Professional Documents
Culture Documents
SUB-HEAD-4
BOARD AND CONTROLS
4.1 Providing & fixing 250V, 50 Hz grade following concealed type sub-
distribution board made of 18-SWG MS sheet complete with hinged type
door, built-in type locking arrangement, one no. 60 A capacity bus-bar with
required no. of holes thereon on insulators at both ends, copper blocks for
neutral and earth terminal, SPMCBs manufactured and tested in accordance
with relevant IEC / VDE / NEMA / BS / JIS standard having minimum
breaking capacity 6 / 10-KA with thermal over current and instantaneous
electromagnetic short circuit release, necessary arrangement for fixing of
MCBs duly painted with powder coating with epoxy polyester resin on all
surfaces of board (gray / off-white) etc. In front side there will be tempered
thick fiber glass with rubber gaskets etc.
With SPMCB's of DORMAN SMITH / MEM / SIEMENS / VIRTZRO / HAGER
/ FEDERAL / KAWAMURA / ABB / HAVELLS / LEGRAND / MERLIN GERIN
/ SCHNEIDER or equivalent brand accepted / approved by the engineer.
4.1 (i) 3-Way SDB (with box size minimum 220mm x 132mmx148mm)
incoming : 1 x 30 amps. & out-going: 3 x 5 / 10 amps SPMCB.
each Tk. 3,924.00
4.1 (ii) 4-Way SDB (with box size minimum 220mmx 132mmx148mm)
incoming : 1 x 40 amps. & out-going:4 x 5 / 10 / 15 amps SPMCB.
each Tk. 4,649.00
4.2 Providing and fixing single phase distribution board (SPDB) [concealed /
surface] having the following components and specifications: [Fig : 4.2]
1. Steel board : size 20"x15"x4"
MS sheet : 18SWG with hinged type door and locking
arrangement duly painted with powder coating with epoxy
polyester resin on all surfaces of board (gray / off-white) etc. In
front side there will be tempered thick fiber glass with rubber
gaskets to observe the inside arrangement.
2. Copper bar: size 10"x 1"x 3mm (2 nos.) and 6"x 1"x 3mm
(1 no) mounted on insulator
capacity: 60-100A at both ends.
3. 1 no. TPMCCB (main control) and following nos. TPMCCB for feeders.
TPMCB's are manufactured and tested in accordance with relevant IEC
/ VDE / NEMA / BS / JIS standard. Minimum breaking capacity 10-16
KA with thermal overcurrent and Instantaneous electromagnetic short
circuit release.
4.4 Providing & fixing on a prepared board 250 volt grade following single pole
miniature circuit breaker (SPMCBS) having minimum breaking capacity 6-
KA with thermal over-current and instantaneous electromagnetic short circuit
release provision.
TPMCB
4.5 Providing & fixing on a prepared board 500 volt grade following Triple pole
miniature circuit Breaker (TPMCB) having minimum breaking capacity 6-KA
with thermal over-current and instantaneous electromagnetic short circuit
release provision.
TPMCCB
4.6 Providing & fixing on a prepared board 500 volt grade following triple-pole
molded case circuit breaker (TPMCCB) with thermal over-current and
instantaneous electromagnetic short circuit release provision, manufactured
and tested in accordance with relevant IEC / VDE / NEMA / BS / JIS
standards.
BUS - BAR
4.7 Providing and fixing 500 V 3-phase bus-bar system assembled in prelaid
board with porcelain insulators. There will be equal size holes on every bar
at 0.5" interval and bar to bar gap shall be 2" - 3".
4.8.1 Supply and fixing bus bar trunking system (800 A and above) both feeder
and plugging having the following specification:-
* Short circuit rating: 800 A - 1000 A (40-60 KA/sec) 2500 A - 4000 A (165 -
220 KA/sec)* Housing: Constructed of code gauge steel and aluminum to
reduce hysteresis and eddy current losses. It shall be totally enclosed non
ventilated and anticorrosive ability.* Bus bar: Hard drawn silver plated high
conductivity copper of 99.9 % purity.Bus-bar insulation: class B or class F
rated polyester film. (No epoxy insulation).
* Joint: Bus bar trunking joint shall be of the one-bolt type and
shall be possible to remove any joint connection assembly to
allow electrical isolation of bus bar trunking length.
* Indoor feeder and plug-in trunking shall be hanged 3 meters
horizontally and 4.88 meters vertically spacing.
* Line to line voltage drop shall not exceed 4% at full connected
load.
* Temperature rise at any point of the bus bar trunking enclosure
shall no exceed 550C.
Bus bar trunking system with flange, elbow, plug in points and fixing
supports.
BOARD
4.9 Supplying and fixing of almirah type 18 SWG metal board of depth 228mm
(6”) duly painted with powder coating with epoxy polyester resin on all
surfaces of board (gray / off-white) having built in push type / suitable
locking arrangement including metal bridges of suitable size for fixing of all
electrical control devices complete with suitable anchoring arrangement in
wall / column and keeping provision for cable inlets and exits as required
(only front surface of the board will be considered for measurement).
