Technical
Data Book
SINGLE for South East Asia
(R410A, Cooling Only)
Improve EER level : average 13~15% higher than Even cooling For spacious space
conventional models.
Universal outdoor unit makes more efficient More compatibility with new controllers.
stock management.
Nomenclature
Indoor Unit
Model Name
AC 052 T N 4 D K C EA
(1) (2) (3) (4) (5) (6) (7) (8) Buyer
(6) Feature
(8) Mode
Model Name
AC 052 T X A D K C EA
(1) (2) (3) (4) (5) (6) (7) (8) Buyer
(6) Feature
(2) Capacity
F Flagship
X 1/10 kW (3 digits) S Standard
D Deluxe
P Premium
(3) Version
T 2020
(7) Rating Voltage
N Indoor Unit
X Outdoor Unit (8) Mode
Capacity (kW)
Model
3.5 5.2 7.1 10.0 12.0 14.0 16.0
Wind-
Free 1Way
Cassette
Wind-
Free 4Way
Cassett
360 Cassette
Duct
Ceiling
Line-up
Outdoor Unit
Capacity (kW)
Model
3.5 5.2 7.1 10.0 12.0 / 14.0 16.0
1Phase
3Phase
Contents
1. Specification 11
2. Summary Table 14
3. Capacity Table 15
4. Dimensional Drawing 16
5. Center of Gravity 18
6. Electrical Wiring Diagram 19
7. Sound Data 20
8. Temperature and airflow distribution 21
Features & Benefits
Wind-Free 1Way Cassette
Comfort wind implementation by Wind-Free cooling Even cooling For spacious space
Kitchen
Micro hole
Living room
Conventional
68 mm
Wind-Free
100 mm
5.5m
0.6m
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
Wind-Free 1Way Cassette
Performance Characteristics
Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 4.1 - High 9.0 38
AC035TN1DKC/EA 9.2 Std. 3.5 - Mid 8.2 35
Min. 1.0 - Low 7.2 32
Max. 6.0 - High 14.0 41
AC052TN1DKC/EA 13.4 Std. 5.0 - Mid 13.0 38
Min. 1.5 - Low 12.0 35
Max. 7.8 - High 15.0 46
AC071TN1DKC/EA 13.4 Std. 6.1 - Mid 14.0 42
Min. 1.8 - Low 12.5 38
NOTE
•• Sound data is based on cooling operation.
Electric Characteristics
NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
Wind-Free 1Way Cassette
(1) AC035TN1DKC/EA+AC035TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 3.4 2.5 0.78 3.6 2.6 0.80 3.7 2.7 0.81 3.9 2.7 0.83 3.9 2.7 0.84 4.1 2.7 0.84 4.3 2.6 0.86
21 3.3 2.4 0.82 3.4 2.5 0.84 3.6 2.5 0.85 3.7 2.6 0.87 3.7 2.6 0.88 3.9 2.6 0.89 4.1 2.5 0.91
35 3.1 2.4 0.98 3.3 2.5 1.00 3.4 2.5 1.02 3.5 2.6 1.05 3.6 2.6 1.06 3.7 2.6 1.07 3.9 2.5 1.09
46 2.6 2.1 0.92 2.8 2.2 0.94 2.9 2.3 0.96 3.0 2.3 0.98 3.0 2.3 0.99 3.2 2.3 1.00 3.3 2.2 1.02
48 2.3 1.9 0.87 2.4 2.0 0.89 2.5 2.0 0.91 2.8 2.2 0.93 2.7 2.1 0.94 2.8 2.0 0.95 3.0 2.0 0.96
50 2.0 1.7 0.82 2.1 1.7 0.84 2.2 1.8 0.85 2.6 2.1 0.87 2.3 1.8 0.88 2.4 1.8 0.89 2.6 1.8 0.91
(2) AC052TN1DKC/EA+AC052TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 4.7 3.5 1.35 4.9 3.7 1.37 5.2 3.8 1.40 5.3 3.9 1.43 5.4 3.8 1.44 5.7 3.8 1.46 6.0 3.7 1.49
21 5.3 3.8 1.16 5.6 3.9 1.19 5.8 4.0 1.21 6.0 4.2 1.23 6.1 4.1 1.25 6.4 4.1 1.26 6.7 4.0 1.28
35 4.4 3.6 1.38 4.7 3.7 1.41 4.9 3.8 1.44 5.0 3.9 1.47 5.1 3.9 1.48 5.4 3.8 1.50 5.6 3.7 1.53
46 4.8 3.6 2.36 5.0 3.7 2.41 5.2 3.8 2.45 5.4 3.9 2.50 5.5 3.9 2.53 5.8 3.8 2.55 6.1 3.7 2.61
48 4.5 3.4 2.37 4.7 3.5 2.42 4.9 3.6 2.47 5.1 3.7 2.52 5.2 3.7 2.54 5.4 3.7 2.57 5.7 3.6 2.62
50 4.2 3.3 2.38 4.4 3.4 2.43 4.6 3.5 2.48 4.7 3.6 2.53 4.8 3.6 2.56 5.0 3.5 2.58 5.3 3.4 2.64
(3) AC071TN1DKC/EA+AC071TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 6.0 4.1 2.23 6.3 4.3 2.28 6.6 4.4 2.32 6.8 4.5 2.37 6.9 4.5 2.40 7.3 4.5 2.42 7.6 4.4 2.47
21 6.6 4.5 1.90 6.9 4.6 1.94 7.2 4.8 1.98 7.4 4.9 2.02 7.6 4.9 2.04 8.0 4.8 2.06 8.4 4.7 2.10
35 5.4 4.1 1.85 5.7 4.2 1.89 5.9 4.3 1.93 6.1 4.5 1.97 6.2 4.4 1.99 6.5 4.4 2.01 6.9 4.3 2.05
46 5.1 3.8 2.68 5.4 3.9 2.74 5.6 4.0 2.79 5.8 4.2 2.85 5.9 4.1 2.88 6.2 4.1 2.91 6.5 4.0 2.96
48 4.8 3.7 2.64 5.1 3.8 2.69 5.3 3.9 2.75 5.5 4.0 2.80 5.6 4.0 2.83 5.9 3.9 2.86 6.1 3.9 2.92
50 4.5 3.5 2.59 4.8 3.7 2.65 5.0 3.8 2.70 5.1 3.9 2.76 5.2 3.8 2.78 5.5 3.8 2.81 5.8 3.7 2.87
NOTE
•• The performance table shows the average value of each conditions.
4. Dimensional Drawing
Wind-Free 1Way Cassette
AC035TN1DKC/EA
Units : mm [inches]
NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
4. Dimensional Dra
Drawing
Wind-Free 1Way Cassette
AC052TN1DKC/EA, AC071TN1DKC/EA
Units : mm [inches]
Description
No. Name
AC052TN1DKC/EA AC071TN1DKC/EA
1 Gas pipe connection Ø12.7 (1/2) 15.88 (5/8)
2 Liquid pipe connection Ø6.35 (1/4)
3 Drain pipe connection VP25 (OD 32,ID 25)
4 Power supply & Communication wiring conduit -
5 Air outlet louver -
6 Air inlet grille -
NOTE
• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
5. Center of Gravity
Wind-Free 1Way Cassette
Units : mm [inches]
Model A B C D E
1,198 500 108 555 200
AC035TN1DKC/EA
[47-3/16] [19-11/16] [4-1/2] [21-7/8] [7-7/8]
AC052TN1DKC/EA 1,410 500 108 755 200
AC071TN1DKC/EA [55-1/2] [19-11/16] [4-1/2] [29-3/8] [7-7/8]
6. Electrical Wiring Diagram
Wind-Free 1Way Cassette
SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
FLOAT SWITCH Check the FLOATING S/W EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)
NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
Wind-Free 1Way Cassette
• NC Curve
1) AC035TN1DKC/EA 2) AC052TN1DKC/EA
2) AC071TN1DKC/EA
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
8. Temperature and airflow distribution
Wind-Free 1Way Cassette
AC035TN1DKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
AC052TN1DKC/EA
• •Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
AC071TN1DKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
Wind-Free 4Way Cassette
1. Specification 24
2. Summary Table 33
3. Capacity Table 34
4. Dimensional Drawing 36
5. Center of Gravity 38
6. Electrical Wiring Diagram 39
7. Sound Data 40
8. Temperature and air flow distribution 42
F
eatures & Benefits
Wind-Free 4Way Cassette
Stage a beautiful yet comfortable environment The Samsung Wind-Free 4Way Cassette indoor air
conditioning system delivers polish, comfort and
With its newly improved design, Wind-Free 4Way Cassette efficiency with features such as:
supports a clean, aesthetically appealing atmosphere and
adds a sense of sophistication to work and living spaces. • Stylishly clean design. Add panache to interior
Not only is this unit attractively designed, but it also spaces with a choice of clean, streamlined panel
uses advanced technologies to optimize comfort in any patterns in a lightweight build.
environment. • Robust operation. Control the atmosphere perfectly
with an advanced design for superior air flow and
cooling/heating performance.
• Low maintenance and simple installation. Ease
installation and minimize maintenance with a
detachable, no-drip design.
11kg 17kg
1. Specification
Wind-Free 4Way Cassette
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Wind-Free 4Way Cassette
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Wind-Free 4Way Cassette
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
Wind-Free 4Way Cassette
Performance Characteristics
Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 6.0 - High 16.9 35
AC052TN4DKC/EA 14.5 Std. 5.0 - Mid 15.9 33
Min. 1.0 - Low 14.9 31
Max. 8.5 - High 20.8 40
AC071TN4DKC/EA 14.5 Std. 7.1 - Mid 17.8 36
Min. 2.2 - Low 14.8 32
Max. 12.0 - High 30.3 43
AC100TN4DKC/EA 20.0 Std. 10.0 - Mid 24.3 38
Min. 3.0 - Low 19.4 33
Max. 14.0 - High 31.5 44
AC120TN4DKC/EA 20.0 Std. 12.1 - Mid 25.5 40
Min. 3.5 - Low 20.5 35
Max. 15.5 - High 31.5 44
AC140TN4DKC/EA 20.0 Std. 13.4 - Mid 26.7 41
Min. 3.5 - Low 21.8 37
NOTE
•• Sound data is based on cooling operation.
Electric Characteristics
Model Outdoor Unit Maximum Input Current [A] Power Supply
Rated Voltage range Outdoor Unit Indoor
Indoor Unit Outdoor Unit Total MCA MFA
Hz Volts Min. Max. Cooling Heating Unit
AC052TN4DKC/EA AC052TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC071TN4DKC/EA AC071TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC100TN4DKC/EA AC100TXADKC/EA 50 220 to 240 198 264 24.0 - 2.0 26.0 26.0 30.0
AC100TN4DKC/EA AC100TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
AC120TN4DKC/EA AC120TXADKC/EA 50 220 to 240 198 264 32.0 - 2.0 34.0 34.0 40.0
AC120TN4DKC/EA AC120TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
AC140TN4DKC/EA AC140TXADKC/EA 50 220 to 240 198 264 32.0 - 2.0 34.0 34.0 40.0
AC140TN4DKC/EA AC140TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
Wind-Free 4Way Cassette
(1) AC052TN4DKC/EA+AC052TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 5.1 4.3 1.18 5.4 4.4 1.20 5.6 4.5 1.23 5.8 4.7 1.25 5.9 4.6 1.27 6.2 4.6 1.28 6.5 4.5 1.30
21 5.4 4.4 1.12 5.7 4.5 1.15 5.9 4.7 1.17 6.1 4.8 1.19 6.2 4.7 1.20 6.5 4.7 1.22 6.8 4.6 1.24
35 4.4 3.9 1.33 4.7 4.1 1.35 4.9 4.2 1.38 5.0 4.2 1.41 5.1 4.3 1.42 5.4 4.2 1.44 5.6 4.1 1.47
46 5.0 4.2 2.37 5.3 4.3 2.42 5.5 4.5 2.47 5.7 4.6 2.52 5.8 4.6 2.55 6.1 4.5 2.57 6.4 4.4 2.62
48 4.7 4.1 2.43 5.0 4.2 2.48 5.2 4.3 2.53 5.4 4.5 2.58 5.5 4.4 2.60 5.7 4.4 2.63 6.0 4.3 2.68
50 4.5 4.0 2.48 4.7 4.1 2.53 4.9 4.2 2.58 5.0 4.4 2.63 5.2 4.3 2.66 5.4 4.3 2.69 5.7 4.2 2.74
(2) AC071TN4DKC/EA+AC071TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 6.9 5.2 2.19 7.3 5.4 2.23 7.6 5.6 2.28 7.8 5.7 2.33 8.0 5.7 2.35 8.4 5.6 2.37 8.8 5.5 2.42
21 8.1 5.9 2.14 8.6 6.1 2.19 8.9 6.2 2.23 9.2 6.4 2.28 9.4 6.4 2.30 9.9 6.3 2.32 10.4 6.2 2.37
35 6.3 5.1 2.06 6.6 5.2 2.10 6.9 5.4 2.14 7.1 5.6 2.19 7.2 5.5 2.21 7.6 5.5 2.23 8.0 5.3 2.27
46 6.0 4.9 2.71 6.3 5.0 2.77 6.6 5.2 2.82 6.8 5.4 2.88 7.0 5.3 2.91 7.3 5.3 2.94 7.7 5.2 3.00
48 5.6 4.7 2.64 5.9 4.9 2.70 6.2 5.0 2.75 6.4 5.2 2.81 6.5 5.1 2.84 6.8 5.1 2.87 7.2 5.0 2.92
50 5.3 4.6 2.58 5.5 4.7 2.63 5.8 4.8 2.68 5.9 5.0 2.74 6.1 4.9 2.76 6.4 4.9 2.79 6.7 4.8 2.85
(3) AC100TN4DKC/EA+AC100TXAD*C/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 9.7 7.8 2.46 10.2 8.1 2.51 10.7 8.3 2.56 11.0 8.6 2.61 11.2 8.5 2.64 11.8 8.4 2.66 12.4 8.2 2.71
21 10.5 8.1 2.44 11.0 8.3 2.49 11.5 8.6 2.54 11.8 8.8 2.59 12.1 8.8 2.61 12.7 8.7 2.64 13.3 8.5 2.69
35 8.8 7.3 2.94 9.3 7.5 3.00 9.7 7.8 3.06 10.0 8.0 3.13 10.2 7.9 3.16 10.7 7.9 3.19 11.2 7.7 3.25
46 7.6 6.6 3.45 8.0 6.8 3.52 8.3 7.0 3.59 8.6 7.2 3.66 8.8 7.2 3.70 9.2 7.1 3.74 9.7 7.0 3.81
48 7.1 6.5 3.20 7.5 6.7 3.26 7.8 6.9 3.33 8.1 7.1 3.40 8.2 7.0 3.43 8.6 7.0 3.47 9.1 6.8 3.54
50 6.7 6.4 2.95 7.0 6.6 3.01 7.3 6.8 3.07 7.6 7.0 3.13 7.7 6.9 3.16 8.1 6.9 3.20 8.5 6.7 3.26
NOTE
•• The performance table shows the average value of each conditions.
