Record no:
INSPECTION AND TEST RECORD
Description : Contract no.: Sheet:
INTERTRIP & INTERLOCK TEST 1
Customer : Customer ref.: Cont:
HQC– MAADEN PHOSPHATE PROJECT 2
Site : Drawing ref.: Project no.:
SUBSTATION : 31

1. GENERAL DATA AND INFORMATION

Designation No: 239PD-SWB-201-F11 TO HANDWA INCOMER-1

2. MECHANICAL CHECK AND VISUAL INSPECTION


ITEM DESCRIPTION CHECKED
1 Inspect for physical, electrical, and mechanical condition. OK
2 Inspect all doors, panels, and sections for paint, dents, scratches and missing hardware. OK
3 Check tightness of all connection. OK
4 Check Ferrules. OK
5 Check Apparatus list. OK
6 Verify proper operation. OK
7 Inspect all mechanical indicating devices for proper operation. OK
8 Test all electrical and mechanical interlock systems for proper operation and sequencing. OK

3. ELECTRICAL TEST

1) INTERLOCK FROM HV

STATUS
FUNCTION CLOSE
DESCRIPTION CONDITION TICK YES OR NO IF REMARKS
BLOCK/PERMISSE
VERIFIED
All Protections are
1 Downstream ISO Q1 CLS & CB Q0 normal, ISO Q1 is DOWNSTREAM CB Q0 Yes No OK
OPEN Open & & CB Q0 is cannot be Closed
closed
All Protections are
2 DOWNSTREAM ISO Q1 CLS & normal, ISO Q1 is DOWNSTREAM CB Q0 Yes No OK
CB Q0 OPEN Closed & & CB Q0 is cannot be Closed
Open
All Protections are
3 DOWNSTREAM ISO Q1 CLS & normal, ISO Q1 is DOWNSTREAM CB Q0 Yes No OK
CB Q0 OPEN Closed & CB Q0 is can be Closed
Closed
HV Protn Trip , ISO
4 DOWNSTREAM ISO Q1 CLS & DOWNSTREAM CB Q0 Yes No OK
Q1 is closed & CB Q0
CB Q0 OPEN CLOSE BLOCKED
is open
HV ISO Q1 is Open
5 DOWNSTREAM ISO Q1 OPEN & OR Close & E/S Q5 is DOWNSTREAM CB Q0 Yes No OK
ES Q5-OPEN open OR Close & CB can be Closed
Q0 is Open OR close

TESTED BY :ABB WITNESSED BY: SNC REVIEWED BY: MAADEN REP


JEBA JOSEPH/RONALD BASE M.A SALEEM JOEY MIRAN/SAM SALMANZADEH
Test equipment used: FREJA 300, MULTIMETER Designation no.: Date :
239PD-SWB-201-F11 20 SEP 2016

SWITCHGEAR Page 1 of 2
ABB
Record no:
INSPECTION AND TEST RECORD
Description : Contract no.: Sheet:
INTERTRIP & INTERLOCK TEST 2
Customer : Customer ref.: Cont:
HQC– MAADEN PHOSPHATE PROJECT ----
Site : Drawing ref.: Project no.:
SUBSTATION : 31

6 DOWNSTREAM ISO Yes No OK


DOWNSTREAM ISO Q1-OPEN HV E/S Q5 is open
Q1 can be closed

7 DOWNSTREAM ISO Yes No OK


DOWNSTREAM ISO Q1-OPEN HV E/S Q5 is closed
Q1 can not be closed

8 DOWNSTREAM E/S Q5 Yes No OK


DOWNSTREAM ES Q5-OPEN HV ISO Q1 is open
can be closed

9 DOWNSTREAM E/S Q5 Yes No OK


DOWNSTREAM ES Q5-OPEN HV ISO Q1 is closed
can not be closed
2) INTERLOCK FROM DOWNSTREAM

1 HV ISO Q1 IS CLS & CB Q0 IS DOWNSTREAM BF HV CB Q0 can not be Yes No OK


OPEN TRIP closed

2 DOWNSTREAM E/S HV ISO Q1 can be Yes No OK


HV ISO Q1-OPEN
Q5 open closed

3 DOWNSTREAM E/S HV ISO Q1 can not be Yes No OK


HV ISO Q1-OPEN
Q5 closed closed

4 DOWNSTREAM ISO Yes No OK


HV E/S Q5-OPEN HV E/S Q5 can be closed
Q1 is open

5 DOWNSTREAM ISO HV E/S Q5 can not be Yes No OK


HV E/S Q5-OPEN
Q1 is closed closed

3) INTERTRIP FROM HV TO DOWNSTREAM


HV ISO Q1 closed, DOWNSTREAM CB Q0
1 DOWNSTREAM CB Q0 is closed & Yes No OK
CB Q0 closed & CB TRIP
ISO Q1 is closed
Q0 open
DOWNSTREAM CB Q0 is closed & DOWNSTREAM CB Q0
2 HV Prot. trip Yes No OK
ISO Q1 is closed TRIP
DOWNSTREAM CB Q0 is closed & DOWNSTREAM CB
3 HV Prot. BF trip Yes No OK
ISO Q1 is closed Q0 TRIP
HV ISO Q1 closed, DOWNSTREAM CB Q0
4 DOWNSTREAM CB Q0 is Closed Yes No OK
CB Q0 Closed & Can not be TRIP
& ISO Q1 is Open
Intertrip

4) INTERTRIP FROM DOWNSTREAM TO HV


STATUS
DESCRIPTION CONDITION FUNCTION TICK YES OR NO IF REMARKS
VERIFIED
1 HV ISO Q1 IS CLS & CB Q0 IS DOWNSTREAM Protn INTER TRIP PROTN &HV Yes No OK
CLOSED trip CB Q0 trip

2 HV ISO Q1 IS CLS & CB Q0 IS DOWNSTREAM BF INTER TRIP PROT &HV Yes No OK


CLOSED TRIP CB Q0 trip

TESTED BY :ABB WITNESSED BY: SNC REVIEWED BY: MAADEN REP


JEBA JOSEPH/RONALD BASE M.A SALEEM JOEY MIRAN/SAM SALMANZADEH
Test equipment used: FREJA 300,MULTIMETER Designation no.: Date :
239PD-SWB-201-F11 20 SEP 2016