Professional Documents
Culture Documents
Firetube Boilers
Installation Manual
STEAM
750-452 11/2021
! WARNING
DANGER
Do not operate the equipment until the unit is properly installed
and commissioned by an authorized service technician.
To the Installer
This manual presents information to assist in the installation of Cleaver-Brooks firetube boilers. Items cov-
ered include lifting and moving the boiler, placement of the boiler, boiler room requirements, and connec-
tions to the boiler, system operating requirements, and water treatment requirements. The information is
presented to enable the installer to quickly install the unit with the least risk of damage to the equipment.
Recommendations given in this manual are the minimum requirements pertaining to CB firetube boilers.
Insurance and local or state regulatory codes may contain additional or more stringent requirements than
those noted in this manual. Installation must conform to the requirements of the owner's insurance carrier,
state/provincial and local codes governing such equipment, and/or any other authority having jurisdiction.
Prior to installation, the proper authorities having jurisdiction are to be consulted, permits obtained, and
other preparatory actions taken as necessary.
This manual contains an installation checklist which should be completed before the initial start up of the
boiler. Refer to manual 750-454 for start-up procedures after the boiler has been properly installed.
Additional information may be obtained from your local Cleaver Brooks factory authorized representative.
Refer to the specific Dimension Diagram of the boiler for project specifics, tappings, and connection loca-
tions.
Throughout this manual, procedures or operations that require special attention are emphasized with a
cautionary note. The notes are identified by the symbols WARNING!, CAUTION! or NOTE, signifying the
following:
NOTE: Indicates information that is vital to the operation or maintenance of the equipment.
FIRETUBE PRODUCT NOMENCLATURE
CBEX-2W-200-500-150ST
Boiler horsepower ST = Steam
Number of passes HW = Hot water
Turnaround design
W = Water back
D = Dry back
natural gas, light oil, or combina- natural gas, light oil, or combina- natural gas, light oil, or combina-
tion tion tion
50-250+ psig steam High and low pressure steam High and low pressure steam
iii
ADDITIONAL RESOURCES
BURNER
MODEL BHP NOX RATING BURNER
MANUAL
STANDARD V
100-200 750-237
30 PPM LNV
STANDARD E
CBJT-2W 250-800 750-297
30 PPM LNE
STANDARD XL
900-1200 750-339
30 PPM LNXL
STANDARD K 750-282
100-300
30 PPM LND 750-204
CBJT-3W STANDARD D
350-800 750-204
CBJT-4W 30 PPM LND
STANDARD S1
900-1600 750-208
30 PPM LNS1
iv
CONTENTS
LIFTING AND MOVING THE BOILER 1
Roller Rails 2
THE BOILER ROOM 3
Placement of the Boiler 3
Clearances 3
Combustion/Ventilation Air Supply 4
BOILER CONNECTIONS (GENERAL) 6
Bottom Blowdown 6
Safety Valve 6
Electrical Connections 8
Flue Vent Connections 8
STEAM BOILER CONNECTIONS 10
Steam Supply 10
Feedwater Makeup 11
Water Column Drain 12
Surface Blowoff 12
Other Options 12
FUEL SYSTEM 13
Main gas train 13
Pilot train 14
Burner drawer 14
Gas Supply Requirements 15
Oil Piping: 100 and 200 Fuel Series 18
WATER REQUIREMENTS 19
WATER TREATMENT 20
INSTALLATION CHECKLIST 21
v
NOTES
vi
LIFTING AND MOVING THE BOILER
Cleaver Brooks firetube boilers are equipped with two lifting lugs located on the top centerline of the vessel.
These lugs should be used to the lift the boiler. Do not move the boiler by pushing, prying or pulling on the
boiler casing.
Consult the Cleaver-Brooks Boiler Book for specific models to find the lifting lug locations for each model by
size. The following recommendations are generic and apply to all boiler models.