3. Capacity Table
Wind-Free 4Way Cassette
(4) AC120TN4DKC/EA+AC120TXAD*C/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 11.8 8.9 2.64 12.4 9.2 2.70 12.9 9.4 2.75 13.3 9.7 2.81 13.6 9.6 2.84 14.3 9.5 2.86 15.0 9.4 2.92
21 11.2 8.5 2.78 11.8 8.7 2.84 12.3 9.0 2.90 12.7 9.3 2.96 13.0 9.2 2.99 13.6 9.1 3.01 14.3 8.9 3.08
35 10.7 8.2 3.45 11.3 8.5 3.52 11.7 8.7 3.60 12.1 9.0 3.67 12.3 8.9 3.71 13.0 8.8 3.74 13.6 8.7 3.82
46 9.3 8.1 3.13 9.8 8.3 3.19 10.2 8.6 3.26 10.5 8.8 3.33 10.7 8.8 3.36 11.3 8.7 3.39 11.8 8.5 3.46
48 8.3 7.3 2.96 8.7 7.6 3.02 9.1 7.8 3.08 9.4 8.0 3.14 9.6 8.0 3.17 10.0 7.9 3.20 10.5 7.7 3.27
50 7.3 6.6 2.78 7.7 6.8 2.84 8.0 7.0 2.90 8.2 7.2 2.96 8.4 7.2 2.99 8.8 7.1 3.01 9.3 7.0 3.08
(5) AC140TN4DKC/EA+AC140TXAD*C/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 13.1 9.8 3.18 13.8 10.1 3.25 14.3 10.5 3.31 14.8 10.8 3.38 15.1 10.7 3.42 15.8 10.6 3.45 16.6 10.4 3.52
21 12.4 9.4 3.35 13.1 9.7 3.42 13.6 10.0 3.49 14.1 10.3 3.56 14.4 10.2 3.60 15.1 10.1 3.63 15.8 9.9 3.70
35 11.9 8.8 4.16 12.5 9.1 4.24 13.0 9.3 4.33 13.4 9.6 4.42 13.7 9.5 4.46 14.4 9.4 4.51 15.1 9.3 4.60
46 10.1 8.7 3.77 10.6 9.0 3.85 11.0 9.3 3.92 11.4 9.6 4.01 11.6 9.5 4.05 12.2 9.4 4.09 12.8 9.2 4.17
48 8.9 7.9 3.56 9.4 8.1 3.63 9.7 8.4 3.71 10.1 8.6 3.78 10.3 8.5 3.82 10.8 8.4 3.86 11.3 8.3 3.94
50 7.7 7.0 3.35 8.1 7.2 3.42 8.4 7.4 3.49 8.7 7.7 3.56 8.9 7.6 3.60 9.3 7.5 3.63 9.8 7.4 3.70
NOTE
• The performance table shows the average value of each conditions.
4. Dimensional Drawing
Wind-Free 4Way Cassette
AC052TN4DKC/EA, AC071TN4DKC/EA
Units : mm [inches]
(Ceiling opening)
735 [28-15/18]
840 [33-1/16]
80 [3-1/8]
40 [1-9/16]
133 [5-1/4]
185 [7-1/4]
239 [9-3/8]
70 [2-3/4]
61 [7-1/4] 101
[2-3/8] 80 [3-1/8]
93 [3-11/16] [4]
[4-3/4]
120
[8-7/16]
[7-11/16]
[8-1/8]
215
206
196
[6]
[4-1/8]
153
105
950
[37-3/8]
48 [1-7/8]
[8-1/16]
204
[37-3/8]
[5-3/16]
950
132
[2-1/2]
64
Description
No. Name
AC052TN4DKC/EA AC071TN4DKC/EA
1 Liquid pipe connection Φ6.35(1/4)
2 Gas pipe connection Φ12.7(1/2) Φ15.88(5/8)
3 Drain pipe connection VP-25(OD32, ID25)
4 Power supply & Communication wiring conduit
5 Fresh air intake knockout hole Φ10[4] , Use M4 Screw
NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
4. Dimensional Drawing
Wind-Free 4Way Cassette
(Ceiling opening)
735 [28-15/16]
417 [16-7/16]
Adjustable (until 550mm)
Adjustable (until 21-5/16 inches)
427 [16-13/16]
840 Ø101
239 61 55 55
[33-1/16] [ Ø4] 80 [3-1/8]
40 [1-9/16]
133 [5-1/4]
185 [7-1/4]
70 [2-3/4]
80 [3-1/8]
222 [8-3/4]
[11-5/16]
48 [1-7/8]
288
[6-3/4]
[5-3/16]
172
330 237 132 195
[13] [9-5/16] 8
[7-11/16]
3 302 4 1 2
185 [11-7/8]
[7-5/16] 5
176 950
[6-15/16] [37-3/8]
238
[9]
370 (4 x 92.5)
127
[5]
A
[14-9/16 (4 x 3-5/8)]
A
[37-3/8]
[4-3/4 (2 x 2-3/8)]
950
[98-7/16 or more]
7
120 (2 x 60)
2500 or more
101 [4]
166 [6-1/2]
351 [13-13/16]
DETAIL A
6
SCALE 1:3
NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
5. Center of Gravity
Wind-Free 4Way Cassette
Units : mm [inches]
445 [17-1/2]
A B
AC052/071TN4DKC/EA 221 [8-11/16] 70 [2-3/4]
AC100/120/140TN4DKC/EA 305 [12] 130 [5-1/8]
6. Electrical Wiring Diagram
Wind-Free 4Way Cassette
SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
FLOAT SWITCH Switch of the float of Drain EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)
NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
Wind-Free 4Way Cassette
Microphone
• NC Curve
1) AC052TN4DKC/EA 2) AC071TN4DKC/EA
3) AC100TN4DKC/EA 4) AC120TN4DKC/EA
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
7. Sound Data
Wind-Free 4Way Cassette
1.5m
Microphone
• NC Curve
1) AC140TN4DKC/EA
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
8. Temperature and air flow distribution
Wind-Free 4Way Cassette
AC052TN4DKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)
AC071TN4DKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)
AC100TN4DKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)
8. Temperature and air flow distribution
Wind-Free 4Way Cassette
AC120TN4DKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)
AC140TN4DKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 45 degree) (Discharge angle : 45 degree)
360 Cassette
1. Specification 46
2. Summary Table 56
3. Capacity Table 57
4. Dimensional Drawing 59
5. Center of Gravity 67
6. Electrical Wiring Diagram 68
7. Sound Data 69
8. Temperature and air flow distribution 71
Features
& Benefits
360 Cassette
A bladeless design softly disperses cool air across the An innovative Booster Fan enables cool air to be
room, making you comfortably cool without feeling a expelled at much lower angles. It creates a low pressure
cold draft**. With no blades to block the air flow, it also area around the outlet, so that cool air comes out
expels 25% more air* and spreads it farther. parallel to the ceiling and disperses across a wider area.
Circular to perfectly fit in everywhere All round simpler & intuitive control
Its innovative circular design can match a multitude of Intuitively control its performance and see where the
interior designs, so it perfectly fits in everywhere. Its air is going. The Wireless Remote Controller's* Jog
minimalist modern styling creates a sophisticated look shuttle and button offer a fun way to adjust the air flow
and its circular shape stands out beautifully. and a Circular LED Display shows its direction.
*Optional
1. Specification
360 Cassette
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
360 Cassette
Performance Characteristics
Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 6.0 - High 17.7 36
AC052TN4PKC/EA 20.2 Std. 5.0 - Mid 15.6 34
Min. 1.0 - Low 14.1 32
Max. 8.5 - High 21.3 41
AC071TN4PKC/EA 20.2 Std. 7.1 - Mid 16.8 37
Min. 2.2 - Low 13.2 33
Max. 12.0 - High 31.2 44
AC100TN4PKC/EA 25.5 Std. 10.0 - Mid 25.5 39
Min. 3.0 - Low 19.8 33
Max. 14.0 - High 32.0 45
AC120TN4PKC/EA 25.5 Std. 12.1 - Mid 26.0 41
Min. 3.5 - Low 19.5 36
Max. 15.5 - High 33.3 45
AC140TN4PKC/EA 25.5 Std. 13.4 - Mid 27.0 42
Min. 3.5 - Low 21.7 38
NOTE
•• Sound data is based on cooling operation.
