INSPECTION AND TEST RECORD
Description : Contract no.: Sheet:
INTERTRIP & INTERLOCK TEST 1
Customer : Customer ref.: Cont:
HQC– MAADEN PHOSPHATE PROJECT 2
Site : Drawing ref.: Project no.:
SUBSTATION : 31
3. ELECTRICAL TEST
1) INTERLOCK FROM HV
STATUS
FUNCTION CLOSE
DESCRIPTION CONDITION TICK YES OR NO IF REMARKS
BLOCK/PERMISSE
VERIFIED
All Protections are
1 Downstream ISO Q1 CLS & CB Q0 normal, ISO Q1 is DOWNSTREAM CB Q0 Yes No OK
OPEN Open & & CB Q0 is cannot be Closed
closed
All Protections are
2 DOWNSTREAM ISO Q1 CLS & normal, ISO Q1 is DOWNSTREAM CB Q0 Yes No OK
CB Q0 OPEN Closed & & CB Q0 is cannot be Closed
Open
All Protections are
3 DOWNSTREAM ISO Q1 CLS & normal, ISO Q1 is DOWNSTREAM CB Q0 Yes No OK
CB Q0 OPEN Closed & CB Q0 is can be Closed
Closed
HV Protn Trip , ISO
4 DOWNSTREAM ISO Q1 CLS & DOWNSTREAM CB Q0 Yes No OK
Q1 is closed & CB Q0
CB Q0 OPEN CLOSE BLOCKED
is open
HV ISO Q1 is Open
5 DOWNSTREAM ISO Q1 OPEN & OR Close & E/S Q5 is DOWNSTREAM CB Q0 Yes No OK
ES Q5-OPEN open OR Close & CB can be Closed
Q0 is Open OR close
SWITCHGEAR Page 1 of 2
ABB
Record no:
INSPECTION AND TEST RECORD
Description : Contract no.: Sheet:
INTERTRIP & INTERLOCK TEST 2
Customer : Customer ref.: Cont:
HQC– MAADEN PHOSPHATE PROJECT ----
Site : Drawing ref.: Project no.:
SUBSTATION : 31