60°
MAX
! Caution
In order to avoid damage to the unit, lifting or mov-
ing the boiler should only be done by experienced
personnel with suitable equipment for moving
heavy industrial equipment.
Suitable equipment adequate to safely lift and support the boiler within the restrictions of the chain angles
should be on hand when the boiler arrives at the project site. Approximate shipping weights (dry weight) for
specific models can be found in the Cleaver-Brooks Boiler Book.
If rollers are used to transport the boiler, they should be positioned under the base in line with the lifting lugs
(see below). If pipes or other rollers are used to move the boiler, the boiler must be supported by at least
three evenly spaced rollers at all times.
If an overhead lifting device is not available, jack plates may be welded to the base rails to allow lifting by the
base for placement of rollers. Plates should be as close as possible to the boiler legs to avoid bending the
base rails.
750-452 1
Firetube Installation - Steam
LIFTING AND MOVING THE BOILER
Roller Lifts
(fixed @ legs)
If the opening for the boiler is too narrow to permit the boiler to pass through, determine what controls may
be removed from the package to permit access. This should be discussed with the local Cleaver Brooks rep-
resentative before any items are removed.
! Caution
Remove the (optional) roller rail assembly before
installing boiler. Failure to do so may result in
damage to the equipment.
2 750-452
Firetube Installation - Steam
THE BOILER ROOM
The boiler must be installed on a level non-combustible floor. If the floor is not level, piers or a raised pad will
make the boiler installation and leveling easier.
Six-inch high mounting piers are recommended for use beneath the boiler base frame. The use of these
piers provides increased inspection accessibility to the boiler and added height for washing down the area
beneath the boiler. See the Boiler Book for specific models for mounting pier length and width dimensions.
The floor, pad or piers must be of sufficient load bearing strength to safely support the operating weight of the
boiler and any additional equipment that may be installed with it. Approximate boiler operating weights can
be found in the Boiler Book section for the respective model.
After the boiler is placed, it must be leveled from side to side and front to back. If shims are required, the
weight of the boiler must be evenly distributed at all points of support.
! Caution
The pressure vessel support legs are welded to mounting skids in front and secured by bolts at the rear of the
pressure vessel. The bolts are tightened for shipment. When the boiler is installed, and prior to initial fir-
ing, the bolts securing the rear legs to the skid must be loosened to allow for expansion and contrac-
tion caused by differences in temperature between pressure vessel and skids.
2.2 - Clearances
The boiler must be installed so that all components are accessible for inspection, cleaning, or maintenance.
Field installed piping and electrical connections to the burner or boiler must be arranged in a manner that
permits swing out of the burner.
In addition to maintaining clearances to walls or other obstructions, boiler surfaces that become heated
during operation require minimum clearances to combustible materials.
Overall boiler room width must be sufficient to accommodate dimensions A (minimum distance between
boiler and wall) and B (distance between boilers) as shown below. These dimensions for specific models can
be found in the appropriate Boiler Book section.
750-452 3
Firetube Installation - Steam
THE BOILER ROOM
A B
FEEDWATER
TANK
BOILER
FEEDWATER
PUMP
DRAIN
TRENCH
Boiler room length should allow for tube cleaning and replacement. Consult the Boiler Book for specific mod-
els for tube replacement clearances.
A method of supplying combustion air, satisfactory for complete fuel combustion in the boiler and proper
ventilation of the boiler room, must be provided.
The volume of air required and the duct or air supply opening in square feet shall be determined relative to
the rating of the burner and the altitude of the project installation. Air inlets shall be sized in accordance with
applicable engineering guidelines and regulatory codes.
