.6 2.54 11.8 8.8 2.59 12.1 8.8 2.61 12.7 8.7 2.64 13.3 8.5 2.69
35 8.8 7.3 2.94 9.3 7.5 3.00 9.7 7.8 3.06 10.0 8.0 3.13 10.2 7.9 3.16 10.7 7.9 3.19 11.2 7.7 3.25
46 7.6 6.6 3.45 8.0 6.8 3.52 8.3 7.0 3.59 8.6 7.2 3.66 8.8 7.2 3.70 9.2 7.1 3.74 9.7 7.0 3.81
48 7.1 6.5 3.20 7.5 6.7 3.26 7.8 6.9 3.33 8.1 7.1 3.40 8.2 7.0 3.43 8.6 7.0 3.47 9.1 6.8 3.54
50 6.7 6.4 2.95 7.0 6.6 3.01 7.3 6.8 3.07 7.6 7.0 3.13 7.7 6.9 3.16 8.1 6.9 3.20 8.5 6.7 3.26

NOTE
•• The performance table shows the average value of each conditions.
3. Capacity Table
360 Cassette

(4) AC120TN4PKC/EA+AC120TXAD*C/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 11.8 8.9 2.64 12.4 9.2 2.70 12.9 9.4 2.75 13.3 9.7 2.81 13.6 9.6 2.84 14.3 9.5 2.86 15.0 9.4 2.92
21 11.2 8.5 2.78 11.8 8.7 2.84 12.3 9.0 2.90 12.7 9.3 2.96 13.0 9.2 2.99 13.6 9.1 3.01 14.3 8.9 3.08
35 10.7 8.2 3.45 11.3 8.5 3.52 11.7 8.7 3.60 12.1 9.0 3.67 12.3 8.9 3.71 13.0 8.8 3.74 13.6 8.7 3.82
46 9.3 8.1 3.13 9.8 8.3 3.19 10.2 8.6 3.26 10.5 8.8 3.33 10.7 8.8 3.36 11.3 8.7 3.39 11.8 8.5 3.46
48 8.3 7.3 2.96 8.7 7.6 3.02 9.1 7.8 3.08 9.4 8.0 3.14 9.6 8.0 3.17 10.0 7.9 3.20 10.5 7.7 3.27
50 7.3 6.6 2.78 7.7 6.8 2.84 8.0 7.0 2.90 8.2 7.2 2.96 8.4 7.2 2.99 8.8 7.1 3.01 9.3 7.0 3.08

(5) AC140TN4PKC/EA+AC140TXAD*C/EA

Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 13.1 9.8 3.18 13.8 10.1 3.25 14.3 10.5 3.31 14.8 10.8 3.38 15.1 10.7 3.42 15.8 10.6 3.45 16.6 10.4 3.52
21 12.4 9.4 3.35 13.1 9.7 3.42 13.6 10.0 3.49 14.1 10.3 3.56 14.4 10.2 3.60 15.1 10.1 3.63 15.8 9.9 3.70
35 11.9 8.8 4.16 12.5 9.1 4.24 13.0 9.3 4.33 13.4 9.6 4.42 13.7 9.5 4.46 14.4 9.4 4.51 15.1 9.3 4.60
46 10.1 8.7 3.77 10.6 9.0 3.85 11.0 9.3 3.92 11.4 9.6 4.01 11.6 9.5 4.05 12.2 9.4 4.09 12.8 9.2 4.17
48 8.9 7.9 3.56 9.4 8.1 3.63 9.7 8.4 3.71 10.1 8.6 3.78 10.3 8.5 3.82 10.8 8.4 3.86 11.3 8.3 3.94
50 7.7 7.0 3.35 8.1 7.2 3.42 8.4 7.4 3.49 8.7 7.7 3.56 8.9 7.6 3.60 9.3 7.5 3.63 9.8 7.4 3.70

NOTE
• The performance table shows the average value of each conditions.
4. Dimensional Drawing
360 Cassette (Square)

AC052TN4PKC/EA, AC071TN4PKC/EA
Units : mm [inches]

947
[37-5/16]

[11-1/16]
281
4. Dimensional Drawing
360 Cassette (Square)

Description
No. Name No. Name Description
AC052 AC071
1 Liquid pipe connection Φ6.35(1/4) 7 Suction rim for Booster fan
2 Gas pipe connection Φ12.7(1/2) Φ15.88(5/8) 8 Decoration cover
3 Drain pipe connection VP-25(OD32, ID25) 9 Drain hose(Accessory)
4 Power supply & Communication wiring conduit 10 Fresh air intake knockout hole Use M4 Screw
5 Air Discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver

NOTE
•• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
•• Make sure the spacing between the ceiling and the cassette is no more than 29mm[1-1/4].
Max ceiling opening : 960mm[36-13/16].
•• When the condition exceed 30℃ and RH 80% in the ceiling or fresh air is inducted into the ceiling,
and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
4. Dimensional Drawing
360 Cassette (Square)

AC100TN4PKC/EA, AC120TN4PKC/EA, AC140TN4PKC/EA


Units : mm [inches]

200 or less
[7-7/8] 318
[12-1/2]

950~960 [37-3/8 ~ 37-13/16]


(Suspension position)
645 [25-3/8]

(Ceiling opening)
Adjustable (0~584)

372 [14-5/8]
[0~23]

430 [16-15/16]
645 [25-3/8]
(Suspension position)
385 [15-1/8] 403 [15-7/8] 950~960 [37-3/8 ~ 37-13/16]
(Ceiling opening)
360 947
[14-3/16] [37-5/16]
128 [5-1/16]
190 [7-1/2]

[12-1/2]

[14-3/8]
317

365
[7-3/16]
[6-1/2]

182
166

29 29 [1-1/8]
[1-1/8]

3
1 2 4 Front View
435 79 [3-1/8]
[17-1/8]
428
100 [16-7/8]
[4] 10

12
5
[8-5/8]
219

[5-1/2]
140

11
[39-3/8]
[2-5/8]

1000

788
66

[31-1/16] 6
[98-7/16] or More

Back View
2500 or More

1000
[39-3/8]
4. Dimensional Drawing
360 Cassette (Square)

No. Name Description No. Name Description


1 Liquid pipe connection Ø9.52 (3/8) 7 Suction rim for Booster fan
2 Gas pipe connection Ø15.88 (5/8) 8 Decoration cover
3 Drain hose VP25(OD32, ID25) 9 Drain hose(Accessory)
4 Power & Communication wiring conduits 10 Fresh air intake knockout hole
5 Air discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver

NOTE
•• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
•• Make sure the spacing between the ceiling and the cassette is no more than 29mm[1-1/4].
Max ceiling opening : 960mm[36-13/16].
•• When the condition exceed 30℃ and RH 80% in the ceiling or fresh air is inducted into the ceiling,
and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
4. Dimensional Drawing
360 Cassette (Circle)

AC052TN4PKC/EA, AC071TN4PKC/EA
Units : mm [inches]

947
[37-5/16]

[11-1/16]
281
4. Dimensional Drawing
360 Cassette (Circle)

Description
No. Name No. Name Description
AC052 AC071
1 Liquid pipe connection Φ6.35(1/4) 7 Suction rim for Booster fan
2 Gas pipe connection Φ12.7(1/2) Φ15.88(5/8) 8 Decoration cover
3 Drain pipe connection VP-25(OD32, ID25) 9 Drain hose(Accessory)
4 Power supply & Communication wiring conduit 10 Fresh air intake knockout hole Use M4 Screw
5 Air Discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver

NOTE
• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
• Make sure the spacing between the ceiling and the cassette is no more than 29mm[1-1/4].
Max ceiling opening : 960mm[36-13/16].
• When the condition exceed 30℃ and RH 80% in the ceiling or fresh air is inducted into the ceiling,
and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
4. Dimensional Drawing
360 Cassette (Circle)

AC100TN4PKC/EA, AC120TN4PKC/EA, AC140TN4PKC/EA


Units : mm [inches]

200 or less
[7-7/8] 318
[12-1/2]

(Suspension position)
645 [25-3/8]
[0~21-5/8]
Adjustable (0~550)

372 [14-5/8]
430 [16-15/16]
645 [25-3/8]
(Suspension position)
385 [15-1/8] 403 [15-7/8]

360 947
[14-3/16] 55 [2-3/16] [37-5/16] 55 [2-3/16]

[11-3/8]
94 [3-11/16]

289

[14-3/8]
[6-3/8]

365
[6-1/16]
[5-7/16]

162

154
138

100
[4]

3
1 2 4 Front View
79 [3-1/8]
435 [17-1/8] 427
100 [16-7/8]
[4] 10

12
5
[7-1/2]
191

[4-3/8]
111

11

788
[31-1/16] 6
[98-7/16] or More

Back View
2500 or More

1050 [41-3/8]
4. Dimensional Drawing
360 Cassette (Circle)

No. Name Description No. Name Description


1 Liquid pipe connection Ø9.52 (3/8) 7 Suction rim for Booster fan
2 Gas pipe connection Ø15.88 (5/8) 8 Decoration cover
3 Drain hose VP25(OD32, ID25) 9 Drain hose(Accessory)
4 Power & Communication wiring conduits 10 Fresh air intake knockout hole
5 Air discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver

NOTE
•• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
•• Make sure the spacing between the ceiling and the cassette is no more than 29mm[1-1/4].
Max ceiling opening : 960mm[36-13/16].
•• When the condition exceed 30℃ and RH 80% in the ceiling or fresh air is inducted into the ceiling,
and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
•• The circular panel is by default available in exposed installation.
Make inspection holes on the ceiling for easier installation and maintenance, as shown in the following table.
(The size of an inspection hole must be at least 450 mm x 450 mm.)
•• A suspended ceiling structure can substitute for the inspection holes.
5. Center of Gravity
360 Cassette

Units : mm [inches]

A B
AC052/071TN4PKC/EA 233 [9-3/16] 165 [6-1/2]
AC100/120/140TN4PKC/EA 317 [12-1/2] 220 [8-5/8]
6. Electrical Wiring Diagram
360 Cassette

SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)

M-BLDC BLDC Motor EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)

NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
360 Cassette

Sound Pressure level


Unit: dB(A)
Model HIGH MID LOW
AC052TN4PKC/EA 36 34 32
AC071TN4PKC/EA 41 37 33
1.5m AC100TN4PKC/EA 44 39 33
AC120TN4PKC/EA 45 41 36

Microphone

• NC Curve
1) AC052TN4PKC/EA 2) AC071TN4PKC/EA

3) AC100TN4PKC/EA 4) AC120TN4PKC/EA

NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
7. Sound Data
360 Cassette

Sound Pressure level


Unit: dB(A)
Model HIGH MID LOW
AC052TN4PKC/EA 45 42 38

1.5m

Microphone

• NC Curve
1) AC052TN4PKC/EA

NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
8. Temperature and air flow distribution
360 Cassette

AC052TN4PKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)

AC071TN4PKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)

AC100TN4PKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
8. Temperature and air flow distribution
360 Cassette

AC120TN4PKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)

AC140TN4PKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
Duct

1. Specification 76
2. Summary Table 88
3. Capacity Table 89
4. Dimensional Drawing 92
5. Center of Gravity 96
6. Electrical Wiring Diagram 99
7. Sound Data 102
8. Fan Characteristics 104
Features
 & Benefits
Slim Duct - Ultra-light, adaptable design

Various installation options


Slim Duct S adopts an ultra-compact, slim size with its
thin width, which is 200 mm narrower than conventional
products. This slender build enables flexible installation
and maintenance in various environments.

World’s lightest weight


The efficient Slim Duct S is the lightest duct air
conditioning unit on the market. At a weight that’s
Temper any environment with industry-best 15 percent lighter than conventional units, Slim
lightweight design and optimized airflow Duct S offers the best in convenient installation and
maintenance.
The new Samsung Slim Duct visually blends into the
ceiling while providing powerful cool and warm airflow.
It’s also easy to install and maintain in any interior
regardless of the surrounding environment with its
compact size and weight—the lightest in the industry.
900mm

Flexible setup
The air inlet can be set up either on the bottom or rear of
the unit, giving users greater flexibility in installation. 700mm 200 mm
Narrower

Rear Side Air Inlet Bottom Side Air Inlet

Easy access, easy maintenance


Slim Duct features a flexible design that enables users to
Diffuser

Diffuser

Diffuser

easily access its parts to maintain the unit.


TEX
TEX
TEX
TEX
Suction Duct
Suction Duct
Suction Duct
Suction Duct
Features & Benefits
Duct S

Overview Smart pressure control


Samsung Ducted Type air conditioning units are a smart Samsung Ducted Type units feature a smart pressure
solution for low-maintenance, consistent cooling and control system. This system adjusts the fan speed
heating performance in any environment. Their compact, based on the external static pressure (ESP), delivering
slim frame blends seamlessly into ceilings, enhancing consistent cooling and heating power, regardless of
the beauty of the interior space and affording users more the surrounding environment.
flexible installation options. Offering a comprehensive
lineup, Samsung Ducted Type air conditioning units offer Convenient installation
just the right solution for every need--from the office or
The optional lift-up drain pump lifts condensed
shop to the restaurant kitchen.
water up to 750 mm, compared to a limit of 700 mm
on conventional models, for flexible and convenient
installation.

Experience performance and convenient comfort for The Duct S indoor air conditioning unit delivers smooth,
any weather condition consistent operation and convenience with features such
as:
Samsung Duct S delivers unparalleled cooling and
heating and flexible management with customizable •• Efficient operation. Stage the desired atmosphere
comfort settings in any climate—all year round. Plus, it with energy-efficient performance and customized
boasts a slim, compact size and multiple access points airflow.
for easy setup exactly where needed. •• Smart management. Cool spaces efficiently and
manage the air conditioning unit even while away,
with features designed for efficiency and control.
•• Easy, flexible setup. Install and maintain even
multiple units with a compact and easily accessible
design.
1. Specification
Duct

System Indoor Unit AC035TNLDKC/EA AC052TNLDKC/EA AC071TNMDKC/EA


Model Name
Outdoor Unit AC035TXADKC/EA AC052TXADKC/EA AC071TXADKC/EA
Mode - Cooling only Cooling only Cooling only
kW 1.0 / 3.5 / 4.1 1.2 / 5.0 / 5.6 2.2 / 6.5 / 8.0
Cooling
Capacity Btu/h 3,410/12,000/13,990 4,090/17,000/19,110 7,510/22,000/27,300
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.24/1.075/1.5 0.35/1.565/2.2 0.35/2.13/3.6
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 1.6/5.5/7.5 2.1/7.4/10.0 2.0/9.7/16.0
Power
(Min/Std/Max) Heating A - - -
MCA A 11.7 22.3 22.3
Current
MFA A 12.9 25.0 25.0
EER Cooling - 3.25 3.20 3.05
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 6.35 (1/4) 6.35 (1/4) 6.35 (1/4)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 9.52 (3/8) 12.7 (1/2) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 20 30 50
(ODU-IDU) Elevation m 15 20 30
Chargeless m 20 5 5
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 1.05 1.30 2.00
1. Specification
Duct

Indoor Indoor Unit AC035TNLDKC/EA AC052TNLDKC/EA AC071TNMDKC/EA


Unit Model Name
Outdoor Unit AC035TXADKC/EA AC052TXADKC/EA AC071TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Hydrophille Hydrophille
Type - Sirocco Sirocco Sirocco
Quantity EA 2 2 2
m³/min 9.5/8.5/7.5 14.5/12.0/9.5 18.0/14.5/11.0
Fan Air Flow Rate H/M/L
l/s 160/140/130 240/200/160 300/240/180
External mmAq 0/2.5/4.0 0/3.0/5.0 0/3.0/15.0
Min/Std/Max
Static Pressure Pa 0/24.5/39 0/29.5/49 0/29.5/147
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 69 x 1 153 x 1 153 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 30/28/26 33/30/27 37/33/29
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 14.8 26.5 26.5
External Shipping Weight kg 17.7 30.5 30.5
Dimension Net Dimensions (WxHxD) ㎜ 700 x 199 x 440 850 x 250 x 700 850 x 250 x 700
Shipping Dimensions (WxHxD) ㎜ 949 x 280 x 544 1,064 x 320 x 784 1,064 x 320 x 784
Casing Material - GI Steel Plate GI Steel Plate GI Steel Plate
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - - Optional Optional
Drain Pump Max. lifting Height
㎜ / Liter/h - - -
/ Displacement
External
- - MDP-G075SP MDP-G075SP
Model
Internal
- - MDP-G075SQ MDP-G075SQ
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - 750/24 750/24
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - - Optional Optional
1. Specification
Duct

Outdoor Indoor Unit AC035TNLDKC/EA AC052TNLDKC/EA AC071TNMDKC/EA


Unit Model Name
Outdoor Unit AC035TXADKC/EA AC052TXADKC/EA AC071TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophille Anti-Corrosion Anti-Corrosion
Model Name UG9AJ3090FER UG9TK3150FE4 UG8T265FXAEW
Type - Single BLDC Twin BLDC Twin BLDC
Compressor Output kW 0.83 1.42 2.32
Type - POE POE POE
Oil
Initial charge cc 320 500 700
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 1 1
m³/min 40 50 60
Air Flow Rate
l/s 670 840 1,000
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 40 x 1 125 x 1 125 x 1
Sound Pressure
Cooling dB(A) 48 50 50
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 30.5 40.5 52.5
External Shipping Weight kg 32.5 43.5 56.5
Dimension Net Dimensions (WxHxD) ㎜ 790 x 548 x 285 880 x 638 x 310 880 x 798 x 310
Shipping Dimensions (WxHxD) ㎜ 913 x 622 x 371 1,023 x 730 x 413 1,023 x 881 x 413
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Duct

System Indoor Unit AC100TNMDKC/EA AC100TNMDKC/EA AC120TNMDKC/EA


Model Name
Outdoor Unit AC100TXADKC/EA AC100TXADNC/EA AC120TXADKC/EA
Mode - Cooling only Cooling only Cooling only
kW 3.0 / 10.0 / 12.0 3.0 / 10.0 / 12.0 3.5 / 12.1 / 14.0
Cooling
Capacity Btu/h 10,240/34,000/40,940 10,240/34,000/40,940 11,940/41,500/47,770
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.6/3.125/4.7 0.6/3.125/4.7 0.8/3.67/5.3
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 3.0/14.8/20.4 1.5/5.2/7.1 3.7/16.7/23.0
Power
(Min/Std/Max) Heating A - - -
MCA A 26.5 18.6 34.5
Current
MFA A 30.0 18.6 40.0
EER Cooling - 3.20 3.20 3.30
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 50 50 75
(ODU-IDU) Elevation m 30 30 30
Chargeless m 30 30 30
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 3.00 3.00 3.40
1. Specification
Duct

Indoor Indoor Unit AC100TNMDKC/EA AC100TNMDKC/EA AC120TNMDKC/EA


Unit Model Name
Outdoor Unit AC100TXADKC/EA AC100TXADNC/EA AC120TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Hydrophille Hydrophille Hydrophille
Type - Sirocco Sirocco Sirocco
Quantity EA 3 3 3
m³/min 28.0/25.0/22.0 28.0/25.0/22.0 33.0/28.0/23.0
Fan Air Flow Rate H/M/L
l/s 470/420/370 470/420/370 550/470/380
External mmAq 0/4.0/15.0 0/4.0/15.0 0/5.2/15
Min/Std/Max
Static Pressure Pa 0/39.0/147 0/39.0/147 0/51.0/147
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 244 x 1 244 x 1 244 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 36/33/30 36/33/30 37/34/30
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 38.5 38.5 38.5
External Shipping Weight kg 43.5 43.5 43.5
Dimension Net Dimensions (WxHxD) ㎜ 1,300 x 300 x 700 1,300 x 300 x 700 1,300 x 300 x 700
Shipping Dimensions (WxHxD) ㎜ 1,529 x 370 x 779 1,529 x 370 x 779 1,529 x 370 x 779
Casing Material - GI Steel Plate GI Steel Plate GI Steel Plate
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - Optional Optional Optional
Drain Pump Max. lifting Height
㎜ / Liter/h - - -
/ Displacement
External
- MDP-G075SP MDP-G075SP MDP-G075SP
Model
Internal
- MDP-G075SQ MDP-G075SQ MDP-G075SQ
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h 750/24 750/24 750/24
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - Optional Optional Optional
1. Specification
Duct

Outdoor Indoor Unit AC100TNMDKC/EA AC100TNMDKC/EA AC120TNMDKC/EA


Unit Model Name
Outdoor Unit AC100TXADKC/EA AC100TXADNC/EA AC120TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 3,4,380-415,50 1,2,220-240,50
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG8T300FUBJU UG8T300FUCJU UG5TK1450FJX
Type - Twin BLDC Twin BLDC Twin BLDC
Compressor Output kW 2.82 2.82 4.19
Type - POE POE POE
Oil
Initial charge cc 1,200 1,200 1,700
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 1 2
m³/min 76 76 110
Air Flow Rate
l/s 1,270 1,270 1,840
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 125 x 1 125 x 1 125 x 2
Sound Pressure
Cooling dB(A) 53 53 53
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 71.0 71.0 86.5
External Shipping Weight kg 76.0 76.0 96.5
Dimension Net Dimensions (WxHxD) ㎜ 940 x 998 x 330 940 x 998 x 330 940 x 1,210 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,096 x 426 995 x 1,096 x 426 995 x 1,388 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Duct

