INSTRUCTIONS
Line of Sight
Infrared Hydrocarbon Gas Detector
Model AutroPath HC800
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 1
OPERATION overview detectable gases
standard output
The AutroPath HC800 receiver module provides an analog
4–20 mA signal output. HART and RS-485 Modbus serial
2M @ 50% LFL = 1 LFL-M
communication are available at either module. The 4–20
mA current loop corresponding to 0–5 LFL-meters is
provided for connection to analog input devices such
as gas controllers, logic controllers, or distributed
control systems (DCS). To convert the mA reading to
10M @ 10% LFL = 1 LFL-M
LFL-meters, use the following formula:
mA Reading –4
A2665
X 5 = LFL-Meters
16
HC800 OUTPUT EQUALS 1 LFL-M IN ALL THREE SCENARIOS
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 2
Table 1—LFL-m to PPM-m Conversion
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 3
optional relays 3. Synchronized LEDs on each device can signal a
common system status condition. Without the link,
The AutroPath HC800 can be furnished with factory
the transmitter is unable to signal alarm status.
installed relays — two programmable alarm relay
outputs and one fault relay output. All relays are sealed
4. Transmitter variables can be configured via con-
and provide form C (NO/NC) contacts. The high and
nection to the receiver. Configurable transmitter
low alarm relays are programmable, and can be set
variables include lamp power and heater settings.
for latching / non-latching operation, and a normally
energized / de-energized coil (see Table 3). The low
Note
alarm cannot be set above the high alarm threshold.
Alarm setpoints in the receiver cannot be changed
Alarm configuration can be done with the HART or
from the transmitter.
Modbus interface. The onboard multi-color LEDs
indicate a LOW alarm condition via a flashing red
5. The communication link provides the ability to
color, and a HIGH alarm condition via a steady red
initiate Calibration from either the transmitter or
color. Latched alarms can be reset using the internal
receiver.
magnetic switch, an external switch connected to the
calibration line terminal, a HART Field Communicator,
For retrofit applications where an inter-connecting wire
or Modbus communication. A short-duration magnetic
is not available or possible, the system can operate
switch activation of one second will reset latched
without the link. If the link is not connected, the system
alarms. Holding the magnetic switch closed for a three
will not indicate a “link fault.”
second duration will start the calibration sequence.
A “link fault” feature can be enabled (using a HART
When the optional relays are ordered, the AutroPath
handheld or Modbus device), which will indicate a fault
HC800 receiver is certified for Ex d operation.
if the link is broken. The “link fault” can only be detected
and annunciated by the receiver.
optional communication link
note
By connecting the transmitter and receiver via a three-
The default setting for the ”link fault” feature is
wire shielded cable, an optional “communication link”
Disabled.
can be created between the two devices.
NOTE
The communication link offers the following advantages:
All third-party performance and hazardous
location approvals apply with and without the
1. Single point system diagnostics – The link offers
communication link connected.
the ability to view device variables of the receiver
while connected to the transmitter, or vice versa
(using a HART handheld or Modbus device). history logs
These variables include signal strength, status,
Non-volatile memory is provided in the receiver to save
and configuration parameters such as alarm set
a record of the 100 most recent calibrations and 1000
points, heater settings, gas type, etc.
most recent alarm/fault events. Operating temperature
and voltage of the receiver are also recorded with
2. Dynamic lamp power – The link enables the sys-
each event log. A real time clock is provided for time
tem to optimize lamp power per the application.
stamping events. This information is accessible using
This optimization only happens during the zero
HART or Modbus communication.
calibration process.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 4
operation
reset criteria have been met and will change to flashing Figure 2—Location of Internal Magnetic Switch
on Receiver Module
yellow (5 Hz) when the calibration period has been met
(>3 seconds, <30 seconds). The device will reset if the FACTORY RESET COMMAND
switch is released during a flashing green LED and
will enter calibration if the switch is released during a The AutroPath HC800 provides a factory reset
flashing yellow LED. command that sets all user configurable parameters
back to their default settings. This command can be
accessed via HART or Modbus communication.
Module Identification
See Figure 3 for identification of the transmitter and receiver
Operating Modes
modules. The functional and electrical characteristic
differences of the two devices are described in Table 2. The AutroPath HC800 has three operating modes:
warm-up, normal (measuring / monitoring), and
calibrate.
Table 2—Functional and Electrical Comparison of Transmitter and Receiver
Functional Description Contains a xenon flash lamp, and Contains opto-electronics, signal processing, output
generates optical energy to enable drivers, and diagnostic electronics.
hydrocarbon detection.
Electrical Connections Connections for power, HART, RS-485, Connections for power, 4-20 mA, HART, RS-485, relay
Communication Link. contacts (optional), Communication Link, and calibration/
reset.
Onboard LED Indicators Indicates device status. Indicates normal, alarm, fault, and calibration status.
Green indicates normal operation. Green indicates normal operation. Blinking red indicates
Yellow indicates fault condition. low gas alarm condition.
When the Communication Link is used, Steady red indicates high gas alarm condition.
the transmitter LED operation matches Yellow indicates system fault. See Tables 4 and 5 for
receiver LED operation, including alarm details.
status. LED operation for fault status is non-latching. LED
operation for gas alarms is configurable for latching/non-
latching.
Magnetic Calibration Switch N/A Momentary activation provides reset function for latched
(See Figure 2 for switch alarm outputs. Activation for longer than 3 seconds will
location.) initiate zero calibration.
Adjustable Settings Programmable IR signal intensity and Factory calibrated for methane, propane, and butane, 0-5
heater operation. HART or Modbus LFL-meters full scale. Default gas depends on model.
communication is required to change the See Table 3 for receiver factory default settings. HART or
factory default settings. Modbus communication is required to change the factory
default settings.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 5
A2647 TRANSMITTER RECEIVER
Warm-up Normal
Warm-up mode is entered upon application of 24 Vdc After warm-up mode is completed, the device
operating power. During warm-up, the 0-20 mA current automatically enters the Normal mode, and all analog
loop output will indicate warm-up, the indicating LED and alarm outputs are enabled. The AutroPath HC800
is yellow, and the alarm outputs are disabled. The modules must be properly aligned before normal
warm-up time typically lasts from 15 to 150 seconds, operation is attained. See “Installation” section for
depending upon alignment accuracy. details.
Calibrate
Table 3—Factory Default Settings
After alignment is completed, zero calibration is
required. Span calibration of the AutroPath HC800 is
Default Configurable Options performed at the factory; however, the user has the
option to verify proper calibration if necessary. It is
Gas Type Methane Methane, Propane, Butane recommended that the zero calibration procedure be
performed annually. Refer to the “Calibration” section
Low Alarm
0.5 to 4.5 in this manual for details.
Threshold 1
(10% to 90%)
(LFL-M)
High Alarm 4-20 mA Current Loop Output
0.5 to 4.5
Threshold 3
(10% to 90%) The AutroPath HC800 provides a linear current loop
(LFL-M)
output that is proportional to the detected gas level.
High & Low Fault and calibration status are also indicated by this
Non-Latching, Latching/Non-Latching,
Alarm Relays
De-Energized Energized/De-Energized output.
(Optional)
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 6
HEATER CONTROL
Table 5—Typical AutroPath HC800 Window Temperature Rise (Degrees C)
The AutroPath HC800 optics in both transmitter for Various Heater Settings and Ambient Temperatures
and receiver are heated to provide moisture and
ice resistance. These heaters are microprocessor
controlled and can be configured to operate in the AMBIENT TEMPERATURE
AutroPath HC800 Window
following modes: Temperature Rise (C) -55°C -40°C 0°C 25°C
– Always On Receiver 5.1 5.3 4.5 3.0
30%
Heater
– Always Off Transmitter 4.2 4.1 4.2 3.0
Setting
– Smart Mode (default) 50% Receiver 7.2 6.8 7.0 5.0
Heater
1) Heaters maintain a user programmable temperature Setting Transmitter 5.3 5.2 5.3 3.6
set point (default = 50°C).
