You are on page 1of 1

UPS SIZING CALCULATION

PROJECT: XXXXXX
ARCHITECT: LOGO
ELEC. CONSULTANT:
UPS SIZING CALCULATION
REV: R____ DATE:
SR NO DESCRIPTION UNIT QTY. UNIT LOAD CONNECTED LOAD
A. SELECTION OF SIZE OF UPS WORKSTATIONS
1) Workstations NO 50 150.00 Watt 7.50 KW

5 200.00 Watt 1.00 KW

2) Others (Printer / Ploter etc) NO 5 150.00 Watt 0.75 KW

3) Server Load NO 1 2500.00 Watt 2.50 KW

TOTAL 11.75 KW

SELECTION OF SIZE OF UPS

KVA Rating = K.W./p.f. PF 80% 14.69 KVA

SIZE OF UPS CONSIDERING LOADING Load Factor 80% 18.36 KVA

SAY 19.00 KVA

HENCE SELECT __2__ NO. 10KVA UPS FOR __100_% LOAD