Electric Characteristics
Model Outdoor Unit Maximum Input Current [A] Power Supply
Rated Voltage range Outdoor Unit Indoor
Indoor Unit Outdoor Unit Total MCA MFA
Hz Volts Min. Max. Cooling Heating Unit
AC052TN4PKC/EA AC052TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC071TN4PKC/EA AC071TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC100TN4PKC/EA AC100TXADKC/EA 50 220 to 240 198 264 24.0 - 2.0 26.0 26.0 30.0
AC100TN4PKC/EA AC100TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
AC120TN4PKC/EA AC120TXADKC/EA 50 220 to 240 198 264 32.0 - 2.0 34.0 34.0 40.0
AC120TN4PKC/EA AC120TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
AC140TN4PKC/EA AC140TXADKC/EA 50 220 to 240 198 264 32.0 - 2.0 34.0 34.0 40.0
AC140TN4PKC/EA AC140TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.0 18.1 18.1 18.1
NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
360 Cassette
(1) AC052TN4PKC/EA+AC052TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 5.1 4.3 1.18 5.4 4.4 1.20 5.6 4.5 1.23 5.8 4.7 1.25 5.9 4.6 1.27 6.2 4.6 1.28 6.5 4.5 1.30
21 5.4 4.4 1.12 5.7 4.5 1.15 5.9 4.7 1.17 6.1 4.8 1.19 6.2 4.7 1.20 6.5 4.7 1.22 6.8 4.6 1.24
35 4.4 3.9 1.33 4.7 4.1 1.35 4.9 4.2 1.38 5.0 4.3 1.41 5.1 4.3 1.42 5.4 4.2 1.44 5.6 4.1 1.47
46 5.0 4.2 2.37 5.3 4.3 2.42 5.5 4.5 2.47 5.7 4.6 2.52 5.8 4.6 2.55 6.1 4.5 2.57 6.4 4.4 2.62
48 4.7 4.1 2.43 5.0 4.2 2.48 5.2 4.3 2.53 5.4 4.5 2.58 5.5 4.4 2.60 5.7 4.4 2.63 6.0 4.3 2.68
50 4.5 4.0 2.48 4.7 4.1 2.53 4.9 4.2 2.58 5.0 4.4 2.63 5.2 4.3 2.66 5.4 4.3 2.69 5.7 4.2 2.74
(2) AC071TN4PKC/EA+AC071TXADKC/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 6.9 5.2 2.19 7.3 5.4 2.23 7.6 5.6 2.28 7.8 5.7 2.33 8.0 5.7 2.35 8.4 5.6 2.37 8.8 5.5 2.42
21 8.1 5.9 2.14 8.6 6.1 2.19 8.9 6.2 2.23 9.2 6.4 2.28 9.4 6.4 2.30 9.9 6.3 2.32 10.4 6.2 2.37
35 6.3 5.0 2.06 6.6 5.2 2.10 6.9 5.3 2.14 7.1 5.5 2.19 7.2 5.4 2.21 7.6 5.4 2.23 8.0 5.3 2.27
46 6.0 4.9 2.71 6.3 5.0 2.77 6.6 5.2 2.82 6.8 5.4 2.88 7.0 5.3 2.91 7.3 5.3 2.94 7.7 5.2 3.00
48 5.6 4.7 2.64 5.9 4.9 2.70 6.2 5.0 2.75 6.4 5.2 2.81 6.5 5.1 2.84 6.8 5.1 2.87 7.2 5.0 2.92
50 5.3 4.6 2.58 5.5 4.7 2.63 5.8 4.8 2.68 5.9 5.0 2.74 6.1 4.9 2.76 6.4 4.9 2.79 6.7 4.8 2.85
(3) AC100TN4PKC/EA+AC100TXAD*C/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 9.7 7.8 2.46 10.2 8.1 2.51 10.7 8.3 2.56 11.0 8.6 2.61 11.2 8.5 2.64 11.8 8.4 2.66 12.4 8.2 2.71
21 10.5 8.1 2.44 11.0 8.3 2.49 11.5 8.6 2.54 11.8 8.8 2.59 12.1 8.8 2.61 12.7 8.7 2.64 13.3 8.5 2.69
35 8.8 7.3 2.94 9.3 7.5 3.00 9.7 7.8 3.06 10.0 8.0 3.13 10.2 7.9 3.16 10.7 7.9 3.19 11.2 7.7 3.25
46 7.6 6.6 3.45 8.0 6.8 3.52 8.3 7.0 3.59 8.6 7.2 3.66 8.8 7.2 3.70 9.2 7.1 3.74 9.7 7.0 3.81
48 7.1 6.5 3.20 7.5 6.7 3.26 7.8 6.9 3.33 8.1 7.1 3.40 8.2 7.0 3.43 8.6 7.0 3.47 9.1 6.8 3.54
50 6.7 6.4 2.95 7.0 6.6 3.01 7.3 6.8 3.07 7.6 7.0 3.13 7.7 6.9 3.16 8.1 6.9 3.20 8.5 6.7 3.26
NOTE
•• The performance table shows the average value of each conditions.
3. Capacity Table
360 Cassette
(4) AC120TN4PKC/EA+AC120TXAD*C/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 11.8 8.9 2.64 12.4 9.2 2.70 12.9 9.4 2.75 13.3 9.7 2.81 13.6 9.6 2.84 14.3 9.5 2.86 15.0 9.4 2.92
21 11.2 8.5 2.78 11.8 8.7 2.84 12.3 9.0 2.90 12.7 9.3 2.96 13.0 9.2 2.99 13.6 9.1 3.01 14.3 8.9 3.08
35 10.7 8.2 3.45 11.3 8.5 3.52 11.7 8.7 3.60 12.1 9.0 3.67 12.3 8.9 3.71 13.0 8.8 3.74 13.6 8.7 3.82
46 9.3 8.1 3.13 9.8 8.3 3.19 10.2 8.6 3.26 10.5 8.8 3.33 10.7 8.8 3.36 11.3 8.7 3.39 11.8 8.5 3.46
48 8.3 7.3 2.96 8.7 7.6 3.02 9.1 7.8 3.08 9.4 8.0 3.14 9.6 8.0 3.17 10.0 7.9 3.20 10.5 7.7 3.27
50 7.3 6.6 2.78 7.7 6.8 2.84 8.0 7.0 2.90 8.2 7.2 2.96 8.4 7.2 2.99 8.8 7.1 3.01 9.3 7.0 3.08
(5) AC140TN4PKC/EA+AC140TXAD*C/EA
Cooling
TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input
Indoor Temperature (℃, DB / WB)
Outdoor
20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
(℃, DB)
kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
-15 13.1 9.8 3.18 13.8 10.1 3.25 14.3 10.5 3.31 14.8 10.8 3.38 15.1 10.7 3.42 15.8 10.6 3.45 16.6 10.4 3.52
21 12.4 9.4 3.35 13.1 9.7 3.42 13.6 10.0 3.49 14.1 10.3 3.56 14.4 10.2 3.60 15.1 10.1 3.63 15.8 9.9 3.70
35 11.9 8.8 4.16 12.5 9.1 4.24 13.0 9.3 4.33 13.4 9.6 4.42 13.7 9.5 4.46 14.4 9.4 4.51 15.1 9.3 4.60
46 10.1 8.7 3.77 10.6 9.0 3.85 11.0 9.3 3.92 11.4 9.6 4.01 11.6 9.5 4.05 12.2 9.4 4.09 12.8 9.2 4.17
48 8.9 7.9 3.56 9.4 8.1 3.63 9.7 8.4 3.71 10.1 8.6 3.78 10.3 8.5 3.82 10.8 8.4 3.86 11.3 8.3 3.94
50 7.7 7.0 3.35 8.1 7.2 3.42 8.4 7.4 3.49 8.7 7.7 3.56 8.9 7.6 3.60 9.3 7.5 3.63 9.8 7.4 3.70
NOTE
• The performance table shows the average value of each conditions.
4. Dimensional Drawing
360 Cassette (Square)
AC052TN4PKC/EA, AC071TN4PKC/EA
Units : mm [inches]
947
[37-5/16]
[11-1/16]
281
4. Dimensional Drawing
360 Cassette (Square)
Description
No. Name No. Name Description
AC052 AC071
1 Liquid pipe connection Φ6.35(1/4) 7 Suction rim for Booster fan
2 Gas pipe connection Φ12.7(1/2) Φ15.88(5/8) 8 Decoration cover
3 Drain pipe connection VP-25(OD32, ID25) 9 Drain hose(Accessory)
4 Power supply & Communication wiring conduit 10 Fresh air intake knockout hole Use M4 Screw
5 Air Discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver
NOTE
•• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
•• Make sure the spacing between the ceiling and the cassette is no more than 29mm[1-1/4].
Max ceiling opening : 960mm[36-13/16].
•• When the condition exceed 30℃ and RH 80% in the ceiling or fresh air is inducted into the ceiling,
and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
4. Dimensional Drawing
360 Cassette (Square)
200 or less
[7-7/8] 318
[12-1/2]
(Ceiling opening)
Adjustable (0~584)
372 [14-5/8]
[0~23]
430 [16-15/16]
645 [25-3/8]
(Suspension position)
385 [15-1/8] 403 [15-7/8] 950~960 [37-3/8 ~ 37-13/16]
(Ceiling opening)
360 947
[14-3/16] [37-5/16]
128 [5-1/16]
190 [7-1/2]
[12-1/2]
[14-3/8]
317
365
[7-3/16]
[6-1/2]
182
166
29 29 [1-1/8]
[1-1/8]
3
1 2 4 Front View
435 79 [3-1/8]
[17-1/8]
428
100 [16-7/8]
[4] 10
12
5
[8-5/8]
219
[5-1/2]
140
11
[39-3/8]
[2-5/8]
1000
788
66
[31-1/16] 6
[98-7/16] or More
Back View
2500 or More
1000
[39-3/8]
4. Dimensional Drawing
360 Cassette (Square)
NOTE
•• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
•• Make sure the spacing between the ceiling and the cassette is no more than 29mm[1-1/4].
Max ceiling opening : 960mm[36-13/16].
•• When the condition exceed 30℃ and RH 80% in the ceiling or fresh air is inducted into the ceiling,
and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
4. Dimensional Drawing
360 Cassette (Circle)
AC052TN4PKC/EA, AC071TN4PKC/EA
Units : mm [inches]
947
[37-5/16]
[11-1/16]
281
4. Dimensional Drawing
360 Cassette (Circle)
Description
No. Name No. Name Description
AC052 AC071
1 Liquid pipe connection Φ6.35(1/4) 7 Suction rim for Booster fan
2 Gas pipe connection Φ12.7(1/2) Φ15.88(5/8) 8 Decoration cover
3 Drain pipe connection VP-25(OD32, ID25) 9 Drain hose(Accessory)
4 Power supply & Communication wiring conduit 10 Fresh air intake knockout hole Use M4 Screw
5 Air Discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver
NOTE
• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
• Make sure the spacing between the ceiling and the cassette is no more than 29mm[1-1/4].
Max ceiling opening : 960mm[36-13/16].
• When the condition exceed 30℃ and RH 80% in the ceiling or fresh air is inducted into the ceiling,
and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
4. Dimensional Drawing
360 Cassette (Circle)
200 or less
[7-7/8] 318
[12-1/2]
(Suspension position)
645 [25-3/8]
[0~21-5/8]
Adjustable (0~550)
372 [14-5/8]
430 [16-15/16]
645 [25-3/8]
(Suspension position)
385 [15-1/8] 403 [15-7/8]
360 947
[14-3/16] 55 [2-3/16] [37-5/16] 55 [2-3/16]
[11-3/8]
94 [3-11/16]
289
[14-3/8]
[6-3/8]
365
[6-1/16]
[5-7/16]
162
154
138
100
[4]
3
1 2 4 Front View
79 [3-1/8]
435 [17-1/8] 427
100 [16-7/8]
[4] 10
12
5
[7-1/2]
191
[4-3/8]
111
11
788
[31-1/16] 6
[98-7/16] or More
Back View
2500 or More
1050 [41-3/8]
4. Dimensional Drawing
360 Cassette (Circle)
NOTE
•• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
•• Make sure the spacing between the ceiling and the cassette is no more than 29mm[1-1/4].
Max ceiling opening : 960mm[36-13/16].
•• When the condition exceed 30℃ and RH 80% in the ceiling or fresh air is inducted into the ceiling,
and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
•• The circular panel is by default available in exposed installation.
Make inspection holes on the ceiling for easier installation and maintenance, as shown in the following table.
(The size of an inspection hole must be at least 450 mm x 450 mm.)
•• A suspended ceiling structure can substitute for the inspection holes.
5. Center of Gravity
360 Cassette
Units : mm [inches]
A B
AC052/071TN4PKC/EA 233 [9-3/16] 165 [6-1/2]
AC100/120/140TN4PKC/EA 317 [12-1/2] 220 [8-5/8]
6. Electrical Wiring Diagram
360 Cassette
SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
M-BLDC BLDC Motor EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)
NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
360 Cassette
Microphone
• NC Curve
1) AC052TN4PKC/EA 2) AC071TN4PKC/EA
3) AC100TN4PKC/EA 4) AC120TN4PKC/EA
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
7. Sound Data
360 Cassette
1.5m
Microphone
• NC Curve
1) AC052TN4PKC/EA
NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
8. Temperature and air flow distribution
360 Cassette
AC052TN4PKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
AC071TN4PKC/EA
•• Cooling Air Velocity distribution •• Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
AC100TN4PKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
8. Temperature and air flow distribution
360 Cassette
AC120TN4PKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
AC140TN4PKC/EA
• Cooling Air Velocity distribution • Cooling temperature distribution
(Discharge angle : 60 degree) (Discharge angle : 60 degree)
Duct
1. Specification 76
2. Summary Table 88
3. Capacity Table 89
4. Dimensional Drawing 92
5. Center of Gravity 96
6. Electrical Wiring Diagram 99
7. Sound Data 102
8. Fan Characteristics 104
Features
& Benefits
Slim Duct - Ultra-light, adaptable design
Flexible setup
The air inlet can be set up either on the bottom or rear of
the unit, giving users greater flexibility in installation. 700mm 200 mm
Narrower
Diffuser
Diffuser
Experience performance and convenient comfort for The Duct S indoor air conditioning unit delivers smooth,
any weather condition consistent operation and convenience with features such
as:
Samsung Duct S delivers unparalleled cooling and
heating and flexible management with customizable •• Efficient operation. Stage the desired atmosphere
comfort settings in any climate—all year round. Plus, it with energy-efficient performance and customized
boasts a slim, compact size and multiple access points airflow.
for easy setup exactly where needed. •• Smart management. Cool spaces efficiently and
manage the air conditioning unit even while away,
with features designed for efficiency and control.
•• Easy, flexible setup. Install and maintain even
multiple units with a compact and easily accessible
design.