70% Receiver 9.8 9.1 7.5 7.1
2) Heaters increase to full power when signal strength Heater
is degraded due to moisture or condensation on the Setting Transmitter 7.8 6.6 5.1 3.8
window, or any obscuration faults are active.
100% Receiver 15.8 14.9 8.6 7.3
3) Heaters shut off when the input voltage drops below Heater
Setting Transmitter 13.3 10.6 5.9 4.5
a user defined level (default = 18.5 Vdc).
note
Higher heater settings reduce or eliminate
moisture buildup on the window, thereby
providing optimum detector performance.
Detection
Warm up 1.0 1.0 De-energized Disabled Yellow - Solid
Disabled
Zero
1.0 2.2 Configuration Energized Disabled Yellow - Flashing @ 5 Hz
Calibration
Note: When the Communication Link is used, the transmitter LED operation matches receiver LED operation, including alarm status.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 7
Table 6—AutroPath HC800 Receiver Fault Conditions
Detection
RAM Fault 1.0 1.2 De-energized Disabled Yellow - Solid
Disabled
Detection
Data Flash Fault 1.0 1.2 De-energized Disabled Yellow - Solid
Disabled
Detection
Flash CRC Fault 1.0 1.2 De-energized Disabled Yellow - Solid
Disabled
Detection
AFE Fault 1.0 1.2 De-energized Disabled Yellow - Solid
Disabled
Detection
Internal Voltage Fault 1.0 1.2 De-energized Disabled Yellow - Solid
Disabled
Detection
Active Signal Saturated 1.0 1.2 De-energized Disabled Yellow - Solid
Disabled
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 8
Table 6—AutroPath HC800 Receiver Fault Conditions (Continued)
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 9
status and Fault Indication Specifications
Status and fault conditions are indicated using the 4–20 operating Voltage (Both Modules)—
mA analog signal output. Signaling modes include two 24 Vdc nominal. Operating range is 18 to 30 Vdc.
predefined modes, and a user defined mode for third Ripple cannot exceed 0.5 volts P-P.
party compatibility. The user defined mode allows users
to define a mA output level (range 1.0 - 3.6 mA) for Power Consumption—
each of the three status / fault categories: configuration, Power Consumption (Watts)
advisory, and detection disabled. Refer to Table 4 for Transmitter Receiver
status indications and Table 5 for fault conditions. Maximum Maximum
Status and fault indication configuration options can Total Unit,
be changed via HART or Modbus communication. No Heaters 6.5 2.6
or Relays
(Refer to the “Troubleshooting” section for additional
information regarding fault identification.) 30% Heater Only 1.4 1.1
TRANSMITTER LAMP—
Xenon flashlamp, field-replaceable module
(10 yr warranty).
Warmup Time—
15 seconds minimum, 150 seconds maximum from
power-up, depending upon alignment accuracy.
Current Output—
Linear 4–20 mA (isolated/non-isolated) rated at 600
ohms maximum loop resistance @ 24 Vdc operating
voltage, with the ability to go below 4 mA to indicate a
fault condition.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 10
RElay outputS (optional)— DEtEction RanGE—
Available on Ex d approved models only. Short Range 5-60 meters
Long Range 30-120 meters.
alaRM RElayS— Note: It may be necessary to add the aperture (supplied)
Low and High to the transmitter when operating at the lower 10-15
Form C Type (NO/NC). De-Energized during Normal meters of each range.
mode, Energized on Alarm.
Contact Rating: 3 amperes at 30 Vdc.
Programmable for Latching or Non-Latching Operation. MiSaliGnMEnt tolERancE—
Low Alarm: 0.5 to 4.5 LFL-meters ±0.8 degree minimum (~±56cm @ 40m; ~±168cm @
(default = 1 LFL-meters, Non-latching). 120m). The AutroPath HC800 is third party verified
High Alarm: 0.5 to 4.5 LFL-meters to maintain specified accuracy within the entire 0.8
(default = 3 LFL-meters, Non-latching). degree field of view for both Receiver and Transmitter.
Alarm relays are programmable using HART or Modbus Note: The receiver has a circular field of view. The
communication. transmitter has an oval shaped field of view with a
minimum 0.8 degree tolerance along the horizontal axis
CautIon and a minimum 1.5 degree tolerance along the vertical
When the AutroPath HC800 Gas Detector is axis (Manufacturer verified).
used in conjunction with an appropriate certifi ed
Control Unit and confi gured for a non-latching calibRation—
high alarm, the control unit must always latch and AutroPath HC800 systems are span calibrated for
require a deliberate manual action to clear a high methane, propane, and butane at the factory. Span
gas alarm. When used as a stand alone device, calibration in the field is not required.
the high alarm must always be programmed for
latching operation. Zero calibration is accomplished in the field by one of
the following methods:
Fault RElay— – On-board magnetic reed switch
Form C Type (NO/NC). – Modbus communication
Energized during Normal mode, De-Energized on – HART communication
Fault or loss of power. – External calibration switch.
Contact Rating: 3 amperes at 30 VDC.
Non-Latching Operation only — not programmable. RESponSE tiME—
Refer to the appropriate Approval/Certification
ViSual StatuS inDicatoR— Appendix for details.
LEDs – Transmitter:
Red = Low alarm, high alarm* accuRacy—
Green = Power on / OK Refer to the appropriate Approval/Certification
Yellow = Fault / warm-up / calibration*. Appendix for details. Accuracy specification applies
*Communication link required for low / high alarm and to full operating temperature, humidity, and pressure
calibration indication. ranges listed, unless noted otherwise.
LEDs – Receiver:
Red = Low alarm, high alarm NoTe
Green = Power on / OK Misalignment will cause the manufacturer stated
Yellow = Fault / warm-up / calibration. Accuracy limits to increase, but remain within the
limits of eN 60079-29-4 and IeC 60079-29-4.
See Tables 4 and 5 for details.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 11
Temperature Range— Wiring—
Operating: –55°C to +75°C (–67°F to +167°F) Field wiring screw terminals are UL/CSA rated for up
Relay version: –55°C to +65°C (–67°F to +149°F) to 14 AWG shielded wire, and are DIN/VDE rated for
2.5 mm2 wire. Screw terminal required torque range is
Storage: –55°C to +85°C (–67°F to +185°F)
3.5–4.4 lb.-in. (0.4-0.5 N•m).
Hazardous Locations: Refer to the appropriate The receiver can be wired using 3 or 4 wires. The
Approval/Certification transmitter requires two wires (power only). The use of
Appendix for correct ambient shielded wiring is recommended.
temperature range.
Field wiring for supply connection must be rated to
95°C (203°F).
HUMIDITY—
5 to 99% relative humidity; designed for outdoor
Certification—
applications.
For complete approval details, refer to the appropriate
Appendix:
operating pressure—
91.5 - 105.5 kPA non-compensated.
Measurement Range—
Appendix A- ATEX
0–5 LFL-meters.
Appendix B - IECEx
Note: A Negative Zero Drift fault is indicated at –9% of Appendix C - Additional Approvals
full scale.
Dimensions—
Interference resistance— See Figure 4 for dimensions of the transmitter and
Immune to sun and flare radiation, tested to Figure 5 for dimensions of the receiver.
800 ±50 W/m2 at ≥ 3° to optical axis and common
contaminants. Mounting & Alignment Bracket adjustment
range—
SELF-DIAGNOSTIC TEST— ±12 degrees from center, both vertical and horizontal.
Fail-Safe operation ensured by performing all critical
tests once per second. warranty—
5 year limited warranty.
Module Housing Material— 10 year warranty on IR source.
316 stainless steel (CF8M).
Shipping Weight—
Conduit Entry Options— Transmitter and receiver with mounting hardware:
3/4 inch NPT or M25, with two entries for transmitter and 85 pounds (38 kg)
four entries for receiver.