When determining boiler room air requirements for an unconfined space*, the size of the room, airflow, and
velocity of air must be reviewed as follows:
4 750-452
Firetube Installation - Steam
THE BOILER ROOM
1. Size (area) and location of combustion air supply for the boiler:
a. Two (2) permanent air supply openings in the outer walls of the boiler room are recommended. Locate one
(1) at each end of the boiler room, preferably below a height of 7 feet. This allows air to sweep the entire
length of the boiler.
b. Air supply openings can be louvered for weather protection, but they should not be covered with fine mesh
wire as this type of covering has poor air flow qualities and is subject to clogging with dust or dirt.
c. A vent fan in the boiler room is not recommended as it could create a slight vacuum under certain conditions
and cause variations in the quantity of combustion air. This would result in unsatisfactory or unsafe burner
performance.
d. Under no circumstance shall the total area of the air supply be less than one square foot.
e. Size the openings by using the formula:
= a total of 10 cfm per Bhp up to 1000 feet elevation. Add 3% more per each 1000 feet of added elevation.
3. Acceptable air velocity in the Boiler Room (fpm) feet per minute.
a. From floor to 7 feet in height - 250 fpm
b. Above 7 feet in height - 500 fpm
c. Duct from air supply to boiler - 1000 fpm
EXAMPLE: To determine the area of the boiler room air supply opening for a 60hp boiler at 700 ft elevation
with air opening 8 ft above the floor level:
ft2 = 10 cfm(60)/500 fpm from steps 2 and 3 above.
750-452 5
Firetube Installation - Steam
BOILER CONNECTIONS (GENERAL)
NOTE: Connection sizes and locations and associated boiler trim components may vary. For installation
purposes consult the Dimension Diagram provided with the boiler.
Connections for bottom blowdown are provided at the front and/or rear of the bottom drum.
A blowdown valve(s) must be piped from this connection to a safe point of discharge; piping is not supplied
with the boiler.
For high pressure boilers a quick open valve and a slow open valve are normally piped from the blowdown
connection; these valves must be rated at 150 psig or greater. If two blowdown connections are provided on
the boiler, two quick open valves piped in common to a single slow open valve may be utilized.
The safety valve is an essential device. Its purpose is to relieve pressure buildup within the vessel in excess
of the maximum design pressure. The size, rating, and quantity of valves on a boiler are determined in
accordance with the A.S.M.E. code or other code/specification requirements. Check the boiler dimension
diagram for the number and size of the boiler's safety relief devices. The location of the safety valve(s) is on
the top centerline of the vessel near the rear. Safety valves are shipped unmounted, normally in a separate
box or carton.
Each relief device must be mounted in a vertical position with no shutoff devices between it and the boiler
connection. Discharge piping must be properly piped to a safe point of discharge to the roof or to an area of
discharge that will not expose personnel to escaping steam or water. See figure below for suggested steam
pressure relief valve piping using a drip pan elbow. Discharge piping from the safety valve is not furnished by
Cleaver-Brooks.
6 750-452
Firetube Installation - Steam
BOILER CONNECTIONS (GENERAL)
NOTES
1. SUPPORT FROM BUILDING CONSTRUCTION
2. DISCHARGE OPENING MUST BE EQUAL TO OR LARGER THAN INLET
3. BACK PRESSURE OF STEAM EXHAUST SYSTEM MUST BE LESS THAN 6% OF SAFETY VALVE SETTING
Discharge piping must be arranged and properly supported so that the piping weight does not bear upon the
valve; piping should be as short and direct as possible.
Do not paint, oil, or otherwise cover any interior or working parts of the relief valve. A relief valve does not
require any lubrication or protective coating to work properly.
Ensure that the relieving capacity matches the output requirement of the boiler as stamped on the boiler and
on the relief valve.
NOTE: Discharge piping from relief valves, blowdown valves, and other drains must be arranged so that all
components remain accessible for inspections, cleaning, or maintenance. Relief valves and their discharge
piping are to be installed to conform to A.S.M.E. Code requirements.
750-452 7
Firetube Installation - Steam
BOILER CONNECTIONS (GENERAL)
! Caution
Care must be exercised in the installation of a relief valve to ensure that the valve functions as designed.
Apply only a moderate amount of pipe compound to male threads. Avoid over-tightening, as this may dis-
tort valve seating surfaces. Use only flatted wrenches on the flats of the valve.