1. Specification
Duct
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Duct
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Duct
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Duct
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
Duct
Performance Characteristics
Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 4.1 - High 9.5 30
AC035TNLDKC/EA 14.8 Std. 3.5 - Mid 8.5 28
Min. 1.0 - Low 7.5 26
Max. 5.6 - High 14.5 33
AC052TNLDKC/EA 26.5 Std. 5.0 - Mid 12.0 30
Min. 1.2 - Low 9.5 27
Max. 8.0 - High 18.0 37
AC071TNMDKC/EA 26.5 Std. 6.5 - Mid 14.5 33
Min. 2.2 - Low 11.0 29
Max. 12.0 - High 28.0 36
AC100TNMDKC/EA 38.5 Std. 10.0 - Mid 25.0 33
Min. 3.0 - Low 22.0 30
Max. 14.0 - High 33.0 37
AC120TNMDKC/EA 38.5 Std. 12.1 - Mid 28.0 34
Min. 3.5 - Low 23.0 30
Max. 15.5 - High 33.0 37
AC140TNMDKC/EA 38.5 Std. 13.4 - Mid 28.0 34
Min. 3.5 - Low 23.0 30
Max. 18.0 - High 50.0 44
AC160TNMDKC/EA 53.5 Std. 15.8 - Mid 44.5 40
Min. 4.3 - Low 39.0 36
NOTE
•• Sound data is based on cooling operation.
Electric Characteristics
Model Outdoor Unit Maximum Input Current [A] Power Supply
Rated Voltage range Outdoor Unit Indoor
Indoor Unit Outdoor Unit Total MCA MFA
Hz Volts Min. Max. Cooling Heating Unit
AC035TNLDKC/EA AC035TXADKC/EA 50 220 to 240 198 264 10.0 - 1.7 11.7 11.7 12.9
AC052TNLDKC/EA AC052TXADKC/EA 50 220 to 240 198 264 20.0 - 2.3 22.3 22.3 25.0
AC071TNMDKC/EA AC071TXADKC/EA 50 220 to 240 198 264 20.0 - 2.3 22.3 22.3 25.0
AC100TNMDKC/EA AC100TXADKC/EA 50 220 to 240 198 264 24.0 - 2.5 26.5 26.5 30.0
AC100TNMDKC/EA AC100TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC120TNMDKC/EA AC120TXADKC/EA 50 220 to 240 198 264 32.0 - 2.5 34.5 34.5 40.0
AC120TNMDKC/EA AC120TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC140TNMDKC/EA AC140TXADKC/EA 50 220 to 240 198 264 32.0 - 2.5 34.5 34.5 40.0
AC140TNMDKC/EA AC140TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC160TNMDKC/EA AC160TXADKC/EA 50 220 to 240 198 264 32.0 - 3.5 35.5 35.5 40.0
AC160TNMDKC/EA AC160TXADNC/EA 50 380 to 415 342 456.5 16.1 - 3.5 19.6 19.6 19.6
NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
Duct
(1) AC035TNLDKC/EA+AC035TXADKC/EA
Cooling
(2) AC052TNLDKC/EA+AC052TXADKC/EA
Cooling
(3) AC071TNMDKC/EA+AC071TXADKC/EA
Cooling
NOTE
•• The performance table shows the average value of each conditions.
3. Capacity Table
Duct
(4) AC100TNMDKC/EA+AC100TXAD*C/EA
Cooling
(5) AC120TNMDKC/EA+AC120TXAD*C/EA
Cooling
(6) AC140TNMDKC/EA+AC140TXAD*C/EA
Cooling
NOTE
• The performance table shows the average value of each conditions.
3. Capacity Table
Duct
(7) AC160TNMDKC/EA+AC160TXAD*C/EA
Cooling
NOTE
• The performance table shows the average value of each conditions.
4. Dimensional Drawing
Duct
AC035TNLDKC/EA
Units : mm [inches]
566
382
312
7.8
100 173
1 99
71
86 52
173
566 5
7
746 Suspension podition
8
316 Suspension podition
440
4-28
6 5x100=500
542 Air outlet duct flange
700
16-Ø3.2
440
700
800 500 4
19
1 50
1 00
23.2
2 1 3
NO Name Description
1 Liquid pipe connection Φ6.35(1/4)
2 Gas pipe connection Ø9.52 (3/8)
3 Drain pipe connection without drain pump VP25 (OD ø32,ID ø25)
4 Drain pipe connection with drain pump VP25 (OD ø32,ID ø25)
5 Power supply/Communication connection -
6 Air discharge grille flange -
7 Return air side -
8 Hook ø9.52 or M10
4. Dimensional Drawing
Duct
AC052TNLDKC/EA, AC071TNMDKC/EA
Units : mm [inches]
[9-13/16]
250
Description
No. Name
AC052TNLDKC/EA AC071TNMDKC/EA
1 Liquid pipe connection Φ6.35(1/4)
2 Gas pipe connection Φ12.7(1/2) Φ15.88(5/8)
3 Drain pipe connection VP-25(OD32, ID25)
4 Power supply & Communication wiring conduit
5 Air suction flange
6 Air discharge flange
7 Hook Use M8~M10 bolt(4ea)
4. Dimensional Drawing
Duct
25 or More
[1]
25or More
[1]
6
Ceiling
1350 [53-1/8]
7 500 [19-11/16] or More
Air Inlet (Service Space)
(Service Space)
[27-9/16]
[23-3/4]
700
604
Air Outlet
1300 [51-3/16] 5
1402 [55-3/16]
Air Inlet Air Outlet 5 2 1 3 6
[2 X 4-1/2 = 9-1/16]
2 X 115 = 230
94[3-11/16]
53 [2-1/8]
[11-13/16]
[10-5/8]
[10-5/8]
270
270
300
[1-1/16]
[7-1/4]
[6-1/2]
185
166
27
125
[4-15/16] 4
58 [2-1/4]
1268 [49-15/16] 213
[8-3/8]
11 X 100 = 1100
[11 X 3-15/16 = 43-5/16] 324
84 [3-5/16] [12-3/4]
AC160TNMDKC/EA
Units : mm [inches]
1236
[ 48-5/8 ]
1200 500[ 9-11/16 ] or More
[ 47-1/4 ] (Service Space)
[ 21-1/16 ]
[ 25-5/8 ]
650
690
534
1334
[ 52-1/2 ]
2 1
122 [ 4-13/16 ]
137 [ 5-3/8 ]
27 [ 1-1/16 ]
[ 7-7/8 ]
[ 14-3/16 ]
200
360
351
[ 13-13/16 ] 3
6x150=900
406
[ 6x5-7/8=35-7/16 ] [ 16 ]
50 [ 2 ] 480
5 [ 18- 7/8 ]
AC035TNLDKC/EA
Units : mm [inches]
Model A B C
AC035TNLDKC/EA 450 335 105
5. Center of Gravity
Duct
AC052TNLDKC/EA, AC071TNMDKC/EA
AC100TNMDKC/EA, AC120TNMDKC/EA, AC140TNMDKC/EA Units : mm [inches]
A B C D E F
AC052TNLDKC/EA
AC071TNMDKC/EA 450 [17-11/16] 220 [8-5/8] 1100 [43-5/16] 520 [20-1/2] 200 [7-7/8] 100 [3-15/16]
AC100TNMDKC/EA
AC120TNMDKC/EA 700 [27-9/16] 265 [10-7/16] 1350 [53-1/8] 650 [25-5/8] 300 [11-13/16] 150 [5-15/16]
AC140TNMDKC/EA
5. Center of Gravity
Duct
AC160TNMDKC/EA
Units : mm [inches]
C
F
Model A B C D E F
AC035TNLDKC/EA
MAIN PCB Printed circuit board(MAIN) M-BLDC BLDC Motor ROOM-TH(10K) Thermistor ROOM
DISPLAY PCB Printed circuit board(Display_Option) EEV Electronic Expansion Valve(Option) EVA IN-TH(10K) Thermistor EVA IN
FLOAT SWITCH Switch of the float of Drain SPI S-Plasma ion(Option) EVA OUT-TH(10K) Thermistor EVA OUT
NOTE
• This wiring diagram applies only to the Indoor unit.
• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
• Protective earth(screw)
6. El
Electric
ectrical
al Wiring Diagram
Diagram
Duct
SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
M-BLDC BLDC Motor EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)
NOTE
• This wiring diagram applies only to the Indoor unit.
• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
• Protective earth(screw)
6. Electrical Wiring Diagram
Duct
AC160TNMDKC/EA
MAIN PBA Printed Circuit Board(MAIN) M-BLDC BLDC Motor ROOM(10K) Thermistor ROOM OUT(10K)
BLDC DRIVER PBA Printed Circuit Board(BLDC DRIVER) EEV Electronic Expansion Valve EVA-IN(10K) Thermistor EVA IN(10K)
SUB PBA Printed Circuit Board(SUB) EXT_CONTROL EXTERNAL_CONTROL EVA-OUT(10K) Thermistor EVA OUT(10K)
EMI PBA Printed circuit board(EMI) DISCHARGE(10K) Thermistor DISCHARGE(10K)
NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
Duct
• NC Curve
1) AC035TNLDKC/EA 2) AC052TNLDKC/EA
3) AC071TNMDKC/EA 4) AC100TNMDKC/EA
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
7. Sound D
Data
ata
Duct
Microphone
• NC Curve
1) AC120TNMDKC/EA 2) AC140TNMDKC/EA
3) AC160TNMDKC/EA
NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
8. Fan Characteristics
Duct
1) AC035TNLDKC/EA
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤ SP ≤2.5 01C17C-1C05F6-272300-370008 2.5< SP ≤4 01C17C-1C097B-272300-370008
19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]
2) AC052TNLDKC/EA
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤ SP ≤3 01B17C-1C00F1-273400-374000 3< SP ≤5 01B17C-1C0457-273400-374000
19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]
14 14
13 13
12 12
11 11
10 10
9 9
8 8
7 7 HIGH Upper limit of
6 6 external
5 HIGH Upper limit of 5 static pressure
external MIDDLE 2
4 static pressure 4
3 MIDDLE 3 LOW
1 Lower limit of Lower limit of
2 LOW 2 external
1 external 1
static pressure static pressure
0 0
5 10 15 20 25 5 10 15 20 25
3) AC071TNMDKC/EA
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0 ≤ SP ≤ 3 01B17C-1C0456-274700-376000 3 < SP ≤6 01B17C-1C04CB-274700-376000
19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
6<SP≤9 01B17C-1C083E-274700-376000 9<SP≤12 01B17C-1C09A2-274700-376000
19 19
18 18
17 17
16 16
15 15 HIGH
External Static Pressure [mmAq]
External Static Pressure [mmAq]
14 14
13 13 Upper limit of
12 HIGH 12 external
11 11 static pressure 4
10 Upper limit of 10
9 external 9 MIDDLE
8 static pressure 3 8
7 MIDDLE 7
6 6
Lower limit of
5 5 external
4 Lower limit of 4 static pressure
3 external 3
2 static pressure 2
1 LOW 1 LOW
0 0
10 15 20 25 10 15 20 25
19
18 HIGH
17
16
15
External Static Pressure [mmAq]
Upper limit of
14 external 5
13 static pressure
12
11 MIDDLE
10
9
8 Lower limit of
7 external
6 static pressure
5
4
3 LOW
2
1
0
10 15 20 25
8. Fan Characteristics
Duct
4) AC100TNMDKC/EA
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤4 01B17C-1C00C4-276400-374040 4<SP≤8 01B17C-1C0552-276400-374040
19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 01B17C-1C05C5-276400-374040 12<SP≤15 01B17C-1C0908-276400-374040
19 19
18 18
17 17 Upper limit of
16 16 HIGH external
static pressure
15 15
External Static Pressure [mmAq]
External Static Pressure [mmAq]
5) AC120TNMDKC/EA
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤5.2 01B17C-1C0424-277800-374040 5.2<SP≤8 01B17C-1C0489-277800-374040
19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 01B17C-1C04FE-277800-374040 12<SP≤15 01B17C-1C0940-277800-374040
19 19
18 18
17 17 HIGH
16 16 Upper limit of
15 HIGH 15 external
External Static Pressure [mmAq]
External Static Pressure [mmAq]
14 14 static pressure 4
13 Upper limit of 13
12 external 12 MIDDLE
static pressure
11 3 11
10 MIDDLE 10
9 9 Lower limit of
8 8 external
7 7 static pressure
6 Lower limit of 6
5 external 5
4 static pressure 4 LOW
3 LOW 3
2 2
1 1
0 0
20 25 30 35 40 45 50 20 25 30 35 40 45 50
8. Fan Characteristics
Duct
6) AC140TNMDKC/EA
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤5.2 01B17C-1C0424-278CA0-374040 5.2<SP≤8 01B17C-1C0489-278CA0-374040
19 19
18 18
17 17
16 16
15 15
External Static Pressure [mmAq]
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 01B17C-1C04FE-278CA0-374040 12<SP≤15 01B17C-1C0940-278CA0-374040
19 19
18 18
17 17 HIGH
16 16 Upper limit of
15 HIGH 15 external
External Static Pressure [mmAq]
External Static Pressure [mmAq]
14 14 static pressure 4
13 Upper limit of 13
12 external 12 MIDDLE
static pressure
11 3 11
10 MIDDLE 10
9 9 Lower limit of
8 8 external
7 7 static pressure
6 Lower limit of 6
5 external 5
4 static pressure 4 LOW
3 LOW 3
2 2
1 1
0 0
20 25 30 35 40 45 50 20 25 30 35 40 45 50
19
External Static Pressure [mmAq]
18
HIGH Upperlimit of
17 external
16 static pressure
15
5 Lowerlimit of
14 external
13 static pressure
12 MID
11
10
9
8 LOW
7
6
5
4
3
2
1
0
10 15 20 25
External St
External St
12 12
Upperlimit of 4 Lowerlimit of
11 external 11 external
10 static pressure 10 static pressure
9 9 MID
8 3 Lowerlimit of 8
external
7 static pressure 7
6 6
8. Fan Characteristics 5
4
3 MID
HIGH 5
4
3
LOW
2 2
LOW
1 1
Duct 0
10 15 20 25
0
10 15 20 25
7) AC160TNMDKC/EA
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
1 2
0≤SP≤5.2 01116C-1C0924-27A000-370040 5.2<SP≤8 01116C-1C0978-27A000-370040
19 19
18 18
17 17
16 16
15 15 HIGH
External Static Pressure [mmAq]
External Static Pressure(mmAq) Option Code External Static Pressure(mmAq) Option Code
3 4
8<SP≤12 01116C-1C09CC-27A000-370040 12<SP≤15 01116C-1C09FF-27A000-370040
19 19
18 HIGH 18 HIGH
17 17
16 16 MIDDLE Upper limit of
15 15 external
External Static Pressure [mmAq]
External Static Pressure [mmAq]
14 14 static pressure 4
13 MIDDLE Upper limit of
external 13
12 static pressure 12
11 3 11
10 10 LOW
9 9 Lower limit of
external
8 LOW 8 static pressure
7 7
6 Lower limit of 6
5 external 5
static pressure
4 4
3 3
2 2
1 1
0 0
35 40 45 50 55 60 35 40 45 50 55 60
NOTE
•• Adjust option code according to the actual installation condition (external static pressure).
