Professional Documents
Culture Documents
INSULATED
HEATING CABLE
Considerations for application
of mineral-insulated electrical
resistance heating cable
59
Digital Object Identifier 10.1109/MIA.2007.901381
1077-2618/07/$25.00©2007 IEEE
MI Cable Construction ture. The resistance of pure copper, for example, when
MI cables are comprised of one or more solid conductors maintaining a pipe at 200 ◦ C (392 ◦ F) is about two
that run longitudinally in the cable, a mineral powder elec- times its resistance at room temperature. Temperature
trical insulation, and a continuous metal sheath, as shown resistance change needs to be taken into account when
in Figure 1. the heater is designed. Typical values for a selection of
the materials commonly used for the heating
Conductors conductor(s) of MI cables are listed in Table 1.
In MI heating cable, the conductors selected are usually a
resistance alloy or copper depending on the resistance per MI Cable Dielectric Insulation
unit length required and the desired dielectric rating The electrical insulation may be one of a number of dif-
which impacts the finished cable diameter. The resis- ferent ceramic powders such as aluminum oxide or boron
tance of heating cables ranges from as high as 56 /m nitride, but magnesium oxide (MgO) is by far the dielec-
down to 0.0021 /m (17 /ft down to 0.000641 /ft). tric of choice because it is readily available, inexpensive,
For most alloys, the resistance increases with tempera- easy to process, and has good thermal and electrical prop-
erties when compressed. The physical structure of
MgO is stable to extremely high temperatures
(1,000 ◦ C or 1,830 ◦ F).
Compressed MgO has a higher thermal conduc-
tivity compared to other insulation types (see Table
Insulation 2) and, therefore, the heat is more rapidly transferred
(Magnesium Oxide) out of the cable. For this reason, the conductor will
Solid Heating be cooler than that of a polymer-insulated cable
Conductors loaded to the same watt density and operating at the
Solid Sheath
same sheath temperature.
The insulation resistance of compressed MgO
decreases with increasing temperature (see Figure 2).
Dual-Conductor Cable Similarly, as shown in Figure 3, the dielectric
1 strength of compressed MgO decreases with increas-
Typical MI cable construction. ing temperature.
Metal Sheath
TABLE 1. PROPERTIES OF RESISTANCE ALLOYS.
IEEE INDUSTRY APPLICATIONS MAGAZINE • SEPT|OCT 2007 • WWW.IEEE.ORG/IAS
V per mm of Insulation
Length Determination
Single Conductor Heaters Since MI heaters are series type and
5 often not intended to be cut to
Single-conductor MI cable configuration. length in the field, you must have
good approximation or accurate mea-
sure of required lengths. This is easier on pipes that are 3
in and larger if supplied as prefabricated “spool pieces.”
These pipe lengths can be determined well ahead of
time. Smaller pipe is usually field run, and the length
cannot be confirmed until the pipe installation is com-
plete. If an MI heater is used on field run piping, it is
recommended that the pipe length be measured before
ordering the heater, including allowances for heat sinks.
Some minor length adjustments can be made by
slight changes to the adders for heat sinks. It is not a
good idea to double the heater back on the end of the
pipe to adsorb extra cable. Doubling the heat input can
result in a significant increase of the pipe temperature
in that area and should not be done arbitrarily in haz-
ardous areas. Using extra cable at the heat sinks will
6
not drive the temperature as much due to the higher
Reduced passes of MI heating cable adder on pipe and heat losses of the device (pipe support or valve) in that
62
heat sinks. area of the pipe.
Heating Section Elongation IEEE 515-2004 [1] for a complete description of all con-
The heater gets hotter than the pipe it is installed on, so ditions to be considered. Due to the complexity of these
it will expand to a greater length than the pipe when abnormal design conditions, it is recommended that you
energized. Installation methods should allow for this use the heating cable manufacturer’s design software. This
expansion in a manner that does not concentrate the flex- software’s accuracy is verified by approval agency during
ing of the MI heater in specific small areas. Failure to do their system approval testing.
so can result in fatigue of the sheath at those locations. It is possible to lower a heating cable’s sheath tempera-
The flexing should occur over greater distances. For tures with the use of a heat transfer aid such as metal foils
example, if fastened tightly with metal strapping, the or heat transfer compounds. Care in maintenance is
expansion will be forced to occur between the straps, required to be sure these aids are never removed or lost. If
increasing the likelihood of fatigue and failure at the
strapping point. It is best to install the cable loosely,
allowing the expansion to occur along the pipe. Weatherproof Outer Lagging (−20 °C)
Operating-Voltage Considerations
When using voltages greater than 240 V, the quality of the Insulation Layer
supply should be considered. Large motors and solid-state
drives on the same transformer may create significant volt-
age spikes that exceed the electrical insulation strength of
the MI heating cable. This is most easily accommodated by
limiting electrical equipment on the heater cable supply
transformer to noninductive items (no motors or solid-state
power drives). If that is not possible, then use specially
sized surge suppressors that will clip any peak voltages
Pipe (500 °C)
below the expected break-over point on the MgO insula-
tion (based on projected maximum wire and sheath tem- MI Cable
7
peratures). Standard surge suppressors clipping voltages are
usually too high to provide protection to these situations. MI heating cable mounted directly on pipe.
High-Temperature Considerations
There are a variety of sheath materials utilized in MI Weatherproof Outer
Lagging (−20 °C)
as the cement ages and is subjected to thermal stresses cools from the annealing process, the metal jacket
during heater cycling. Typical maximum temperatures shrinks at a higher rate than the MgO insulation.
for heat transfer compound are 190 ◦ C (375 ◦ F) for This results in a slight hoop stress existing in the
resin-based nonhardening types and epoxy-based com- metal sheath. Additional stresses are induced during
pound, and 371–675 ◦ C (700–1,200 ◦ F) for water-based the bending of the cable during the installation
compound. process. If chloride ions and moisture are introduced
to the stressed sheath, chloride stress corrosion
Flexing Pipe Joints, such as Loading Arms cracking will result. Even low-halide thermal insu-
MI heating cable cannot traverse these moving joints. Seg- lations (below 50 ppm) can experience a concentrat-
ment the cable at these locations by wiring separate cold ing effect from rainwater leaks or leaky pipe seals.
leads to connection boxes on each pipe segment. Use flex- The moisture will carry the leached chloride ions to
Maintenance
Periodic maintenance is important not only to verify
operation of the heater and to service control compo-
nents, but also to inspect the system for damage that
will affect its operation. IEEE 515-2004 [1] provides
general maintenance information that applies to all
types of heating devices (cables and panels) and
includes a “Maintenance Log Record” (Annex-K) to
TDR support maintenance records.
Open
10 Troubleshooting
TDR trace if heater is open circuited. In the event that a malfunction is suspected, understand-
ing the symptoms is important to a prompt and effective
solution to the problem. It is important to understand
that a low-temperature condition is not always the result
of a malfunctioning heat-tracing circuit. In an adaptation
of the paper titled “Calculating Electrical Risk and Reli-
ability,” [5] the author applied the principles of reliabili-
ty to electrical heat-tracing systems, compiling data from
various sources to help understand the nature of the
problems reported. Based on that study, it was suggested
that the primary cause of system failure was damaged,
wet, or missing thermal insulation. (In each of these
cases, the electric heat-tracing system was properly
TDR
installed and checked out during startup before data was
Short
collected for this study). The second most common cause
11
of system failure was cable abuse and the third was
improper or damaged terminations and connections.
IEEE INDUSTRY APPLICATIONS MAGAZINE • SEPT|OCT 2007 • WWW.IEEE.ORG/IAS