! Warning
Incorrect or improper installation of the relief valve may affect valve operation. Only certified personnel
such as the relief valve manufacturer's representative should adjust or repair the boiler relief valve.
Failure to observe this warning could result in serious injury or death.
Electrical power supply to the boiler must be of proper voltage, phase, and hertz as inscribed on the burner
or electrical nameplate. All connections made to the boiler must comply with the National Electric Code and
local code requirements and must be arranged so that all components remain accessible for inspection,
cleaning, and maintenance. Refer to the wiring diagram (WD) prepared by Cleaver-Brooks for the specific
project when wiring to the boiler.
The breeching between the boiler and the chimney/exhaust stack must be no smaller in diameter than the
connection provided on the boiler. The proper sizing of stacks and breeching is required in order to maintain
proper flue gas velocity with a static draft condition (0" w.c.) although the burner can work within a +/- 0.25"
variance. Therefore the pressure drop in the breeching and stack should not exceed these parameters.
The horizontal run to the stack should be held to a minimum and all horizontal runs pitched away from the
boiler at a minimum of 0.25" per 100 feet. A drain connection should be provided at all low spots. Round
breeching or stacks are recommended and are more efficient than square or rectangular shapes. In multiple
boiler applications, connections to the common breeching should be with sweeping elbows; avoid bull head
tees.
Material type of the breeching and stack will be governed by local codes and jurisdictions. For these pur-
poses most CB firetube boilers are considered a Class III appliance, defined as a non condensing positive
pressure venting product. Therefore, the stack/breeching must be of the positive pressure design, normally
double wall type (if single wall, stack/breeching should be insulated). Roof or wall penetrations should be in
accordance with UL and local code requirements.
The maximum load on the flue vent connection at the boiler is 2000 pounds. Boilers can be reinforced to
support up to 3000 pounds.
8 750-452
Firetube Installation - Steam
BOILER CONNECTIONS (GENERAL)
PITCH UP TO STACK
o
10 MAX
o
45
MAINTAIN ON
ONE PLANE
Breeching size for multiple boilers should take into account the volume of flue gas that will flow through suc-
cessive additions of boilers and breeching runs. Do not merely size the breeching for multiple boilers relative
to the exhaust connection of each boiler. Draft calculations should be performed and the common stack/
breeching designed accordingly.
750-452 9
Firetube Installation - Steam
STEAM BOILER CONNECTIONS
Gauge Glass
Blowdown
Bottom Blowdown
Surface
Blowoff
Chemical
Feedwater Feed
Water Column
Blowdown
Connection to the system header or system supply line is made at the fitting at the upper drum near the cen-
ter of the boiler.
10 750-452
Firetube Installation - Steam
STEAM BOILER CONNECTIONS
ASME code requires a stop valve in each steam outlet as near the boiler nozzle as possible. Valves of over
2" pipe size must be Outside Stem and Yoke (OS&Y), rising stem type.
If the boiler was not shipped with a stop valve, the installing contractor will have to supply the proper valve.
Check valves (non-return), where used, should be piped in the horizontal position to minimize the likelihood
of contaminant build up on the valve seat and disc.
Steam piping must be connected per the ASME Code and local jurisdictions and as defined in the project
specifications.
The boiler feed piping requires a globe valve and a check valve (ASME Power Piping B31.1 Section
122.1.3). The connection size is noted on the boiler dimension diagram.
See the table below for the water quantity required based on the evaporation rate of the boiler; ensure the
pumps are rated greater than this capacity.
As an option, the boiler may have been provided with an electrically powered modulating feedwater valve or
an on/off feedwater valve. If so, this assembly will need to be piped to the boiler and may include a 3-valve
by-pass around the feedwater control valve. This assembly is generally factory pre-piped and shipped sepa-
rately from the boiler.
750-452 11
Firetube Installation - Steam
STEAM BOILER CONNECTIONS
The primary water column is equipped with a column drain valve. This must be piped to a safe point of dis-
charge.