Replacement Transmitter: 23 lbs (10.4 kg)
Optics Protection— Replacement Receiver: 20 lbs (9 kg)
Microprocessor controlled heated optics mitigate Transmitter Electronics Module: 10.4 lbs (4.7 kg)
against ice and dew formation. Brow provides a degree Receiver Electronics Module: 7.8 lbs (3.6 kg)
of protection against windblown dirt and rain. See
“Mounting Instructions” for brow installation procedure.
Ingress Protection—
NEMA Type 4X certified,
IP66/67 (Manufacturer verified).
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 12
5.0 5.0
(12.7) (12.7)
5.0
5.0
(12.7)
(12.7)
10.8
(27.5)
10.8
(27.5)
16.1 14.3
(40.8) (36.3)
7.3
(18.5)
7.9
(20.1)
7.0 7.0
(17.8) (17.9)
7.5 8.1
A2659 (19.1) (20.6) A2660
Figure 4—Mounted Dimensions of AutroPath HC800 Transmitter Figure 5—Mounted Dimensions of AutroPath HC800 Receiver
in Inches (cm) in Inches (cm)
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 13
iMpoRtant SafEtY notES NoTe
The terminal compartment for AutroPath HC800
without relays is designed for either an increased
CautIon safety “e” termination or a fl ameproof “d”
The wiring procedures in this manual are intended termination of the supply cable. If a fl ameproof
to ensure proper functioning of the system under connection is chosen, then an ATeX certifi ed
normal conditions. However, because of the cable entry device must be used. The AutroPath
many variations in wiring codes and regulations, HC800 with relays requires ex d cable entry
total compliance to these ordinances cannot be devices only.
guaranteed. Be certain that all wiring complies
with the NeC as well as all local ordinances. If
in doubt, consult the authority having jurisdiction inStallation
before wiring the system. Installation must be
done by a properly trained person. IDentIFICAtIon oF VApor(S) to Be DeteCteD
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 14
Avoid installation in areas with obstructions such as System Mounting Elevation
steam vents and plumes, smoke stacks and chimneys, In all cases, the modules should be installed at the same
walkways and personnel areas, splash and sprayed elevation above grade to ensure that alignment capability
water, parking, loading, cranes, vehicle-related areas and foul weather performance are not compromised.
such as bus stops, road junctions, and vegetation such For detection of lighter than air vapors such as methane,
as trees, shrubs, grass etc. installation of modules at approximately 2 meters above
grade minimizes typical beam block conditions due to
Contact Autronica Fire and Security if guidance on human activities, while enabling satisfactory detection
optimum installation locations is required. Additional capability. For detection of heavier than air vapors,
guidance on the positioning of gas detectors for installation of detectors below the expected leakage source
optimum coverage is contained in BS6959 and other is generally recommended unless nuisance beam blocks
national codes. Consult these codes of practice when will occur at an unacceptable rate. In this case, identification
determining where detectors are to be located. and analysis of application specific conditions should be
completed to determine the optimum installation elevation.
Consideration of the following system location
guidelines is also recommended. Routine maintenance Sources of Heavy Contamination
is recommended after abnormal events. Avoid locations where high levels of contaminants will
persistently be blown onto the detector windows. Potential
Module Separation Distance sources of heavy contamination include generator / turbine
The transmitter and receiver modules must be installed exhausts, flare stacks, drilling equipment, process vents /
directly facing each other across the area to be chimneys, etc. If sources of heavy contamination cannot be
protected. Physical obstructions in the direct line of sight avoided, consider fitting extra shielding and/or providing
between the modules are not permitted. The overall good access for routine cleaning.
line of sight distance between the modules must not fall
outside the specified operating distance range (refer to LED Visibility
the “Specifications” section of this manual for details). Whenever possible, select a mounting orientation where
the status indication LED is visible to personnel within the
Multiple System Installations area.
If multiple AutroPath HC800 systems are to be installed,
ensure that each receiver can view only the intended The AutroPath HC800 provides the option to turn off
transmitter. For fence line applications, the recommended the Green LED in the Normal mode when no alarms or
order is Tx-Rx, Rx-Tx, Tx-Rx, etc. as shown in Figure 6. faults are occurring. When configured for OFF mode,
the green LED will turn OFF after a specified period of
For redundant systems, spacing between units should time. The default is 60 seconds, with a selectable range
be a minimum of 3 ft (1 meter) and the receiver should from 30 to 600 seconds.
be set back from the transmitter a minimum of 12 inches
(30 cm) as shown in Figure 7. Do NOT expect the LED to turn off immediately after
changing the setting. Also note that momentary closure
of the magnetic switch, fault clear, and alarm clear
will reset the OFF mode timer, and the green LED will
remain lit for the selected time delay period.
HC800 SYSTEMS
SEPARATED BY MINIMUM Tx
3 FEET (1 METER)
Rx
Tx Rx Rx Tx Tx Rx
LATERALLY
A2692
Figure 6—Proper Order of Modules for a Figure 7—HC800 Systems in Redundant Configuration
Multiple System Installation
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 15
Snow and Ice in Ambients Below –20°C Module Mounting Recommendations
The heated optics on both modules will melt snow or AutroPath HC800 modules must be affixed to a solid,
ice on the windows in ambient temperatures down to non-vibrating structure capable of supporting a minimum of
approximately –20°C. Below this temperature, snow 100 lbs (46 kg), located within the system’s rated separation
or ice blown onto the window will not be melted until distance.
the ambient temperature rises. If long term outdoor
operation in very cold climates is intended, extra A building wall, a heavy steel I-beam, or nearly any
shielding / covers are recommended to prevent type of masonry typically provides the most rigid
accumulation of snow and ice on the windows. mounting surface available. However, avoid the use of
wood structures or supports if the possibility of warping
Deluge and Flooding exists.
The modules are rated IP66/IP67 and will not be damaged
by occasional deluge or flooding. However, during such When using a vertical post, the post must be absolutely
an event, the unit will completely lose it’s IR signal and will stable and without vibration. Square stock pole is
enter the “Beam-Block / Fault” state. In addition, when recommended. Mounting height should not exceed 3
the deluge / flooding subsides, there is the possibility meters.
that contaminants will be left on the windows. Install the
modules away from areas prone to deluge or flooding. The post can be set into the ground or attached to
a secure surface. If a post is set into the ground, the
Areas Prone to Subsidence and Settling portion below grade should be set in concrete at least
Avoid installation of the modules in areas where 1 meter deep.
problems with subsidence, settling or thawing of
permafrost can occur or cause significant movement. IMPORTANT
If such locations cannot be avoided, the foundations In all cases, consider whether additional bracing or
of the mounting structure should be engineered to support is needed to ensure the structural integrity
minimize any angular movements between the receiver of the module installation. See Figure 8. Remember
and transmitter.” that accurate module alignment is essential for
proper performance of a line of sight gas detection
Areas Prone to Earthquakes system. Movement may have a detrimental effect
on alignment. This is especially true for installations
In the event of an earthquake, there is a chance that the with significant module separation distances.
modules will become misaligned with respect to each
other. As long as the modules do not suffer from direct Module mounting options include:
mechanical impact damage during an earthquake,
they should remain undamaged by such events. After • A vertical or horizontal post with a nominal outside
an earthquake, it is recommended that the system diameter of 4.5” (11.43 cm). Acceptable outside
alignment be checked. Anti-vibration mounts are diameter range is 4” to 4 5/8” (10.16 to 11.75 cm).
unlikely to be of any benefit and are not recommended. See Figure 8.
• For flat surface mounting, refer to Figure 10.
Misalignment by Accidental Impact
Locations where there is a significant likelihood of note
equipment, personnel or moving objects accidentally Anti-seize material (provided) must be applied
knocking the modules out of alignment should be to the U-bolt threads at the time of installation to
avoided where possible. If such locations cannot be prevent galling.
avoided, measures including improved mechanical
protection and warning notices should be considered. note
To ease installation and future removal, all
threaded covers, stopping plugs, and thread
adapters must be installed using thread lubricant.