System Indoor Unit AC120TNMDKC/EA AC140TNMDKC/EA AC140TNMDKC/EA


Model Name
Outdoor Unit AC120TXADNC/EA AC140TXADKC/EA AC140TXADNC/EA
Mode - Cooling only Cooling only Cooling only
kW 3.5 / 12.1 / 14.0 3.5 / 13.4 / 15.5 3.5 / 13.4 / 15.5
Cooling
Capacity Btu/h 11,940/41,500/47,770 11,940/45,500/52,890 11,940/45,500/52,890
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.8/3.67/5.5 0.8/4.42/6.4 0.8/4.42/6.4
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 2.1/5.9/8.8 3.7/20.4/28.0 2.1/7.1/9.5
Power
(Min/Std/Max) Heating A - - -
MCA A 18.6 34.5 18.6
Current
MFA A 18.6 40.0 18.6
EER Cooling - 3.30 3.03 3.03
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 75 75 75
(ODU-IDU) Elevation m 30 30 30
Chargeless m 30 30 30
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 3.40 3.40 3.40
1. Specification
Duct

Indoor Indoor Unit AC120TNMDKC/EA AC140TNMDKC/EA AC140TNMDKC/EA


Unit Model Name
Outdoor Unit AC120TXADNC/EA AC140TXADKC/EA AC140TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Hydrophille Hydrophille Hydrophille
Type - Sirocco Sirocco Sirocco
Quantity EA 3 3 3
m³/min 33.0/28.0/23.0 33.0/28.0/23.0 33.0/28.0/23.0
Fan Air Flow Rate H/M/L
l/s 550/470/380 550/470/380 550/470/380
External mmAq 0/5.2/15.0 0/5.2/15 0/5.2/15.0
Min/Std/Max
Static Pressure Pa 0/51.0/147 0/51.0/147 0/51.0/147
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 244 x 1 244 x 1 244 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 37/34/30 37/34/30 37/34/30
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 38.5 38.5 38.5
External Shipping Weight kg 43.5 43.5 43.5
Dimension Net Dimensions (WxHxD) ㎜ 1,300 x 300 x 700 1,300 x 300 x 700 1,300 x 300 x 700
Shipping Dimensions (WxHxD) ㎜ 1,529 x 370 x 779 1,529 x 370 x 779 1,529 x 370 x 779
Casing Material - GI Steel Plate GI Steel Plate GI Steel Plate
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - Optional Optional Optional
Drain Pump Max. lifting Height
㎜ / Liter/h - - -
/ Displacement
External
- MDP-G075SP MDP-G075SP MDP-G075SP
Model
Internal
- MDP-G075SQ MDP-G075SQ MDP-G075SQ
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h 750/24 750/24 750/24
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - Optional Optional Optional
1. Specification
Duct

Outdoor Indoor Unit AC120TNMDKC/EA AC140TNMDKC/EA AC140TNMDKC/EA


Unit Model Name
Outdoor Unit AC120TXADNC/EA AC140TXADKC/EA AC140TXADNC/EA
Power Supply Ø, #, V, Hz 3,4,380-415,50 1,2,220-240,50 3,4,380-415,50
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG5TK1450FJX UG5TK1450FJX UG5TK1450FJX
Type - Twin BLDC Twin BLDC Twin BLDC
Compressor Output kW 4.19 4.19 4.19
Type - POE POE POE
Oil
Initial charge cc 1,700 1,700 1,700
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 2 2 2
m³/min 110 110 110
Air Flow Rate
l/s 1,840 1,840 1,840
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 125 x 2 125 x 2 125 x 2
Sound Pressure
Cooling dB(A) 53 54 54
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 86.5 86.5 86.5
External Shipping Weight kg 96.5 96.5 96.5
Dimension Net Dimensions (WxHxD) ㎜ 940 x 1,210 x 330 940 x 1,210 x 330 940 x 1,210 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,388 x 426 995 x 1,388 x 426 995 x 1,388 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Duct

System Indoor Unit AC160TNMDKC/EA AC160TNMDKC/EA


Model Name
Outdoor Unit AC160TXADKC/EA AC160TXADNC/EA
Mode - Cooling only Cooling only
kW 4.3 / 15.8 / 18.0 4.4 / 15.8 / 18.0
Cooling
Capacity Btu/h 14,670/54,000/61,420 15,010/54,000/61,420
Performance
(Min/Std/Max) kW - -
Heating
Btu/h - -
Power Input Cooling kW 0.95/5.215/6.8 1.1/5.215/6.8
(Min/Std/Max) Heating kW - -
Current Input Cooling A 4.0/23.8/31.0 2.0/8.4/10.0
Power
(Min/Std/Max) Heating A - -
MCA A 35.5 19.6
Current
MFA A 40.0 19.6
EER Cooling - 3.03 3.03
Efficiency
COP Heating - - -
Type Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 19.02 (3/4) 19.02 (3/4)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5
Piping length Max. m 75 75
(ODU-IDU) Elevation m 30 30
Chargeless m 30 30
Wiring Min. ㎟ 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2
Type - R410A R410A
Refrigerant
Factory Charging kg 3.80 3.80
1. Specification
Duct

Indoor Indoor Unit AC160TNMDKC/EA AC160TNMDKC/EA


Unit Model Name
Outdoor Unit AC160TXADKC/EA AC160TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile
Type - Sirocco Sirocco
Quantity EA 2 2
m³/min 50.0/44.5/39.0 50.0/44.5/39.0
Fan Air Flow Rate H/M/L
l/s 840/740/650 840/740/650
External mmAq 2.5/5.2/15.0 2.5/5.2/15.0
Min/Std/Max
Static Pressure Pa 24.5/51.0/147 24.5/51.0/147
Type - BLDC BLDC
Fan Motor
Output Wxn 450 x 1 450 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 44/40/36 44/40/36
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 53.5 53.5
External Shipping Weight kg 60.5 60.5
Dimension Net Dimensions (WxHxD) ㎜ 1,200 x 360 x 650 1,200 x 360 x 650
Shipping Dimensions (WxHxD) ㎜ 1,456 x 440 x 778 1,456 x 440 x 778
Casing Material - GI Steel Plate GI Steel Plate
Control Infrared remote control - AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N
Drain Pump - Optional Optional
Drain Pump Max. lifting Height
㎜ / Liter/h - -
/ Displacement
External
- - -
Model
Internal
- MDP-M075SGU2D MDP-M075SGU2D
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h 750/24 750/24
Displacement
Air Filter - Removable / Washable Removable / Washable
Virus Doctor - - -
1. Specification
Duct

Outdoor Indoor Unit AC160TNMDKC/EA AC160TNMDKC/EA


Unit Model Name
Outdoor Unit AC160TXADKC/EA AC160TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 3,4,380-415,50
Type - Fin & Tube Fin & Tube
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion
Model Name UG5TK5450FJX UG5TK5450FJX
Type - Twin BLDC Twin BLDC
Compressor Output kW 4.12 4.12
Type - POE POE
Oil
Initial charge cc 1,700 1,700
Type - Propeller Propeller
Discharge direction - Front Front
Fan Quantity EA 2 2
m³/min 143 143
Air Flow Rate
l/s 2,390 2,390
Type - BLDC BLDC
Fan Motor
Output Wxn 125 x 2 125 x 2
Sound Pressure
Cooling dB(A) 56 56
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 96.0 96.0
External Shipping Weight kg 106.0 106.0
Dimension Net Dimensions (WxHxD) ㎜ 940 x 1,420 x 330 940 x 1,420 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,595 x 425 995 x 1,595 x 425
Casing Material Body - EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50
Temp. Range Heating ℃ - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
Duct

Performance Characteristics
Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 4.1 - High 9.5 30
AC035TNLDKC/EA 14.8 Std. 3.5 - Mid 8.5 28
Min. 1.0 - Low 7.5 26
Max. 5.6 - High 14.5 33
AC052TNLDKC/EA 26.5 Std. 5.0 - Mid 12.0 30
Min. 1.2 - Low 9.5 27
Max. 8.0 - High 18.0 37
AC071TNMDKC/EA 26.5 Std. 6.5 - Mid 14.5 33
Min. 2.2 - Low 11.0 29
Max. 12.0 - High 28.0 36
AC100TNMDKC/EA 38.5 Std. 10.0 - Mid 25.0 33
Min. 3.0 - Low 22.0 30
Max. 14.0 - High 33.0 37
AC120TNMDKC/EA 38.5 Std. 12.1 - Mid 28.0 34
Min. 3.5 - Low 23.0 30
Max. 15.5 - High 33.0 37
AC140TNMDKC/EA 38.5 Std. 13.4 - Mid 28.0 34
Min. 3.5 - Low 23.0 30
Max. 18.0 - High 50.0 44
AC160TNMDKC/EA 53.5 Std. 15.8 - Mid 44.5 40
Min. 4.3 - Low 39.0 36

NOTE
•• Sound data is based on cooling operation.

Electric Characteristics
Model Outdoor Unit Maximum Input Current [A] Power Supply
Rated Voltage range Outdoor Unit Indoor
Indoor Unit Outdoor Unit Total MCA MFA
Hz Volts Min. Max. Cooling Heating Unit
AC035TNLDKC/EA AC035TXADKC/EA 50 220 to 240 198 264 10.0 - 1.7 11.7 11.7 12.9
AC052TNLDKC/EA AC052TXADKC/EA 50 220 to 240 198 264 20.0 - 2.3 22.3 22.3 25.0
AC071TNMDKC/EA AC071TXADKC/EA 50 220 to 240 198 264 20.0 - 2.3 22.3 22.3 25.0
AC100TNMDKC/EA AC100TXADKC/EA 50 220 to 240 198 264 24.0 - 2.5 26.5 26.5 30.0
AC100TNMDKC/EA AC100TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC120TNMDKC/EA AC120TXADKC/EA 50 220 to 240 198 264 32.0 - 2.5 34.5 34.5 40.0
AC120TNMDKC/EA AC120TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC140TNMDKC/EA AC140TXADKC/EA 50 220 to 240 198 264 32.0 - 2.5 34.5 34.5 40.0
AC140TNMDKC/EA AC140TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC160TNMDKC/EA AC160TXADKC/EA 50 220 to 240 198 264 32.0 - 3.5 35.5 35.5 40.0
AC160TNMDKC/EA AC160TXADNC/EA 50 380 to 415 342 456.5 16.1 - 3.5 19.6 19.6 19.6

NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
Duct

(1) AC035TNLDKC/EA+AC035TXADKC/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 3.3 2.4 0.86 3.4 2.5 0.88 3.6 2.6 0.89 3.7 2.7 0.91 3.7 2.7 0.92 3.9 2.6 0.93 4.1 2.6 0.95
21 3.4 2.4 0.73 3.5 2.5 0.75 3.7 2.6 0.76 3.8 2.7 0.78 3.9 2.6 0.79 4.1 2.6 0.80 4.3 2.6 0.81
35 3.1 2.4 1.01 3.3 2.5 1.03 3.4 2.6 1.05 3.5 2.6 1.08 3.6 2.6 1.09 3.7 2.6 1.10 3.9 2.5 1.12
46 2.9 2.3 1.29 3.0 2.4 1.32 3.2 2.4 1.35 3.3 2.5 1.37 3.3 2.5 1.39 3.5 2.5 1.40 3.7 2.4 1.43
48 2.6 2.2 1.23 2.8 2.2 1.25 2.9 2.3 1.28 3.0 2.4 1.30 3.0 2.4 1.32 3.2 2.3 1.33 3.4 2.3 1.35
50 2.4 2.1 1.16 2.5 2.1 1.18 2.6 2.2 1.21 2.7 2.2 1.23 2.8 2.2 1.24 2.9 2.2 1.25 3.0 2.2 1.28

(2) AC052TNLDKC/EA+AC052TXADKC/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 4.9 4.0 1.12 5.1 4.1 1.14 5.3 4.3 1.16 5.5 4.4 1.19 5.6 4.4 1.20 5.9 4.3 1.21 6.2 4.2 1.23
21 4.6 3.8 1.17 4.9 4.0 1.20 5.1 4.1 1.22 5.3 4.2 1.25 5.4 4.2 1.26 5.6 4.1 1.27 5.9 4.0 1.30
35 4.4 3.8 1.47 4.7 3.9 1.50 4.9 4.0 1.53 5.0 4.1 1.57 5.1 4.1 1.58 5.4 4.0 1.60 5.6 4.0 1.63
46 4.3 3.9 1.32 4.5 4.0 1.35 4.7 4.1 1.38 4.9 4.3 1.40 5.0 4.2 1.42 5.2 4.2 1.43 5.5 4.1 1.46
48 4.2 3.9 1.25 4.5 4.0 1.27 4.6 4.1 1.30 4.8 4.2 1.33 4.9 4.2 1.34 5.1 4.2 1.35 5.4 4.1 1.38
50 4.1 3.8 1.17 4.4 4.0 1.20 4.5 4.1 1.22 4.7 4.2 1.25 4.8 4.2 1.26 5.0 4.1 1.27 5.3 4.0 1.30

(3) AC071TNMDKC/EA+AC071TXADKC/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 6.8 5.0 2.10 7.2 5.2 2.14 7.5 5.3 2.18 7.7 5.5 2.23 7.9 5.4 2.25 8.3 5.4 2.27 8.7 5.3 2.32
21 7.8 5.5 2.19 8.3 5.7 2.23 8.6 5.9 2.28 8.9 6.1 2.32 9.0 6.0 2.35 9.5 5.9 2.37 10.0 5.8 2.42
35 5.8 4.6 2.00 6.1 4.8 2.05 6.3 4.9 2.09 6.5 5.1 2.13 6.6 5.0 2.15 7.0 5.0 2.17 7.3 4.9 2.22
46 5.7 4.5 2.76 6.0 4.7 2.82 6.3 4.8 2.88 6.5 5.0 2.93 6.6 4.9 2.96 7.0 4.9 2.99 7.3 4.8 3.05
48 5.3 4.3 2.67 5.6 4.5 2.73 5.9 4.6 2.78 6.0 4.8 2.84 6.2 4.7 2.87 6.5 4.7 2.90 6.8 4.6 2.95
50 5.0 4.2 2.58 5.2 4.3 2.64 5.4 4.4 2.69 5.6 4.6 2.75 5.7 4.5 2.77 6.0 4.5 2.80 6.3 4.4 2.86

NOTE
•• The performance table shows the average value of each conditions.
3. Capacity Table
Duct

(4) AC100TNMDKC/EA+AC100TXAD*C/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 9.7 7.5 2.46 10.2 7.8 2.51 10.7 8.0 2.56 11.0 8.2 2.61 11.2 8.2 2.64 11.8 8.1 2.66 12.4 7.9 2.71
21 10.5 7.9 2.44 11.0 8.1 2.49 11.5 8.4 2.54 11.8 8.7 2.59 12.1 8.6 2.61 12.7 8.5 2.64 13.3 8.3 2.69
35 8.8 8.1 2.94 9.3 8.4 3.00 9.7 8.6 3.06 10.0 8.9 3.13 10.2 8.8 3.16 10.7 8.7 3.19 11.2 8.6 3.25
46 7.6 6.9 3.45 8.0 7.1 3.52 8.3 7.4 3.59 8.6 7.6 3.66 8.8 7.5 3.70 9.2 7.4 3.74 9.7 7.3 3.81
48 7.1 6.9 3.20 7.5 7.1 3.26 7.8 7.3 3.33 8.1 7.6 3.40 8.2 7.5 3.43 8.6 7.4 3.47 9.1 7.3 3.54
50 6.7 6.9 2.95 7.0 7.1 3.01 7.3 7.3 3.07 7.6 7.5 3.13 7.7 7.4 3.16 8.1 7.4 3.20 8.5 7.2 3.26

(5) AC120TNMDKC/EA+AC120TXAD*C/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 11.8 9.1 2.64 12.4 9.3 2.70 12.9 9.6 2.75 13.3 9.9 2.81 13.6 9.8 2.84 14.3 9.7 2.86 15.0 9.5 2.92
21 11.2 8.6 2.78 11.8 8.9 2.84 12.3 9.2 2.90 12.7 9.4 2.96 13.0 9.4 2.99 13.6 9.3 3.01 14.3 9.1 3.08
35 10.7 8.4 3.45 11.3 8.6 3.52 11.7 8.9 3.60 12.1 9.2 3.67 12.3 9.1 3.71 13.0 9.0 3.74 13.6 8.8 3.82
46 9.3 8.2 3.13 9.8 8.4 3.19 10.2 8.7 3.26 10.5 8.9 3.33 10.7 8.9 3.36 11.3 8.8 3.39 11.8 8.6 3.46
48 8.3 7.5 2.96 8.7 7.7 3.02 9.1 7.9 3.08 9.4 8.2 3.14 9.6 8.1 3.17 10.0 8.0 3.20 10.5 7.9 3.27
50 7.3 6.8 2.78 7.7 7.0 2.84 8.0 7.2 2.90 8.2 7.4 2.96 8.4 7.3 2.99 8.8 7.3 3.01 9.3 7.1 3.08

(6) AC140TNMDKC/EA+AC140TXAD*C/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 13.1 9.8 3.18 13.8 10.1 3.25 14.3 10.5 3.31 14.8 10.8 3.38 15.1 10.7 3.42 15.8 10.6 3.45 16.6 10.4 3.52
21 12.4 9.4 3.35 13.1 9.7 3.42 13.6 10.0 3.49 14.1 10.3 3.56 14.4 10.2 3.60 15.1 10.1 3.63 15.8 9.9 3.70
35 11.9 8.9 4.16 12.5 9.2 4.24 13.0 9.5 4.33 13.4 9.8 4.42 13.7 9.7 4.46 14.4 9.6 4.51 15.1 9.4 4.60
46 10.1 8.7 3.77 10.6 9.0 3.85 11.0 9.3 3.92 11.4 9.6 4.01 11.6 9.5 4.05 12.2 9.4 4.09 12.8 9.2 4.17
48 8.9 7.9 3.56 9.4 8.1 3.63 9.7 8.4 3.71 10.1 8.6 3.78 10.3 8.5 3.82 10.8 8.4 3.86 11.3 8.3 3.94
50 7.7 7.0 3.35 8.1 7.2 3.42 8.4 7.4 3.49 8.7 7.7 3.56 8.9 7.6 3.60 9.3 7.5 3.63 9.8 7.4 3.70

NOTE
• The performance table shows the average value of each conditions.
3. Capacity Table
Duct

(7) AC160TNMDKC/EA+AC160TXAD*C/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 17.1 12.8 4.67 18.0 13.2 4.77 18.8 13.6 4.86 19.3 14.0 4.96 19.7 13.9 5.01 20.7 13.7 5.06 21.8 13.5 5.16
21 15.6 12.1 4.57 16.4 12.4 4.66 17.1 12.8 4.76 17.6 13.2 4.85 18.0 13.1 4.90 18.9 13.0 4.95 19.8 12.7 5.05
35 14.0 11.3 4.91 14.7 11.6 5.01 15.3 12.0 5.11 15.8 12.4 5.22 16.1 12.2 5.27 16.9 12.1 5.32 17.8 11.9 5.43
46 10.0 9.8 4.08 10.5 10.1 4.16 10.9 10.4 4.25 11.3 10.8 4.33 11.5 10.7 4.38 12.1 10.6 4.42 12.7 10.3 4.51
48 9.6 9.4 4.02 10.1 9.7 4.10 10.5 10.0 4.18 10.9 10.3 4.27 11.1 10.2 4.31 11.6 10.1 4.35 12.2 9.9 4.44
50 9.3 9.0 3.95 9.7 9.3 4.03 10.2 9.6 4.12 10.5 9.9 4.20 10.7 9.8 4.24 11.2 9.7 4.28 11.8 9.5 4.37

NOTE
• The performance table shows the average value of each conditions.
4. Dimensional Drawing
Duct

AC035TNLDKC/EA
Units : mm [inches]

566
382
312
7.8
100 173
1 99
71

86 52
173
566 5

7
746 Suspension podition
8
316 Suspension podition
440

4-28

6 5x100=500
542 Air outlet duct flange
700
16-Ø3.2
440

700
800 500 4
19
1 50
1 00
23.2

2 1 3

NO Name Description
1 Liquid pipe connection Φ6.35(1/4)
2 Gas pipe connection Ø9.52 (3/8)
3 Drain pipe connection without drain pump VP25 (OD ø32,ID ø25)
4 Drain pipe connection with drain pump VP25 (OD ø32,ID ø25)
5 Power supply/Communication connection -
6 Air discharge grille flange -
7 Return air side -
8 Hook ø9.52 or M10
4. Dimensional Drawing
Duct