4.9.3 The front side of the boards should be covered with required size tempered
thick fiber glass with rubber gaskets to observe the inside arrangement. sqm Tk. 16,904.00
4.9.4 Providing and fixing of pedestal type 18 SWG M.S. sheet steel board for
outside use with proper reinforcement by M.S. flat bars, water tight
arrangement duly painted with powder coated paint over prime
anticorrosive red oxide coat fitted on floor with necessary cc work, angle iron
clamps / legs as per direction of the engineer. sqm Tk. 4,951.00
4.9.5 Supplying and fixing of surface / concealed 18 SWG G.P. sheet board of
76.2 mm(3”) depth(with open front) duly painted inner & outer surfaces with
gray enamel paint, anchoring arrangement to be fitted in wall (only back
surface of the board will be considered for measurement). sqm Tk. 6,098.00
board of 76.2 mm(3”) depth (with open front) duly painted inner & outer
surfaces with anchoring arrangement to be fitted in wall (only back surface
of the board will be considered for measurement).
4.9.7 Providing and fixing of 3mm.thick ebonite sheet cover including making
hole / groove etc. as required.
sqm Tk. 1,485.00
SOCKET OUTLETS
4.10 Providing & fixing 250 volt single phase 3-pin combined switch socket outlet
(surface / Concealed type) manufactured and tested in accordance with
relevant IEC / VDE / NEMA / BS / JIS standards mounted on required size
18 SWG galvanized plain sheet board / Plastic Board (Self-extinguishing
650oC) of 76.2 mm. (3") depth.
(Manufacturer shall have certificate of standard which they follow).
(a). 13 / 15 / 16 / 20 Amps.
4.10.1.(i) Made in ENGLAND / GERMANY / JAPAN / USA or EU countries. each Tk. 1,008.00
4.10.1.(ii). Made in HONGKONG / MALAYSIA / SINGAPORE / S KOREA / THAILAND each Tk. 586.00
4.10.1.(iii) Assembled and made in BANGLADESH / CHINA / INDIA / TURKEY / VIETNAM each Tk. 344.00
(b). 5 - 10 Amps.
4.10.2.(i) Made in ENGLAND / GERMANY / JAPAN / USA or EU countries. each Tk. 887.00
4.10.2.(ii). Made in HONGKONG / MALAYSIA / SINGAPORE / S KOREA / THAILAND each Tk. 465.00
4.10.2.(iii) Assembled and made in BANGLADESH / CHINA / INDIA / TURKEY / VIETNAM each Tk. 344.00
4.10.3 Providing & fixing 250 volt single phase universal combined switch socket
outlet (surface / concealed type) manufactured and tested in accordance
with relevant IEC / VDE / NEMA / BS / JIS standards mounted on required
size 18 SWG galvanized plain sheet board / plastic board (self-extinguishing
650oC) of 76.2 mm. (3") depth. Sample to be approved by the Engineer.
(Manufacturer shall have certificate of standard which they follow)
(a). 13 / 15 / 16 / 20 Amps.
4.10.3.(i) Made in ENGLAND / GERMANY / JAPAN / USA or EU countries. each Tk. 1,129.00
4.10.3.(ii). Made in HONGKONG / MALAYSIA / SINGAPORE / S KOREA / THAILAND each Tk. 646.00
4.10.3.(iii) Assembled and made in BANGLADESH / CHINA / INDIA.. / TURKEY / VIETNAM each Tk. 404.00
(b). 5 - 10 Amps.
4.10.4.(i) Made in ENGLAND / GERMANY / JAPAN / USA or EU countries. each Tk. 948.00
4.10.4.(ii). Made in HONGKONG / MALAYSIA / SINGAPORE / S KOREA / THAILAND each Tk. 586.00
4.10.4.(iii) Assembled and made in BANGLADESH / CHINA / INDIA. / TURKEY / VIETNAM each Tk. 344.00
SUB-HEAD-4 PWD SoR 2018 FOR E/M WORKS 7
GANG SWITCH.
4.11 Providing & fixing 250 volts. 5 / 6 amps (minimum) concealed type following
switch / switch socket manufactured and tested in accordance with relevant
IEC / VDE / NEMA / BS / JIS standards mounted on required size 18 SWG
galvanized plain sheet / PVC board (Self-extinguishing 650oC) of 76.2 mm
(3") depth. All electrical contacts shall be of brass / copper. (Manufacturer
shall have certificate of standard which they follow)
4.12.(i) Made in ENGLAND / GERMANY / JAPAN / USA or EU countries. each Tk. 1,491.00
4.12.(ii) Made in HONGKONG / MALAYSIA / SINGAPORE / S KOREA / THAILAND each Tk. 887.00
4.12(iii) Assembled and made in BANGLADESH / CHINA / INDIA / TURKEY / VIETNAM
each Tk. 767.00
4.13.(i) Made in ENGLAND / GERMANY / JAPAN / USA or EU countries. each Tk. 525.00
4.13.(ii) Made in MALAYSIA / THAILAND / SINGAPORE / HONGKONG / S.KOREA.