See “Ordering Information” for part number —
avoid the use of silicone grease. For devices with
NPT threads, Teflon tape or thread seal lubricant
must be used for enhanced sealing capability. A
minimum torque of 20 foot-pounds is required to
maintain ingress protection. To maintain the IP or
NEMA ratings when using NPT stopping plugs,
one to three wraps of Teflon tape is required.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 16
3 METERS
MAXIMUM HEIGHT
IMMOVABLE
STRUCTURE
1 METER
OR BELOW
FROST LINE
A2666
Figure 8—Example of Bracing Added to Vertical Mounting Poles for Increased Robustness of AutroPath HC800 Installation
Figure 9—AutroPath HC800 Gas Detector Mounted to Vertical Post Figure 10—AutroPath HC800 Gas Detector Mounted to Flat Surface
(Refer to "Dimensions" in the “Specifications” section for mounting
plate hole spacing dimensions.)
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 17
RePLACING AN exIStING moDeL HC600 24 VDC PoweR SuPPLy RequIRemeNtS
wItH AN AutRoPAtH HC800
Calculate the total gas detection system power
Flat Surface Mount consumption rate in watts from cold start-up. Select
An optional adapter plate (part number 012718-003) is a power supply with adequate capability for the
available for converting an existing HC600 flat surface calculated load. Ensure that the selected power supply
mount to an AutroPath HC800 flat surface mount provides regulated and filtered 24 Vdc power for the
without drilling new holes. See Figure 11 for dimensions. entire system. If a back-up power system is required,
The mounted AutroPath HC800 will have the following a float-type battery charging system is recommended.
offsets compared to the HC600 detector (when looking If an existing source of 24 Vdc power is being utilized,
straight at the wall/beam). verify that system requirements are met.
Left/right = 0” NoTe
Up/down = 1 inch lower If disconnection of power is required, separate
In/out = 0.3” closer to the wall/beam for the AutroPath disconnect capability must be provided.
HC800.
wIRING CABLe RequIRemeNtS
Pole Mount
Always use proper cabling type and diameter for input
The AutroPath HC800 can be mounted to the same power as well as output signal wiring. 14 to 18 AWG
pole as the Model HC600 using U-bolts. The AutroPath (2.5 to 1.0 mm2) shielded stranded copper wire is
HC800 will have the following offsets compared to the recommended.
HC600 detector.
Left/right = 0” Always install a properly sized master power fuse or
breaker on the system power circuit.
Up/down = 0” if the top U-bolt for the AutroPath HC800
is mounted 1” lower than the top U-bolt of the HC600
NoTe
detector.
The use of shielded cable in conduit or shielded
In/out = 0.8” closer to the pole for the AutroPath HC800. armored cable is required for ATeX conformance.
In applications where the wiring is installed in
conduit, dedicated conduit is recommended.
Avoid low frequency, high voltage, and non-
6.0 signaling conductors to prevent nuisance eMI
(15.24)
0.5
problems.
(1.27) 5.0 4X 0.5
(12.7) (1.27)
CautIon
The use of proper conduit installation techniques,
2X 0.5
(1.27) breathers, glands, and seals is required to prevent
2X 5.0
water ingress and/or maintain the explosion-proof
(12.7)
rating.
2X 3/8-16 UNC THRU
WarnInG
It is required that each conduit plug or fi tting be
14.0 2X 13.0
wrench tightened to an appropriate installation
(35.6) (33.02)
torque and meet the minimum thread engagement
requirements per the applicable local standards,
codes and practices in order to retain the defi ned
ingress protection rating. All unused entries must
contain appropriately rated conduit plugs or
fi ttings. PTFe sealant (or equivalent) should be
4X 0.41 THRU used on NPT threads.
2X 0.5
B2668 (1.27)
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 18
power wiring size and maximum length AC voltage should not be switched directly using the
AutroPath HC800 relays. The use of an external relay
1. To ensure proper operation, AutroPath HC800
is required if AC voltage must be switched by the
power terminals and 4–20 mA terminals must
AutroPath HC800 relays. Note: External relay is not
receive 18 Vdc minimum. 24 Vdc is recommended.
covered by any Certifications.
2. Always determine voltage drops that will occur to
In order to change alarm relay settings from the factory
ensure that 24 Vdc is delivered to the AutroPath
default settings, it is recommended to use a HART
HC800.
Field Communicator. Contact the factory for further
assistance.
3. Normally, nothing smaller than 18 AWG (1.0 mm2)
is recommended by Autronica Fire and Security for
NOTE
AutroPath HC800 power cabling.
Refer to “Alarm Relays” in the “Specifications”
section of this manual for important information
Wire size requirements are dependent upon power
regarding alarm relays.
supply voltage and wire length.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 19
note
For proper HART communication, it is required
that an analog signal loop resistance of 250 to
500 ohms be present at the receiver analog
output terminals. For AutroPath HC800 systems
using HART communication, the maximum wiring
distance is 2,000 feet. No external resistance
needs to be added to the transmitter wiring for
proper HART operation.
SHIELD 7 SHIELD 17
HART
RS-485 B 8 RS-485 A 18
A2646
HART
Figure 13—Wiring Terminal Identification for AutroPath HC800 Receiver with Relays
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 20
0V COM 1 SPARE 11
0V COM 1 SPARE 11
0V COM 2 +24 VDC 12
0V COM 2 +24 VDC 12
0V COM 3 +24 VDC 13
0V COM 3 +24 VDC 13
SHIELD 4 SHIELD 14
SHIELD 4 SHIELD 14
INTR B 5 INTR A 15 INTR B 5 INTR A 15
CAL 6 INTR GND 16 CAL 6 INTR GND 16
SHIELD 7 SHIELD 17 SHIELD 7 SHIELD 17
RS-485 B 8 RS-485 A 18 RS-485 B 8 RS-485 A 18
–mA 9 +mA 19 –mA 9 +mA 19
HART HART
* * 4 to 20 MA
4 to 20 MA
– +
– + – +
+ –
24 VDC
24 VDC
B2649
B2650
*TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM. *TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.
NOTE: SHIELDED CABLE RECOMMENDED (REQUIRED FOR ATEX). NOTE: SHIELDED CABLE RECOMMENDED (REQUIRED FOR ATEX).
Figure 16—Receiver Wired for non-isolated 4-20 ma Figure 18—Receiver Wired for non-isolated 4-20 ma
current output (Sinking) current output (Sourcing)
HART HART
4 to 20 MA 4 to 20 MA
– +
* + – * – +
+ –
24 VDC 24 VDC
B2651 B2652
*TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM. *TOTAL LOOP RESISTANCE = 250 OHMS MINIMUM, 600 OHMS MAXIMUM.
NOTE: SHIELDED CABLE RECOMMENDED (REQUIRED FOR ATEX). NOTE: SHIELDED CABLE RECOMMENDED (REQUIRED FOR ATEX).
Figure 17—Receiver Wired for isolated 4-20 ma current output Figure 19—Receiver Wired for isolated 4-20 ma current output
(Sinking) (Sourcing)
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 21
0V COM 1 SPARE 11
0V COM 2 +24 VDC 12
0V COM 3 +24 VDC 13
SHIELD 4 SHIELD 14
INTR B 5 250 TO 500 INTR A 15
OHMS
CAL 6 INTR GND 16
SHIELD 7 SHIELD 17
RS-485 B 8 RS-485 A 18
–mA 9 +mA 19
HART
HART CONNECTORS
– +
24 VDC
B2653
A2672
startup
TRANSMITTER
0V COM 2 +24 VDC 12 When the AutroPath HC800 is installed and wired as
0V COM 3 +24 VDC 13 described in the “Installation” section, it is ready for
SHIELD 4 SHIELD 14
commissioning. If the application requires that specific
changes be made to the factory settings, HART
INTR B 5 INTR A 15
communication will be required.
SPARE 6 INTR GND 16
7 17
SHIELD SHIELD
note
RS-485 B 8 RS-485 A 18 Ensure that alarm devices are bypassed during
HART commissioning.
RECEIVER Note
0V COM 1 SPARE 11 The safety function (gas input-to-actuation/
0V COM 2 +24 VDC 12 notification) must always be verified upon
0V COM 3 +24 VDC 13
completion of installation and/or modification.