•• The graphs display the available external static pressure range of installed indoor units. Therefore, they do
not reflect the actual change of external static pressure and airflow rate according to adjusted airflow
(High-Mid-Low) of installed indoor units.
Ceiling
1. Specification 113
2. Summary Table 125
3. Capacity Table 126
4. Dimensional Drawing 128
5. Center of Gravity 131
6. Electrical Wiring Diagram 133
7. Sound Data 135
8. Temperature and air flow distribution 137
Features
& Benefits
Ceiling Type - Slim yet functional design
Size Weight
200%
136%
Smaller 123% Lighter
118%
100% 100%
Company B
Company B
Company A
Company A
SAMSUNG
SAMSUNG
7.1kW Model
Under Ceiling
Features
& Benefits
Ceiling Type (large capacity) - Powerful cooling with a long distance wind
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Ceiling
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Ceiling
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
1. Specification
Ceiling
NOTE
• Specification may be subject to change without prior notice.
• Performances are based on the following test conditions.
- Cooling : Indoor temperature 27°C DB, 19°C WB, Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB, Outdoor temperature 7°C DB, 6°C WB
- Equivalent refrigerant pipe length 5m, Level differences 0m
• Select wire size based on the value of MCA
• Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
• Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
• These products contain R410A which is fluorinated greenhouse gas.
2. Summary Table
Ceiling
Performance Characteristics
Capacity
Net Weight Airflow Sound Pressure
Model Code Cooling Heating Fan Speed
(kg) (CMM) Level (dBA)
(kW) (kW)
Max. 5.6 - High 12.6 41
AC052TNCDKC/EA 20.0 Std. 5.0 - Mid 11.3 39
Min. 1.7 - Low 10.0 36
Max. 9.2 - High 23.0 45
AC071TNCDKC/EA 32.6 Std. 7.1 - Mid 19.0 40
Min. 2.3 - Low 15.0 35
Max. 12.0 - High 26.0 42
AC100TNCDKC/EA 42.0 Std. 10.0 - Mid 23.0 38
Min. 3.0 - Low 19.0 34
Max. 14.0 - High 30.0 44
AC120TNCDKC/EA 42.0 Std. 12.1 - Mid 24.0 41
Min. 3.5 - Low 20.0 37
Max. 15.5 - High 34.0 46
AC140TNCDKC/EA 42.0 Std. 13.4 - Mid 27.0 42
Min. 3.5 - Low 23.0 38
Max. 17.6 - High 37.0 50
AC160TNCDKC/EA 42.0 Std. 15.0 - Mid 31.0 47
Min. 4.3 - Low 26.0 43
NOTE
•• Sound data is based on cooling operation.
Electric Characteristics
Model Outdoor Unit Maximum Input Current [A] Power Supply
Rated Voltage range Outdoor Unit Indoor
Indoor Unit Outdoor Unit Total MCA MFA
Hz Volts Min. Max. Cooling Heating Unit
AC052TNCDKC/EA AC052TXADKC/EA 50 220 to 240 198 264 20.0 - 1.5 21.5 21.5 25.0
AC071TNCDKC/EA AC071TXADKC/EA 50 220 to 240 198 264 20.0 - 2.5 22.5 22.5 25.0
AC100TNCDKC/EA AC100TXADKC/EA 50 220 to 240 198 264 24.0 - 2.5 26.5 26.5 30.0
AC100TNCDKC/EA AC100TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC120TNCDKC/EA AC120TXADKC/EA 50 220 to 240 198 264 32.0 - 2.5 34.5 34.5 40.0
AC120TNCDKC/EA AC120TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC140TNCDKC/EA AC140TXADKC/EA 50 220 to 240 198 264 32.0 - 2.5 34.5 34.5 40.0
AC140TNCDKC/EA AC140TXADNC/EA 50 380 to 415 342 456.5 16.1 - 2.5 18.6 18.6 18.6
AC160TNCDKC/EA AC160TXADKC/EA 50 220 to 240 198 264 32.0 - 3.0 35.0 35.0 40.0
AC160TNCDKC/EA AC160TXADNC/EA 50 380 to 415 342 456.5 16.1 - 3.0 19.1 19.1 19.1
NOTE
•• MCA : Minimum circuit amperes
•• MFA : Maximum fuse amperes
•• Select wire size based on the value of MCA
3. Capacity Table
Ceiling
(1) AC052TNCDKC/EA+AC052TXADKC/EA
Cooling
(2) AC071TNCDKC/EA+AC071TXADKC/EA
Cooling
(3) AC100TNCDKC/EA+AC100TXAD*C/EA
Cooling
NOTE
•• The performance table shows the average value of each conditions.
3. Capacity Table
Ceiling
(4) AC120TNCDKC/EA+AC120TXAD*C/EA
Cooling
(5) AC140TNCDKC/EA+AC140TXAD*C/EA
Cooling
(6) AC160TNCDKC/EA+AC160TXAD*C/EA
Cooling
NOTE
• The performance table shows the average value of each conditions.
4. Dimensional Drawing
Ceiling
AC052TNCDKC/EA
Units : mm [inches]
NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
4. Dimensional Drawing
Ceiling
AC071TNCDKC/EA
Units : mm [inches]
NOTE
• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
4. Dimensional Drawing
Ceiling
Description
No. Name
AC100/120/140TNCDKC/EA AC160TNCDKC/EA
1 Liquid pipe connection Φ9.52(3/8)
2 Gas pipe connection Φ15.88(5/8) Φ19.02 (3/4)
3 Drain pipe connection VP-25(OD32, ID25)
4 Air filter
5 Air suction grille
6 Knockout hole for piping (upper)
7 Knockout hole for piping (rear)
8 Conduit Hole Φ28 [1-1/8]
9 Knockout hole for drain hose Φ42 [1-5/16]
10 Knockout hole for Fresh air intake
11 Cover side
12 Knockout hole for piping (side)
NOTE
•• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)
5. Center of Gravity
Ceiling
AC052TNCDKC/EA
Units : mm [inches]
5. Center of Gravity
Ceiling
AC071TNCDKC/EA
Units : mm [inches]
100
[4]
[9-1/4]
235
[26-9/16]
675
[12-3/8]
680 315
[26-3/4]
1350
[53-1/8]
AC052TNCDKC/EA
SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
FLOAT S/W Switch of the float of Drain EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)
NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
•• Protective earth(screw)
6. Electrical Wiring Diagram
Ceiling
SPI S-Plasma ion EEV Electronic Expansion Valve ROOM Thermistor ROOM in (10K)
M-BLDC BLDC Motor EVA-IN Thermistor EVA IN(10K) EVA-OUT Thermistor EVA OUT(10K)
NOTE
•• This wiring diagram applies only to the Indoor unit.
•• Symbols show as follow : blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
•• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remotecontroller transmission F3-F4.
•• Protective earth(screw)
7. Sound Data
Ceiling
• NC Curve
1) AC052TNCDKC/EA 2) AC071TNCDKC/EA
3) AC100TNCDKC/EA 4) AC120TNCDKC/EA
NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
7. Sound Data
Ceiling
1m
Model HIGH MID LOW
AC140TNCDKC/EA 46 42 38
1m
AC160TNCDKC/EA 50 47 43
Microphone
• NC Curve
1) AC140TNCDKC/EA 2) AC160TNCDKC/EA
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
8. Temperature and air flow distribution
Ceiling
AC100TNCDKC/EA
• Cooling Air Velocity distribution
(Discharge angle : 32 degree)
AC120TNCDKC/EA
•• Cooling Air Velocity distribution
(Discharge angle : 32 degree)
AC140TNCDKC/EA
• Cooling Air Velocity distribution
(Discharge angle : 32 degree)
AC160TNCDKC/EA
• Cooling Air Velocity distribution
(Discharge angle : 32 degree)
AC140RNCDKG/EU
Performance Characteristics
Capacity Net Size Net Weight Airflow Sound Pressure Level (dBA)
Model Code
kW (WxHxD mm) (kg) (CMM) Cooling Heating
3.5 AC035TXADKC/EA 790 x 548 x 285 30.5 40 48 -
5.2 AC052TXADKC/EA 880 x 638 x 310 40.5 50 50 -
7.1 AC071TXADKC/EA 880 x 798 x 310 52.5 60 50 -
10.0 AC100TXAD*C/EA 940 x 998 x 330 71.0 76 53 -
12.0 AC120TXAD*C/EA 940 x 1,210 x 330 86.5 110 53 -
14.0 AC140TXAD*C/EA 940 x 1,210 x 330 86.5 110 54 -
16.0 AC160TXAD*C/EA 940 x 1,420 x 330 96.0 143 56 -
NOTE
•• Sound power level is based on cooling operation.