AC052TNLDKC/EA, AC071TNMDKC/EA
Units : mm [inches]

[9-13/16]
250

Description
No. Name
AC052TNLDKC/EA AC071TNMDKC/EA
1 Liquid pipe connection Φ6.35(1/4)
2 Gas pipe connection Φ12.7(1/2) Φ15.88(5/8)
3 Drain pipe connection VP-25(OD32, ID25)
4 Power supply & Communication wiring conduit
5 Air suction flange
6 Air discharge flange
7 Hook Use M8~M10 bolt(4ea)
4. Dimensional Drawing
Duct

AC100TNMDKC/EA, AC120TNMDKC/EA, AC140TNMDKC/EA


Units : mm [inches]

25 or More
[1]
25or More
[1]
6

Ceiling
1350 [53-1/8]
7 500 [19-11/16] or More
Air Inlet (Service Space)

700 [27-9/16] or More


740 [29-1/8]

(Service Space)
[27-9/16]

[23-3/4]
700

604

Air Outlet
1300 [51-3/16] 5
1402 [55-3/16]
Air Inlet Air Outlet 5 2 1 3 6

[2 X 4-1/2 = 9-1/16]
2 X 115 = 230
94[3-11/16]
53 [2-1/8]
[11-13/16]
[10-5/8]

[10-5/8]
270

270

300

[1-1/16]
[7-1/4]

[6-1/2]
185

166

27

125
[4-15/16] 4
58 [2-1/4]
1268 [49-15/16] 213
[8-3/8]
11 X 100 = 1100
[11 X 3-15/16 = 43-5/16] 324
84 [3-5/16] [12-3/4]

No. Name Description


1 Liquid pipe connection Ø9.52 (3/8)
2 Gas pipe connection Ø15.88 (5/8)
3 Drain pipe VP25(OD32, ID25)
4 Power & Communication Conduits
5 Air suction flange
6 Air discharge flange
7 Hook Use M8~M10 bolt (4ea)
4. Dimensional Drawing
Duct

AC160TNMDKC/EA
Units : mm [inches]

1236
[ 48-5/8 ]
1200 500[ 9-11/16 ] or More
[ 47-1/4 ] (Service Space)

650[ 25-5/8 ] or More


(Service Space)
[ 27-3/16 ]

[ 21-1/16 ]
[ 25-5/8 ]
650
690

534

1334
[ 52-1/2 ]
2 1

122 [ 4-13/16 ]
137 [ 5-3/8 ]
27 [ 1-1/16 ]
[ 7-7/8 ]

[ 14-3/16 ]
200

360

351
[ 13-13/16 ] 3
6x150=900
406
[ 6x5-7/8=35-7/16 ] [ 16 ]
50 [ 2 ] 480
5 [ 18- 7/8 ]

No. Name Description

1 Liquid pipe connection Φ9.52(3/8)


2 Gas pipe connection Φ19.05(3/4)
3 Drain pipe connection VP-25 (OD32, iD25)
Power supply & Communication
4 -
wiring conduit
5 Hook Use M8-M10 bolt (4ea)
5. Center of Gravity
Duct

AC035TNLDKC/EA
Units : mm [inches]

Model A B C
AC035TNLDKC/EA 450 335 105
5. Center of Gravity
Duct

AC052TNLDKC/EA, AC071TNMDKC/EA
AC100TNMDKC/EA, AC120TNMDKC/EA, AC140TNMDKC/EA Units : mm [inches]

A B C D E F
AC052TNLDKC/EA
AC071TNMDKC/EA 450 [17-11/16] 220 [8-5/8] 1100 [43-5/16] 520 [20-1/2] 200 [7-7/8] 100 [3-15/16]

AC100TNMDKC/EA
AC120TNMDKC/EA 700 [27-9/16] 265 [10-7/16] 1350 [53-1/8] 650 [25-5/8] 300 [11-13/16] 150 [5-15/16]
AC140TNMDKC/EA
5. Center of Gravity
Duct

AC160TNMDKC/EA
Units : mm [inches]

C
F

Model A B C D E F

AC160TNMDKC/EA 1200 590 360 190 650 345


6. El
Electric
ectrical
al Wiring Diagr
Diagram
am
Duct

AC035TNLDKC/EA

MAIN PCB Printed circuit board(MAIN) M-BLDC BLDC Motor ROOM-TH(10K) Thermistor ROOM
DISPLAY PCB Printed circuit board(Display_Option) EEV Electronic Expansion Valve(Option) EVA IN-TH(10K) Thermistor EVA IN
FLOAT SWITCH Switch of the float of Drain SPI S-Plasma ion(Option) EVA OUT-TH(10K) Thermistor EVA OUT

NOTE
• This wiring diagram applies only to the Indoor unit.
• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
• Protective earth(screw)
6. El
Electric
ectrical
al Wiring Diagram
Diagram
Duct

AC052TNLDKC/EA, AC071TNMDKC/EA, AC100TNMDKC/EA, AC120TNMDKC/EA


AC140TNMDKC/EA

SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)

M-BLDC BLDC Motor EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)

NOTE
• This wiring diagram applies only to the Indoor unit.
• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
• Protective earth(screw)
6. Electrical Wiring Diagram
Duct

AC160TNMDKC/EA

MAIN PBA Printed Circuit Board(MAIN) M-BLDC BLDC Motor ROOM(10K) Thermistor ROOM OUT(10K)
BLDC DRIVER PBA Printed Circuit Board(BLDC DRIVER) EEV Electronic Expansion Valve EVA-IN(10K) Thermistor EVA IN(10K)
SUB PBA Printed Circuit Board(SUB) EXT_CONTROL EXTERNAL_CONTROL EVA-OUT(10K) Thermistor EVA OUT(10K)
EMI PBA Printed circuit board(EMI) DISCHARGE(10K) Thermistor DISCHARGE(10K)

NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
Duct

Sound Pressure level


Unit: dB(A)
Discharge Suction Model HIGH MID LOW
Duct Duct AC035TNLDKC/EA 30 28 26
2m 2m
AC052TNLDKC/EA 33 30 27
AC071TNMDKC/EA 37 33 29
AC100TNMDKC/EA 36 33 30
Microphone

• NC Curve
1) AC035TNLDKC/EA 2) AC052TNLDKC/EA

3) AC071TNMDKC/EA 4) AC100TNMDKC/EA

NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
7. Sound D
Data
ata
Duct

Sound Pressure level


Unit: dB(A)
Discharge Suction Model HIGH MID LOW
Duct Duct AC120TNMDKC/EA 37 34 30
2m 2m
AC140TNMDKC/EA 37 34 30
AC160TNMDKC/EA 44 40 36

Microphone

• NC Curve
1) AC120TNMDKC/EA 2) AC140TNMDKC/EA

3) AC160TNMDKC/EA

NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
8. Fan Characteristics
Duct

1) AC035TNLDKC/EA

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤ SP ≤2.5 01C17C-1C05F6-272300-370008 2.5< SP ≤4 01C17C-1C097B-272300-370008

19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]

External Static Pressure [mmAq]


14 14
13 13
12 12
11 11
10 10
9 9 HIGH
8 HIGH 8 MIDDLE
7 7
6 MIDDLE 6 Upper limit of
external
5 Upper limit of 5 static pressure
4 external 4
static pressure 2
3 3
Lower limit of
2 1 Lower limit of 2 external
1 external 1
static pressure static pressure
0 0
5 10 15 20 25 5 10 15 20 25
LOW LOW
Air Flow rate [CMM] Air Flow rate [CMM]

2) AC052TNLDKC/EA

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤ SP ≤3 01B17C-1C00F1-273400-374000 3< SP ≤5 01B17C-1C0457-273400-374000

19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]

External Static Pressure [mmAq]

14 14
13 13
12 12
11 11
10 10
9 9
8 8
7 7 HIGH Upper limit of
6 6 external
5 HIGH Upper limit of 5 static pressure
external MIDDLE 2
4 static pressure 4
3 MIDDLE 3 LOW
1 Lower limit of Lower limit of
2 LOW 2 external
1 external 1
static pressure static pressure
0 0
5 10 15 20 25 5 10 15 20 25

Air Flow rate [CMM] Air Flow rate [CMM]


8. Fan Characteristics
Duct

3) AC071TNMDKC/EA

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0 ≤ SP ≤ 3 01B17C-1C0456-274700-376000 3 < SP ≤6 01B17C-1C04CB-274700-376000

19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]

External Static Pressure [mmAq]


14 14
13 13
12 12
11 11
10 10
9 9 HIGH
8 8 Upper limit of
7 7 external
6 HIGH 6 static pressure
5 Upper limit of 5 MIDDLE 2
external
4 static pressure 4
3 MIDDLE 3
1 Lower limit of Lower limit of
2 2 external
1 external 1
static pressure static pressure
0 0
10 15 20 25 10 15 20 25
LOW LOW
Air Flow rate [CMM] Air Flow rate [CMM]

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
6<SP≤9 01B17C-1C083E-274700-376000 9<SP≤12 01B17C-1C09A2-274700-376000

19 19
18 18
17 17
16 16
15 15 HIGH
External Static Pressure [mmAq]
External Static Pressure [mmAq]

14 14
13 13 Upper limit of
12 HIGH 12 external
11 11 static pressure 4
10 Upper limit of 10
9 external 9 MIDDLE
8 static pressure 3 8
7 MIDDLE 7
6 6
Lower limit of
5 5 external
4 Lower limit of 4 static pressure
3 external 3
2 static pressure 2
1 LOW 1 LOW
0 0
10 15 20 25 10 15 20 25

External Static Pressure(mmAq) Option Code


5
12<SP≤15 01B17C-1C09E9-274700-376000

19
18 HIGH
17
16
15
External Static Pressure [mmAq]

Upper limit of
14 external 5
13 static pressure
12
11 MIDDLE
10
9
8 Lower limit of
7 external
6 static pressure
5
4
3 LOW
2
1
0
10 15 20 25
8. Fan Characteristics
Duct

4) AC100TNMDKC/EA

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤4 01B17C-1C00C4-276400-374040 4<SP≤8 01B17C-1C0552-276400-374040

19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]

External Static Pressure [mmAq]


14 14
13 13
12 12
11 11
10 10 Upper limit of
9 9 HIGH external
static pressure
8 8
7 7 MIDDLE 2
6 HIGH Upper limit of
external 6
5 static pressure 5
4 MIDDLE 4
3 1 3 Lower limit of
2 Lower limit of 2 external
1 LOW external 1 LOW static pressure
static pressure
0 0
20 25 30 35 40 45 20 25 30 35 40 45

Air Flow rate [CMM] Air Flow rate [CMM]

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 01B17C-1C05C5-276400-374040 12<SP≤15 01B17C-1C0908-276400-374040

19 19
18 18
17 17 Upper limit of
16 16 HIGH external
static pressure
15 15
External Static Pressure [mmAq]
External Static Pressure [mmAq]

14 Upper limit of 14 MIDDLE 4


13 HIGH external 13
static pressure
12 12
11 3 11
10 MIDDLE 10 Lower limit of
9 9 external
8 8 static pressure
7 7 LOW
6 Lower limit of 6
5 LOW external 5
4 static pressure 4
3 3
2 2
1 1
0 0
20 25 30 35 40 45 20 25 30 40 45
Flowrate [CMM]
8. Fan Characteristics
Duct

5) AC120TNMDKC/EA

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤5.2 01B17C-1C0424-277800-374040 5.2<SP≤8 01B17C-1C0489-277800-374040

19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]

External Static Pressure [mmAq]


14 14
13 13
12 12
11 11
10 10 HIGH Upper limit of
9 9 external
static pressure
8 Upper limit of 8
HIGH 2
7 external 7 MIDDLE
6 static pressure 6
5 MIDDLE 5
4 1 4 Lower limit of
3 3 external
2 Lower limit of 2 static pressure
1 external 1 LOW
LOW static pressure
0 0
20 25 30 35 40 45 50 20 25 30 35 40 45 50

Air Flow rate [CMM] Air Flow rate [CMM]

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 01B17C-1C04FE-277800-374040 12<SP≤15 01B17C-1C0940-277800-374040

19 19
18 18
17 17 HIGH
16 16 Upper limit of
15 HIGH 15 external
External Static Pressure [mmAq]
External Static Pressure [mmAq]

14 14 static pressure 4
13 Upper limit of 13
12 external 12 MIDDLE
static pressure
11 3 11
10 MIDDLE 10
9 9 Lower limit of
8 8 external
7 7 static pressure
6 Lower limit of 6
5 external 5
4 static pressure 4 LOW
3 LOW 3
2 2
1 1
0 0
20 25 30 35 40 45 50 20 25 30 35 40 45 50
8. Fan Characteristics
Duct

6) AC140TNMDKC/EA

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤5.2 01B17C-1C0424-278CA0-374040 5.2<SP≤8 01B17C-1C0489-278CA0-374040

19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]

External Static Pressure [mmAq]


14 14
13 13
12 12
11 11
10 10 HIGH Upper limit of
9 9 external
static pressure
8 Upper limit of 8
HIGH 2
7 external 7 MIDDLE
6 static pressure 6
5 MIDDLE 5
4 1 4 Lower limit of
3 3 external
2 Lower limit of 2 static pressure
1 external 1 LOW
LOW static pressure
0 0
20 25 30 35 40 45 50 20 25 30 35 40 45 50

Air Flow rate [CMM] Air Flow rate [CMM]

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 01B17C-1C04FE-278CA0-374040 12<SP≤15 01B17C-1C0940-278CA0-374040

19 19
18 18
17 17 HIGH
16 16 Upper limit of
15 HIGH 15 external
External Static Pressure [mmAq]
External Static Pressure [mmAq]

14 14 static pressure 4
13 Upper limit of 13
12 external 12 MIDDLE
static pressure
11 3 11
10 MIDDLE 10
9 9 Lower limit of
8 8 external
7 7 static pressure
6 Lower limit of 6
5 external 5
4 static pressure 4 LOW
3 LOW 3
2 2
1 1
0 0
20 25 30 35 40 45 50 20 25 30 35 40 45 50

External Static Pressure(mmAq) Option Code


5
12< SP ≤15 01B17C-1C59C8-274750-376000

19
External Static Pressure [mmAq]

18
HIGH Upperlimit of
17 external
16 static pressure
15
5 Lowerlimit of
14 external
13 static pressure
12 MID
11
10
9
8 LOW
7
6
5
4
3
2
1
0
10 15 20 25

Air Flow Rate [CMM]


13 13 static pressure

External St

External St
12 12
Upperlimit of 4 Lowerlimit of
11 external 11 external
10 static pressure 10 static pressure
9 9 MID
8 3 Lowerlimit of 8
external
7 static pressure 7
6 6

8. Fan Characteristics 5
4
3 MID
HIGH 5
4
3
LOW

2 2
LOW
1 1
Duct 0
10 15 20 25
0
10 15 20 25

Air Flow Rate [CMM] Air Flow Rate [CMM]

7) AC160TNMDKC/EA

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤5.2 01116C-1C0924-27A000-370040 5.2<SP≤8 01116C-1C0978-27A000-370040

19 19
18 18
17 17
16 16
15 15 HIGH
External Static Pressure [mmAq]

External Static Pressure [mmAq]


14 14
13 13
12 HIGH 12
11 11
10 10 MIDDLE Upper limit of
9 9 external
8 MIDDLE 8 static pressure
7 Upper limit of 7 2
6 external 6
static pressure LOW
5 5
4 LOW 1 4 Lower limit of
3 3 external
2 Lower limit of 2 static pressure
1 external 1
static pressure
0 0
35 40 45 50 55 60 35 40 45 50 55 60

Air Flow rate [CMM] Air Flow rate [CMM]

External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 01116C-1C09CC-27A000-370040 12<SP≤15 01116C-1C09FF-27A000-370040

19 19
18 HIGH 18 HIGH
17 17
16 16 MIDDLE Upper limit of
15 15 external
External Static Pressure [mmAq]
External Static Pressure [mmAq]

14 14 static pressure 4
13 MIDDLE Upper limit of
external 13
12 static pressure 12
11 3 11
10 10 LOW
9 9 Lower limit of
external
8 LOW 8 static pressure
7 7
6 Lower limit of 6
5 external 5
static pressure
4 4
3 3
2 2
1 1
0 0
35 40 45 50 55 60 35 40 45 50 55 60

NOTE
•• Adjust option code according to the actual installation condition (external static pressure).
•• The graphs display the available external static pressure range of installed indoor units. Therefore, they do
not reflect the actual change of external static pressure and airflow rate according to adjusted airflow
(High-Mid-Low) of installed indoor units.
Ceiling

1. Specification 113
2. Summary Table 125
3. Capacity Table 126
4. Dimensional Drawing 128
5. Center of Gravity 131
6. Electrical Wiring Diagram 133
7. Sound Data 135
8. Temperature and air flow distribution 137
Features
 & Benefits
Ceiling Type - Slim yet functional design

Distribute refreshing airflow where needed with a


compact, flexible design
Samsung’s Ceiling Type indoor unit has 2-way installation
options for the ceiling and floor, enabling more efficient
use of available space. Users can enjoy crisp, powerful air
throughout their entire space from the compact unit in
the ceiling or floor.

Small package, big performance


The Samsung Ceiling Type air conditioner boasts a
slim, compact design—half the size of conventional
* In case of floor installation type, 5.2kW model only.
products—with cooling power comparable to larger
units.

Size Weight

200%

136%
Smaller 123% Lighter
118%
100% 100%
Company B

Company B
Company A

Company A
SAMSUNG

SAMSUNG

7.1kW Model

Choice of installation options


Depending on the available space and the purpose of the
air conditioner, the indoor unit can be installed behind
the ceiling the ceiling or on the floor.

Under Ceiling
Features
 & Benefits
Ceiling Type (large capacity) - Powerful cooling with a long distance wind

Combine simple neat and innovated technologies to Simple display


experience superior performance and easy operation
The simple display design with its rounded corners adds
Samsung has been rewriting product descriptions a neat and tidy feeling to your interior.
beyond the industry standards. As one of such
company's product, Samsung Ceiling focused on sending
"sufficient" amount of conditioned air to "distant" places - Ice Blue : Operating
to cover huge area. For convenient installations and - Yellow Green : Schedule
maintenances, the Ceiling concentrated service direction - Red : Error
on one side. Do not get stressed with air conditioning. - Orange : Filter Alarm
Time Limit + Operating Pattern
Just leave it to Samsung Ceiling.