SHIELD 4 SHIELD 14
ALIGNMENT
INTR B 5 INTR A 15
6
CAL INTR GND 16 OVERVIEW
SHIELD 7 SHIELD 17
8
The AutroPath HC800 modules must be properly
RS-485 B RS-485 A 18
aligned before normal operation will be attained.
–mA 9 +mA 19
HART note
4 to 20 MA
Refer to the ATEX or IECEx Appendix for
information regarding the effect of misalignment
– +
+ –
on system accuracy.
24 VDC
C2667
IMPORTANT
NOTE 1: TOTAL LOOP RESISTANCE OF 4-20 MA CIRCUIT =
250 OHMS MINIMUM, 600 OHMS MAXIMUM.
Upon completion of system alignment, ensure
NOTE 2: NOTE: SHIELDED CABLE RECOMMENDED (REQUIRED FOR ATEX). that all bolts on the AutroPath HC800 mounting
CAUTION: DO NOT CONNECT THE COMMUNICATION LINK “INTR GND”
TERMINAL TO POWER SUPPLY COMMON OR ANY OTHER
and alignment bracket are properly tightened.
GROUND CONNECTION.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 22
Equipment Required ALIGNMENT PROCEDURE
1. Properly installed and powered AutroPath HC800 1. Ensure that the system modules are located within
system (transmitter and receiver). Easy access to the specified separation range and securely fixed
both modules is highly recommended. to the support structures. Bypass all external gas
alarm devices that are connected to the receiver
2. AutroPath HC800 Alignment Tool. The alignment outputs.
tool is recommended for use in commissioning all
AutroPath HC800 systems. The following instructions 2. Ensure that the system modules are installed with
cover the use of the Alignment Tool. their windows at approximately the same height
above grade. Each module should be roughly
3. 9/16 inch wrench. aligned to face in the direction of the other module.
Figure 23—AutroPath HC800 Mounting and Alignment Bracket (Receiver Module Shown)
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 23
6. Install the Alignment Tool onto the receiver mod-
ule by inserting the captive thumbscrews into the
threaded holes on the faceplate. See Figure 24.
Ensure that the alignment tool is properly attached,
that the eyepiece is accessible, and that the
thumbscrews are completely tightened.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 24
STEP 1: CENTER CROSS HAIRS ON TARGET USING
ADJUSTMENT BOLTS ON MOUNTING PLATE
(POSITION A).
NOTE
The AutroPath HC800 transmitter lamp output 23. When Basic Alignment and Zero Calibration have
intensity is automatically optimized during the been successfully completed, a green LED should
zero calibration process if the communication be displayed on the receiver module and the ana-
link wires are attached between transmitter and log signal output level should be 4.0 milliamperes.
receiver. If no communication link is installed,
the transmitter lamp output can be adjusted via
Aperture Kit for Short Range Applications
Modbus or HART connection to the transmitter.
This adjustment is rarely needed. (See The Short Range Aperture Kit enables successful
“Transmitter Lamp Voltage” section for more application of the AutroPath HC800 gas detector at
information.) short separation distances (5–15 meters for the short
range model and 30–40 meters for the long range
21. Proper operation should be confirmed by bypass- model). The aperture is made of aluminum and is
ing all system alarms, then placing an optical included with the AutroPath HC800.
test film (sold separately) into the light beam and
checking for the appropriate 4–20 mA output level
or relay actuation. The AutroPath HC800 test film
packet consists of five separate test films. Table
7 shows the response of the different AutroPath Table 7—Typical System Response* in LFL-M (% Full Scale)
Using Gas Test Films
HC800 gas settings to each of the five test films.
Alarm conditions, if present, should clear when the Test Film Methane Butane Propane
test film is removed from the beam.
0.6 1.1 1.3
1
(12%) (22%) (26%)
22. Confirm proper operation by completely blocking
the light beam with a solid object such as a piece 2
1.5 2.3 2.6
of cardboard until a beam block fault is signaled by (29%) (46%) (52%)
the appropriate 4–20 mA output level or relay action 3
2.5 3.6 3.9
(default delay is 60 seconds). The fault should clear (50%) (72%) (78%)
when the blocking device is removed from the beam. 3.7 4.9 5.4
4
(74%) (98%) (108%)
5.0 6.0 6.0
5**
(100%) (120%) (120%)
*Accuracy = ±0.2 LFL-M or ±15% LFL-M from typical system response,
whichever is greater.
**A HART handheld device is needed to read over-range values.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 25
Procedure for System Commissioning Using the Procedure
Aperture 1. Connect the handheld HART communicator to the
1. Align the AutroPath HC800 system using the receiver module’s 4–20 mA circuit.
Basic Alignment procedure. At the completion of
this alignment, the output signal at the receiver 2. Turn on the HART communicator and check for
may indicate a fault condition as a result of signal AutroPath HC800 device recognition. When HART
saturation. communication is established, the AutroPath
HC800 Online menu will be displayed on the com-
2. Attach the aperture to the front of the AutroPath HC800 municator display.
transmitter module using the captive screws provided.
For best weather protection, the aperture hole should be 3. From the Online menu, navigate to the Detector
located at the top of the unit. Setup menu, then select the Sensor Setup menu.
3. Perform a zero calibration. After performing the zero 4. The following screen will be displayed. Observe
calibration, the receiver module should display a normal the level indicated for “Gain.”
condition (green LED) and a steady 4 mA output.
NoTe
Sensor Setup
If the receiver continues to indicate a fault 1) Processing mode xxxx
condition as a result of signal saturation, rotate 2) Interconnect mode xxxx
the aperture 90 degrees and repeat step 3 above. 3) Log interim beam block Y/N
4) Gain Mode xxxx
5) Gain xx Gas Gain number
6) Tx lamp voltage xxxx
ReCommeNDAtIoNS FoR uSING tHe HARt FIeLD 7) Auto voltage during cal E/D
CommuNICAtoR 8) Beam block fault time xxx
WarnInG
The AutroPath HC800 does not use Intrinsically Safe 5. Table 8 can be used as a guideline for new instal-
circuitry for connection to the HART 475 Communicator. lations to assess the detector gain level with
Connecting a HART 475 Communicator to the proper alignment.
AutroPath HC800 may invalidate the Intrinsic Safety
circuits of the HART 475 Communicator.
• The HART communication device must include the table 8—Expected Gas Gain Settings for autropath Hc800
AutroPath HC800 device descriptor (DD) software
menu. The use of HART communication devices Transmitter Type
Distance
without the proper DDs may establish generic mode Short Range Long Range
HART communication, but will not enable proper
operation with AutroPath HC800. Refer to the HART 5 1 (aperture)
Appendix for additional information. 20 5 (aperture)
• A minimum level of understanding with regard to the
30 1 2 (aperture)
operation and navigation of the HART communicator
is required. Please refer to the appropriate HART 40 2-5 5 (aperture)
communicator instruction manual for basic operating
instructions if required. Additional information on the 60 5-10 1-2
use of the HART communicator is provided within the 80 2-5
HART Appendix in this document.
100 2-5
• For proper HART communication to occur, it is required
that a 250-500 ohm resistive load be present in the 120 5-10
AutroPath HC800 analog 4–20 mA signal loop output.