The column drain may be connected to the boiler blowdown piping and also with the water column gauge
glass.
If a float or external probe type Auxiliary Low Water Cutoff control (ALWCO) has been provided, the drain
connection of this control must be piped to a safe point of discharge.
A surface blowoff tapping is standardly provided. As an option, a manually operated surface blowoff valve
may have been provided. If this has been provided, this valve should be piped to a safe discharge or blow-
down separator.
In lieu of an optional manual surface blowoff valve, an optional conductivity control valve assembly may
have been provided, shipped loose. If this has been provided, this assembly should be piped and wired to
the boiler.
There may be additional tappings provided in accordance with the project requirements and these are gen-
erally noted on the boiler dimensional diagram.
12 750-452
Firetube Installation - Steam
FUEL SYSTEM
5 - FUEL SYSTEM
NOTE: For technical details on the burner and fuel delivery systems for CBEX 1300-2200, CBJT, or ultra low
NOx applications, see the appropriate burner manual, provided separately.
A typical gas train is shown below. Local codes, project specifications, or insurance requirements may
require vent lines to be installed on some components.
4 2
5
6 1
1
Depending upon the requirements of the insurance carrier or other governing agencies, the gas train may
consist of some or all of the following items.
1. Shutoff Cocks: For manually opening and closing the main fuel gas supply downstream of the main gas line pres-
sure regulator. A second shutoff cock, downstream of the main gas valve(s), is installed to provide a means of shut-
ting off the gas line whenever a test is made for leakage across the main gas valve.
2. Main Gas Valve: Double body safety shutoff valve. Electrically actuated valves open simultaneously to admit gas to
the burner. The downstream valve is equipped with a with a regulating actuator and a proof of closure switch that is
connected to the pre-ignition interlock circuit.
3. Main Gas Vent Valve (if required; not shown): A normally open solenoid valve installed between the two main gas
valves to vent gas to the atmosphere, should any be present in the main gas line when the gas valves are deener-
gized. The vent valve closes when the gas valves are energized.
4. Low Gas Pressure Switch: A pressure-actuated switch; closed whenever main gas line pressure is above a prese-
lected pressure. Should the pressure drop below the setting, the switch contacts open a circuit causing the main gas
valve(s) to close, or prevent the burner from starting. The switch is usually equipped with a device that must be man-
ually reset after being tripped.
5. High Gas Pressure Switch: A pressure actuated switch; closed whenever main gas line pressure is below a prese-
lected pressure. Should the pressure rise above the setting, the switch contacts will open a circuit causing the main
gas valve(s) to close, or prevent the burner from starting. The switch is usually equipped with a device that must be
manually reset after being tripped.
6. Test Cocks: The body of the gas valve has 1/4-inch NPT fittings for pressure test connection.
7. Butterfly Gas Valve (not shown): The pivoted disc in the valve is directly driven by a servo motor actuator to regulate
the rate of gas flow to the burner. In optional 700-800 HP single point systems, the valve is driven by the modulating
motor through connecting linkage.
750-452 13
Firetube Installation - Steam
FUEL SYSTEM
3 1
4
2
1. Gas Pilot Valve: A solenoid valve that opens during the ignition period to admit fuel to the pilot. It closes
after main flame is established. The sequence of energizing and de-energizing is controlled by the pro-
gramming relay. A second gas pilot valve may be required by insurance regulations.
2. Gas Pilot Shutoff Cock: For manually opening or closing the gas supply to gas pilot valve.
3. Gas Pressure Gauge: Indicates gas pressure to pilot.
4. Gas Pressure Regulator: Reduces incoming gas pressure to suit the pilot.
GAS HOUSING
BURNER SUPPORT
BURNER DRAWER
14 750-452
Firetube Installation - Steam
FUEL SYSTEM
The burner is a nozzle-mixing orifice design with interrupted gas pilot. Burners equipped for oil use a low
pressure, air-atomized oil system.