Single side installation


Due to difficulties in accessing their installed locations,
easiness to maintain ceiling indoor units should be
considered seriously. Relatively thin width of the product
makes locating all service ports at one side difficult.
However, for better customer experience, Samsung
challenged to this difficulty.
Fast cooling, 15m air flow
When users need air conditioning, they really need it
quickly. While the ceiling applied latest flow-efficient
blowers to increase amount of air it discharges, it also
mounted single BLDC motor to reduce noises and
possibilities of abrupt changes of modes. With increased
size of inlet area and fluid dynamically designed inner
passages, customers can experience incomparable
cooling power.
Also, with the advanced blade, which can move from
40 to 450, Samsung ceiling type can refreshingly cool
air that reaches every corner of the room with no blind
spots.
1. Specification
Ceiling

System Indoor Unit AC052TNCDKC/EA AC071TNCDKC/EA AC100TNCDKC/EA


Model Name
Outdoor Unit AC052TXADKC/EA AC071TXADKC/EA AC100TXADKC/EA
Mode - Cooling only Cooling only Cooling only
kW 1.7 / 5.0 / 5.6 2.3 / 7.1 / 9.2 3.0 / 10.0 / 12.0
Cooling
Capacity Btu/h 5,800/17,000/19,110 7,850/24,000/31,390 10,240/34,000/40,940
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.48/1.515/1.9 0.4/2.0/3.3 0.6/3.125/4.7
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 2.8/7.3/9.0 2.4/9.5/15.0 3.0/14.8/20.4
Power
(Min/Std/Max) Heating A - - -
MCA A 21.5 22.5 26.5
Current
MFA A 25.0 25.0 30.0
EER Cooling - 3.30 3.55 3.20
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 6.35 (1/4) 6.35 (1/4) 9.52 (3/8)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 12.7 (1/2) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 30 50 50
(ODU-IDU) Elevation m 20 30 30
Chargeless m 5 5 30
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 1.30 2.00 3.00
1. Specification
Ceiling

Indoor Indoor Unit AC052TNCDKC/EA AC071TNCDKC/EA AC100TNCDKC/EA


Unit Model Name
Outdoor Unit AC052TXADKC/EA AC071TXADKC/EA AC100TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Type - Sirocco Sirocco Sirocco
Quantity EA 2 3 4
m³/min 12.6/11.3/10.0 23.0/19.0/15.0 26.0/23.0/19.0
Fan Air Flow Rate H/M/L
l/s 210/190/170 380/320/250 430/380/320
External mmAq - - -
Min/Std/Max
Static Pressure Pa - - -
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 40 153 x 1 244 x 1
Drain Drain Pipe Φ, ㎜ ID18mm Hose VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 41/39/36 45/40/35 42/38/34
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 20 32.6 42
External Shipping Weight kg 25 38 48
Dimension Net Dimensions (WxHxD) ㎜ 1,000 x 200 x 650 1,350 X 235 X 675 1,650 x 235 x 675
Shipping Dimensions (WxHxD) ㎜ 1,074 x 294 x 726 1,439 X 321 X 758 1,739 x 321 x 758
Casing Material - ABS GI Steel Plate GI Steel Plate
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - - - -
Drain Pump Max. lifting Height
㎜ / Liter/h - - -
/ Displacement
External
- - - -
Model
Internal
- - - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - - -
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - - Optional Optional
1. Specification
Ceiling

Outdoor Indoor Unit AC052TNCDKC/EA AC071TNCDKC/EA AC100TNCDKC/EA


Unit Model Name
Outdoor Unit AC052TXADKC/EA AC071TXADKC/EA AC100TXADKC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG9TK3150FE4 UG8T265FXAEW UG8T300FUBJU
Type - Twin BLDC Twin BLDC Twin BLDC
Compressor Output kW 1.42 2.32 2.82
Type - POE POE POE
Oil
Initial charge cc 500 700 1,200
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 1 1
m³/min 50 60 76
Air Flow Rate
l/s 840 1,000 1,270
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 125 x 1 125 x 1 125 x 1
Sound Pressure
Cooling dB(A) 50 50 53
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 40.5 52.5 71.0
External Shipping Weight kg 43.5 56.5 76.0
Dimension Net Dimensions (WxHxD) ㎜ 880 x 638 x 310 880 x 798 x 310 940 x 998 x 330
Shipping Dimensions (WxHxD) ㎜ 1,023 x 730 x 413 1,023 x 881 x 413 995 x 1,096 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Ceiling

System Indoor Unit AC100TNCDKC/EA AC120TNCDKC/EA AC120TNCDKC/EA


Model Name
Outdoor Unit AC100TXADNC/EA AC120TXADKC/EA AC120TXADNC/EA
Mode - Cooling only Cooling only Cooling only
kW 3.0 / 10.0 / 12.0 3.5 / 12.1 / 14.0 3.5 / 12.1 / 14.0
Cooling
Capacity Btu/h 10,240/34,000/40,940 11,940/41,500/47,770 11,940/41,500/47,770
Performance
(Min/Std/Max) kW - - -
Heating
Btu/h - - -
Power Input Cooling kW 0.6/3.125/4.7 0.8/3.67/5.3 0.8/3.67/5.5
(Min/Std/Max) Heating kW - - -
Current Input Cooling A 1.5/5.2/7.1 3.7/16.7/23.0 2.1/5.9/8.8
Power
(Min/Std/Max) Heating A - - -
MCA A 18.6 34.5 18.6
Current
MFA A 18.6 40.0 18.6
EER Cooling - 3.20 3.30 3.30
Efficiency
COP Heating - - - -
Type Flare connection Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 50 75 75
(ODU-IDU) Elevation m 30 30 30
Chargeless m 30 30 30
Wiring Min. ㎟ 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 3.00 3.40 3.40
1. Specification
Ceiling

Indoor Indoor Unit AC100TNCDKC/EA AC120TNCDKC/EA AC120TNCDKC/EA


Unit Model Name
Outdoor Unit AC100TXADNC/EA AC120TXADKC/EA AC120TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Type - Sirocco Sirocco Sirocco
Quantity EA 4 4 4
m³/min 26.0/23.0/19.0 30.0/24.0/20.0 30.0/24.0/20.0
Fan Air Flow Rate H/M/L
l/s 430/380/320 500/400/330 500/400/330
External mmAq - - -
Min/Std/Max
Static Pressure Pa - - -
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 244 x 1 244 x 1 244 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 42/38/34 44/41/37 44/41/37
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 42 42 42
External Shipping Weight kg 48 48 48
Dimension Net Dimensions (WxHxD) ㎜ 1,650 x 235 x 675 1,650 x 235 x 675 1,650 x 235 x 675
Shipping Dimensions (WxHxD) ㎜ 1,739 x 321 x 758 1,739 x 321 x 758 1,739 x 321 x 758
Casing Material - GI Steel Plate GI Steel Plate GI Steel Plate
Control Infrared remote control - AR-EC03E AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N MWR-WE13N
Drain Pump - - - -
Drain Pump Max. lifting Height
㎜ / Liter/h - - -
/ Displacement
External
- - - -
Model
Internal
- - - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - - -
Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
Virus Doctor - Optional Optional Optional
1. Specification
Ceiling

Outdoor Indoor Unit AC100TNCDKC/EA AC120TNCDKC/EA AC120TNCDKC/EA


Unit Model Name
Outdoor Unit AC100TXADNC/EA AC120TXADKC/EA AC120TXADNC/EA
Power Supply Ø, #, V, Hz 3,4,380-415,50 1,2,220-240,50 3,4,380-415,50
Type - Fin & Tube Fin & Tube Fin & Tube
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG8T300FUCJU UG5TK1450FJX UG5TK1450FJX
Type - Twin BLDC Twin BLDC Twin BLDC
Compressor Output kW 2.82 4.19 4.19
Type - POE POE POE
Oil
Initial charge cc 1,200 1,700 1,700
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 2 2
m³/min 76 110 110
Air Flow Rate
l/s 1,270 1,840 1,840
Type - BLDC BLDC BLDC
Fan Motor
Output Wxn 125 x 1 125 x 2 125 x 2
Sound Pressure
Cooling dB(A) 53 53 53
Sound Level
Sound Power Level dB(A) - - -
Net Weight kg 71.0 86.5 86.5
External Shipping Weight kg 76.0 96.5 96.5
Dimension Net Dimensions (WxHxD) ㎜ 940 x 998 x 330 940 x 1,210 x 330 940 x 1,210 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,096 x 426 995 x 1,388 x 426 995 x 1,388 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50 -15~50
Temp. Range Heating ℃ - - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Ceiling

System Indoor Unit AC140TNCDKC/EA AC140TNCDKC/EA


Model Name
Outdoor Unit AC140TXADKC/EA AC140TXADNC/EA
Mode - Cooling only Cooling only
kW 3.5 / 13.4 / 15.5 3.5 / 13.4 / 15.5
Cooling
Capacity Btu/h 11,940/45,500/52,890 11,940/45,500/52,890
Performance
(Min/Std/Max) kW - -
Heating
Btu/h - -
Power Input Cooling kW 0.8/4.42/6.4 0.8/4.42/6.4
(Min/Std/Max) Heating kW - -
Current Input Cooling A 3.7/20.4/28.0 2.1/7.1/9.5
Power
(Min/Std/Max) Heating A - -
MCA A 34.5 18.6
Current
MFA A 40.0 18.6
EER Cooling - 3.03 3.03
Efficiency
COP Heating - - -
Type Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 15.88 (5/8) 15.88 (5/8)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5
Piping length Max. m 75 75
(ODU-IDU) Elevation m 30 30
Chargeless m 30 30
Wiring Min. ㎟ 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2
Type - R410A R410A
Refrigerant
Factory Charging kg 3.40 3.40
1. Specification
Ceiling

Indoor Indoor Unit AC140TNCDKC/EA AC140TNCDKC/EA


Unit Model Name
Outdoor Unit AC140TXADKC/EA AC140TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile
Type - Sirocco Sirocco
Quantity EA 4 4
m³/min 34.0/27.0/23.0 34.0/27.0/23.0
Fan Air Flow Rate H/M/L
l/s 570/450/380 570/450/380
External mmAq - -
Min/Std/Max
Static Pressure Pa - -
Type - BLDC BLDC
Fan Motor
Output Wxn 244 x 1 244 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 46/42/38 46/42/38
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 42 42
External Shipping Weight kg 48 48
Dimension Net Dimensions (WxHxD) ㎜ 1,650 x 235 x 675 1,650 x 235 x 675
Shipping Dimensions (WxHxD) ㎜ 1,739 x 321 x 758 1,739 x 321 x 758
Casing Material - GI Steel Plate GI Steel Plate
Control Infrared remote control - AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N
Drain Pump - - -
Drain Pump Max. lifting Height
㎜ / Liter/h - -
/ Displacement
External
- - -
Model
Internal
- - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - -
Displacement
Air Filter - Removable / Washable Removable / Washable
Virus Doctor - Optional Optional
1. Specification
Ceiling

Outdoor Indoor Unit AC140TNCDKC/EA AC140TNCDKC/EA


Unit Model Name
Outdoor Unit AC140TXADKC/EA AC140TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 3,4,380-415,50
Type - Fin & Tube Fin & Tube
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion
Model Name UG5TK1450FJX UG5TK1450FJX
Type - Twin BLDC Twin BLDC
Compressor Output kW 4.19 4.19
Type - POE POE
Oil
Initial charge cc 1,700 1,700
Type - Propeller Propeller
Discharge direction - Front Front
Fan Quantity EA 2 2
m³/min 110 110
Air Flow Rate
l/s 1,840 1,840
Type - BLDC BLDC
Fan Motor
Output Wxn 125 x 2 125 x 2
Sound Pressure
Cooling dB(A) 54 54
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 86.5 86.5
External Shipping Weight kg 96.5 96.5
Dimension Net Dimensions (WxHxD) ㎜ 940 x 1,210 x 330 940 x 1,210 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,388 x 426 995 x 1,388 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50
Temp. Range Heating ℃ - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Ceiling

System Indoor Unit AC160TNCDKC/EA AC160TNCDKC/EA


Model Name
Outdoor Unit AC160TXADKC/EA AC160TXADNC/EA
Mode - Cooling only Cooling only
kW 4.3 / 15.0 / 17.6 4.3 / 15.0 / 17.6
Cooling
Capacity Btu/h 14,670/51,000/60,050 14,670/51,000/60,050
Performance
(Min/Std/Max) kW - -
Heating
Btu/h - -
Power Input Cooling kW 0.95/4.95/6.8 0.8/4.95/6.8
(Min/Std/Max) Heating kW - -
Current Input Cooling A 4.0/22.6/31.0 2.0/8.0/10.0
Power
(Min/Std/Max) Heating A - -
MCA A 35.0 19.1
Current
MFA A 40.0 19.1
EER Cooling - 3.03 3.03
Efficiency
COP Heating - - -
Type Flare connection Flare connection
Liquid Pipe
Φ, ㎜ (inch) 9.52 (3/8) 9.52 (3/8)
Type Flare connection Flare connection
Gas Pipe
Φ, ㎜ (inch) 19.02 (3/4) 19.02 (3/4)
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5
Piping length Max. m 75 75
(ODU-IDU) Elevation m 30 30
Chargeless m 30 30
Wiring Min. ㎟ 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2
Type - R410A R410A
Refrigerant
Factory Charging kg 3.80 3.80
1. Specification
Ceiling

Indoor Indoor Unit AC160TNCDKC/EA AC160TNCDKC/EA


Unit Model Name
Outdoor Unit AC160TXADKC/EA AC160TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 1,2,220-240,50
Type - F&T F&T
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile
Type - Sirocco Sirocco
Quantity EA 4 4
m³/min 37.0/31.0/26.0 37.0/31.0/26.0
Fan Air Flow Rate H/M/L
l/s 620/520/430 620/520/430
External mmAq - -
Min/Std/Max
Static Pressure Pa - -
Type - BLDC BLDC
Fan Motor
Output Wxn 244 x 1 244 x 1
Drain Drain Pipe Φ, ㎜ VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure
H/M/L dB(A) 50/47/43 50/47/43
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 42 42
External Shipping Weight kg 48 48
Dimension Net Dimensions (WxHxD) ㎜ 1,650 x 235 x 675 1,650 x 235 x 675
Shipping Dimensions (WxHxD) ㎜ 1,739 x 321 x 758 1,739 x 321 x 758
Casing Material - GI Steel Plate GI Steel Plate
Control Infrared remote control - AR-EC03E AR-EC03E
System Wired remote control - MWR-WE13N MWR-WE13N
Drain Pump - - -
Drain Pump Max. lifting Height
㎜ / Liter/h - -
/ Displacement
External
- - -
Model
Internal
- - -
Drain Pump Model
Additional Max. lifting
Accessories Height / ㎜ / Liter/h - -
Displacement
Air Filter - Removable / Washable Removable / Washable
Virus Doctor - Optional Optional
1. Specification
Ceiling

Outdoor Indoor Unit AC160TNCDKC/EA AC160TNCDKC/EA


Unit Model Name
Outdoor Unit AC160TXADKC/EA AC160TXADNC/EA
Power Supply Ø, #, V, Hz 1,2,220-240,50 3,4,380-415,50
Type - Fin & Tube Fin & Tube
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion
Model Name UG5TK5450FJX UG5TK5450FJX
Type - Twin BLDC Twin BLDC
Compressor Output kW 4.12 4.12
Type - POE POE
Oil
Initial charge cc 1,700 1,700
Type - Propeller Propeller
Discharge direction - Front Front
Fan Quantity EA 2 2
m³/min 143 143
Air Flow Rate
l/s 2,390 2,390
Type - BLDC BLDC
Fan Motor
Output Wxn 125 x 2 125 x 2
Sound Pressure
Cooling dB(A) 56 56
Sound Level
Sound Power Level dB(A) - -
Net Weight kg 96.0 96.0
External Shipping Weight kg 106.0 106.0
Dimension Net Dimensions (WxHxD) ㎜ 940 x 1,420 x 330 940 x 1,420 x 330
Shipping Dimensions (WxHxD) ㎜ 995 x 1,595 x 425 995 x 1,595 x 425
Casing Material Body - EGI Steel Plate EGI Steel Plate
Operating Cooling ℃ -15~50 -15~50
Temp. Range Heating ℃ - -

NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
Ceiling

Performance Characteristics
Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 5.6 - High 12.6 41
AC052TNCDKC/EA 20.0 Std. 5.0 - Mid 11.3 39
Min. 1.7 - Low 10.0 36
Max. 9.2 - High 23.0 45
AC071TNCDKC/EA 32.6 Std. 7.1 - Mid 19.0 40
Min. 2.3 - Low 15.0 35
Max. 12.0 - High 26.0 42
AC100TNCDKC/EA 42.0 Std. 10.0 - Mid 23.0 38
Min. 3.0 - Low 19.0 34
Max. 14.0 - High 30.0 44
AC120TNCDKC/EA 42.0 Std. 12.1 - Mid 24.0 41
Min. 3.5 - Low 20.0 37
Max. 15.5 - High 34.0 46
AC140TNCDKC/EA 42.0 Std. 13.4 - Mid 27.0 42
Min. 3.5 - Low 23.0 38
Max. 17.6 - High 37.0 50
AC160TNCDKC/EA 42.0 Std. 15.0 - Mid 31.0 47
Min. 4.3 - Low 26.0 43

NOTE
•• Sound data is based on cooling operation.

Electric Characteristics
Model Outdoor Unit Maximum Input Current [A] Power Supply
Rated Voltage range Outdoor Unit Indoor
Indoor Unit Outdoor Unit Total MCA MFA
Hz Volts Min. Max. Cooling Heating Unit
AC052TNCDKC/EA AC052TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC071TNCDKC/EA AC071TXADKC/EA 50 220 to 240 198 264 20.0 - 2.5 22.5 22.5 25.0
AC100TNCDKC/EA AC100TXADKC/EA 50 220 to 240 198 264 24.0 - 2.5 26.5 26.5 30.0
AC100TNCDKC/EA AC100TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC120TNCDKC/EA AC120TXADKC/EA 50 220 to 240 198 264 32.0 - 2.5 34.5 34.5 40.0
AC120TNCDKC/EA AC120TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC140TNCDKC/EA AC140TXADKC/EA 50 220 to 240 198 264 32.0 - 2.5 34.5 34.5 40.0
AC140TNCDKC/EA AC140TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC160TNCDKC/EA AC160TXADKC/EA 50 220 to 240 198 264 32.0 - 3.0 35.0 35.0 40.0
AC160TNCDKC/EA AC160TXADNC/EA 50 380 to 415 342 456.5 16.1 - 3.0 19.1 19.1 19.1

NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
Ceiling

(1) AC052TNCDKC/EA+AC052TXADKC/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 5.0 3.7 1.23 5.2 3.8 1.26 5.5 3.9 1.28 5.6 4.0 1.31 5.7 4.0 1.32 6.0 3.9 1.34 6.3 3.9 1.36
21 5.1 3.7 1.14 5.4 3.9 1.16 5.6 4.0 1.19 5.8 4.1 1.21 5.9 4.1 1.22 6.2 4.0 1.24 6.5 3.9 1.26
35 4.4 3.5 1.43 4.7 3.6 1.46 4.9 3.7 1.48 5.0 3.8 1.52 5.1 3.8 1.53 5.4 3.8 1.55 5.6 3.7 1.58
46 5.0 3.7 2.36 5.2 3.8 2.41 5.4 3.9 2.46 5.6 4.0 2.51 5.7 4.0 2.54 6.0 3.9 2.56 6.3 3.9 2.61
48 4.7 3.6 2.42 5.0 3.7 2.47 5.2 3.8 2.52 5.3 3.9 2.58 5.4 3.9 2.60 5.7 3.8 2.63 6.0 3.7 2.68
50 4.5 3.4 2.48 4.7 3.5 2.54 4.9 3.7 2.59 5.1 3.8 2.64 5.2 3.7 2.67 5.4 3.7 2.69 5.7 3.6 2.75

(2) AC071TNCDKC/EA+AC071TXADKC/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 6.9 5.1 1.99 7.3 5.3 2.03 7.6 5.4 2.08 7.8 5.6 2.12 8.0 5.5 2.14 8.4 5.5 2.16 8.8 5.4 2.20
21 8.1 6.1 1.96 8.5 6.3 2.00 8.9 6.5 2.04 9.1 6.7 2.08 9.3 6.7 2.10 9.8 6.6 2.13 10.3 6.5 2.17
35 6.3 5.5 1.88 6.6 5.6 1.92 6.9 5.8 1.96 7.1 6.0 2.00 7.2 5.9 2.02 7.6 5.9 2.04 8.0 5.8 2.08
46 6.0 5.4 2.65 6.3 5.6 2.71 6.6 5.7 2.76 6.8 5.9 2.82 6.9 5.8 2.85 7.3 5.8 2.88 7.6 5.7 2.93
48 5.5 5.2 2.52 5.8 5.3 2.57 6.1 5.5 2.62 6.3 5.7 2.68 6.4 5.6 2.70 6.7 5.5 2.73 7.0 5.4 2.78
50 5.0 4.9 2.38 5.3 5.1 2.43 5.5 5.2 2.48 5.7 5.4 2.53 5.8 5.3 2.56 6.1 5.3 2.58 6.4 5.2 2.63

(3) AC100TNCDKC/EA+AC100TXAD*C/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 9.7 7.8 2.46 10.2 8.0 2.51 10.7 8.3 2.56 11.0 8.5 2.61 11.2 8.4 2.64 11.8 8.4 2.66 12.4 8.2 2.71
21 10.5 8.1 2.44 11.0 8.4 2.49 11.5 8.6 2.54 11.8 8.9 2.59 12.1 8.8 2.61 12.7 8.7 2.64 13.3 8.6 2.69
35 8.8 6.7 2.94 9.3 6.9 3.00 9.7 7.2 3.06 10.0 7.4 3.13 10.2 7.3 3.16 10.7 7.2 3.19 11.2 7.1 3.25
46 7.6 6.7 3.45 8.0 7.0 3.52 8.3 7.2 3.59 8.6 7.4 3.66 8.8 7.3 3.70 9.2 7.2 3.74 9.7 7.1 3.81
48 7.1 6.5 3.20 7.5 6.7 3.26 7.8 6.9 3.33 8.1 7.1 3.40 8.2 7.0 3.43 8.6 7.0 3.47 9.1 6.8 3.54
50 6.7 6.2 2.95 7.0 6.4 3.01 7.3 6.6 3.07 7.6 6.8 3.13 7.7 6.7 3.16 8.1 6.7 3.20 8.5 6.5 3.26

NOTE
•• The performance table shows the average value of each conditions.
3. Capacity Table
Ceiling