See “Wiring Procedure” in the “Installation” section.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 26
6. Verify the gain setting. The gas gain setting options Calibration
are 1, 2, 5, 10, 20, 50, and 100; ideal gain settings
are 2, 5, and 10. CALIBRATION OVERVIEW
Span calibration is not required. The AutroPath HC800
A gain of 1 indicates that the system may be near supports non-intrusive field zero calibration, although
saturation (signal strength is too high). If the gas routine calibration is normally not required.
gain number = 1 and the Active avg or Ref avg
numbers are greater than 1500, use the aperture
kit to reduce signal. See the “Transmitter Lamp Zero Calibration
Voltage” section for additional signal strength Zero Calibration is a one-step process consisting of clean
reduction options as needed. If using the Long air (zero) condition adjustment only, which is performed
range receiver, it may be necessary to switch to automatically by the device. This procedure adjusts the
the Short range version. “clean air” signal output only, and is normally used if the
gas output signal level has drifted. The cause of drift is
A gain of 20 or greater indicates that the system typically due to the presence of background gas during
signal strength is less than expected. Ensure that calibration. Additionally, the zero calibration procedure
the system has a clear beam path, clean windows, will optimize the transmitter lamp output intensity if the
and was properly aligned and calibrated in clear optional communication link is installed. This is useful for
weather. See the Transmitter Lamp Voltage section situations where the signal strength at the receiver is too
for additional signal strength increase options as large (saturation) or too small. Ensure that the optical path
needed. If using the Short range receiver, it may is clear of hydrocarbons prior to calibration initiation to
be necessary to switch to the Long range version. ensure an accurate zero (clean air) condition.
Contact the factory for further information or assis-
tance. important Calibration Notes
note
In all cases, a green LED and 4 mA output indicate Ensure that the detector has been operating for at
that the unit will properly perform its safety func- least two hours before calibrating.
tion. Gain adjustments and checks are simply a
way to optimize the system so that it will perform Note
in the widest variety of application scenarios (e.g., Always ensure that the AutroPath HC800 optics
shifting mounts, inclement weather, mechanical are totally free of all hydrocarbons before initiating
impact, lens obscuration, etc.). calibration.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 27
CALIBRATION INITIATION Calibration Sequence
Calibration may be initiated by any of the following 1. Initiate calibration using one of the methods listed
means: above:
• The onboard magnetic calibration switch A. The LEDs continue to flash yellow at 5 Hz.
B. The current output decreases to 1 mA, 2.2 mA,
• Digital communication via HART (see HART or as configured by the user.
appendix) or Modbus communication (consult factory
for details) 2. When zero calibration is complete:
• Remote calibration line. A. The onboard LEDs change from flashing yellow
to steady green.
Upon initiation, the AutroPath HC800 automatically B. Calibration is complete and the current output
performs the zero calibration adjustment, and then returns to 4 mA.
signals with a green LED when this operation is
complete. Note
Calibration will time out if unsuccessful after 10
Calibration Using Magnetic Switch minutes.
The AutroPath HC800 receiver provides an onboard
magnetic calibration/reset switch for non-intrusive Note
calibration capability. The magnetic switch is actuated To abort an in-process calibration, repeat the
by holding a calibration magnet at the specified calibration initiation sequence (e.g., hold the
location on the device bulkhead. See Figure 2 for magnet for three seconds or more and release).
switch location. An onboard multi-color LED provides The device will revert to its previous calibration
status indication during calibration. setting.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 28
MaintEnancE FuNCtIoNAL CHeCkING
WarnInG Functional checks should be performed as required
Do not open cover when an explosive gas by site conditions and local regulations. For specific
atmosphere may be present. approval requirements regarding functional checks,
see appendices and the AutroPath HC800 safety
NoTe manual.
Refer to the AutroPath HC800 Safety Manual
for specifi c requirements and recommendations Autronica Fire and Security provides two functional
applicable to the proper installation, operation, check options for the AutroPath HC800. The test film
and maintenance of all SIL-Certifi ed AutroPath method provides a basic functional check as described
HC800 IR gas detectors. in step 20 of the basic alignment procedure.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 29
tRoublEShootinG
A Fault status is indicated by a yellow LED and also
by the 4–20 mA output. Refer to Table 9 for assistance
in correcting malfunctions with the AutroPath HC800
Detector.
Low 24 volts
24 Vdc operating voltage is out of range. Verify proper wiring to the detector and correct voltage
output from the power source. Power supply faults are self-clearing when the condition is corrected.
If the fault does not clear, consult the factory.
Dirty Optics
Perform cleaning procedure, then recalibrate as required. (Refer to “Maintenance” for details.)
Calibration Fault If the calibration process is allowed to time-out, the fault is set and can only be reset with a
successful calibration.
Negative Signal Output This fault is indicated when the signal output drops below –0.5 LFL-m. Normally detection capability
is not compromised in this condition.
The device was probably zero calibrated with background gas present.
If the condition persists, purge with clean air and repeat the zero calibration. Ensure that the heaters
are on and the windows are not fogged.
Calibration line active at start- The only way to clear this fault is to correct the wiring and reapply power.
up Be sure that the calibration line is not shorted and that the calibration switch is open. If the fault does
not clear, consult the factory.
Signal Saturation Add aperture to the transmitter module or adjust lamp voltage if needed.
CautIon
Replacement of the AutroPath HC800 transmitter
or receiver module requires disassembly of the
device housing. Remove power to the device
before disassembly.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 30
moDuLe RePLACemeNt PRoCeDuRe 5. Line up the pin on the replacement module with
the hole in the bulkhead and insert the module
Tools Required:
straight into the bulkhead. See Figure 26 for the
– 6 mm hex wrench (transmitter) transmitter and Figure 27 for the receiver.
– 5/16 inch hex wrench (receiver)
6. Transmitter
– Torque wrench capable of accurately measuring 40
Insert and tighten the seven flange bolts in an
inch-pounds
opposing consecutive order in two stages — first
partially tighten all seven bolts equally, and then
1. Bypass system alarms as needed, then remove 24
fully tighten each bolt in an opposing order to 90
Vdc power from the AutroPath HC800 detector.
in-lbs (10.2 N•m) maximum of torque. Bolts are
M8-1.25x 16M.
2. Transmitter
Remove the seven stainless steel flange bolts
CautIon
using a 6 mm hex wrench. See Figure 26. Take
Flange bolts are critical to maintaining the
care to properly support the module as the last
fl ameproof properties of the AutroPath HC800. If
flange bolt is removed.
replacement fl ange bolts are needed, DeC spare
part number 012713-001 must be used in order
Receiver
to maintain the integrity of the enclosure. The use
Using a 5/16 inch hex wrench, loosen the locking
of any other bolts will void the ex d certifi cation of
set screw. Turn the retainer ring by hand to loosen
the AutroPath HC800.
the module. See Figure 27.
Receiver
3. Carefully remove the old module by extracting it
Fully tighten the retainer ring on the receiver mod-
straight out from the bulkhead.
ule, then tighten the set screw to prevent the ring
from being turned.
4. Ensure that the O-ring is present, undamaged, and
correctly seated in the groove. This O-ring is required
to maintain the watertight integrity of the AutroPath
HC800 housing.
RETAINER RING
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 31
BULKHEAD
BULKHEAD
HC800 MODULE
HC800 MODULE
ALIGNMENT
PIN ALIGNMENT
PIN
TO INSTALL REPLACEMENT MODULE,
LINE UP ALIGNMENT PIN ON MODULE WITH TO INSTALL REPLACEMENT MODULE,
HOLE IN BULKHEAD AND INSERT MODULE
LINE UP ALIGNMENT PIN ON MODULE WITH
A2663 FULLY INTO BULKHEAD.
HOLE IN BULKHEAD AND INSERT MODULE
A2664
FULLY INTO BULKHEAD.