Combination gas/oil burners use a fuel selector switch mounted in the control panel. Regardless of which
fuel is used, the burner operates with full modulation within its rated operating range. The burner returns to
minimum firing position for ignition.
The local gas utility should be consulted for specific requirements and authorization and inspection of the gas
supply piping. Installation of gas supply piping and venting must be accomplished in accordance with all
applicable engineering guidelines and regulatory codes. All connections made to the boiler's gas train con-
nection must be arranged so that all components remain accessible for inspection, cleaning, and mainte-
nance.
A manually operated shutoff valve is provided as standard. For some installations, local regulations may
require the installation of an approved gas filter between the gas shutoff valve and the boiler. Local require-
ments should be discussed with the local gas supply utility.
A drip leg should be installed in the supply piping before the connection to the boiler's gas train regulator sup-
plied by Cleaver Brooks. The drip leg should be at minimum as large as the inlet fitting supplied with the
boiler. Consideration must be given to both volume and pressure requirements when choosing gas supply
piping size. Connections to the boiler's gas train should be made with a union or flange so that the gas train
components or the burner may be easily disconnected for inspection or service.
If the upstream gas supply pressure is >5 psig, we recommend that an upstream pressure regulator be
installed to reduce the pressure to 5 psig or less relative to the inlet pressure requirement of the specific
boiler. This can be mounted at each individual boiler, or on the header pipe feeding each boiler.
All gas piping and components to the boiler gas train connection must comply with NFPA54, local codes, and
utility requirements as a minimum. Only gas approved fittings, valves, or pipe should be used. Standard
industry practice for gas piping is normally Schedule 40 black iron pipe and fittings.
For proper operation of a single unit or a multiple unit installation, we recommend that the gas pipe sizing be
sized to allow no more than 0.3" w.c. pressure drop from the source (gas header or utility meter) to the final
unit location. The gas supplier (utility) should be consulted to confirm that sufficient volume and normal pres-
sure are provided to the building at the discharge side of the gas meter or supply pipe.
For installation of a new boiler into an existing building, gas pressure should be measured with a manometer
to ensure sufficient pressure is available. A survey of all connected gas using devices should be made. If
appliances other than the boiler or boilers are connected to the gas supply line, then a determination must be
made of how much gas flow volume (cubic feet per hour) will be demanded at one time and the pressure
drop requirement when all appliances are firing.
The total length of gas piping and all fittings must be considered when sizing the gas piping. See the follow-
ing tables to determine required pipe size. Do not automatically size the supply piping the same size as
the boiler gas train connection. Pipe size will be relative to the pressure available, total length of pip-
750-452 15
Firetube Installation - Steam
FUEL SYSTEM
ing and volume capacity of the selected pipe size. The following tables can be used as a minimum guide-
line.
Table 2 shows capacity of a natural gas line for a given initial pressure with a 5% pressure drop. For exam-
ple, consider a 500 hp boiler, which requires 20,925 ft3 / hr. A 5 psi initial pressure is available for 100 ft of
pipe. To find the correct pipe size, go to the line for initial gas pressure reading 5 pounds. Now move to the
right, until a number larger than 20,925 appears. In this case, the first greater number is 30,500. The number
at the top of that column shows the appropriate pipe size, in this case 4". Table 2 assumes gas at 60°F, 1000
Btu/ft3, and a specific gravity of 0.619.
To substitute a 300 ft pipe length in the above example, find the multiplier for 300 ft at the bottom of the table.
The pipe size will be the first column where the multiplier (.577) times the capacity shown is greater than
20,925 ft3 / hr. Since .577 x 55,400 = 31,965.8, 5” is the appropriate pipe size.
16 750-452
Firetube Installation - Steam
FUEL SYSTEM
Refer to the Boiler Book for gas pressure requirements at the gas train inlet.