2. Dimensional Drawing
Outdoor Units
AC035TXADKC/EA
Units : mm [inches]
601.7
(23-3/4)
(12-1/4)
(13-1/4)
310
336
790 285
(31-1/8) (11-1/4)
105 (4-1/8)
158(6-1/4)
(21-1/2)
548
1
126 (4-15/16)
149 (5-7/8)
601.7 90(3-9/16)
(23-3/4)
254
(10)
3
360
(14-3/16)
Rear View
AC052TXADKC/EA
Units : mm [inches]
AC071TXADKC/EA
Units : mm [inches]
AC100TXADKC/EA, AC100TXADNC/EA
Units : mm [inches]
940
[37]
330
[13]
25
[1]
25 [63/64]
579 [22-51/64] 313
[12-5/16]
1
655 [25-25/32]
2
998 [39-5/16]
4
3
[19-1/2]
495
3
24 [15/16]
[2-3/16]
[2-3/16]
[5-23/64]
[2-3/16]
[3-3/4]
[3-3/4]
[3-1/8]
[3-15/64]
95
95
[6-7/32]
[5-23/64]
80
158
55
[3-15/64]
55
136
136
82
82
55
80 52 [2-1/16]
5 4 30 [1-3/16] [3-1/8] 42 [1-21/32]
4 5
88 30 [1-3/16] 78 [3-5/64] 106 [4-3/16]
[3-1/2]
133
[5-15/64]
153 67 [2-5/8]
[6-1/32]
22 [7/8]
165 620
[6-1/2] [24-3/8] 60 [2-3/8]
3
30 6 17 [11/16]
[1-3/16]
[2-15/16]
75
[7-3/16]
183
[12-7/8]
[15-1/8]
328
384
[9-3/8]
238
[3-13/16]
96
[1-3/16]
37 [1-7/16]
30
330
[13]
[1]
25
578 313
25 [63/64] [22-3/4] [12-5/16]
[21-37/64]
548
1
[47-5/8]
1210
5
5
4
4
3
3
55 [2-3/16]
80 [3-3/16]
[20-11/16]
525
[3-3/4]
95 [3-3/4]
55 [2-3/16]
55 [2-3/16]
95
24 [15/16]
[5-23/64]
[6-7/32]
158
136
82
[3-15/64]
30 [1-3/16] 80 [3-3/16]
136 [5-23/64]
42 [1-21/32]
52 [2-1/16]
82 [3-15/64]
88
[3-1/2]
30 [1-3/16] 78 [3-5/64]
105
153 132 67 [2-5/8] [4-1/8]
[6-1/32] [5-13/64]
22 [7/8]
[12-7/8]
[15-1/8]
328
384
[9-3/8]
238
[3-13/16]
95
37 [1-7/16]
[1-1/8]
29
294 218
[11-9/16] [8-9/16]
AC160TXADKC/EA, AC160TXADNC/EA
Units : mm [inches]
940
[3'-1"]
[4'-7 1/2"]
[4'-8 1/4"]
1412
1428
[4'-8"]
1420
[2'-1 3/4"]
655
621 ④
[2'-0 1/2"]
AC035TXADKC/EA
Units : mm [inches]
[8-3/4]
223
232 165
[9-1/8 [6-1/2]
The position of foundation bolt
AC052TXADKC/EA
Units : mm [inches]
3. Center of Gravity
Outdoor Units
AC071TXADKC/EA
Units : mm [inches]
AC100TXADKC/EA, AC100TXADNC/EA
Units : mm [inches]
3. Center of Gravity
Outdoor Units
AC160TXADKC/EA, AC160TXADNC/EA
Units : mm [inches]
[55-9/10]
1420
[24-3/8]
620
210 160
[8-1/4] [6-5/16]
620 328
[24-3/8] [12-7/8]
Hold location of foundation bolt
Hold location of foundation bolt
4. Electrical Wiring Diagram
Outdoor Units
AC035TXADKC/EA
DRED PCB Printed circuit board(DRED) H-PRESSURE SWITCH High Pressure Switch M-BLDC BLDC Motor
EEV Electronic Expansion Valve OUT-TH(10K) Thermistor AMBIENT DIS-TH(200K) Thermistor DISCHARGE
COND-TH(10K) Thermistor CONDENSOR OLP-TH(200K) Thermistor OLP
NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor-outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
4. Electrical Wiring Diagram
Outdoor Units
AC052TXADKC/EA, AC071TXADKC/EA
DRED PCB Printed circuit board(DRED) H-PRESSURE SWITCH High Pressure Switch M-BLDC BLDC Motor
EEV Electronic Expansion Valve OUT-TH(10K) Thermistor AMBIENT DIS-TH(200K) Thermistor DISCHARGE
COND-TH(10K) Thermistor CONDENSOR OLP-TH(200K) Thermistor OLP
NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor-outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
4. Electrical Wiring Diagram
Outdoor Units
DRED PCB Printed circuit board(DRED) BASE HEATER PBA Printed circuit board(BASE M-BLDC BLDC Motor
HEATER)
EEV Electronic Expansion Valve OUT-Temp(10K) Thermistor AMBIENT COND Temp(10K) Thermistor DISCHARGE
DISCHARGE
Thermistor CONDENSOR OLP Temp(200K) Thermistor OLP
Temp(200K)
NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor-outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
4. Electrical Wiring Diagram
Outdoor Units
DRED PCB Printed circuit board(DRED) BASE HEATER PBA Printed circuit board(BASE M-BLDC BLDC Motor
HEATER)
EEV Electronic Expansion Valve OUT-Temp(10K) Thermistor AMBIENT COND Temp(10K) Thermistor DISCHARGE
DISCHARGE
Thermistor CONDENSOR OLP Temp(200K) Thermistor OLP
Temp(200K)
NOTE
•• This wiring diagram applies only to the outdoor unit.
•• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue
•• When operating, don’t shortcircuit the protection device (High Pressure switch)
•• For connection wiring indoor-outdoor transmission F1-F2, outdoor-outdoor transmission OF1-OF2, refer to
the installation manual.
•• Protective earth(screw), : connector, : The wire quantity
5. Sound Data
Outdoor Units
1.5m 1.5m
AC071TXADKC/EA 50
Front Front
• NC Curve
1) AC035TXADKC/EA 2) AC052TXADKC/EA
3) AC071TXADKC/EA
NOTE
•• Specifications may be subject to change without prior notice.
-- Sound pressure level is obtained in an anechoic room.
-- Sound pressure level is a relative value, depending on the distance and acoustic environment.
-- Sound pressure level may differ depending on operation condition.
-- dBA = A weighted sound pressure level
-- Reference acoustic pressure 0 dB = 20μPa
5. Sound Data
Outdoor Units
1.5m 1.5m
AC120TXADKC/EA 53
AC120TXADNC/EA 53
Front Front
• NC Curve
1) AC100TXADKC/EA 2) AC100TXADNC/EA
3) AC120TXADKC/EA 4) AC120TXADNC/EA
NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
5. Sound Data
Outdoor Units
• NC Curve
1) AC140TXADKC/EA 2) AC140TXADNC/EA
3) AC160TXADKC/EA 4) AC160TXADNC/EA
NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
- Reference acoustic pressure 0 dB = 20μPa
6. Capacity Correction
Outdoor Units
AC035TXADKC/EA
Cooling
10 - - 0.95 0.92
5 - 0.97 0.95 0.92
0 1 0.97 0.95 0.92
-5 - 0.96 0.94 0.91
-10 - - 0.92 0.90
-15 - - - 0.88
-20 - - - -
-25 - - - -
-30 - - - -
AC052TXADKC/EA
Cooling
Cooling
5 - 0.99 0.98 0.97 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88
0 1 0.99 0.98 0.97 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.91 0.90 0.89 0.88
-5 - 0.99 0.98 0.97 0.96 0.95 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.87
-10 - - 0.98 0.97 0.96 0.95 0.94 0.93 0.93 0.92 0.91 0.90 0.89 0.88 0.86
-15 - - - 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.85
-20 - - - - 0.95 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.86 0.84
-25 - - - - - 0.94 0.93 0.93 0.92 0.91 0.90 0.89 0.87 0.86 0.83
-30 - - - - - - 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.85 0.82
7. Operation Range
NOTE
•• The assumed installation conditions are follows
-- The pipe length(including elbow) is 5 m.
-- The level difference is 0 m.
8. Piping Diagram
AC052TN4DKC/EA+AC052TXADKC/EA
AC052TN4PKC/EA+AC052TXADKC/EA
Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)
Indoor
Fan Motor
(IFM)
Outdoor Fan Motor1 (OFM1)
Electronic Thermistor-
Expansion Valve- Indoor Room
Main1 (T_IR)
(E_M1)
Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)
Compressor
(COMP)
8. Piping Diagram
AC035TN1DKC/EA+AC035TXADKC/EA
AC052TN1DKC/EA+AC052TXADKC/EA
Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)
Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)
Compressor
(COMP)
8. Piping Diagram
AC035TNLDKC/EA+AC035TXADKC/EA
AC052TNLDKC/EA+AC052TXADKC/EA
AC052TNCDKC/EA+AC052TXADKC/EA
Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)
Thermistor-
Indoor Room
(T_IR)
Outdoor Fan Motor1 (OFM1)
Electronic
Expansion Valve- Indoor Fan Motor
Main1 (IFM)
(E_M1)
Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)
Compressor
(COMP)
8. Piping Diagram
AC071TN4DKC/EA+AC071TXADKC/EA
AC071TN4PKC/EA+AC071TXADKC/EA
AC100TN4DKC/EA+AC100TXAD*C/EA
AC100TN4PKC/EA+AC100TXAD*C/EA
Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)
Indoor
Fan Motor
(IFM)
Outdoor Fan Motor1 (OFM1)
Electronic Thermistor-
Expansion Valve- Indoor Room
Main1 (T_IR)
(E_M1)
Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)
Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)
Compressor
(COMP)
8. Piping Diagram
AC071TN1DKC/EA+AC071TXADKC/EA
Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)
Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)
Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)
Compressor
(COMP)
8. Piping Diagram
AC071TNMDKC/EA+AC071TXADKC/EA
AC071TNCDKC/EA+AC071TXADKC/EA
AC100TNMDKC/EA+AC100TXAD*C/EA
AC100TNCDKC/EA+AC100TXAD*C/EA
Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)
Thermistor-
Indoor Room
(T_IR)
Outdoor Fan Motor1 (OFM1)
Electronic
Expansion Valve- Indoor Fan Motor
Main1 (IFM)
(E_M1)
Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)
Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)
Compressor
(COMP)
8. Piping Diagram
AC120TN4DKC/EA+AC120TXAD*C/EA
AC120TN4PKC/EA+AC120TXAD*C/EA
AC140TN4DKC/EA+AC140TXAD*C/EA
AC140TN4PKC/EA+AC140TXAD*C/EA
Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)
Indoor
Fan Motor
(IFM)
Outdoor Fan Motor1 (OFM1) Outdoor Fan Motor1 (OFM2)
Electronic Thermistor-
Expansion Valve- Indoor Room
Main1 (T_IR)
(E_M1)
Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)
Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)
Compressor
(COMP)
8. Piping Diagram
AC120TNMDKC/EA+AC120TXAD*C/EA, AC120TNCDKC/EA+AC120TXAD*C/EA
AC140TNMDKC/EA+AC140TXAD*C/EA, AC140TNCDKC/EA+AC140TXAD*C/EA
AC160TNMDKC/EA+AC160TXAD*C/EA, AC160TNCDKC/EA+AC160TXAD*C/EA
Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)
Thermistor-
Indoor Room
(T_IR)
Outdoor Fan Motor1 (OFM1) Outdoor Fan Motor1 (OFM2)
Electronic
Expansion Valve- Indoor Fan Motor
Main1 (IFM)
(E_M1)
Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_CO) Liquid Pipe
(SV_L)
Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)
Compressor
(COMP)
Installation
A 1500 mm or
more
C
C
B
C: 1500 mm or more
2500 mm or more 20 mm
Obstruction CAUTION
• The indoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
AC035TN1DKC AC100TN4DKC maintenance, and repair of the unit. The components
AC052TN4DKC
Model AC052TN1DKC AC120TN4DKC
AC071TN4DKC of the indoor unit must be reachable and removable
AC071TN1DKC AC140TN4DKC
under safe conditions for people and the unit.
A 170 mm 251 mm 355 mm • Do not hold the discharge while carrying the indoor
unit to avoid the possibility of breakage.
B 15 mm 17 mm 17 mm • You must hold the hanger plate on the corner and
carry the indoor unit.
(Unit: mm)
1 way Cassette
(Unit: mm)
150 or more
1500 or more
150 or more
150 or more
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
D D
E
B B
A
A
E
C
C
Insulate the end of the pipe and some curved area by using separate insulator.
NOTE
• A: Reference for the outer circumference of the unit
(When insulating the body of the indoor unit, use A as the reference for its outer circumference.)
(Unit: mm)
Indoor unit A B C D E
1 way Cassette
AC035TN1DKC 990x155 990x155 430x155 430x155 990x430
(970x135x410)
AC052TN1DKC
1 way Cassette
1220x155 1220x155 470x155 470x155 1220x470
(1200x138x450)
AC071TN1DKC
AC052TN4DKC
4 way Cassette <S>
910x151 940x151 610x151 650x151 870x870
(840x204x840)
AC071TN4DKC
AC100TN4DKC
4way Cassette type <L+>
AC120TN4DKC 910x235 940x235 610x235 650x235 870x870
(840x288x840)
AC140TN4DKC
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
CAUTION
• You must install all of the suspension rods.
• It is important to leave sufficient space in the false
ceiling to allow access for maintenance or repairs to
the drainage pipe connection, the refrigerant pipe
connection, or to remove the unit if necessary.
NOTE
5 Hang the indoor unit to the suspension bolts between
• Since the diagram is made of paper, it may shrink
two nuts. Cut a pad stopper and place it on the
or stretch slightly due to temperature or humidity.
suspension bolts to hold the washers. Remove the
For this reason, before drilling the holes, be sure
stopper and screw the nuts to fix the unit.
to maintain the correct dimensions between the
markings.
2 Insert bolt anchors, use existing ceiling supports or Pad stopper
construct a suitable support as shown in figure.
Concrete
Bracket
Hole in anchor Insert
Hole in plug
6 Check the level of the indoor unit by using a leveler.
• A tilt of the indoor unit may cause malfunction of a
Suspension bolt (M8) - field supply built-in float switch and water leaks.
Ceiling support
Level
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
7 Adjust the unit to the appropriate position, taking into 3 Wrap the supplied large sealing pad over the metal
account the installation area for the front panel. clamp and drain hose to insulate and fix it with clamps.
• Place the pattern sheet on the indoor unit. 4 Insulate the complete drain piping inside the building
• Adjust the space between the ceiling and the (field supply).
indoor unit by using a dimension gauge. If the drain hose cannot be sufficiently set on a slope,
fit the hose with drain raising piping (field supply).
• Fix the indoor unit securely after adjusting the level
of the unit by using a leveller. 5 Push the drain hose up to insulation when connecting
the drain hose to drain socket.
• Remove the pattern sheet, connect the other
cables. and install the front panel.
Metal clamp Drain socket
Drain hose
1way Cassette (Standard)
Ceiling Ceiling
Drain pipe
Drain pipe
Ceiling Ceiling
Gauge of dimensions
10 mm 10 mm
<Side view>
CAUTION
Check that the indoor unit is level with the ceiling by
4 way Cassette
using the leveller.