(4) AC120TNCDKC/EA+AC120TXAD*C/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 11.8 8.6 2.64 12.4 8.8 2.70 12.9 9.1 2.75 13.3 9.4 2.81 13.6 9.3 2.84 14.3 9.2 2.86 15.0 9.0 2.92
21 11.2 8.1 2.78 11.8 8.4 2.84 12.3 8.7 2.90 12.7 8.9 2.96 13.0 8.8 2.99 13.6 8.7 3.01 14.3 8.6 3.08
35 10.7 7.9 3.45 11.3 8.2 3.52 11.7 8.4 3.60 12.1 8.7 3.67 12.3 8.6 3.71 13.0 8.5 3.74 13.6 8.3 3.82
46 9.3 7.7 3.13 9.8 7.9 3.19 10.2 8.2 3.26 10.5 8.4 3.33 10.7 8.4 3.36 11.3 8.3 3.39 11.8 8.1 3.46
48 8.3 7.0 2.96 8.7 7.3 3.02 9.1 7.5 3.08 9.4 7.7 3.14 9.6 7.6 3.17 10.0 7.6 3.20 10.5 7.4 3.27
50 7.3 6.4 2.78 7.7 6.6 2.84 8.0 6.8 2.90 8.2 7.0 2.96 8.4 6.9 2.99 8.8 6.9 3.01 9.3 6.7 3.08

(5) AC140TNCDKC/EA+AC140TXAD*C/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 13.1 9.8 3.18 13.8 10.1 3.25 14.3 10.5 3.31 14.8 10.8 3.38 15.1 10.7 3.42 15.8 10.6 3.45 16.6 10.4 3.52
21 12.4 9.4 3.35 13.1 9.7 3.42 13.6 10.0 3.49 14.1 10.3 3.56 14.4 10.2 3.60 15.1 10.1 3.63 15.8 9.9 3.70
35 11.9 8.7 4.16 12.5 9.0 4.24 13.0 9.2 4.33 13.4 9.5 4.42 13.7 9.4 4.46 14.4 9.3 4.51 15.1 9.2 4.60
46 10.1 8.7 3.77 10.6 9.0 3.85 11.0 9.3 3.92 11.4 9.6 4.01 11.6 9.5 4.05 12.2 9.4 4.09 12.8 9.2 4.17
48 8.9 7.9 3.56 9.4 8.1 3.63 9.7 8.4 3.71 10.1 8.6 3.78 10.3 8.5 3.82 10.8 8.4 3.86 11.3 8.3 3.94
50 7.7 7.0 3.35 8.1 7.2 3.42 8.4 7.4 3.49 8.7 7.7 3.56 8.9 7.6 3.60 9.3 7.5 3.63 9.8 7.4 3.70

(6) AC160TNCDKC/EA+AC160TXAD*C/EA

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input


Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 14.6 11.3 3.79 15.4 11.7 3.87 16.1 12.0 3.95 16.6 12.4 4.03 16.9 12.3 4.07 17.7 12.2 4.11 18.6 11.9 4.19
21 13.9 10.8 3.99 14.7 11.1 4.07 15.3 11.5 4.16 15.7 11.8 4.24 16.1 11.7 4.28 16.9 11.6 4.33 17.7 11.3 4.41
35 13.3 9.9 4.66 14.0 10.2 4.75 14.6 10.5 4.85 15.0 10.9 4.95 15.3 10.8 5.00 16.1 10.6 5.05 16.9 10.4 5.15
46 10.6 9.0 4.49 11.2 9.3 4.58 11.7 9.6 4.67 12.0 9.9 4.77 12.3 9.8 4.81 12.9 9.7 4.86 13.5 9.5 4.96
48 9.7 8.4 4.24 10.2 8.6 4.33 10.6 8.9 4.41 11.0 9.2 4.50 11.2 9.1 4.55 11.8 9.0 4.59 12.3 8.8 4.69
50 8.8 7.7 3.99 9.3 8.0 4.07 9.6 8.2 4.16 9.9 8.5 4.24 10.1 8.4 4.28 10.7 8.3 4.33 11.2 8.1 4.41

NOTE
• The performance table shows the average value of each conditions.
4. Dimensional Drawing
Ceiling

AC052TNCDKC/EA
Units : mm [inches]

No. Name Description

1 Liquid pipe connection Φ6.35(1/4)


2 Gas pipe connection Φ12.7(1/2)
3 Drain pipe connection ID18mm [11/16inch] Hose
4 Knockout hole for piping
6 Knockout hole for Fresh air intake Φ50 [2]
7 Knockout hole for drain hose
8 Knockout hole for wiring

NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
4. Dimensional Drawing
Ceiling

AC071TNCDKC/EA
Units : mm [inches]

No. Name Description

1 Gas pipe connection Φ15.88(5/8)


2 Liquid pipe connection Φ6.35(1/4)
3 Drain pipe connection VP-25(OD32, ID25)
4 Power supply & Communication wiring conduit Φ28(1-1/8)
5 Knockout hole for Fresh air intake -

NOTE
• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
4. Dimensional Drawing
Ceiling

AC100TNCDKC/EA, AC120TNCDKC/EA, AC140TNCDKC/EA, AC160TNCDKC/EA


Units : mm [inches]

Description
No. Name
AC100/120/140TNCDKC/EA AC160TNCDKC/EA
1 Liquid pipe connection Φ9.52(3/8)
2 Gas pipe connection Φ15.88(5/8) Φ19.02 (3/4)
3 Drain pipe connection VP-25(OD32, ID25)
4 Air filter
5 Air suction grille
6 Knockout hole for piping (upper)
7 Knockout hole for piping (rear)
8 Conduit Hole Φ28 [1-1/8]
9 Knockout hole for drain hose Φ42 [1-5/16]
10 Knockout hole for Fresh air intake
11 Cover side
12 Knockout hole for piping (side)

NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
5. Center of Gravity
Ceiling

AC052TNCDKC/EA
Units : mm [inches]
5. Center of Gravity
Ceiling

AC071TNCDKC/EA
Units : mm [inches]

100
[4]

[9-1/4]
235
[26-9/16]
675
[12-3/8]
680 315
[26-3/4]
1350
[53-1/8]

AC100TNCDKC/EA, AC120TNCDKC/EA, AC140TNCDKC/EA, AC160TNCDKC/EA


Units : mm [inches]
6. Electrical Wiring Diagram
Ceiling

AC052TNCDKC/EA

SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
FLOAT S/W Switch of the float of Drain EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)

NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
6. Electrical Wiring Diagram
Ceiling

AC071TNCDKC/EA, AC100TNCDKC/EA, AC120TNCDKC/EA, AC140TNCDKC/EA, AC160TNCDKC/EA

SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
M-BLDC BLDC Motor EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)

NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow : blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remotecontroller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
Ceiling

Sound Pressure level


Unit: dB(A)

1m Model HIGH MID LOW


AC052TNCDKC/EA 41 39 36
1m
AC071TNCDKC/EA 45 40 35
AC100TNCDKC/EA 42 38 34
AC120TNCDKC/EA 44 41 37
Microphone

• NC Curve
1) AC052TNCDKC/EA 2) AC071TNCDKC/EA

3) AC100TNCDKC/EA 4) AC120TNCDKC/EA

NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
7. Sound Data
Ceiling

Sound Pressure level


Unit: dB(A)

1m
Model HIGH MID LOW
AC140TNCDKC/EA 46 42 38

1m
AC160TNCDKC/EA 50 47 43

Microphone

• NC Curve
1) AC140TNCDKC/EA 2) AC160TNCDKC/EA

NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
8. Temperature and air flow distribution
Ceiling

AC052TNCDKC/EA (Ceiling Installation)


•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 50 degree) (Discharge angle : 50 degree)

AC052TNCDKC/EA (Floor Installation)

•• Cooling Air Velocity distribution •• Cooling temperature distribution


(Discharge angle : 50 degree) (Discharge angle : 50 degree)

AC071TNCDKC/EA (Ceiling Installation)

• Cooling Air Velocity distribution


(Discharge angle : 32 degree)

• Cooling temperature distribution


(Discharge angle : 32 degree)
8. Temperature and air flow distribution
Ceiling (Ceiling Installation)

AC100TNCDKC/EA
• Cooling Air Velocity distribution
(Discharge angle : 32 degree)

• Cooling temperature distribution


(Discharge angle : 32 degree)

AC120TNCDKC/EA
•• Cooling Air Velocity distribution
(Discharge angle : 32 degree)

•• Cooling temperature distribution


(Discharge angle : 32 degree)
8. Temperature and air flow distribution
Ceiling (Ceiling Installation)

AC140TNCDKC/EA
• Cooling Air Velocity distribution
(Discharge angle : 32 degree)

• Cooling temperature distribution


(Discharge angle : 32 degree)

AC160TNCDKC/EA
• Cooling Air Velocity distribution
(Discharge angle : 32 degree)

• Cooling temperature distribution


(Discharge angle : 32 degree)
8. Temperature and air flow distribution
Ceiling (Ceiling Installation)

AC140RNCDKG/EU

•• Cooling Air Velocity distribution


(Discharge angle : 32 degree)

•• Cooling temperature distribution


(Discharge angle : 32 degree)

•• Heating Air Velocity distribution


(Discharge angle : 32 degree)

•• Heating temperature distribution


(Discharge angle : 32 degree)

Outdoor Units

1. Summary Table 142


2. Dimensional Drawing 143
3. Center of Gravity 149
4. Electrical Wiring Diagram 152
5. Sound Data 156
6. Capacity Correction 159
7. Operation Range 161
8. Piping Diagram 162
1. Summary Table
Outdoor Units

Performance Characteristics

Capacity Net Size Net Weight Airflow Sound Pressure Level (dBA)
Model Code
kW (WxHxD mm) (kg) (CMM) Cooling Heating
3.5 AC035TXADKC/EA 790 x 548 x 285 30.5 40 48 -
5.2 AC052TXADKC/EA 880 x 638 x 310 40.5 50 50 -
7.1 AC071TXADKC/EA 880 x 798 x 310 52.5 60 50 -
10.0 AC100TXAD*C/EA 940 x 998 x 330 71.0 76 53 -
12.0 AC120TXAD*C/EA 940 x 1,210 x 330 86.5 110 53 -
14.0 AC140TXAD*C/EA 940 x 1,210 x 330 86.5 110 54 -
16.0 AC160TXAD*C/EA 940 x 1,420 x 330 96.0 143 56 -

NOTE
•• Sound power level is based on cooling operation.
2. Dimensional Drawing
Outdoor Units

AC035TXADKC/EA
Units : mm [inches]

601.7
(23-3/4)

(12-1/4)

(13-1/4)
310

336
790 285
(31-1/8) (11-1/4)

105 (4-1/8)
158(6-1/4)
(21-1/2)
548
1

126 (4-15/16)
149 (5-7/8)
601.7 90(3-9/16)
(23-3/4)
254
(10)

3
360
(14-3/16)

Rear View

No. Name Description


1 Refrigerant gas pipe Φ9.52(3/8)
2 Refrigerant liquid pipe Φ6.35(1/4)
3 Drain Hole Connection with the provided drain plug.
2. Dimensional Drawing
Outdoor Units

AC052TXADKC/EA
Units : mm [inches]

No. Name Description


1 Refrigerant gas pipe Φ12.7(1/2)
2 Refrigerant liquid pipe Φ6.35(1/4)
3 Drain Hole Φ20
2. Dimensional Drawing
Outdoor Units

AC071TXADKC/EA
Units : mm [inches]

No. Name Description


1 Refrigerant gas pipe Φ15.88(5/8)
2 Refrigerant liquid pipe Φ6.35(1/4)
3 Drain Hole Connection with the provided drain plug.
2. Dimensional Drawing
Outdoor Units

AC100TXADKC/EA, AC100TXADNC/EA
Units : mm [inches]
940
[37]

330
[13]
25
[1]

25 [63/64]
579 [22-51/64] 313
[12-5/16]

1
655 [25-25/32]

2
998 [39-5/16]

4
3

[19-1/2]
495
3
24 [15/16]

[2-3/16]
[2-3/16]
[5-23/64]

[2-3/16]
[3-3/4]
[3-3/4]

[3-1/8]
[3-15/64]

95
95

[6-7/32]
[5-23/64]

80
158
55

[3-15/64]
55
136

136
82

82

55

80 52 [2-1/16]
5 4 30 [1-3/16] [3-1/8] 42 [1-21/32]
4 5
88 30 [1-3/16] 78 [3-5/64] 106 [4-3/16]
[3-1/2]
133
[5-15/64]

153 67 [2-5/8]
[6-1/32]
22 [7/8]

165 620
[6-1/2] [24-3/8] 60 [2-3/8]
3
30 6 17 [11/16]
[1-3/16]
[2-15/16]
75
[7-3/16]
183

[12-7/8]

[15-1/8]
328

384
[9-3/8]
238
[3-13/16]
96

[1-3/16]

37 [1-7/16]
30

Hole For Anchor Bolt (4Positions , M10)


294 218
[11-9/16] [8-9/16]

No. Name Description


1 Liquid pipe connection Ø9.52 (3/8)
2 Gas pipe connection Ø15.88 (5/8)
3 Piping intake knockout hole Front / Side / Rear / Bottom
4 Power wiring conduit Front / Side / Rear / Ø34 (1-3/8)
5 Communication wiring conduit Front / Side / Rear / Ø22 (7/8)
6 Drain hole Connect with the provided drain plug.
2. Dimensional Drawing
Outdoor Units

AC120TXADKC/EA, AC120TXADNC/EA, AC140TXADKC/EA, AC140TXADNC/EA


Units : mm [inches]
940
[37]

330
[13]
[1]
25

578 313
25 [63/64] [22-3/4] [12-5/16]
[21-37/64]
548

1
[47-5/8]
1210

5
5
4
4
3
3
55 [2-3/16]
80 [3-3/16]

[20-11/16]
525
[3-3/4]

95 [3-3/4]
55 [2-3/16]
55 [2-3/16]
95
24 [15/16]

[5-23/64]

[6-7/32]
158
136
82

[3-15/64]

30 [1-3/16] 80 [3-3/16]
136 [5-23/64]

42 [1-21/32]
52 [2-1/16]
82 [3-15/64]

88
[3-1/2]
30 [1-3/16] 78 [3-5/64]
105
153 132 67 [2-5/8] [4-1/8]

[6-1/32] [5-13/64]
22 [7/8]

165 620 60 [2-3/8]


[6-1/2] [24-3/8]
17 [11/16] 3
30 6
[1-3/16]
[2-15/16]
75
[7-3/16]
183

[12-7/8]

[15-1/8]
328

384
[9-3/8]
238
[3-13/16]
95

37 [1-7/16]
[1-1/8]
29

Hole For Anchor Bolt (4Positions , M10)

294 218
[11-9/16] [8-9/16]

No. Name Description


1 Liquid pipe connection Ø9.52 (3/8)
2 Gas pipe connection Ø15.88 (5/8)
3 Piping intake knockout hole Front / Side / Rear / Bottom
4 Power wiring conduit Front / Side / Rear / Ø34 (1-3/8)
5 Communication wiring conduit Front / Side / Rear / Ø22 (7/8)
6 Drain hole Connect with the provided drain plug.
2. Dimensional Drawing
Outdoor Units

AC160TXADKC/EA, AC160TXADNC/EA
Units : mm [inches]

940
[3'-1"]
[4'-7 1/2"]

[4'-8 1/4"]
1412

1428
[4'-8"]
1420

[2'-1 3/4"]
655

621 ④
[2'-0 1/2"]

No. Name No. Name


1 Refrigerant gas pipe 3 Drain hose
2 Refrigerant liquid pipe 4 Power & Comm. wiring conduits
3. Center of Gravity
Outdoor Units

AC035TXADKC/EA
Units : mm [inches]

[8-3/4]
223
232 165
[9-1/8 [6-1/2]
The position of foundation bolt

AC052TXADKC/EA
Units : mm [inches]
3. Center of Gravity
Outdoor Units

AC071TXADKC/EA
Units : mm [inches]

AC100TXADKC/EA, AC100TXADNC/EA
Units : mm [inches]
3. Center of Gravity
Outdoor Units

AC120TXADKC/EA, AC120TXADNC/EA, AC140TXADKC/EA, AC140TXADNC/EA


Units : mm [inches]

AC160TXADKC/EA, AC160TXADNC/EA
Units : mm [inches]
[55-9/10]
1420
[24-3/8]
620

210 160
[8-1/4] [6-5/16]
620 328
[24-3/8] [12-7/8]
Hold location of foundation bolt
Hold location of foundation bolt
4. Electrical Wiring Diagram
Outdoor Units

AC035TXADKC/EA

DRED PCB Printed circuit board(DRED) H-PRESSURE SWITCH High Pressure Switch M-BLDC BLDC Motor
EEV Electronic Expansion Valve OUT-TH(10K) Thermistor AMBIENT DIS-TH(200K) Thermistor DISCHARGE
COND-TH(10K) Thermistor CONDENSOR OLP-TH(200K) Thermistor OLP

NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor-outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
4. Electrical Wiring Diagram
Outdoor Units

AC052TXADKC/EA, AC071TXADKC/EA

DRED PCB Printed circuit board(DRED) H-PRESSURE SWITCH High Pressure Switch M-BLDC BLDC Motor
EEV Electronic Expansion Valve OUT-TH(10K) Thermistor AMBIENT DIS-TH(200K) Thermistor DISCHARGE
COND-TH(10K) Thermistor CONDENSOR OLP-TH(200K) Thermistor OLP

NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor-outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
4. Electrical Wiring Diagram
Outdoor Units

AC100TXADKC/EA, AC120TXADKC/EA, AC140TXADKC/EA, AC160TXADKC/EA

DRED PCB Printed circuit board(DRED) BASE HEATER PBA Printed circuit board(BASE M-BLDC BLDC Motor
HEATER)
EEV Electronic Expansion Valve OUT-Temp(10K) Thermistor AMBIENT COND Temp(10K) Thermistor DISCHARGE
DISCHARGE
Thermistor CONDENSOR OLP Temp(200K) Thermistor OLP
Temp(200K)

NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor-outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
4. Electrical Wiring Diagram
Outdoor Units

AC100TXADNC/EA, AC120TXADNC/EA, AC140TXADNC/EA, AC160TXADNC/EA

DRED PCB Printed circuit board(DRED) BASE HEATER PBA Printed circuit board(BASE M-BLDC BLDC Motor
HEATER)
EEV Electronic Expansion Valve OUT-Temp(10K) Thermistor AMBIENT COND Temp(10K) Thermistor DISCHARGE
DISCHARGE
Thermistor CONDENSOR OLP Temp(200K) Thermistor OLP
Temp(200K)

NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor-outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
5. Sound Data
Outdoor Units

Sound Pressure level


Unit: dB(A)
Model Cooling
Microphone 1m Microphone 1m
AC035TXADKC/EA 48
AC052TXADKC/EA 50

1.5m 1.5m
AC071TXADKC/EA 50

Front Front

• NC Curve
1) AC035TXADKC/EA 2) AC052TXADKC/EA

3) AC071TXADKC/EA

NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
5. Sound Data
Outdoor Units

Sound Pressure level


Unit: dB(A)
Model Cooling
Microphone 1m Microphone 1m
AC100TXADKC/EA 53
AC100TXADNC/EA 53

1.5m 1.5m
AC120TXADKC/EA 53
AC120TXADNC/EA 53
Front Front

• NC Curve
1) AC100TXADKC/EA 2) AC100TXADNC/EA

3) AC120TXADKC/EA 4) AC120TXADNC/EA

NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
5. Sound Data
Outdoor Units

Sound Pressure level


Unit: dB(A)
Model Cooling
Microphone 1m Microphone 1m
AC140TXADKC/EA 54
AC140TXADNC/EA 54
1.5m 1.5m
AC160TXADKC/EA 56
AC160TXADNC/EA 56
Front Front

• NC Curve
1) AC140TXADKC/EA 2) AC140TXADNC/EA

3) AC160TXADKC/EA 4) AC160TXADNC/EA

NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
6. Capacity Correction
Outdoor Units

AC035TXADKC/EA

Cooling

Pipe Length (m)


5 10 15 20
30 - - - -
25 - - - -
20 - - - -
15 - - - 0.92
Level Difference (m)

10 - - 0.95 0.92
5 - 0.97 0.95 0.92
0 1 0.97 0.95 0.92
-5 - 0.96 0.94 0.91
-10 - - 0.92 0.90
-15 - - - 0.88
-20 - - - -
-25 - - - -
-30 - - - -

AC052TXADKC/EA

Cooling

Pipe Length (m)


5 10 15 20 25 30
30 - - - - - -
25 - - - - - -
20 - - - 0.92 0.90
15 - - 0.94 0.92 0.90
Level Difference (m)

10 - 0.96 0.94 0.92 0.90


5 0.98 0.96 0.94 0.92 0.90
0 1 0.98 0.96 0.94 0.92 0.90
-5 0.97 0.95 0.93 0.91 0.89
-10 - 0.94 0.93 0.91 0.89
-15 - - 0.92 0.90 0.88
-20 - - - - 0.89 0.86
-25 - - - - - -
-30 - - - - -
6. Capacity Correction
Outdoor Units

AC071TXADKC/EA, AC100TXADKC/EA, AC100TXADNC/EA

Cooling

Pipe Length (m)