750-452 17
Firetube Installation - Steam
FUEL SYSTEM
NOZZLE AIR
AIR STRAINER PRESSURE GAUGE
MANIFOLD OIL BURNER NOZZLE
BLOCK
LUBE OIL
OIL METERING
VALVE
OIL MODULATING
CAM
OIL RETURN
BACK PRESSURE ORIFICE
OIL RELIEF
VALVE
FUEL OIL
RETURN
FUEL OIL VACUUM
STRAINER CHECK GAUGE
VALVE
OIL SUPPLY FUEL OIL
PRESSURE SUPPLY PUMP
GAUGE SHUTOFF
PRIMING
TEE VALVE
FUEL
OIL
INLET
NOT SUPPLIED
FUEL OIL BY CLEAVER BROOKS
STRAINER
18 750-452
Firetube Installation - Steam
WATER REQUIREMENTS
6 - WATER REQUIREMENTS
Feed Pump Operation
Before turning on the pump motor be certain that all valves in the water feed line are open to prevent possi-
ble damage to the feed pump mechanism. After opening the valves, momentarily energize the feed pump
motor to establish correct pump rotation. With the correct rotation established, close the boiler feed pump
entrance switch. The pump should shut down when the water level reaches the proper level.
Feedwater pumps must have adequate capacity to maintain required water level under all operating condi-
tions. Check the feedwater pumps periodically and maintain as necessary to prevent unexpected break-
downs.
NOTE: Prior to operating the pump, carefully check the alignment of the flexible coupling, if one is used. A prop-
erly aligned coupling will last a long time and provide trouble-free mechanical operation.
NOTE: In the event that water column isolation valves are provided, it must be established that the valves are
open and sealed or locked in the open position. If the valves are installed, it is illegal to operate the boiler with
closed or unsealed open valves.
! Warning
The isolation valves and the water column piping must be locked open during operation. Failure to do so may
result in a low water condition. Failure to follow these instructions could result in serious injury or death.
5 1
3
6 ITEM DESCRIPTION
2
1 Globe Valve
2 Check Valve
3 Gate Valve
4 Globe Valve
5 Feedwater Valve
6 Strainer
4 3
750-452 19
Firetube Installation - Steam
WATER TREATMENT
7 - WATER TREATMENT
To protect the integrity of the boiler and ensure it continues to produce good steam quality, it is important to
properly treat the feedwater, or the water going into the boiler. Close attention to water quality will pay divi-
dends in the form of greater efficiency, improved performance, longer life, less downtime, and prevention of
costly repairs. The water used to fill the boiler or to make up for system losses should be free of dissolved
oxygen, corrosive gases, sediments, or other contaminants and should be at a minimum temperature of 70
degrees Fahrenheit.
Refer to the boiler startup and maintenance manuals for additional information regarding boil out, temporary
service, and water treatment.
The water treatment program should be developed in consultation with a qualified water treatment specialist.
An effective strategy will:
• prevent deposits on boiler surfaces that weaken metal and cause heat transfer losses,
• prevent oxygen corrosion, which causes pitting of boiler tubes and rust deposits,
• prevent low pH (below 9 causes corrosion), and
• prevent steam condensate contamination.
Recommended Guidelines
General guidelines to prevent corrosion and scaling for applications up to 300 psi are as follows:
For higher pressures contact CB. In all cases, due to the variety of factors which may influence water treat-
ment decisions, it is essential to obtain the services of a water treatment specialist.
20 750-452
Firetube Installation - Steam
INSTALLATION CHECKLIST
8 - INSTALLATION CHECKLIST
The following checklist is provided as a means to ensure that the boiler is ready for its initial start-up. The list
includes items that we feel, if not completed, cause delays in start-up. Prior to requesting a scheduled start-
up from your local Cleaver-Brooks authorized service representative, the installation must be completed and
all items checked off. A copy of this checklist could be copied and sent to the start-up representative for their
records and use in scheduling.