20 mm
• Install air ventilation to drain condensation smoothly.
Indoor unit
Ceiling Air ventilation
17 mm
Gauge of dimensions
1 Push the supplied drain hose as far as possible over • If it is necessary to increase the height of the drain
the drain socket. pipe, install the drain pipe straight within 300 mm
from the drain hose port. If it is raised higher than 550
2 Tighten the metal clamp as shown in the picture.
mm, there may be water leaks.
300 mm
or less 20 mm or more
Band joint
1/100 or more
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
Under gradient
Indoor unit
Flexible hose
NOTE
• If a concentrated drain pipe is installed, refer to the figure below.
Individual air
vent 200 mm or more
300 to 550 mm
• If 3 or more units are installed, install the main air vent at the front of the farthest indoor unit from the main drain pipe.
• To prevent water from flowing back to indoor units, install an individual air vent at the top of each indoor unit.
– The air vents should be T or 7 shaped to prevent dust or foreign substances from entering.
– You may not need to install air vent if the horizontal drain pipe is in proper slope.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
3 phase
13.8
19
Outdoor
M3.5 8.0 to 12.0
Unit M4 12.0 to 18.0
1(L) 2(N) L N F1 F2
• 1 N·m = 10 kgf·cm
• Power supply cords of parts of appliances for outdoor use
shall not be lighter than polychloroprene sheathed flexible
Cable cord. (Code designation IEC:60245 IEC 57 / CENELEC:
Cable
Tie H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F)
clamp
• Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
• When installing the indoor unit in a computer
room or network room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
2. 360 Cassette
Spacing requirements
A
'C'
A
Indoor unit
A
10 mm
2500 mm or more 20 mm
A
1500 mm or
more
Obstruction
A : 1500 mm or more
(Unit: mm)
Model AC052TN4PKC/EA AC071TN4PKC/EA AC100TN4PKC/EA AC120TN4PKC/EA AC140TN4PKC/EA
CAUTION
• The indoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
maintenance, and repair of the unit.
The components of the indoor unit must be reachable
and removable under safe conditions for people and
the unit.
• Do not hold the discharge while carrying the indoor
unit to avoid the possibility of breakage.
A
• You must hold the hanger plate on the corner and
carry the indoor unit.
Insulate the end of the pipe and some curved area by
using separate insulator.
NOTE
• A: Reference for the outer circumference of the unit
(When insulating the body of the indoor unit,
use A as the reference for its outer circumference.)
(Unit: mm)
Indoor unit type and models Dimensions
AC052TN4PKC
Optional: Insulating the body of 360 cassette type <S>
1610 x 130
(947 x 947 x 281)
the indoor unit AC071RN4PKC
AC100TN4PKC
If you install a cassette type indoor unit on the ceiling
when temperature is over 27°C and humidity is over 360 cassette type <L+>
AC120TN4PKC 2610 x 215
(947 x 947 x 365)
80%, you must apply an extra 10 mm thick polyethylene
AC140TN4PKC
insulation or a similar type of insulation to the body of the
indoor unit.
Cut away the part where pipes are pulled out for the
insulating work.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
Ceiling support
NOTE
• Since the diagram is made of paper, it may shrink
or stretch slightly due to temperature or humidity.
For this reason, before drilling the holes, be sure
to maintain the correct dimensions between the
markings.
CAUTION
2 Perform the following steps to install inspection holes
• Make sure that the ceiling is strong enough to support
in accordance with the panel type.
the weight of the indoor unit. Before hanging the unit,
a For the recessed installation of the square panel. test the strength of each attached suspension bolt.
• Install an inspection hole to the direction of • If the length of the suspension bolt is more than 1.5 m,
connection parts of the refrigerant pipe and the you are required to prevent vibration.
drain hose. (1 point)
5 Screw eight pairs of nuts and washers to the
Refrigerant pipe
suspension bolts, making space for hanging the indoor
unit.
CAUTION
Indoor unit
Inspection hole display • You must install all of the suspension rods.
• It is important to leave sufficient space in the false
b For recessed installation of the circular panel ceiling to allow access for maintenance or repairs to
• Install inspection holes to both directions of the the drainage pipe connection, the refrigerant pipe
connection part of the refrigerant pipe and the connection, or to remove the unit if necessary.
drain hose and of the indoor unit display.
(2 points) 6 Hang the indoor unit to the suspension bolts between
two nuts. Cut a pad stopper and place it on the
Inspection hole suspension bolts to hold the washers. Remove the
Refrigerant pipe stopper and screw the nuts to fix the unit.
2
Indoor unit display
Inspection hole
1
3 Insert bolt anchors, use existing ceiling supports or
2
construct a suitable support as shown in figure.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
7 Adjust the unit to the appropriate position, taking into PVC Tube Joint
Drain hose + VP25 (OD: 32 mm, ID: 25 mm)
account the installation area for the front panel.
• Place the pattern sheet on the indoor unit.
• Adjust the space between the ceiling and the
indoor unit by using a dimension gauge. Drain pipe
Ceiling
Installing the drain hose and drain pipe • If it is necessary to increase the height of the drain
pipe, install the drain pipe straight within 300 mm
1 Push the supplied drain hose as far as possible over
from the drain hose port. If it is raised higher than
the drain socket. 550 mm, there may be water leaks.
2 Tighten the metal clamp as shown in the picture.
300 mm or less 20 mm or more
550 mm or less
Band joint
Drain hose
Ceiling
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
Support pieces
1 to 1.5 m
Connecting the power and
communication cables
CAUTION
1/100 or more
• Always remember to connect the refrigerant pipes
before performing the electric connections.
Ceiling When disconnecting the system, always disconnect
the electric cables before disconnecting the
• Install horizontally.
refrigerant pipes.
• Always remember to connect the air conditioner to
Be horizontal the grounding system before performing the electric
connections. Use a crimp ring terminal at the end of
each wire.
Indoor unit
The indoor unit is powered through the outdoor unit by
means of a H07 RN-F connection cable (or a more power
model), with insulation in synthetic rubber and a jacket
Flexible hose
in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.
• Max. allowable axis gap. 1 Remove the screw on the electrical component box
and remove the cover plate.
2 Route the connection cord through the side of the
indoor unit and connect the cable to the terminals
refer to the figure below.
3 Route the other end of the cable to the outdoor unit
Indoor unit through the ceiling & the hole on the wall.
4 Reassemble the electrical component box cover,
carefully tightening the screw.
Max. 20 mm
Wire insert
hole
Max. 30°
Indoor unit
NOTE
• If a concentrated drain pipe is installed, refer to the
figure below.
Outdoor unit
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
12.6 9.0
M4 12.0 to 18.0
• 1 N·m = 10 kgf·cm
3. Duct Type
Optional: Insulating the body of the
Space requirements for installation indoor unit
AC052TNLDKC
AC035TNLDKC
Indoor AC071TNMDKC
Unit
Unit Depth(D)
AC100TNMDKC
AC120TNMDKC AC160TNMDKC
Indoor
• You must have 20 mm or more space between the Unit AC140TNMDKC
ceiling and the bottom of indoor unit. Otherwise, the 1300 X 700 X 300 1200 X 650 X 360
noise from the vibration of indoor unit may bother
the user. When the ceiling is under construction, the A 1300 X 300 1200 X 360
hole for check-up must be made to take service, clean B 1300 X 300 1200 X 360
and repair the unit.
C 700 X 300 650 X 360
• It is possible to install the unit at an height of
between 2.2~2.5 m from the ground, if the unit has a D 700 X 300 650 X 360
duct with a well defined lenght (300 mm or more), to
avoid fan motor blower contact. Insulate the front and back side in proper size at
Front/
the same time when insulating the suction duct and
• If you install the cassette or duct type indoor unit on Back
discharge duct.
the ceiling with humidity over 80%, you must apply
extra 10 mm of polyethylene foam or other insulation (Unit: mm)
with similar material on the body of the indoor unit.
NOTE
• Insulate the end of the pipe and some curved area by
using separate insulator.
• Insulate the discharge and suction part at the same
time when you insulate connection duct.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
NOTE
• Since the diagram is made of paper, it may shrink or
CAUTION
stretch slightly due to temperature or humidity. For • Piping must be laid and connected inside the
this reason, before drilling the holes maintain the ceiling when suspending the unit. If the ceiling is
correct dimensions between the markings. already constructed, lay the piping into position for
connection to the unit before placing the unit inside
2 Insert bolt anchors. Use existing ceiling supports or
the ceiling.
construct a suitable support as shown in figure.
6 Screw the nuts to suspend the unit.
Concrete
7 Adjust level of the unit by using measurement plate for
all 4 sides.
CAUTION
Hole in anchor Insert
Hole in plug • For proper drainage of condensate, give a 3mm slant
to the left or right side of the unit which will be
connected with the drain hose, as shown in the figure.
Suspension bolt (M8) - field supply
Make a tilt when you wish to install the drain pump,
too.
3 Install the suspension bolts depending on the ceiling type.
When the drain hose is installed to the right.
Ceiling support
3mm
Drain hose port
CAUTION CAUTION
• Noise will increase 3~6 dB(A) when the air flow
• Ensure that the ceiling is strong enough to support the
enters from the bottom side (Only for Slim Duct Type
weight of the indoor unit. Before hanging the unit, test
product).
the strength of each attached suspension bolt.
• If the length of suspension bolt is more than 1.5m,
it is required to prevent vibration.
• If this is not possible, create an opening on the false
ceiling in order to be able to use it to perform the
required operations on the indoor unit.
4 Screw eight nuts to the suspension bolts making space Air Flow
for hanging the indoor unit.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
Drain hose
Within
Drain pipe
300~550mm
Horizontal drainpipe
Flexible hose
Be sure to bond the drain Ceiling more than 1/100 slope
Large seailng pad
hose and the main pipe.
Drain pipe
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
Connecting the power and The indoor unit is powered through the outdoor unit by
means of a H07 RN-F connection cable (or a more power
communication cables model), with insulation in synthetic rubber and a jacket
in polychloroprene (neoprene), in accordance with the
CAUTION requirements specified in the standard EN 60335-2-40.
• Always remember to connect the refrigerant pipes 1 Remove the screw on the electrical component box and
before performing the electric connections. When remove the cover plate.
disconnecting the system, always disconnect the electric 2 Route the connection cord through the side of the indoor
cables before disconnecting the refrigerant pipes. unit and connect the cable to the terminals refer to the
figure below.
CAUTION 3 Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
• Always remember to connect the air conditioner to the
grounding system before performing the electric connections. 4 Reassemble the electrical component box cover, carefully
tightening the screw.
Use a crimp ring terminal at the end of each wire.
Indoor Unit
Indoor Unit
1(L) 2(N) 1 2 F1 F2 V1 V2 F3 F4
1(L) 2(N) 1 2 F1 F2 V1 V2 F3 F4
1(L) 2(N) L N F1 F2
1(L) 2(N) L1(R) L2(S) L3(T) N F1 F2
Cable clamp
Outdoor Cable clamp
Unit
Outdoor
Unit
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
L N F1 F2 L N F1 F2
Outdoor
Outdoor Unit
Unit
1(L) 2(N) L N 1(L) 2(N) L1(R) L2(S) L3(T) N
Indoor Power Communication cable Indoor Power 3 Phase 4 Wires power Communication cable
Main power cable
cable (AC 380V)
**035/160**
AC power: M4 screw Communication: M3.5 screw
CAUTION
• When installing the indoor unit in a computer
**052/071/100/120/140** room or a server room, use the double shielded
AC power: M4 screw Communication: M3.5 screw communication cable (tape aluminum / polyester
10.3 13.8 10.1 11.4 braid + copper) of FROHH2R type.
19.2
19.2
M4 12.0 to 18.0
• 1 N·m = 10 kgf·cm
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
4. Ceiling
300 mm
NOTE
• Use the pattern sheet to select pipe directions.
50 mm
2 Install the hanging plate according to the distance and
mount it.
Floor installation
300 mm
300 mm
AC071/100/120/140/160TNCDKC
Ceiling installation
300 mm 50 mm
Ceiling Ceiling
Wall
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
1° or less
1 Select pipe directions.
When the directions are selected, drill 3-1/8''-(100mm,
for pipe and cables) and 1-3/4''-(40mm, for drain hose)
diameter holes on the wall so that it slants slightly
4 When Hanging the set, firstly unscrew the screws from
downwards toward the outdoor for smooth water flow.
the both of sides, and then disassemble the Case-sides,
NOTE or else the case-side will be damaged by disassembling
it directly.
• Use the pattern sheet to select pipe directions.
NOTE
Unscrew two screws from the both of sides.
• Use the pattern sheet.
5 Reassemble the Case-sides, tightening the screws after
3 Install the unit onto the ceiling. Be sure to arrange the
hanging the set.
drain hose so that it is leveled lower than the drain hose
connecting port of the indoor unit.