5 10 15 20 25 30 35 40 45 50
30 - - - - - - 0.93 0.92 0.91 0.90
25 - - - - - 0.94 0.93 0.92 0.91 0.90
20 - - - - 0.96 0.94 0.93 0.92 0.91 0.90
15 - - - 0.97 0.96 0.94 0.93 0.92 0.91 0.90
Level Difference (m)

10 - - 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90


5 - 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
0 1 0.99 0.98 0.97 0.96 0.94 0.93 0.92 0.91 0.90
-5 - 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.89
-10 - - 0.97 0.96 0.95 0.94 92 0.91 0.90 0.88
-15 - - - 0.95 0.95 0.93 0.92 0.91 0.89 0.88
-20 - - - - 0.94 0.93 0.92 0.90 0.89 0.87
-25 - - - - - 0.92 0.91 0.90 0.88 0.86
-30 - - - - - - 0.91 0.89 0.88 0.85

AC120TXADKC/EA, AC120TXADNC/EA, AC140TXADKC/EA, AC140TXADNC/EA


AC160TXADKC/EA, AC160TXADNC/EA
Cooling

Pipe Length (m)


5 10 15 20 25 30 35 40 45 50 55 60 65 70 75
30 - - - - - - 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88
25 - - - - - 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88
20 - - - - 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88
15 - - - 0.97 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88
10 - - 0.98 0.97 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88
Level Difference (m)

5 - 0.99 0.98 0.97 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88
0 1 0.99 0.98 0.97 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88
-5 - 0.99 0.98 0.97 0.96 0.95 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.87
-10 - - 0.98 0.97 0.96 0.95 0.94 0.93 0.93 0.92 0.91 0.90 0.89 0.88 0.86
-15 - - - 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.85
-20 - - - - 0.95 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.86 0.84
-25 - - - - - 0.94 0.93 0.93 0.92 0.91 0.90 0.89 0.87 0.86 0.83
-30 - - - - - - 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.85 0.82
7. Operation Range

Outdoor Unit Indoor Unit Indoor Unit


Mode
Temperature(DB) Temperature(DB) Humidity(RH)
Cooling -15°C ~ 50°C 18°C ~ 32°C 80% or less
Drying -15°C ~ 50°C 18°C ~ 32°C 80% or less

NOTE
•• The assumed installation conditions are follows
-- The pipe length(including elbow) is 5 m.
-- The level difference is 0 m.
8. Piping Diagram

AC052TN4DKC/EA+AC052TXADKC/EA
AC052TN4PKC/EA+AC052TXADKC/EA

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Indoor
Fan Motor
(IFM)
Outdoor Fan Motor1 (OFM1)
Electronic Thermistor-
Expansion Valve- Indoor Room
Main1 (T_IR)
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)

Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)
8. Piping Diagram

AC035TN1DKC/EA+AC035TXADKC/EA
AC052TN1DKC/EA+AC052TXADKC/EA

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Outdoor Fan Motor1 (OFM1) Thermistor- Indoor


Indoor Room Fan Motor
Electronic (T_IR) (IFM)
Expansion Valve-
Main1
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)

Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)
8. Piping Diagram

AC035TNLDKC/EA+AC035TXADKC/EA
AC052TNLDKC/EA+AC052TXADKC/EA
AC052TNCDKC/EA+AC052TXADKC/EA

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Thermistor-
Indoor Room
(T_IR)
Outdoor Fan Motor1 (OFM1)
Electronic
Expansion Valve- Indoor Fan Motor
Main1 (IFM)
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)

Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)
8. Piping Diagram

AC071TN4DKC/EA+AC071TXADKC/EA
AC071TN4PKC/EA+AC071TXADKC/EA
AC100TN4DKC/EA+AC100TXAD*C/EA
AC100TN4PKC/EA+AC100TXAD*C/EA

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Indoor
Fan Motor
(IFM)
Outdoor Fan Motor1 (OFM1)
Electronic Thermistor-
Expansion Valve- Indoor Room
Main1 (T_IR)
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)

Accumulator
(AC)

Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)
8. Piping Diagram

AC071TN1DKC/EA+AC071TXADKC/EA

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Outdoor Fan Motor1 (OFM1) Thermistor- Indoor


Indoor Room Fan Motor
Electronic (T_IR) (IFM)
Expansion Valve-
Main1
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)

Accumulator
(AC)

Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)
8. Piping Diagram

AC071TNMDKC/EA+AC071TXADKC/EA
AC071TNCDKC/EA+AC071TXADKC/EA
AC100TNMDKC/EA+AC100TXAD*C/EA
AC100TNCDKC/EA+AC100TXAD*C/EA

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Thermistor-
Indoor Room
(T_IR)
Outdoor Fan Motor1 (OFM1)
Electronic
Expansion Valve- Indoor Fan Motor
Main1 (IFM)
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)

Accumulator
(AC)

Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)
8. Piping Diagram

AC120TN4DKC/EA+AC120TXAD*C/EA
AC120TN4PKC/EA+AC120TXAD*C/EA
AC140TN4DKC/EA+AC140TXAD*C/EA
AC140TN4PKC/EA+AC140TXAD*C/EA

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Indoor
Fan Motor
(IFM)
Outdoor Fan Motor1 (OFM1) Outdoor Fan Motor1 (OFM2)
Electronic Thermistor-
Expansion Valve- Indoor Room
Main1 (T_IR)
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)

Accumulator
(AC)

Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)
8. Piping Diagram

AC120TNMDKC/EA+AC120TXAD*C/EA, AC120TNCDKC/EA+AC120TXAD*C/EA
AC140TNMDKC/EA+AC140TXAD*C/EA, AC140TNCDKC/EA+AC140TXAD*C/EA
AC160TNMDKC/EA+AC160TXAD*C/EA, AC160TNCDKC/EA+AC160TXAD*C/EA

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Thermistor-
Indoor Room
(T_IR)
Outdoor Fan Motor1 (OFM1) Outdoor Fan Motor1 (OFM2)
Electronic
Expansion Valve- Indoor Fan Motor
Main1 (IFM)
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)

Accumulator
(AC)

Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)
Installation

1. ( Wind-Free) 1Way & 4Way 4 way Cassette

Cassette (Unit: mm)


C
C
Spacing requirements

A 1500 mm or
more
C
C
B
C: 1500 mm or more
2500 mm or more 20 mm

Obstruction CAUTION
• The indoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
AC035TN1DKC AC100TN4DKC maintenance, and repair of the unit. The components
AC052TN4DKC
Model AC052TN1DKC AC120TN4DKC
AC071TN4DKC of the indoor unit must be reachable and removable
AC071TN1DKC AC140TN4DKC
under safe conditions for people and the unit.
A 170 mm 251 mm 355 mm • Do not hold the discharge while carrying the indoor
unit to avoid the possibility of breakage.
B 15 mm 17 mm 17 mm • You must hold the hanger plate on the corner and
carry the indoor unit.
(Unit: mm)

1 way Cassette

(Unit: mm)

150 or more
1500 or more

150 or more
150 or more

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Optional: Insulating the body of the indoor unit


If you install a cassette type indoor unit on the ceiling when temperature is over 27°C and humidity is over 80%, you
must apply an extra 10 mm thick polyethylene insulation or a similar type of insulation to the body of the indoor unit.
Cut away the part where pipes are pulled out for the insulating work.

1 way Cassette 4 way Cassette

D D

E
B B
A
A

E
C
C

Insulate the end of the pipe and some curved area by using separate insulator.

NOTE
• A: Reference for the outer circumference of the unit
(When insulating the body of the indoor unit, use A as the reference for its outer circumference.)

(Unit: mm)

Indoor unit A B C D E
1 way Cassette
AC035TN1DKC 990x155 990x155 430x155 430x155 990x430
(970x135x410)
AC052TN1DKC
1 way Cassette
1220x155 1220x155 470x155 470x155 1220x470
(1200x138x450)
AC071TN1DKC

AC052TN4DKC
4 way Cassette <S>
910x151 940x151 610x151 650x151 870x870
(840x204x840)
AC071TN4DKC

AC100TN4DKC
4way Cassette type <L+>
AC120TN4DKC 910x235 940x235 610x235 650x235 870x870
(840x288x840)
AC140TN4DKC

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Installing the indoor unit CAUTION


When deciding on the location of the air conditioner the • Make sure that the ceiling is strong enough to support
following restrictions must be taken into account. the weight of the indoor unit. Before hanging the unit,
1 Place the pattern sheet on the ceiling at the spot test the strength of each attached suspension bolt.
where you want to install the indoor unit. • If the length of the suspension bolt is more than 1.5 m,
you are required to prevent vibration.
4 Screw eight pairs of nuts and washers to the
suspension bolts, making space for hanging the indoor
unit.

CAUTION
• You must install all of the suspension rods.
• It is important to leave sufficient space in the false
ceiling to allow access for maintenance or repairs to
the drainage pipe connection, the refrigerant pipe
connection, or to remove the unit if necessary.
NOTE
5 Hang the indoor unit to the suspension bolts between
• Since the diagram is made of paper, it may shrink
two nuts. Cut a pad stopper and place it on the
or stretch slightly due to temperature or humidity.
suspension bolts to hold the washers. Remove the
For this reason, before drilling the holes, be sure
stopper and screw the nuts to fix the unit.
to maintain the correct dimensions between the
markings.
2 Insert bolt anchors, use existing ceiling supports or Pad stopper
construct a suitable support as shown in figure.

Concrete

Bracket
Hole in anchor Insert
Hole in plug
6 Check the level of the indoor unit by using a leveler.
• A tilt of the indoor unit may cause malfunction of a
Suspension bolt (M8) - field supply built-in float switch and water leaks.

3 Install the suspension bolts, depending on the ceiling


type.

Ceiling support

Level

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

7 Adjust the unit to the appropriate position, taking into 3 Wrap the supplied large sealing pad over the metal
account the installation area for the front panel. clamp and drain hose to insulate and fix it with clamps.
• Place the pattern sheet on the indoor unit. 4 Insulate the complete drain piping inside the building
• Adjust the space between the ceiling and the (field supply).
indoor unit by using a dimension gauge. If the drain hose cannot be sufficiently set on a slope,
fit the hose with drain raising piping (field supply).
• Fix the indoor unit securely after adjusting the level
of the unit by using a leveller. 5 Push the drain hose up to insulation when connecting
the drain hose to drain socket.
• Remove the pattern sheet, connect the other
cables. and install the front panel.
Metal clamp Drain socket
Drain hose
1way Cassette (Standard)

Ceiling Ceiling
Drain pipe

Gauge of dimensions Large seailng pad Be sure to bond the drain


15 mm 15 mm hose and the main pipe.
<Side view>

PVC Tube Joint +


Drain hose VP25 (OD: 32 mm, ID: 25 mm)
1way Cassette (Wind-Free)

Drain pipe
Ceiling Ceiling

Gauge of dimensions
10 mm 10 mm
<Side view>

CAUTION
Check that the indoor unit is level with the ceiling by
4 way Cassette
using the leveller.
20 mm
• Install air ventilation to drain condensation smoothly.
Indoor unit
Ceiling Air ventilation

17 mm
Gauge of dimensions

Installing the drain hose and drain pipe Ceiling

1 Push the supplied drain hose as far as possible over • If it is necessary to increase the height of the drain
the drain socket. pipe, install the drain pipe straight within 300 mm
from the drain hose port. If it is raised higher than 550
2 Tighten the metal clamp as shown in the picture.
mm, there may be water leaks.

300 mm
or less 20 mm or more

Band joint
1/100 or more

Drain hose 550 mm


or less
Ceiling

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

• Do not give the hose an upward gradient beyond • Install horizontally.


the connection port. This will cause water to flow
backwards when the unit is stopped, resulting in water
leaks. Be horizontal

Under gradient
Indoor unit

Flexible hose

Ceiling • Max. allowable axis gap.

• Do not apply force to the piping on the unit side when


connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
Indoor unit
close to the unit as possible.

Support pieces Max. 20 mm


1 to 1.5 m

• Max. allowable bending angle.


1/100 or more

Ceiling Indoor unit


Max. 30˚

NOTE
• If a concentrated drain pipe is installed, refer to the figure below.

Hanger 1~1.5m Main air vent

Individual air
vent 200 mm or more

300 to 550 mm

Centralized horizontal drainpipe


Main drainpipe
(more than 1/100 slope)

• If 3 or more units are installed, install the main air vent at the front of the farthest indoor unit from the main drain pipe.
• To prevent water from flowing back to indoor units, install an individual air vent at the top of each indoor unit.
– The air vents should be T or 7 shaped to prevent dust or foreign substances from entering.
– You may not need to install air vent if the horizontal drain pipe is in proper slope.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

3 phase

Connecting the power and


communication cables Indoor Unit
1(L)
F2
2(N)
CAUTION F1

• Always remember to connect the refrigerant pipes Outdoor


before performing the electric connections. Unit
When disconnecting the system, always disconnect 1(L) 2(N)L1(R) L2(S) L3(T) N F1 F2
the electric cables before disconnecting the
refrigerant pipes.
• Always remember to connect the air conditioner to the
grounding system before performing the electric connections. Cable
Tie Cable
Use a crimp ring terminal at the end of each wire. clamp

The indoor unit is powered through the outdoor unit by


means of a H07 RN-F connection cable (or a more power
model), with insulation in synthetic rubber and a jacket
in polychloroprene (neoprene), in accordance with the Indoor 3 Phase 4 Wires power cable Communication
Power (AC 380V) cable
requirements specified in the standard EN 60335-2-40.
1 Remove the screw on the electrical component box
and remove the cover plate. Indoor power supply
2 Route the connection cord through the side of the Power supply Max/Min(V) Indoor power cable
indoor unit and connect the cable to the terminals
refer to the figure below. 220 to 240V, 50 Hz ±10% 0.75 mm² ↑, 3 wires
3 Route the other end of the cable to the outdoor unit
Communication cable
through the ceiling & the hole on the wall.
4 Reassemble the electrical component box cover, 0.75 mm², 2 wires
carefully tightening the screw. (Unit: mm)
AC power: M4 screw Communication: M3.5 screw
1 phase 12.6 9.0

13.8
19

Indoor Unit 9.8 7.5


1(L)
F2
2(N) Tightening torque (kgf • cm)
F1

Outdoor
M3.5 8.0 to 12.0
Unit M4 12.0 to 18.0
1(L) 2(N) L N F1 F2
• 1 N·m = 10 kgf·cm
• Power supply cords of parts of appliances for outdoor use
shall not be lighter than polychloroprene sheathed flexible
Cable cord. (Code designation IEC:60245 IEC 57 / CENELEC:
Cable
Tie H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
clamp
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.

Indoor Power Main power cable Communication


cable

CAUTION
• When installing the indoor unit in a computer
room or network room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

2. 360 Cassette

Spacing requirements

A
'C'
A
Indoor unit

A
10 mm
2500 mm or more 20 mm
A
1500 mm or
more
Obstruction
A : 1500 mm or more

(Unit: mm)
Model AC052TN4PKC/EA AC071TN4PKC/EA AC100TN4PKC/EA AC120TN4PKC/EA AC140TN4PKC/EA

C 261 345 345 345 345

CAUTION
• The indoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
maintenance, and repair of the unit.
The components of the indoor unit must be reachable
and removable under safe conditions for people and
the unit.
• Do not hold the discharge while carrying the indoor
unit to avoid the possibility of breakage.
A
• You must hold the hanger plate on the corner and
carry the indoor unit.
Insulate the end of the pipe and some curved area by
using separate insulator.

NOTE
• A: Reference for the outer circumference of the unit
(When insulating the body of the indoor unit,
use A as the reference for its outer circumference.)

(Unit: mm)
Indoor unit type and models Dimensions

AC052TN4PKC
Optional: Insulating the body of 360 cassette type <S>
1610 x 130
(947 x 947 x 281)
the indoor unit AC071RN4PKC

AC100TN4PKC
If you install a cassette type indoor unit on the ceiling
when temperature is over 27°C and humidity is over 360 cassette type <L+>
AC120TN4PKC 2610 x 215
(947 x 947 x 365)
80%, you must apply an extra 10 mm thick polyethylene
AC140TN4PKC
insulation or a similar type of insulation to the body of the
indoor unit.
Cut away the part where pipes are pulled out for the
insulating work.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Installing the indoor unit


Concrete
When deciding on the location of the air conditioner the
following restrictions must be taken into account.
1 Determine the positions of the pipe and the drain hose Hole in anchor Insert
hole as shown in the pattern sheet, and drill the hole Hole in plug
with an inner diameter of 14 mm.

Suspension bolt (M10) - eld supply

4 Install the suspension bolts, depending on the ceiling


type.

Ceiling support

NOTE
• Since the diagram is made of paper, it may shrink
or stretch slightly due to temperature or humidity.
For this reason, before drilling the holes, be sure
to maintain the correct dimensions between the
markings.
CAUTION
2 Perform the following steps to install inspection holes
• Make sure that the ceiling is strong enough to support
in accordance with the panel type.
the weight of the indoor unit. Before hanging the unit,
a For the recessed installation of the square panel. test the strength of each attached suspension bolt.
• Install an inspection hole to the direction of • If the length of the suspension bolt is more than 1.5 m,
connection parts of the refrigerant pipe and the you are required to prevent vibration.
drain hose. (1 point)
5 Screw eight pairs of nuts and washers to the
Refrigerant pipe
suspension bolts, making space for hanging the indoor
unit.

CAUTION
Indoor unit
Inspection hole display • You must install all of the suspension rods.
• It is important to leave sufficient space in the false
b For recessed installation of the circular panel ceiling to allow access for maintenance or repairs to
• Install inspection holes to both directions of the the drainage pipe connection, the refrigerant pipe
connection part of the refrigerant pipe and the connection, or to remove the unit if necessary.
drain hose and of the indoor unit display.
(2 points) 6 Hang the indoor unit to the suspension bolts between
two nuts. Cut a pad stopper and place it on the
Inspection hole suspension bolts to hold the washers. Remove the
Refrigerant pipe stopper and screw the nuts to fix the unit.

2
Indoor unit display

Inspection hole
1
3 Insert bolt anchors, use existing ceiling supports or
2
construct a suitable support as shown in figure.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

7 Adjust the unit to the appropriate position, taking into PVC Tube Joint
Drain hose + VP25 (OD: 32 mm, ID: 25 mm)
account the installation area for the front panel.
• Place the pattern sheet on the indoor unit.
• Adjust the space between the ceiling and the
indoor unit by using a dimension gauge. Drain pipe

• Fix the indoor unit securely after adjusting the level


of the unit by using a leveller.
• Remove the pattern sheet and install the front
panel. CAUTION
Check that the indoor unit is level with the ceiling by
using the leveller.
Ceiling
Indoor unit • Install air ventilation to drain condensation smoothly.
Air ventilation

Gauge of For the recessed installation of the


dimensions square panel: 11.5 mm
For the recessed installation of the
circular panel: 41.5 mm

Ceiling

Installing the drain hose and drain pipe • If it is necessary to increase the height of the drain
pipe, install the drain pipe straight within 300 mm
1 Push the supplied drain hose as far as possible over
from the drain hose port. If it is raised higher than
the drain socket. 550 mm, there may be water leaks.
2 Tighten the metal clamp as shown in the picture.
300 mm or less 20 mm or more

550 mm or less
Band joint

Drain hose

Ceiling

• Do not give the hose an upward gradient beyond the


3 Wrap the supplied large sealing pad over the metal
connection port. This will cause water to flow backwards
clamp and drain hose to insulate and fix it with clamps.
when the unit is stopped, resulting in water leaks.
4 Insulate the complete drain piping inside the building
(field supply). Under gradient
If the drain hose cannot be sufficiently set on a slope,
fit the hose with drain raising piping (field supply).
5 Push the drain hose up to insulation when connecting
the drain hose to drain socket.

Metal clamp Drain socket Ceiling


Drain hose
• Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
Drain pipe
close to the unit as possible.

Be sure to bond the drain


Large seailng pad hose and the main pipe.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Support pieces
1 to 1.5 m
Connecting the power and
communication cables
CAUTION
1/100 or more
• Always remember to connect the refrigerant pipes
before performing the electric connections.
Ceiling When disconnecting the system, always disconnect
the electric cables before disconnecting the
• Install horizontally.
refrigerant pipes.
• Always remember to connect the air conditioner to
Be horizontal the grounding system before performing the electric
connections. Use a crimp ring terminal at the end of
each wire.
Indoor unit
The indoor unit is powered through the outdoor unit by
means of a H07 RN-F connection cable (or a more power
model), with insulation in synthetic rubber and a jacket
Flexible hose
in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.

• Max. allowable axis gap. 1 Remove the screw on the electrical component box
and remove the cover plate.
2 Route the connection cord through the side of the
indoor unit and connect the cable to the terminals
refer to the figure below.
3 Route the other end of the cable to the outdoor unit
Indoor unit through the ceiling & the hole on the wall.
4 Reassemble the electrical component box cover,
carefully tightening the screw.
Max. 20 mm

Example) 1 phase model


• Max. allowable bending angle.