A. GENERAL
Yes No
_______ _______ 1. Are the boiler, burner, trim and controls in good operating condition? If not, note items that require
attention:
_______ _______ 2. Is the burner fuel and pilot supply properly installed?
_______ _______ 3. Is the boiler level?
_______ _______ 4. Where required, will qualified boiler operators be present for start-up?
_______ _______ 5. Will operating personnel be available for training during start-up?
_______ _______ 6. Will a person be available whenever needed to assist the service technician with miscellaneous
tasks in the boiler room?
_______ _______ 7. A full capacity load (sufficient for high fire fuel/air ratio adjustment) will be required for complete
burner adjustment. Can this load be absorbed by the system, and have provisions been made to
put a full load on the boiler during start-up?
B. BOILER
Yes No
_______ _______ 1. Are the boiler, burner, and auxiliary equipment installed in accordance with the manufacturer's and
insurer's requirements, and applicable insurance and regulatory codes?
_______ _______ 2. Has all system piping to and from the boiler been completed?
_______ _______ 3. Is the safety relief valve(s) properly installed?
_______ _______ 4. Is the safety relief valve discharge piping properly installed with no weight or strain on the
valve(s)?
_______ _______ 5. Are the boiler drain valve(s) or bottom blowoff valves installed properly?
_______ _______ 6. Are boiler drain or bottom blowoff valves and relief valves piped to a safe discharge, and are the
drain lines installed in accordance with all applicable regulatory codes?
_______ _______ 9. If supplied, has the stack thermometer been installed?
_______ _______ 10. Has the breeching/stack been properly installed?
_______ _______ 11. Has the source of combustion air been verified and properly sized?
_______ _______ 12. Have all shipped loose items been accounted for and installed?
750-452 21
Firetube Installation - Steam
INSTALLATION CHECKLIST
C. ELECTRICAL
Yes No
_______ _______ 1. Is the available power supply (voltage, phase, and hertz) correct per the burner data plate and wiring
diagram information?
_______ _______ 2. Have all electrical connections been made for the boiler, burner, and all auxiliary equipment?
_______ _______ 3. Have emergency and safety devices been installed in accordance with regulatory codes?
_______ _______ 4. Have all boiler field-wired connections been made according to the wiring diagram supplied by
Cleaver-Brooks for the particular installation?
_______ _______ 5. Is the equipment properly grounded to earth ground?
D. WATER
Yes No
_______ _______ 1. Have the make-up water system and pressure regulating valve been connected and are they opera-
ble?
_______ _______ 2. Have the boiler and system been filled with properly treated water at a minimum of 70 degrees Fahr-
enheit (21.1 Celsius)?
_______ _______ 3. Have the boiler and system been pressure tested to check for leaks?
_______ _______ 4. Has the system piping been flushed and cleaned or will this be accomplished during start-up?
E. GAS
Yes No
_______ _______ 1. Have all gas lines been pressure tested according to local codes, then purged of air?
_______ _______ 2. Is gas pressure and volume sufficient for the boiler(s) at maximum firing rate as stated on the burner
nameplate?
_______ _______ 3. Are gas pressure gauges installed and are they indicating proper gas pressure upstream of the boiler
mounted gas regulator?
_______ _______ 4. Are gas vents including vent valves, properly piped to a point of safe discharge?
_______ _______ 5. Has insurance inspection, if required, been completed?
_______ _______ 6. If upstream gas pressure exceeds 5 psig (34.5 kpa), have gas pressure relief valves been installed?
E. OIL
Yes No
_______ _______ 1. Has the oil supply line been pressure tested?
_______ _______ 2. Have proper min/max pressures to the CB oil pump been verified?
_______ _______ 3. Is the supply line sized for twice the maximum rated capacity of the burner?
_______ _______ 4. Have the fuel oil tank outlet valves been properly installed?
_______ _______ 5. Have the oil system shutoff valves, strainer, and vacuum gauge been properly installed?
_______ _______ 6. Is a return line piped back to the oil tank?
22 750-452
Firetube Installation - Steam