Figure 26—Transmitter Module Removed from Bulkhead Figure 27—Receiver Module Removed from Bulkhead
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 32
ORDERING INFORMATION SPARE PARTS
When ordering, please refer to the AutroPath HC800 Model Part Number Description
Matrix: 116-102740-002 Calibration Magnet
116-104346-154 O-Ring, 3.75” i.d., for wiring compartment cover
alignment equipment 116-104346-046 O-Ring, 4.25”, for front flange, Transmitter
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 33
AutroPath HC800 Model Matrix
MODEL DESCRIPTION
Autro-
Path Line of Sight Infrared Gas Detector
HC800
TYPE MATERIAL
S Stainless Steel
TYPE CONDUIT ENTRY THREAD TYPE
N 3/4" NPT, 4 Port Receiver, 2 Port Transmitter
M Metric M25, 4 Port Receiver, 2 Port Transmitter
TYPE OUTPUT
00 None (Transmitter only)
18 4-20 mA, RS485, HART (Receiver or Kit)
25 4-20 mA, RS485, HART w/Optional Relays (Receiver or Kit) – Ex d only
TYPE RANGE
N None (Transmitter only)
S Short Range, 5-60 Meters (Receiver or Kit)
L Long Range, 30-120 Meters (Receiver or Kit)
TYPE FACTORY SET TARGET GAS*
N None (Transmitter only)
M Methane (Receiver or Kit)
P Propane (Reciever or Kit
B Butane (Receiver or Kit)
TYPE APPROVALS†
S SIL
E ATEX/IECEx
TYPE CLASSIFICATION
1 Division and/or Ex d e
2 Division and/or Ex d
TYPE CONFIGURATION
S Transmitter/Receiver/Mounting Hardware
T Transmitter Only
R Receiver Only
TM Spare Transmitter Electronics Module
RM Spare Receiver Electronics Module
*The AutroPath HC800 is factory calibrated to Methane, Propane, and Butane gas types. This selection indicates which gas type the device
was configured to detect when it left the factory. This selection can be changed in the field via HART or Modbus.
†Type Approvals can use one or more letters to designate the approvals of the product.
NOTE: “Kit” is a complete system, consisting of a transmitter, receiver, aperture, and mounting hardware.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 34
appEnDix a
ATEX APPROVAL DESCRIPTION
The following items, functions, and options describe the ATEX approval.
APPRoVAL
Line of Sight Infrared Hydrocarbon Gas Detector, Model AutroPath HC800.
Receiver Transmitter
0539
FM
APPROVED
II 2 G
®
0539
FM
II 2 G
APPROVED
®
Performance verified with Methane, Butane, and Propane in accordance with EN 60079-29-4.
• The Model AutroPath HC800 shall be installed in places where there is low risk of mechanical damage.
• The field wiring terminal connections are certified for a single wire in size from 0.2 to 2.5 mm2, (or two conductors
with same cross section 0.2 to 0.75 mm2). The screws must be tightened down with a torque of 0.4 to 0.5 Nm.
• The metal housings of the Model AutroPath HC800 Gas Detector must be electrically connected to earth ground.
• The Model AutroPath HC800 has an ambient temperature rating of –55°C to +75°C.
• Only suitable certified Ex d or Ex e (as applicable) cable entries, adapters, and blanking elements are to be used,
including 1/2 inch NPT, 3/4 inch NPT, M20 and M25 sizes, with IP66/67 rating.
• Flameproof joints are not user serviceable; contact Autronica Fire and Security AS.
• Seven special fasteners are provided for the Transmitter electronics module, M8 bolts per ISO 965 with M6 head,
SST with a yield strength of 483 N/mm2 (70,000 PSI). The tightening torque in an opposing order is 19 Nm (169
inch-pounds) per flange bolt.
WarnInG
Always ensure that the detector/junction box hazardous (classifi ed) location ratings are applicable for the
intended use.
WarnInG
Potential electrostatic charging hazard on brow. Use caution when servicing in an explosive environment.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 35
Additional Safety Notes:
• For ambient temperatures below –10°C, use field wiring suitable for the expected conditions, and for ambient
temperatures above +60°C, use field wiring and cable glands suitable for 15°C above the maximum expected
conditions.
ATEX Standards:
EN 60079-29-4: 2010
Performance Approved for Methane, Butane, and Propane
EN 60079-0: 2012 +A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-28: 2007
EN 60529:1991+A1: 2000
EN 50270: 2015
EN 50271: 2010
response time
T90: 2 seconds (2.5 LFL-meters applied).
alignment
Misalignment will cause the manufacturer stated accuracy limits to increase, but remain within the limits of EN
60079-29-4.
Accessories with the following part numbers are approved for use with the AutroPath HC800:
116-011773-001 Short Range Aperture Kit
116-012287-XXX AutroPath HC800 Alignment Tool
116-009246-002 Gas Test Cell
116-012673-001 System Test Film
116-012312-001 Transmitter Brow
116-012300-001 Receiver Brow
116-012660-001 Mounting Bracket
116-103922-001 HART Handheld Communicator
116-011824-001 Modbus Program
116-102740-002 Calibration Magnet
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 36
NOTES
Approval of the AutroPath HC800 does not include or imply approval of the apparatus to which the detector
may be connected and which processes the electronic signal for eventual end use. In order to maintain an
approved system, the apparatus to which the detector is connected must also be approved.
This Approval does not include or imply Approval of the communications protocol or functions provided by
the software of this instrument or the communications apparatus or software connected to this instrument.
Manufactured by:
Detector Electronics Corporation
www.det-tronics.com
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 37
Appendix B
IECEx Approval Description
The following items, functions, and options describe the IECEx approval.
Approval
Line of Sight Infrared Hydrocarbon Gas Detector, Model AutroPath HC800.
Receiver Transmitter
IECEx UL 15.0037X IECEx UL 15.0037X
Ex db eb IIC T4 IEC 60079-29-4 IP66/67 Ex db eb IIC T4 IEC 60079-29-4 IP66/67
T4 (Tamb –50°C to +75°C) T4 (Tamb –50°C to +75°C)
(Receiver without relays) --OR--
--OR-- Ex db IIC T4 IEC 60079-29-4 IP66/67
Ex db IIC T4 IEC 60079-29-4 IP66/67 T4 (Tamb –55°C to +75°C)
T4 (Tamb –55°C to +75°C)
(Receiver with relays)
Performance verified with Methane, Butane, and Propane in accordance with IEC 60079-29-4.
IEC Standards:
IEC 60079-0: 2011
IEC 60079-1: 2014
IEC 60079-7: 2007
IEC 60079-28: 2006
IEC 60529, 2.1 ed.+Corr.1: 2003+2:2007
IEC 61000-4-3: 2010
IEC 61000-4-1: 2006, IEC 61000-4-4: 2012
IEC 60079-29-4: 2010
Performance Approved for Methane, Butane, and Propane
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 38
WarnInG
Always ensure that the detector/junction box hazardous (classifi ed) location ratings are applicable for the
intended use.
WarnInG
Potential electrostatic charging hazard on brow. Use caution when servicing in an explosive environment.
ReSPoNSe tIme
T90: 2 seconds (2.5 LFL-meters applied).
ALIGNmeNt
Misalignment will cause the manufacturer stated accuracy limits to increase, but remain within the limits of IEC
60079-29-4.
Accessories with the following part numbers are approved for use with the AutroPath HC800:
116-011773-001 Short Range Aperture Kit
116-012287-XXX AutroPath HC800 Alignment Tool
116-009246-002 Gas Test Cell
116-012673-001 System Test Film
116-012312-001 Transmitter Brow
116-012300-001 Receiver Brow
116-012660-001 Mounting Bracket
116-103922-001 HART Handheld Communicator
116-011824-001 Modbus Program
116-102740-002 Calibration Magnet
NoTeS
Approval of the AutroPath HC800 does not include or imply approval of the apparatus to which the detector
may be connected and which processes the electronic signal for eventual end use. In order to maintain an
approved system, the apparatus to which the detector is connected must also be approved.
This Approval does not include or imply Approval of the communications protocol or functions provided by
the software of this instrument or the communications apparatus or software connected to this instrument.
Manufactured by:
Detector Electronics Corporation
www.det-tronics.com
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 39
Appendix C
Additional Approvals
The following items, functions, and options describe various other approvals applicable to the AutroPath HC800.
SIL Approval
DNV GL
Type Approval Certificate No. TAA000002M.
Application
Location Classes
MODEL TEMPERATURE HUMIDITY VIBRATION EMC ENCLOSURE
LS2000 D B A/B B C/IP66/IP67
Type Location within main area Machinery Control room, Pump room, Holds, Open
spaces Accommodation Bridge Rooms with no heating Deck
EMC (Electro-
magnetic All locations within specified main areas A A B A B
compatibility
Submerged application D — — D D
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 40
Appendix D
HART Communication
Digital communication with the AutroPath HC800 is necessary to monitor internal status and to modify the factory
settings. This appendix provides guidance on establishing HART communication, and describes the communication
menu structure when using the AutroPath HC800 with the HART Handheld Communicator.