Wire insert
hole

Indoor unit For connecting the power and


communication cables

Max. 30°
Indoor unit
NOTE
• If a concentrated drain pipe is installed, refer to the
figure below.
Outdoor unit

Full thread bolt hanger 1000 to 1500 mm

Main air vent


(must be installed)
200 mm
or more
300 to
550 mm

Indoor power Main power cable Communication


Centralized horizontal drain pipe cable
Main drain pipe (more than 1/100 slope)

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Indoor power supply For the installation of the circular panel


Power supply Max/Min(V) Indoor power cable
Making a circular opening on the ceiling
220 to 240V, 50 Hz ±10% 0.75 mm² ↑, 3 wires
Use a paper compass printed on the indoor unit package.
Communication cable (attached inside to the upper part)
0.75 mm², 2 wires 1 Use a bolt or a pin to fix pivot point of the paper
compass on center of the ceiling. (in the middle of
location for installation)
(Unit: mm)
AC power: M4 screw Communication: M3.5 screw
9.8 7.5
13.8
19.0

12.6 9.0

2 Put a pencil at the opposite side of the pivot point


Tightening torque (kgf • cm) fixed in place.
M3.5 8.0 to 12.0

M4 12.0 to 18.0

• 1 N·m = 10 kgf·cm

• Power supply cords of parts of appliances for outdoor


use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: 3 Rotate the paper compass on its pivot point to draw a
H07RN-F) line on the ceiling.
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.

4 Rotate the paper compass diametrically to draw a


CAUTION circle on the ceiling.
• When installing the indoor unit in a computer room or
a server room, use the double shielded communication
cable (tape aluminum / polyester braid + copper) of
FROHH2R type.

For the painting of the panel


• Make sure to only apply paints and varnishes for resins
(ABS, HIPS) or paint thinners.
• If you apply lacquers for general use on the panel, it
may lead to discoloration or erosion on the surface of
the panel.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

3. Duct Type
Optional: Insulating the body of the
Space requirements for installation indoor unit

Construction Standard for Inspection Hole D

1 In case, the ceiling is tex tile, Inspection hole dose not


need.
B
2 In case, the ceiling is plaster board, Inspection hole A
depends on Inside height of the ceiing.

a Height is more than 0.5m : Only "B" [Inspection


for PBA] is applied.
C
b Height is less than 0.5m : Both "A"&"B" are
applied.

c "A"&"B" are inspection holes . Thickness: more than 10mm

AC052TNLDKC
AC035TNLDKC
Indoor AC071TNMDKC
Unit
Unit Depth(D)

700 X 440 X 199 850 X 700 X 250

A 700 X 199 850 X 250

Unit Width(W) B 700 X 199 850 X 250


"A"=W+100mm "B"=500mm
C 440 X 199 700 X 250

D 440 X 199 700 X 250

Insulate the front and back side in proper size at


Front/
the same time when insulating the suction duct and
Back
discharge duct.
20mm or more

20mm or more (Unit: mm)

AC100TNMDKC
AC120TNMDKC AC160TNMDKC
Indoor
• You must have 20 mm or more space between the Unit AC140TNMDKC

ceiling and the bottom of indoor unit. Otherwise, the 1300 X 700 X 300 1200 X 650 X 360
noise from the vibration of indoor unit may bother
the user. When the ceiling is under construction, the A 1300 X 300 1200 X 360
hole for check-up must be made to take service, clean B 1300 X 300 1200 X 360
and repair the unit.
C 700 X 300 650 X 360
• It is possible to install the unit at an height of
between 2.2~2.5 m from the ground, if the unit has a D 700 X 300 650 X 360
duct with a well defined lenght (300 mm or more), to
avoid fan motor blower contact. Insulate the front and back side in proper size at
Front/
the same time when insulating the suction duct and
• If you install the cassette or duct type indoor unit on Back
discharge duct.
the ceiling with humidity over 80%, you must apply
extra 10 mm of polyethylene foam or other insulation (Unit: mm)
with similar material on the body of the indoor unit.
NOTE
• Insulate the end of the pipe and some curved area by
using separate insulator.
• Insulate the discharge and suction part at the same
time when you insulate connection duct.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Installing the indoor unit NOTE


• You must install all the suspension rods.
When deciding on the location of the air conditioner
with the owner, the following restrictions must be taken 5 Hang the indoor unit to the suspension bolts between
into account two nuts.
1 Place the pattern sheet on the ceiling at the spot where
you want to install the indoor unit.
2

NOTE
• Since the diagram is made of paper, it may shrink or
CAUTION
stretch slightly due to temperature or humidity. For • Piping must be laid and connected inside the
this reason, before drilling the holes maintain the ceiling when suspending the unit. If the ceiling is
correct dimensions between the markings. already constructed, lay the piping into position for
connection to the unit before placing the unit inside
2 Insert bolt anchors. Use existing ceiling supports or
the ceiling.
construct a suitable support as shown in figure.
6 Screw the nuts to suspend the unit.

Concrete
7 Adjust level of the unit by using measurement plate for
all 4 sides.

CAUTION
Hole in anchor Insert
Hole in plug • For proper drainage of condensate, give a 3mm slant
to the left or right side of the unit which will be
connected with the drain hose, as shown in the figure.
Suspension bolt (M8) - field supply
Make a tilt when you wish to install the drain pump,
too.
3 Install the suspension bolts depending on the ceiling type.
When the drain hose is installed to the right.

Ceiling support

3mm
Drain hose port

• When installing the indoor unit, make sure it is not


tilted toward front or back side.

CAUTION CAUTION
• Noise will increase 3~6 dB(A) when the air flow
• Ensure that the ceiling is strong enough to support the
enters from the bottom side (Only for Slim Duct Type
weight of the indoor unit. Before hanging the unit, test
product).
the strength of each attached suspension bolt.
• If the length of suspension bolt is more than 1.5m,
it is required to prevent vibration.
• If this is not possible, create an opening on the false
ceiling in order to be able to use it to perform the
required operations on the indoor unit.

4 Screw eight nuts to the suspension bolts making space Air Flow
for hanging the indoor unit.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Installing the drain hose and


1~1.5m
drain pipe Hanger
Flexible hose
1 Push the supplied drain hose as far as possible over the
drain socket.
Ceiling Horizontal drainpipe
2 Tighten the metal clamp as shown in the picture. more than 1/100 slope

With the drain pump

1 The drain pipe should be installed within 300mm to


550mm from the flexible hose and then lift down 20mm
or more.
2 Install horizontal drainpipe with a slope of 1/100 or
3 Wrap the supplied large sealing pad over the metal more and fix it by hanger space of 1.0~1.5m.
clamp and drain hose to insulate and fix it with clamps. 3 Install the air vent in the horizontal drainpipe to prevent
4 Insulate the complete drain piping inside the building water flow back to the indoor unit.
(field supply).
If the drain hose cannot be sufficiently set on a slope, fit NOTE
the hose with drain raising piping (field supply).
• You may not need to install it if there were proper
5 Push the drain hose up to insulation when connecting slope in the horizontal drainpipe.
the drain hose to drain socket.
4 The flexible hose should not be installed upward
position, it may cause water flow back to the indoor unit.
Metal clamp Drain socket

Drain hose

Air vent 200mm 1~1.5m


or more
300mm or less Hanger
20mm
or more

Within
Drain pipe
300~550mm
Horizontal drainpipe
Flexible hose
Be sure to bond the drain Ceiling more than 1/100 slope
Large seailng pad
hose and the main pipe.

PVC Tube Joint


Drain hose + VP25 (OD: 32 mm, ID: 25 mm)

Drain pipe

Without the drain pump

1 Install horizontal drainpipe with a slope of 1/100 or


more and fix it by hanger space of 1.0~1.5m.
2 Install U-trap at the end of the drainpipe to prevent a
nasty smell to reach the indoor unit.
3 Do not install the drainpipe to upward position. It may
cause water flow back to the unit.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Connecting the power and The indoor unit is powered through the outdoor unit by
means of a H07 RN-F connection cable (or a more power
communication cables model), with insulation in synthetic rubber and a jacket
in polychloroprene (neoprene), in accordance with the
CAUTION requirements specified in the standard EN 60335-2-40.
• Always remember to connect the refrigerant pipes 1 Remove the screw on the electrical component box and
before performing the electric connections. When remove the cover plate.
disconnecting the system, always disconnect the electric 2 Route the connection cord through the side of the indoor
cables before disconnecting the refrigerant pipes. unit and connect the cable to the terminals refer to the
figure below.
CAUTION 3 Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
• Always remember to connect the air conditioner to the
grounding system before performing the electric connections. 4 Reassemble the electrical component box cover, carefully
tightening the screw.
Use a crimp ring terminal at the end of each wire.

1 phase (**035/160**) 3 phase(**035/160**)

Indoor Unit
Indoor Unit

1(L) 2(N) 1 2 F1 F2 V1 V2 F3 F4
1(L) 2(N) 1 2 F1 F2 V1 V2 F3 F4

1(L) 2(N) L N F1 F2
1(L) 2(N) L1(R) L2(S) L3(T) N F1 F2

Cable clamp
Outdoor Cable clamp
Unit
Outdoor
Unit

Indoor Power Communication cable


Main power cable Indoor Power 3 Phase 4 Wires power Communication cable
cable (AC 380V)

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

1 phase (**052/071/100/120/140**) 3 phase(**100/120/140**)

Indoor Unit Indoor Unit

L N F1 F2 L N F1 F2

Outdoor
Outdoor Unit
Unit
1(L) 2(N) L N 1(L) 2(N) L1(R) L2(S) L3(T) N

Cable Cable Tie


Tie Cable Cable
clamp clamp

Indoor Power Communication cable Indoor Power 3 Phase 4 Wires power Communication cable
Main power cable
cable (AC 380V)

Indoor power supply • Power supply cords of parts of appliances for


Power supply Max/Min(V) Indoor power cable
outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245
220 to 240V, 50 Hz ±10% 0.75 to 1.5 mm², 3 wires IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
Communication cable
• Since it has the external power supply, refer to the
0.75㎟↑, 2wires outdoor unit installation manual for MAIN POWER.

**035/160**
AC power: M4 screw Communication: M3.5 screw

9.8 12.6 7.5 9.0


13.8
19

CAUTION
• When installing the indoor unit in a computer
**052/071/100/120/140** room or a server room, use the double shielded
AC power: M4 screw Communication: M3.5 screw communication cable (tape aluminum / polyester
10.3 13.8 10.1 11.4 braid + copper) of FROHH2R type.
19.2
19.2

Tightening torque (kgf • cm)

M3.5 8.0 to 12.0

M4 12.0 to 18.0

• 1 N·m = 10 kgf·cm

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

4. Ceiling

Spacing requirements Installing the indoor unit

AC052TNCDKC Floor installation (AC052TNCDKC)

1 Select pipe directions.


Ceiling installation
When the directions are selected, drill 3-1/8''
(100mm,for pipe and cables) and 1-3/4'' (40mm, for
drain hose) diameter holes on the wall so that it slants
slightly downwards toward the outdoor for smooth
water flow.

300 mm
NOTE
• Use the pattern sheet to select pipe directions.
50 mm
2 Install the hanging plate according to the distance and
mount it.
Floor installation

300 mm

300 mm

3 Install the unit and be sure to arrange the drain hose so


that it is leveled lower than the drain hose connecting
port of the indoor unit.

AC071/100/120/140/160TNCDKC

Ceiling installation

Drain hose Drain hose

300 mm 50 mm

Ceiling Ceiling

Wall

50 mm 300 mm or more 300 mm or more

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Ceiling installation (AC052/071/100/120/140/


160TNCDKC) wall

1° or less
1 Select pipe directions.
When the directions are selected, drill 3-1/8''-(100mm,
for pipe and cables) and 1-3/4''-(40mm, for drain hose)
diameter holes on the wall so that it slants slightly
4 When Hanging the set, firstly unscrew the screws from
downwards toward the outdoor for smooth water flow.
the both of sides, and then disassemble the Case-sides,
NOTE or else the case-side will be damaged by disassembling
it directly.
• Use the pattern sheet to select pipe directions.

2 Drill holes for anchor bolts according to the distance and


mount them.

NOTE
Unscrew two screws from the both of sides.
• Use the pattern sheet.
5 Reassemble the Case-sides, tightening the screws after
3 Install the unit onto the ceiling. Be sure to arrange the
hanging the set.
drain hose so that it is leveled lower than the drain hose
connecting port of the indoor unit.

NOTE
• For proper drainage of condensate, give a 1° or less slant
to the side of the unit which will be connected with the
drain hose as shown in the figure. (The gap between the
lower end of the indoor unit and the ceiling should be
12 mm or less.)
Remove the Case-sides from the both of sides.

1° or less

Connection pipe
Purging inert gas from the indoor unit
The indoor unit comes with nitrogen gas (inert gas)
Drain hose
charged at the factory. Therefore, all inert gas must be
purged before connecting the assembly piping.

Unscrew the pinch pipe at the end of each refrigerant pipe.


Connection pipe

AC052TNCDKC
Drain hose

CAUTION
• Ensure that the ceiling is strong enough to support the
weight of the indoor unit.
• Before hanging the unit, test the strength of each
attached suspension bolt.
• Install the drain hose from the rear of the unit.
AC071/100/120/140/160TNCDKC
NOTE
• AC052TNCDKC:The gap between the lower end of the
indoor unit and the ceiling should be 1˚ (16 mm) or less.
• AC071TNCDKC:The gap between the lower end of the
indoor unit and the ceiling should be 1˚ (23 mm) or less.
• AC100/120/140/160TNCDKC:The gap between the lower
Side cover
end of the indoor unit and the ceiling should be 1˚ (28
mm)
m) or ss.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Installing the drain hose and When passing the drain hose through the hole drilled in the
wall, check that none of the following situations occur:
drain pipe
Care must be taken when installing the drain hose for AC052TNCDKC
the indoor unit to ensure that any condensation water is
correctly drained outside.

NOTE
• Installing the drain hose should be the shorter, the
better.
• In order to discharge condensate water, a downward
gradient should be maintained.
• Fix the drain hose with Cable-Tie, so that it will not The hose must NOT The hose must NOT Do NOT bend the
separate from the machine. slope upwards. slope The end of the hose in different
drain hose must NOT directions.
be placed in water.
1 Insert the drain hose to bottom of the outfall of water
basin.
2 Lock flexible hose clamp of the drain hose according to
the figure.
3 Wind and wrap flexible hose clamp and drain hose fully
with thermal insulation sponge; fix both ends of external
layer with ribbon for thermal insulation.
4 After being installed, drain hose must be insulated fully 5cm
by heat insulating material. (To be provided at site.) less

• Be sure to tighten the flexible hose clamp of the drain Ditch

hose. The hose must NOT Do NOT place the


slope Keep a clearance end of the drain
• Wrap the insulation after attaching the flexible hose of at least 5-cm hose in a hollow.
between the end of the
clamp. hose and the ground.

Flexible hose clamp of drain hose NOTE


Joint of drain hose Fix with Cable-Tie • When the drain pipe is not long enough to use, you can
extend the drain pipe by connecting an extra drain pipe,
A
Drain hose as shown in the figure:

Indoor unit

A A-A’
Drain hose
Wrap thermal sleeve hose

Insulation

Tighten flexible hose clamp After tightening the flexible hose


of the drain hose. clamp, attach the Insulation.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

AC071/100/120/140/160TNCDKC 3 Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
wall
4 Reassemble the electrical component box cover, carefully
hole tightening the screw.

1 phase(**071**)

Wired Remot
Controller
Indoor Unit (Optional)
No grade

Outdoor Unit

1(L) 2(N) 1 2 F1 F2

No slack No in the water water


Cable
clamp

Indoor Main power Communication


Power cable cable

After installing the pipes, close the piping 1 phase(**100/120/140/160**)


connection hole to prevent inflow of dust.
(Use the insulation included with the unit, or
purchase materials that suit your site.)
Indoor Unit

Connecting the power and


1(L) 2(N) F1 F2 V1 V2 F3 F4
communication cables

CAUTION
• Always remember to connect the refrigerant pipes before 1(L) 2(N) L N F1 F2
performing the electric connections.
When disconnecting the system, always disconnect the
electric cables before disconnecting the refrigerant pipes.
• Always remember to connect the air conditioner to the Cable
grounding system before performing the electric connections. clamp

Use a crimp ring terminal at the end of each wire.


The indoor unit is powered through the outdoor unit by
means of a H07 RN-F connection cable (or a more power
Indoor Main power Communication
model), with insulation in synthetic rubber and a jacket Power cable cable
in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.
1 Remove the screw on the electrical component box and
remove the cover plate.
2 Route the connection cord through the side of the indoor
unit and connect the cable to the terminals refer to the
figure below.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

3 phase (**100/120/140/160**) • Power supply cords of parts of appliances for outdoor


use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC:60245 IEC 57 /
Indoor Unit CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
H07RN-F)
• Since it has the external power supply, refer to the
1(L) 2(N) F1 F2 V1 V2 F3 F4 outdoor unit installation manual for MAIN POWER.

1(L) 2(N) L1(R) L2(S) L3(T) N F1 F2

CAUTION
• When installing the indoor unit in a computer room or
Cable clamp
a server room, use the double shielded communication
cable (tape aluminum / polyester braid + copper) of
FROHH2R type.

Indoor 3 Phase 4 Wires power cable Communication


Power (AC 380V) cable

Indoor power supply

Power supply Max/Min(V) Indoor power cable

220 to 240V, 50 Hz ±10% 0.75 to 1.5 mm², 3 wires

Communication cable

0.75㎟↑, 2wires

**052**
AC power: M4 screw Communication: M3.5 screw

9.8 12.6 7.5 9.0


13.8
19

**071/100/120/140/160**
AC power: M4 screw Communication: M3.5 screw

10.3 13.8 10.1 11.4


19.2
19.2

Tightening torque (kgf • cm)

M3.5 8.0 to 12.0

M4 12.0 to 18.0

• 1 N·m = 10 kgf·cm

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

CAUTION
8. Outdoor Unit • You have just purchased a system air conditioner
and it has been installed by your installation
Installation location requirements specialist.
• This device must be installed according to the
national electrical rules.
• Do not place the outdoor unit on its side or upside
down. Failing to do so may cause the compressor • If your outdoor unit exceeds a net weight of 60 kg,
lubrication oil to run into the cooling circuit and lead do not install it on a suspended wall, but stand it
to a serious damage to the unit. on a floor.

• Install the unit in a well-ventilated location away • When installing the outdoor unit at the seaside, make
from direct sunlight or strong winds. sure that it is not directly exposed to sea breeze. If
you cannot find an adequate place free from direct
• Install the unit in a location that would not obstruct
sea breeze, construct a protection wall or a protective
any passageways or thoroughfares.
fence.
• Install the unit in a location that would not
– Install the outdoor unit in a place (such as near
inconvenience or disturb your neighbors, as they
buildings etc.) where it can be prevented from sea
could be affected by the noise or the airflow coming
breeze. Failure to do so may cause a damage to
from the unit.
the outdoor unit.
• Install the unit in a location where the pipes and the
cables can be easily connected to the indoor unit. Sea breeze Sea breeze

• Install the unit on a flat, stable surface that can


withstand the weight of the unit. Otherwise, the unit
Sea Sea
can generate noise and vibration during operation. Outdoor Unit Outdoor Unit

• Install the unit so that the air flow is directed towards


the open area.
• If you cannot avoid installing the outdoor unit at the
• Maintain sufficient clearance around the outdoor unit,
seaside, construct a protection wall around to block
especially from a radio, computer, stereo system, etc.
the sea breeze.
• Construct a protection wall with a solid material such
Fuse
Fuse as concrete to block the sea breeze. Make sure that
Indoor Unit the height and the width of the wall are 1.5 times
larger than the size of the outdoor unit. Also, secure
Control
a space larger than 700 mm between the protection
wall and the outdoor unit for exhausted air to
1.5 m or more

ventilate.
1 m or more

1 m or more

1.5 m or more

1.5 m or more Outdoor Unit


300 mm Sea breeze Protection wall

Sea

Stereo Computer etc


Outdoor Unit
200 mm
CAUTION
Air Guide Duct (This product is not provided by Samsung)
• Depending on the condition of power supply, unstable
power or voltage may cause malfunction of the parts
• Install the unit at a height where its base can be or control system. (At the ship or places using power
firmly fixed in place. supply from electric generator...etc)

• Make sure that the water dripping from the drain • Install the unit in a place where water can drain
hose runs away correctly and safely. smoothly.
• If you have any difficulty finding installation location
as prescribed above, contact your manufacturer for
details.
• Be sure to clean the sea water and the dust on the
heat exchanger of the outdoor unit and apply a
corrosion inhibitor on it. (At least once in a year.)

