Professional Documents
Culture Documents
4.3 Controls
• 4.3.1.1 Visibility at control positions Any control position
shall allow the operator to see the resulting movements.
Control System
• 4.3.1.2 Unlocking or Enabling device.
Control Location
4.3 Controls
4.3 Controls
4.3.8 Platform level adjustment.
Control system
4.3 Controls
4.3.9 Automatic or programmed operation
• Automatic or programmed operation performed with the
primary function joystick, lever or switch released is
permissible provided a separate control is continuously
activated and release interrupts the movement. The use of an
unlocking or enabling device shall precede the use of the
control itself.
• 4.5 Stability
• 1-1/2 rated load capacity (platform and material
handling if equipped) on level ground
• 1-1/3 rated capacity on 5 degree slope
• Lightest configuration
• Outriggers/No outriggers
Slope indicators
• 4.5.4 Slope Indicator. An indicator(s) shall be provided
that is visible to the operator during set up to show
whether the aerial device is positioned within limits
permitted by the manufacturer. The allowable limits shall
be shown on the unit and in the manual. For units
designed for mobile operation, such an indicator(s) shall
be supplied in the cab.
• Larger slopes
Slopes greater than 5 degrees
• No wording in ANSI
• Limitations
• Requirements
Stability
• Category A Barehand
• Category B Hot Sticks
• Category C Gloving
• Category D Not Gloving
• Category E Low Voltage
Insulating Aerial Device Categories
Category A
• Upper boom is primary insulation
• All conductive components are bonded at the boom tip.
• Lower test electrode system
• Gradient Shield and Corona Rings above 138kV
• Metal platforms or conductive liners
Insulating Aerial Device Categories
Category A Atmospheric Vent Valves
• Importance
• Accessibility
Insulating Aerial Device Categories
Category B
• Upper boom is secondary insulation
• Distance/MAD is primary insulation
• Lower test electrode system
• Corona Rings and Gradient Shield only if need to pass dielectric test
Insulating Aerial Device Categories
Category C.
• Boom is secondary protection
• Gloves and Cover up are primary insulation
• These aerial devices are designed for gloving work and tool methods at
voltages of 46kV and below. They shall meet the requirements of Section
4.10
3. Definitions
Category A & B
• These units may be designed and configured
for gloving work provided they meet the
requirements of Section 4.10.
Insulating Aerial Device Categories
Category D.
• Aerial devices which are designed and manufactured for
work in which the insulating system is not considered as
primary insulation, but secondary. They do not need to
meet the requirements of Section 4.10 as these aerial
devices are NOT designed for gloving work methods.
They are rated at voltages of 46kV and below.
Insulating Aerial Device Categories
Category E
• Aerial devices which are designed for lower voltage
applications. Insulation requirements of the standard
may be accomplished through guarding or isolation
methods. These units are designed and manufactured
for work in which the unit is not considered as primary
insulation, but secondary. They are rated at voltages of
20kV, 5kV, 1kV and below.
Highly Resistive Controls
• 5.4.2.6 Confirmation Test of Upper Control
Components with High Electrical Resistance. Upper
controls that incorporate components for their
electrical resistance shall be tested to ensure resistance
by testing them at 40 kV ac for 3 minutes with a
maximum allowable current of 400 microamperes
(Figure 6).
Rubber Glove Classes
Meaning of Control Colors?
• ISO-Grip – Green
• Secondary Controls – Blue
• Emergency Stop - Red
Secondary lanyard protection
• Dielectric protection
• 7200 lb testing
Lanyard attachment
• 4.9.4 Anchorage(s) for Personal Fall Protection
• 4.9.4.1 Location(Boom tip, platform or platform
mounting)
• 4.9.4.2 Markings
Lanyard attachment
• 4.9.4 Anchorage(s) for Personal Fall Protection
• 4.9.4.3 Strength Requirement(3600 Lbs/person)
Lanyard attachment
• 7.6 Ingress/Egress
•
• 7.6.1 Steps/ Ladders. Distance between the ground or lower platform surface
to the top surface of the first step should not exceed 27 inches where possible.
Distance between the top surface of steps or rungs should not exceed 16 inches
where possible. Each step or rung with should have a minimum width of 6
inches for placement of one foot or 12 inches for placement of two feet and
minimum rung diameter of 1 inch.
•
• 7.6.2 Access opening/passage. Access opening/passage should have a
minimum width of 18 inches and minimum opening height of 30 inches.
•
• 7.6.3 Three Point Support. Steps or ladders whose inclined angle from
horizontal is greater then 50 degrees should incorporate supports which would
permit a person to use simultaneously two hands and one foot or two feet and
one hand for support while ascending or descending.
Section 7
Section 9 Users
• 9.4 Application. The employer and authorized
operator(s) shall insure that the aerial device is used only
for intended applications as defined in the operating
manual and that all recognized safety practices are
observed. The aerial device shall not be operated while
the mobile unit is positioned on trucks, trailers, railway
cars, floating vessels, scaffolds, or similar equipment
unless the application is approved in writing by the
manufacturer or a qualified person.
Minimize preventative
maintenance
No external components
- Protected from damage
Minimal impact to
scheduled maintenance
Load Indication
Green, Yellow, Red
Overload Indication
Blue
m
ar
- Chirp = 100 – 110%
Al
- Solid Tone = >110%
- Chirp duration increases
with load %
• Thank you!