Note
The HART protocol incorporates a concept called the “Device Description Language” that enables all
suppliers of HART instruments to define and document their products in a single consistent format. This
format is readable by handheld communicators, PC’s and other process interface devices that support DDL.
DDL enables full interoperability of devices, regardless of manufacturer, allowing full functionality from any
HART device.
In the event that your Communicator does not establish communications with the AutroPath HC800, you may need
to ensure that the appropriate DDL’s for the AutroPath HC800 are included within your Communicator. To review
the device descriptions programmed into your HART Communicator:
2. From the Offline menu, press New Configurations to access the list of device descriptions programmed into
your HART Communicator. The Manufacturer menu displays a list of each manufacturer with device descrip-
tions currently installed in your Communicator’s Memory Module. The standard 12 MB Memory Module is
recommended, as it allows for more device descriptions.
3. Select a manufacturer, and the Model menu displays, containing a list of currently installed device models
provided by the selected manufacturer.
4. Review the different manufacturers and models to determine the installed HART-compatible devices in your
Communicator.
If you cannot find the AutroPath HC800 device on your Communicator, the device revision you are looking for is
not programmed into the Memory Module. In this instance, you are limited to what is available using the generic
interface built into your HART Communicator.
The HART Communication Foundation (www.ccsi.com/hart) manages a library of Manufacturer Device Descriptions,
which are distributed to programming sites for inclusion in master devices. A complete listing of the HCF DD Library
is available for download in manufacturer and device type sequence.
NOTE
If a device is found, the HART Communicator displays the Online menu. If no device is found, the Communicator
displays the Main menu. If no device is found, check the connections, verify the presence of a minimum of
250 ohms load resistance in series in the loop, and retry by selecting “Online.” To poll multiple devices in the
loop, refer to the HART Communicator manual.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 41
Device Status
Process Variables
General Info 1. Warming up ON/OFF
Gen Configuration 2. Any Fault ON/OFF
1) Gas xxxxxxx
1) Manufacturer xxxxxxx 3. Calibration Active ON/OFF
2) PV x.xx LFL-M Rx Heater Control
2) Model xxxxxxxx 4. Output loop fixed ON/OFF
3) PV %rnge 0.00% 1) Processing Mode xxxx
3) Tag xxxxxxxxx 5. Alignment Active ON/OFF
4) Loop current x.xx mA 2) PV Units xxx 1) Heater mode xxxxxxx
4) Long tag xxxxxxxxx 6. Configuration change ON/OFF
5) Device temp. x.xx Deg C 3) Green LED setting xxxx 2) Heater power
5) Descriptor xxxxxxxxx 7. Temperature over range ON/OFF
6) GAS URV x.xx LFL-M 4) Green LED turn off time xx 3) Heater turn on temp xxx
6) Message xxxxxxxxx 8. Undefined ON/OFF
7) GAS LRV x.xx LFL-M 5) Rx Heater Control -> 4) Heater cut off voltage xxxx
7) Final Asmbly Num xxx
8) Gas trend 6) Tx Heater Control -> More Device Status
8) Dev ID xxxxxxxxx
9) Date **/**/**
Tx Heater Control 1. Low Alarm Active ON/OFF
Hart Configuration 2. High Alarm Active ON/OFF
Device Info 3. Response Test Active ON/OFF
1) Heater mode xxxxxxx
Device Diagnostics 1) Tag xxxxxx 2) Heater power 4. Self Test Active ON/OFF
1) Cfg change count xxx 5. Multidrop mode Active ON/OFF
2) Long tag xxxxx 3) Heater turn on temp xxx
1)Response test 2) Write protect Yes/No 6. Interim Beam Block ON/OFF
3) Descriptor xxxxxx 4) Heater cut off voltage xxxx
2)Loop test 3) Universal rev 7 7. Detector disposition ON/OFF
4) Message xxxxxx
3) General info 4) Fld dev rev xx 8. Undefined ON/OFF
5) Poll Address xxx
4) Device info 5) Software rev xx
6) Num Req Preams 5
5) Sensor info 6) RX flash CRC xxxx Advisory Faults
7) Num Resp Preams 5
6) Fault and Status bits Baud Rate 7) TX Flash CRC xxxx
8) Date xxxxxx
7) History 9) Final asmbly num xxxxxx 1. Zero Calibration Fault ON/OFF
8) RTC 1) 9600 2. Span Calibration Fault ON/OFF
9) Alignment info 2) 19.2K 3. Beam Block ON/OFF
3) 38.4K Sensor Info
4. Ref Sensor Saturated ON/OFF
RS-485 Settings 4) 57.6K 5. Active sensor Saturated ON/OFF
5) 115.2K 1) Active last flash xxxxx
6. Input voltage Low ON/OFF
1) Poll addr xxx 2) Reference last flash xxxxx
7. Zero Drift ON/OFF
2) Baud Rate 3) Active avg xxxxx
8. Undefined ON/OFF
AutroPath HC800 HART Menu Structure
Page 42
5) Gen config 2) Low Alarm Latch xxx Unit 1) Device status 1. Ram Fault ON/OFF
6) Hart Config 3) High Alarm Level xxx LFL-M 2) More Device Status 2. Data Flash Fault ON/OFF
7) RS-485 setup 4) High Alarm Latch xxx PPM-M 3) Advisory faults 3. Flash CRC Fault ON/OFF
8) Gas type setup 5) Low alarm relay NE/DNE 4) More advisory faults 4. AFE Fault ON/OFF
9) Alarm setup 6) High alarm relay NE/DNE 5) Detection disable faults 5. Heater Fault ON/OFF
RTC Setup 6) Transmitter Faults 6. Internal voltage fault ON/OFF
Sensor setup 7) More Transmitter Faults 7. Undefined ON/OFF
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
3) Detection disable fault level x.xx Alignment info 4. Temperature over-range ON/OFF
4) Configuration fault level x.xx 5. Output loop fixed ON/OFF
5) Advisory fault level x.xx 1) Active xxxxxxx 6. Modbus unlocked ON/OFF
2) Reference xxxxxxx 7. Self test active ON/OFF
3) X – Axis xxxxx.xx 8. Undefined ON/OFF
Data Protection Write Protect 4) Y – Axis xxxxx.xx
5) Z – Axis xxxxx.xx
1) Enter Password Not Protected
2) Write Protect Protected
3) Write Protect On/OFF Change Password
This section displays the menu trees for the AutroPath HC800. The Menu tree shows the primary commands and
vice Info Menu RTC Menu
versal Rev. 1) Seconds
d Device Rev. 2) Minutes
tware Rev. 3) Hours
e Protect 4) Date and Hardware
Connections
C Menu 5) Month
nment Status Menu 6) Day
The HART Communicator can interface with the
7) Year
AutroPath HC800 from the control room or from any wiring
termination point
8) Write in the analog output signal loop.
Protect To communicate, connect the HART communicator in parallel
with the AutroPath HC800 analog signal or load resistor. The connections are non-polarized. Refer to the “Wiring
Procedure” section for installation instructions.
Alarm Menu
High Alarm Level Note
High Alarm Latch The HART Communicator needs a minimum of 250 ohms resistance in the loop to function properly. The
Low Alarm Level
Low Alarm Latch
HART Communicator does not measure loop current directly.
Online Menu
When HART communication is established with the receiver, the first menu displayed is the AutroPath HC800
Online menu:
Online
1) Process Variables
2) Device Diagnostics
3) Configure/Setup
To select any of the menu options shown, highlight the desired option using the up/down arrow key, and then press
the “right arrow” key.
ent Menu
X
Y
ence
e Alignment Commonly Used HART commands
e Alignment
The most commonly used HART commands for the AutroPath HC800 are:
8. Interrogating the history menu for information including total running hours, max/min temperature, calibration
and event logs.
Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 43