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Outdoor unit dimensions


(Unit: mm)
A Type F Type
AC035TXADKC AC160TXAD*C
285
940
50 562 12
548

343

330
620

1420
1395

360
384
1095
790 60

558
567
B Type
AC052TXADKC

310
661
638

338

15

880 58 Minimum clearances for the outdoor unit

C Type
When installing 1 outdoor unit
AC071TXADKC

310 (Unit: mm)


661

500 or more
150 or more
338
798

15

880 49

D Type
150 or
more

AC100TXAD*C
or more
1000

150 or 150 or 1000


940
more more or more
620
330
998

360
384
977

150 or
more
528
537
675

or more
500

150
or more
or more
1000

E Type
AC120/140TXAD*C

940
330

620
1210

360
384
1185

675
558
567

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

When installing more than 1 outdoor unit


WARNING
(Unit: mm) • Should adopt bar type louver. Don’t use a type of rain
resistance louver.
1000 200 2000 3000 150
or more or more or more or more or more
[Bar type louver] [Rain resistance louver]

or more
300
or more
150 150 1500 • Louver specifications.
or more or more
– Angle criteria : less than 20˚
– Opening ratio criteria : greater than 80%

Fixing the outdoor unit in place


or more
1000

Install the outdoor unit on a rigid and stable base to


prevent disturbance from any noise caused by vibration.
When installing the unit at a height or in a location
300
or more

exposed to strong winds, fix the unit securely to a


support (i.e., a wall or a ground).
300 150 150 200 Fix the outdoor unit with anchor bolts. Make sure that
or more or more or more or more
the anchor bolts are 20 mm or higher from the base
surface.
500 or more

300 or more

AC035TXADKC (Unit : mm)


Anchor bolt hole
285

317

343
500 or more

300 or more

612

790

AC052/071TXADKC
CAUTION Anchor bolt hole
• The outdoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
357

338

359

maintenance, and repair of the unit.


The components of the outdoor unit must be
reachable and removable under safe conditions for
people and the unit. 661
880

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

AC100/120/140/160TXAD*C (Unit : mm) • Connect the air conditioner to the earthing system
before making the electrical connections.
Anchor bolt hole

NOTE
• Especially, if your outdoor unit is the one designed
330

360

384
for Russian and European markets, consult the supply
authority, if necessary, to estimate and reduce the
supply system impedance before installation.
620
940
Air conditioning system examples

When using earth leakage circuit breaker (ELCB) for a


CAUTION single phase

• Install a drain outlet at the lowest end around the base Communication cable
for outdoor unit drainage Outdoor-to-indoor power cable

• When installing the outdoor unit on the roof,


waterproof the unit and check the ceiling strength. OR Outdoor Unit Communication cable

ELCB
1

Earthing
Main power cable Indoor Unit

Main power Communication cable


cable Outdoor-to-indoor power cable
MCCB
1 ELB Earthing
• Make sure that the wall can support the weights of the
rack and the outdoor unit. OR
ELCB
• Install the rack close to the column as much as
1
possible.
Outdoor Unit Indoor Unit

When using earth leakage circuit breaker (ELCB) for a


3-phase, 4-wire system (3P4W)
Connecting the power cables,
communication cable, and controllers Main power Communication cable
cable Outdoor-to-indoor power cable
MCCB
ELB Earthing
You must connect the following three electrical cables to 3

the outdoor unit: OR


ELCB
• The main power cable between the auxiliary circuit
3
breaker and the outdoor unit.
• The outdoor-to-indoor power cable between the Outdoor Unit Indoor Unit

outdoor unit and the indoor unit.


• The communication cable between the outdoor unit
and the indoor unit. CAUTION
• If the outdoor unit is installed in a location vulnerable
to an electric leak or submergence, make sure to
CAUTION install an ELCB.
• During installation, make first the refrigerant
connections and then the electrical connections. If
the unit is uninstalled, first disconnect the electrical
cables and then the refrigerant connections.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Connecting the main power cable

When using ELB

Power Supply

MCCB 1(L) 2(N) L N F1 F2

ELB

Cable clamp
Cable tie

Outdoor to indoor Communication


Main Power cable
power cable Cable

When using ELB for 1 phase and 3 phase

1-phase

Electrical
component box
Power Supply

MCCB

ELB

Cable tie

Outdoor-to Main power cable Communication cable


indoor power cable

3-phase

The appearance of the unit may be different from the


picture depending on the model.

Indoor Unit
Cable tie

Outdoor-to 3-phase 4-wire Communication


indoor power cable main power cable cable
(AC 380V)

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

CAUTION
• You should connect the power cable into the power cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 2% of supply rating.
If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is exceeded over
4% of supply rating, the indoor unit is protected, stopped and the error mode indicates.
• To protect the product from water and possible shock, you should keep the power cable and the connection cord of
the indoor and outdoor units within ducts. (with appropriate IP rating and material selection for your application)
• Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a least
3 mm.
• Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage
category.
• Keep distances of 50 mm or more between power cable and communication cable.

Main power terminal block specifications


AC035TXADKC AC052/071TXADKC (Unit: mm)

AC power: Comunication:
M4 screw M4 screw

1(L) 2(N) L N F1 F2
10.1
13.8 10.3
11.4

10.1
16.3 12 11.4

• 1-phase terminal block specifications • 3-phase terminal block specifications

AC100/120/140/160TXADKC (Unit: mm) AC100/120/140/160TXADNC (Unit: mm)

10.1 10.1
16.5 12 9.8 14.2
11.4 11.4

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Main power cable specifications


The power cable is not supplied with air conditioner.
• Select the power supply cable in accordance with relevant local and national regulations.
• Wire size must comply with the applicable local and national code.
• Specifications for local wiring power cord and branch wiring are in compliance with local cord.

Model Outdoor unit Input current (A) Power supply


Voltage range (V)
Indoor unit Outdoor unit Hz Outdoor unit Indoor unit Total MCA (A) MFA (A)
Rated Min. Max.
AC035TN1DKC 10 1.5 11.5 11.5 12.7
AC035TXADKC
AC035TNLDKC 10 1.7 11.7 11.7 12.9
AC052TN1DKC 20.0 1.5 21.5 21.5 25.0
AC052TN4PKC 20.0 1.5 21.5 21.5 25.0
AC052TN4DKC AC052TXADKC 20.0 1.5 21.5 21.5 25.0
AC052TNLDKC 20.0 2.3 22.3 22.3 25.0
AC052TNCDKC 20.0 1.5 21.5 21.5 25.0
AC071TN1DKC 20.0 1.5 21.5 21.5 25.0
AC071TN4PKC 20.0 1.5 21.5 21.5 25.0
AC071TN4DKC AC071TXADKC 20.0 1.5 21.5 21.5 25.0
AC071TNMDKC 20.0 2.3 22.3 22.3 25.0
AC071TNCDKC 20.0 2.5 22.5 22.5 25.0
AC100TN4PKC 24.0 2.0 26.0 26.0 30.0
AC100TN4DKC 24.0 2.0 26.0 26.0 30.0
AC100TXADKC 50 220 to 240 198 264
AC100TNMDKC 24.0 2.5 26.5 26.5 30.0
AC100TNCDKC 24.0 2.5 26.5 26.5 30.0
AC120TN4PKC 32.0 2.0 34.0 34.0 40.0
AC120TN4DKC 32.0 2.0 34.0 34.0 40.0
AC120TXADKC
AC120TNMDKC 32.0 2.5 34.5 34.5 40.0
AC120TNCDKC 32.0 2.5 34.5 34.5 40.0
AC140TN4PKC 32.0 2.0 34.0 34.0 40.0
AC140TN4DKC 32.0 2.0 34.0 34.0 40.0
AC140TXADKC
AC140TNMDKC 32.0 2.5 34.5 34.5 40.0
AC140TNCDKC 32.0 2.5 34.5 34.5 40.0
AC160TNMDKC 32.0 3.5 35.5 35.5 40.0
AC160TXADKC
AC160TNCDKC 32.0 3.0 35.0 35.0 40.0
AC100TN4PKC 16.1 2.0 18.1 18.1 18.1
AC100TN4DKC 16.1 2.0 18.1 18.1 18.1
AC100TXADNC 50 380 to 415 342 456.5
AC100TNMDKC 16.1 2.5 18.6 18.6 18.6
AC100TNCDKC 16.1 2.5 18.6 18.6 18.6

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Model Outdoor unit Input current (A) Power supply


Voltage range (V)
Indoor unit Outdoor unit Hz Outdoor unit Indoor unit Total MCA (A) MFA (A)
Rated Min. Max.
AC120TN4PKC 16.1 2.0 18.1 18.1 18.1
AC120TN4DKC 16.1 2.0 18.1 18.1 18.1
AC120TXADNC
AC120TNMDKC 16.1 2.5 18.6 18.6 18.6
AC120TNCDKC 16.1 2.5 18.6 18.6 18.6
AC140TN4PKC 16.1 2.0 18.1 18.1 18.1
50 380 to 415 342 456.5
AC140TN4DKC 16.1 2.0 18.1 18.1 18.1
AC140TXADNC
AC140TNMDKC 16.1 2.5 18.6 18.6 18.6
AC140TNCDKC 16.1 2.5 18.6 18.6 18.6
AC160TNMDKC 16.1 3.5 19.6 19.6 19.6
AC160TXADNC
AC160TNCDKC 16.1 3.0 19.1 19.1 19.1

NOTE
1 Voltage range
• Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above
listed range limits.
2 Maximum allowable voltage variation between phases is 2%.
3 Wire size & type must comply with the applicable local and national code.
• Wire size: Based on the value of MCA.
• Wire type: 60245 IEC57(IEC) or H05RN-F(CENELEC) grade or more.
4 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
5 MCA represents maximum input current.
• MFA represents capacity which may accept MCA
• Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)

Silence mode controller wiring diagram

• AC052/071TXADKC • AC100/120/140/160TXAD*C
Outdoor unit Outdoor unit

CN001

ASSY Control out

CN001
Non-voltage contact
Non-voltage contact

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Connecting the outdoor-to-indoor power cable 3-phase


and the communication cable

L
1-phase Indoor Unit

F1 F2
N
For connecting the power and
communication cables Outdoor Unit

F1 F2
1(L) 2(N) L1(R) L2(S)L3(T) N

Indoor Unit
1(L)
F2
2(N) F1 Cable tie
Outdoor-to-indoor 3-phase 4-wire main Communication cable
power cable power cable (AC 380V)

1(L) 2(N) L N

NOTE
• Lay the electrical wiring so that the front cover does
Outdoor-to-
indoor power not rise up when doing wiring work and attach the
cable front cover securely.
• Ground wire for the indoor unit and outdoor unit
Main power cable Communication cable connection cable must be clamped to a soft copper
Cable clamp
tin-plated eyelet terminal with M4 screw hole(NOT
SUPPLIED WITH UNIT ACCESSORIES).

Outdoor-to-indoor power terminal


For connecting the power and specifications
communication cables
• Connect the cables to the terminal board using the
compressed ring terminal.
• Cover a solderless ring terminal and a connector part
of the power cable and then connect it.
Indoor Unit

Silver solder

Outdoor Unit

Cable tie
Outdoor-to-indoor Main power cable Communication cable
power cable

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Nominal Nominal B D d1 E F L d2 t
dimensions dimensions Standard Standard Standard Standard
for cable for screw dimension Allowance dimension Allowance dimension Allowance Min. Min. Max. dimension Allowance Min.
(mm²) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
(mm) (mm) (mm) (mm)
+0.2
4 9.5 5 20.0 4.3
+0.3 0
4/6 ±0.2 5.6 3.4 ±0.2 6.0 0.9
-0.2 +0.4
8 15.0 9 28.5 8.4
0
+0.3 +0.4
10 8 15.0 ±0.2 7.1 4.5 ±0.2 7.9 9 30.0 8.4 1.15
-0.2 0
+0.3 +0.4
16 8 16.0 ±0.2 9.0 5.8 ±0.2 9.5 13 33.0 8.4 1.45
-0.2 0
8 12.0 +0.5 15 8.4 +0.4
25 ±0.3 11.5 7.7 ±0.2 11.0 34.0 1.7
8 16.5 -0.2 13 8.4 0

8 16.0 +0.5 13 38.0 8.4 +0.4


35 ±0.3 13.3 9.4 ±0.2 12.5 1.8
8 22.0 -0.2 13 43.0 8.4 0

+0.5 + 0.4
50 8 22.0 ±0.3 13.5 11.4 ±0.3 17.5 14 50.0 8.4 1.8
-0.2 0
+0.5 + 0.4
70 8 24.0 ±0.4 17.5 13.3 ±0.4 18.5 20 51.0 8.4 2.0
-0.4 0

• Connect the rated cables only. • Must keep the cable in a protection tube.
• Connect using a driver which is able to apply the rated • Keep distances of 50mm or more between power cable
torque to the screws. and communication cable.
• If the terminal is loose, fire may occur caused by arc. If • When the cables are connected through the hole,
the terminal is connected too firmly, the terminal may remove the Plate bottom.
be damaged.
Outdoor-to-indoor power and communication
Tightening torque (N·m) cables specifications
M4 0.8 to 1.2 Indoor power supply

M5 2.0 to 3.0 Power supply Max/Min (V) Indoor power cable

• 1 N·m = 10 kg·fcm Cassette : 0.75㎟, 2wires


1ø, 220-240V, 50 Hz ±10%
Duct, Ceiling : 1.5㎟, 2wires

Communication cable
CAUTION
0.75㎟, 2wires
• When connecting cables, you can connect the cables to
the electrical part or connect them through the holes • Power supply cords of parts of appliances for outdoor
below depending on the spot. use shall not be lighter than polychloroprene sheathed
• Connect the communication cable between the indoor flexible cord. (Code designation IEC:60245 IEC 57 /
and outdoor units through a conduit to protect against CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
external forces, and feed the conduit through the wall H07RN-F)
together with refrigerant piping. • When installing the indoor unit in a computer room
• Remove all burrs at the edge of the knock-out hole or net work room, use the double shielded (tape
and secure the cable to the outdoor knock-out using aluminium / polyester braid + copper ) cable of
lining and bushing with an electrical insulation such as FROHH2R type.
rubber and so on.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Connecting the refrigerant pipe CAUTION


• After connecting the pipes with knock-out treatment,
plug the space around the pipes.
Maximum allowable length
Items • After connecting the pipes, proceed exactly as
Single installation directed in the guide to prevent interference with the
Applicable outdoor unit internal parts.
AC035TXADKC
models
Max. height difference
Outdoor unit Main pipe
Main pipe (L1) 20 Items between outdoor and
models (L1)
indoor units (h1)
Max. height difference
AC052TXADKC 30 20
between outdoor and 15
AC071TXADKC 50 30
indoor units (h1)
Maximum AC100TXAD*C 50 30
allowable
length AC120TXAD*C 75 30
n=1
AC140TXAD*C 75 30
indoor
L1 AC160TXAD*C 75 30
h1

n=1 indoor
Indoor Unit
Outdoor L1
h1

• Temper grade and minimum thickness of the Outdoor


refrigerant pipe

• Temper grade and minimum thickness of the refrigerant pipe


Outer diameter Minimum
Temper grade
[mm] thickness [mm]
Outer diameter Minimum thickness
Temper grade
ø6.35 0.7 [mm] [mm]
ø9.52 0.7 ø 6.35 0.7
C1220T-O ø 9.52 0.7
ø12.70 0.8 C1220T-O
ø 12.70 0.8
ø15.88 1.0
ø 15.88 1.0
ø15.88 0.8
C1220T-1/2H OR ø 15.88 0.8
ø19.05 0.9 C1220T-1/2H OR
C1220T-H ø 19.05 0.9
C1220T-H
ø22.23 0.9 ø 22.23 0.9

CAUTION
CAUTION
• Be sure to use C1220T-1/2H (Semi-hard) pipe for more
• Be sure to use C1220T-1/2H (Semi-hard) pipe for
than Ø19.05 mm. If you use C1220T-O (Soft) pipe for Ø19.05
more than Ø19.05 mm. If you use C1220T-O (Soft)
mm, the pipe may be broken, which can result in an injury.
pipe for Ø19.05 mm, the pipe may be broken, which
can result in an injury.
Make at least one round:
It will reduce noise and vibration

Make at least one round:


It will reduce noise and vibration

A
• The appearance of the unit may be different from the Block the part.
diagram depending on the model.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

• The appearance of the unit may be different from the


3 If you have any difficulty charging the refrigerant as
diagram depending on the model.
described in the steps above, take the following steps:
CAUTION a Open the liquid stop valve and gas stop valve.
b Operate the air conditioner by pressing the K2
button on the outdoor unit PCB.
c After about 30 minutes, charge the refrigerant
through the service port of the gas stop valve.
Pipe outlet

AC035/052/071TXADKC

Indoor Unit
• Cut the pipe outlet to the exact pipe size. In addition,
remove foreign substances and burres aroud the outlet.
Balance
• Perform cutting with only a cutter (ex. nipper) and Ref
never tap with a hammer near the pipe outlet.
Otherwise, damage to products such as the cabinet Vacuum
being bent may occur. Pump

• After connecting the pipes with pipe outlet, plug the


space around the pipes.
Gas side stop valve
• After connecting the pipes, proceed exactly as directed in (service port)
the guide to prevent interference with the internal parts. Liquid side stop valve
(Non-service port)
• Tighten the nuts to the specified torques. If overtightened,
the nuts could be broken so refrigerant may leak.
• Protect or enclose refrigerant tubing to avoid AC100/120/140/160TXAD*C
mechanical damage. Liquid side stop valve(service port)
Indoor Unit Gas side stop valve(service port)
• After installing pipes, block the unused knock hole
to prevent small animal from entering. However, the
radiant heat hole(A) should be able to intake air.

Balance
Adding refrigerant (R-410A) Outdoor Unit
Ref

• The outdoor unit is loaded with sufficient refrigerant Vacuum


Pump
for the standard piping. Thus, refrigerant must be
added if the piping is lengthened. This operation
can only be performed by a qualified refrigeration
Calculating the quantity of refrigerant to add
specialist. To determine the quantity of refrigerant
charge, see Calculating the quantity of refrigerant to The quantity of additional refrigerant is variable
add on page 22. according to the installation situation. Thus, make sure
1 Check if the stop valve is closed completely. the outdoor unit situation before adding refrigerant.
2 AC052/071TXADKC : Charge the refrigerant through This operation can only be performed by a qualified
the service port of the gas stop valve. refrigeration specialist.
AC100/120/140/160TXAD*C : Charge the refrigerant
through the service port of the liquid stop valve. When installing the outdoor unit only

Interconnection pipe length (m)


NOTE Model
• AC100/120/140/160TXAD*C : Do not charge the 0 to 20 20 to 30 30 to 40 40 to 50

refrigerant through the service port of the gas stop valve.


AC035TXADKC 0

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Interconnection pipe length (m)


Model
0~30 30~40 40~50 50~60 60~70 70~75
AC052TXADKC +15g/m over 5m
AC071TXADKC +10g/m over 5m
AC100TXAD*C +50g/m over 30m
AC120TXAD*C +50g/m over 30m
AC140TXAD*C +50g/m over 30m
AC160TXAD*C +50g/m over 30m

Performing the gas leak test • AC100/120/140/160TXAD*C

LEAK TEST WITH NITROGEN (before opening valves)


In order to detect basic refrigerant leaks, before recreating the
vacuum and recirculating the R-410A, it is the responsibility
of the installer to pressurize the whole system with nitrogen
(using a cylinder with pressure reducer) at a pressure above
0.2MPa, less than 4MPa (gauge).
LEAK TEST WITH R-410A (after opening valves) A (Gas)
Before opening valves, discharge all the nitrogen into the B (liquid)
system and create vacuum. After opening valves check
leaks using a leak detector for refrigerant R-410A.
Once you have completed all the connections, check for
possible leaks using leak detector specifically designed for
HFC refrigerants.
• AC035/052/071TXADKC

A(Gas)
• The designs and shape are subject to change
B (liquid)
according to the model.

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation

Step 11 Connecting the drain hose to AC100/120/140/160TXAD*C


the outdoor unit Drain cap (3EA)
Drain plug (1EA)
1 Make space more than 80 mm between the bottom of
the outdoor unit and the ground for installation of the
drain hose, as shown in figure.
2 Insert the drain plug into the hole on the underside of
the outdoor unit.
3 Connect the drain hose to the drain plug.
4 Ensure that the drained water runs off correctly and safely.

• When installing the product, make sure that the


rack is not placed under the drain hole.
• If the product is installed in a region of heavy snow,
allow enough separation distance between the
product and the ground.

80 mm 13 mm

5 Be sure to plug the rest of drain holes not connected


with drain plugs using drain caps.

AC035TXADKC
Drain cap (5EA)

Drain plug (1EA)

AC052/071TXADKC
Drain cap (4EA)
Drain plug (1EA)

※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
2020. 06
Ver.1.0
Samsung Electronics Co., LTD.
Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677
Website : www.samsung.com, https://partnerhub.samsung.com Email : airconditioner@samsung.com
Images and data in this book may subject to change without prior notice.