NOTE
• For proper drainage of condensate, give a 1° or less slant
to the side of the unit which will be connected with the
drain hose as shown in the figure. (The gap between the
lower end of the indoor unit and the ceiling should be
12 mm or less.)
Remove the Case-sides from the both of sides.
1° or less
Connection pipe
Purging inert gas from the indoor unit
The indoor unit comes with nitrogen gas (inert gas)
Drain hose
charged at the factory. Therefore, all inert gas must be
purged before connecting the assembly piping.
AC052TNCDKC
Drain hose
CAUTION
• Ensure that the ceiling is strong enough to support the
weight of the indoor unit.
• Before hanging the unit, test the strength of each
attached suspension bolt.
• Install the drain hose from the rear of the unit.
AC071/100/120/140/160TNCDKC
NOTE
• AC052TNCDKC:The gap between the lower end of the
indoor unit and the ceiling should be 1˚ (16 mm) or less.
• AC071TNCDKC:The gap between the lower end of the
indoor unit and the ceiling should be 1˚ (23 mm) or less.
• AC100/120/140/160TNCDKC:The gap between the lower
Side cover
end of the indoor unit and the ceiling should be 1˚ (28
mm)
m) or ss.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
Installing the drain hose and When passing the drain hose through the hole drilled in the
wall, check that none of the following situations occur:
drain pipe
Care must be taken when installing the drain hose for AC052TNCDKC
the indoor unit to ensure that any condensation water is
correctly drained outside.
NOTE
• Installing the drain hose should be the shorter, the
better.
• In order to discharge condensate water, a downward
gradient should be maintained.
• Fix the drain hose with Cable-Tie, so that it will not The hose must NOT The hose must NOT Do NOT bend the
separate from the machine. slope upwards. slope The end of the hose in different
drain hose must NOT directions.
be placed in water.
1 Insert the drain hose to bottom of the outfall of water
basin.
2 Lock flexible hose clamp of the drain hose according to
the figure.
3 Wind and wrap flexible hose clamp and drain hose fully
with thermal insulation sponge; fix both ends of external
layer with ribbon for thermal insulation.
4 After being installed, drain hose must be insulated fully 5cm
by heat insulating material. (To be provided at site.) less
Indoor unit
A A-A’
Drain hose
Wrap thermal sleeve hose
Insulation
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
AC071/100/120/140/160TNCDKC 3 Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
wall
4 Reassemble the electrical component box cover, carefully
hole tightening the screw.
1 phase(**071**)
Wired Remot
Controller
Indoor Unit (Optional)
No grade
Outdoor Unit
1(L) 2(N) 1 2 F1 F2
CAUTION
• Always remember to connect the refrigerant pipes before 1(L) 2(N) L N F1 F2
performing the electric connections.
When disconnecting the system, always disconnect the
electric cables before disconnecting the refrigerant pipes.
• Always remember to connect the air conditioner to the Cable
grounding system before performing the electric connections. clamp
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
CAUTION
• When installing the indoor unit in a computer room or
Cable clamp
a server room, use the double shielded communication
cable (tape aluminum / polyester braid + copper) of
FROHH2R type.
Communication cable
0.75㎟↑, 2wires
**052**
AC power: M4 screw Communication: M3.5 screw
**071/100/120/140/160**
AC power: M4 screw Communication: M3.5 screw
M4 12.0 to 18.0
• 1 N·m = 10 kgf·cm
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
CAUTION
8. Outdoor Unit • You have just purchased a system air conditioner
and it has been installed by your installation
Installation location requirements specialist.
• This device must be installed according to the
national electrical rules.
• Do not place the outdoor unit on its side or upside
down. Failing to do so may cause the compressor • If your outdoor unit exceeds a net weight of 60 kg,
lubrication oil to run into the cooling circuit and lead do not install it on a suspended wall, but stand it
to a serious damage to the unit. on a floor.
• Install the unit in a well-ventilated location away • When installing the outdoor unit at the seaside, make
from direct sunlight or strong winds. sure that it is not directly exposed to sea breeze. If
you cannot find an adequate place free from direct
• Install the unit in a location that would not obstruct
sea breeze, construct a protection wall or a protective
any passageways or thoroughfares.
fence.
• Install the unit in a location that would not
– Install the outdoor unit in a place (such as near
inconvenience or disturb your neighbors, as they
buildings etc.) where it can be prevented from sea
could be affected by the noise or the airflow coming
breeze. Failure to do so may cause a damage to
from the unit.
the outdoor unit.
• Install the unit in a location where the pipes and the
cables can be easily connected to the indoor unit. Sea breeze Sea breeze
ventilate.
1 m or more
1 m or more
1.5 m or more
Sea
• Make sure that the water dripping from the drain • Install the unit in a place where water can drain
hose runs away correctly and safely. smoothly.
• If you have any difficulty finding installation location
as prescribed above, contact your manufacturer for
details.
• Be sure to clean the sea water and the dust on the
heat exchanger of the outdoor unit and apply a
corrosion inhibitor on it. (At least once in a year.)
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
343
330
620
1420
1395
360
384
1095
790 60
558
567
B Type
AC052TXADKC
310
661
638
338
15
C Type
When installing 1 outdoor unit
AC071TXADKC
500 or more
150 or more
338
798
15
880 49
D Type
150 or
more
AC100TXAD*C
or more
1000
360
384
977
150 or
more
528
537
675
or more
500
150
or more
or more
1000
E Type
AC120/140TXAD*C
940
330
620
1210
360
384
1185
675
558
567
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
or more
300
or more
150 150 1500 • Louver specifications.
or more or more
– Angle criteria : less than 20˚
– Opening ratio criteria : greater than 80%
300 or more
317
343
500 or more
300 or more
612
790
AC052/071TXADKC
CAUTION Anchor bolt hole
• The outdoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
357
338
359
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
AC100/120/140/160TXAD*C (Unit : mm) • Connect the air conditioner to the earthing system
before making the electrical connections.
Anchor bolt hole
NOTE
• Especially, if your outdoor unit is the one designed
330
360
384
for Russian and European markets, consult the supply
authority, if necessary, to estimate and reduce the
supply system impedance before installation.
620
940
Air conditioning system examples
• Install a drain outlet at the lowest end around the base Communication cable
for outdoor unit drainage Outdoor-to-indoor power cable
ELCB
1
Earthing
Main power cable Indoor Unit
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
Power Supply
ELB
Cable clamp
Cable tie
1-phase
Electrical
component box
Power Supply
MCCB
ELB
Cable tie
3-phase
Indoor Unit
Cable tie
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
CAUTION
• You should connect the power cable into the power cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 2% of supply rating.
If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is exceeded over
4% of supply rating, the indoor unit is protected, stopped and the error mode indicates.
• To protect the product from water and possible shock, you should keep the power cable and the connection cord of
the indoor and outdoor units within ducts. (with appropriate IP rating and material selection for your application)
• Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a least
3 mm.
• Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage
category.
• Keep distances of 50 mm or more between power cable and communication cable.
AC power: Comunication:
M4 screw M4 screw
1(L) 2(N) L N F1 F2
10.1
13.8 10.3
11.4
10.1
16.3 12 11.4
10.1 10.1
16.5 12 9.8 14.2
11.4 11.4
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
NOTE
1 Voltage range
• Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above
listed range limits.
2 Maximum allowable voltage variation between phases is 2%.
3 Wire size & type must comply with the applicable local and national code.
• Wire size: Based on the value of MCA.
• Wire type: 60245 IEC57(IEC) or H05RN-F(CENELEC) grade or more.
4 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
5 MCA represents maximum input current.
• MFA represents capacity which may accept MCA
• Abbreviations
MCA: Min. Circuit Amps. (A)
MFA: Max. Fuse Amps. (A)
• AC052/071TXADKC • AC100/120/140/160TXAD*C
Outdoor unit Outdoor unit
CN001
CN001
Non-voltage contact
Non-voltage contact
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
L
1-phase Indoor Unit
F1 F2
N
For connecting the power and
communication cables Outdoor Unit
F1 F2
1(L) 2(N) L1(R) L2(S)L3(T) N
Indoor Unit
1(L)
F2
2(N) F1 Cable tie
Outdoor-to-indoor 3-phase 4-wire main Communication cable
power cable power cable (AC 380V)
1(L) 2(N) L N
NOTE
• Lay the electrical wiring so that the front cover does
Outdoor-to-
indoor power not rise up when doing wiring work and attach the
cable front cover securely.
• Ground wire for the indoor unit and outdoor unit
Main power cable Communication cable connection cable must be clamped to a soft copper
Cable clamp
tin-plated eyelet terminal with M4 screw hole(NOT
SUPPLIED WITH UNIT ACCESSORIES).
Silver solder
Outdoor Unit
Cable tie
Outdoor-to-indoor Main power cable Communication cable
power cable
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
Nominal Nominal B D d1 E F L d2 t
dimensions dimensions Standard Standard Standard Standard
for cable for screw dimension Allowance dimension Allowance dimension Allowance Min. Min. Max. dimension Allowance Min.
(mm²) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
(mm) (mm) (mm) (mm)
+0.2
4 9.5 5 20.0 4.3
+0.3 0
4/6 ±0.2 5.6 3.4 ±0.2 6.0 0.9
-0.2 +0.4
8 15.0 9 28.5 8.4
0
+0.3 +0.4
10 8 15.0 ±0.2 7.1 4.5 ±0.2 7.9 9 30.0 8.4 1.15
-0.2 0
+0.3 +0.4
16 8 16.0 ±0.2 9.0 5.8 ±0.2 9.5 13 33.0 8.4 1.45
-0.2 0
8 12.0 +0.5 15 8.4 +0.4
25 ±0.3 11.5 7.7 ±0.2 11.0 34.0 1.7
8 16.5 -0.2 13 8.4 0
+0.5 + 0.4
50 8 22.0 ±0.3 13.5 11.4 ±0.3 17.5 14 50.0 8.4 1.8
-0.2 0
+0.5 + 0.4
70 8 24.0 ±0.4 17.5 13.3 ±0.4 18.5 20 51.0 8.4 2.0
-0.4 0
• Connect the rated cables only. • Must keep the cable in a protection tube.
• Connect using a driver which is able to apply the rated • Keep distances of 50mm or more between power cable
torque to the screws. and communication cable.
• If the terminal is loose, fire may occur caused by arc. If • When the cables are connected through the hole,
the terminal is connected too firmly, the terminal may remove the Plate bottom.
be damaged.
Outdoor-to-indoor power and communication
Tightening torque (N·m) cables specifications
M4 0.8 to 1.2 Indoor power supply
Communication cable
CAUTION
0.75㎟, 2wires
• When connecting cables, you can connect the cables to
the electrical part or connect them through the holes • Power supply cords of parts of appliances for outdoor
below depending on the spot. use shall not be lighter than polychloroprene sheathed
• Connect the communication cable between the indoor flexible cord. (Code designation IEC:60245 IEC 57 /
and outdoor units through a conduit to protect against CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
external forces, and feed the conduit through the wall H07RN-F)
together with refrigerant piping. • When installing the indoor unit in a computer room
• Remove all burrs at the edge of the knock-out hole or net work room, use the double shielded (tape
and secure the cable to the outdoor knock-out using aluminium / polyester braid + copper ) cable of
lining and bushing with an electrical insulation such as FROHH2R type.
rubber and so on.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
n=1 indoor
Indoor Unit
Outdoor L1
h1
CAUTION
CAUTION
• Be sure to use C1220T-1/2H (Semi-hard) pipe for more
• Be sure to use C1220T-1/2H (Semi-hard) pipe for
than Ø19.05 mm. If you use C1220T-O (Soft) pipe for Ø19.05
more than Ø19.05 mm. If you use C1220T-O (Soft)
mm, the pipe may be broken, which can result in an injury.
pipe for Ø19.05 mm, the pipe may be broken, which
can result in an injury.
Make at least one round:
It will reduce noise and vibration
A
• The appearance of the unit may be different from the Block the part.
diagram depending on the model.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
AC035/052/071TXADKC
Indoor Unit
• Cut the pipe outlet to the exact pipe size. In addition,
remove foreign substances and burres aroud the outlet.
Balance
• Perform cutting with only a cutter (ex. nipper) and Ref
never tap with a hammer near the pipe outlet.
Otherwise, damage to products such as the cabinet Vacuum
being bent may occur. Pump
Balance
Adding refrigerant (R-410A) Outdoor Unit
Ref
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
A(Gas)
• The designs and shape are subject to change
B (liquid)
according to the model.
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Installation
80 mm 13 mm
AC035TXADKC
Drain cap (5EA)
AC052/071TXADKC
Drain cap (4EA)
Drain plug (1EA)
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
2020. 06
Ver.1.0
Samsung Electronics Co., LTD.
Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677
Website : www.samsung.com, https://partnerhub.samsung.com Email : airconditioner@samsung.com
Images and data in this book may subject to change without prior notice.