. each Tk. 404.00
4.13.(iii) Assembled and made in BANGLADESH / CHINA / VIETNAM / INDIA / TURKEY. each Tk. 284.00
SUB-HEAD-4 PWD SoR 2018 FOR E/M WORKS 8
CALL BELL
4.15.1 Providing & fixing ding dong 250 V grade call bell on prepared board
including required length of PVC twin flexible cord etc. complete. each Tk. 622.00
4.15.2 Providing & fixing 250v, 50 Hz grade remote control call bell complete
(foreign made).
each Tk. 767.00
CHANGE OVER SWITCH
4.16 Providing & fixing of 18 SWG metal clad 500 volt 3 phase two way change-
over switch of following capacity complete with moving & fixed copper
contacts, copper buses, brass nuts and bolts, 3mm thick ebonite sheet
separators insulators, operating handle etc. complete including necessary
hammer painting on enclosure.
EARTHING
4.17 Earthing the electrical installation with 40 mm (1.5") Dia. G.I. pipe (earth
electrode) having 6.35 mm. Dia. hole across the pipe at 305 mm. interval
securely bonded by soldering with 2 nos. of No-2 SWG HDBC earth leads
(at the top of the electrode) with its protection by 20 mm. (3/4") Dia. G.I.
pipe up-to plinth level run at a depth of 609.6 mm (2 ft..) below G.L up-to
main board to be earthed including necessary connecting copper sockets,
bolts, nuts, etc. complete for maintaining earth resistance within 1 ohm.
[Fig : 4.17]
4.17 (i) Depth of bottom of main electrode at 6858 mm. (22.5 ft.) from GL & length of
electrode 6096 mm. (20 ft..).
per set Tk. 15,697.00
4.17 (ii) Depth of bottom of main electrode at 12954 mm. (42.5 ft.) from GL & length
of electrode 12192 mm. (40 ft.) per set Tk. 17,508.00
4.17 (iii) Depth of bottom of main electrode at 19050 mm. (62.5 ft.) from GL & length
of electrode 18288 mm. (60 ft.) per set Tk. 19,319.00
4.17 (iv) Depth of bottom of main electrode at 25146 mm. (82.5 ft.) from GL & length
of electrode 24384 mm. (80 ft.). per set Tk. 21,130.00
4.17 (v) Depth of bottom of main electrode at 31242 mm. (102.5 ft.) from GL & length per set Tk. 22,941.00
SUB-HEAD-4 PWD SoR 2018 FOR E/M WORKS 9
4.17 (vi) Depth of bottom of main electrode at 37338 mm. (122.5 ft.) from GL & length
of electrode 36576 mm. (120 ft.). per set Tk. 24,753.00
4.19 Providing & fixing 25.4 mm (1") Dia. 457 mm (1.5 ft.) long solid copper rod
with 6.6 mm thick 150 mm x 150 mm copper made base with sharp end top,
fixed on the top of 2.0"( 2.5 - 3 mm thick ) Dia. 10' long GI pole by
necessary accessories . The pole shall fixed on parapet wall with
necessary CC work and other accessories for arresting lightning as per plan
(enclosed) and as per direction of the engineer. [Fig : 4.19] per set Tk. 5,796.00
4.20 Providing & drawing no-2 HDBC wire through 12.7 mm. (½") Dia. G.I. pipe
including fitting, fixing the G.I. pipe in wall or column complete as required. meter Tk. 857.00
4.21.3 Supply and installation of lightning event counter of the following technical
specification - Register capacity: 0-999 mechanical counting without
external power supply (LCD display)The down conductor shall pass the hole
of the counter and the same shall be fixed vertically at any point. Brand:
ABB / LPI or equivalent product. Standard : (UL listed) each Tk. 42,502.00
4.21.4 Supply and installation of earth test box with the following arrangement
inside it.
Test Joint : (79mm x 50mm x 20mm) made of copper.
30mm x 2mm and Dia. 8mm line coupling made of copper. each Tk. 1,328.00
4.21.5 Supply and drawing of copper made down conductor having Dia. 12.7 mm
or copper strip (30mmx2mm) with fixing holder on vertical and horizontal
surface. The fixing shall have 40mm to 50mm length or height and will be
placed 3 nos. meter as per direction and sample approved by the engineer. meter Tk. 1,923.00
GI Pole: Dia. 3”, Length: 15’ (L-10’ D- 3”, L-5’ D- 2” Dia.) duly painted with
powder coating with epoxy polyester resin.
There will be minimum three guy wire for erection of the pole properly. The
base of the pole and guy will be installed by CC on the roof-top and the size
will be as required to hold the pole at any circumstances. each Tk. 11,833.00
4.21.7 Construction of earthing ( 2 nos.) for the lightning arrester as per instruction
and enclosed Diagram ( Fig : 4.21) and as per direction of the engineer in
the following way-
(i). Soil digging: Size–3000mmx400mmx400mm (2 nos.)
(ii). Construction of pit by brick and RCC slab on it. On the top of the slab there
will be a hole and a pit cover made by cast iron will be fixed on it.
Size of the pit: (600mmx600mmx600mm) (2 nos.)
(iii). Copper plate: (300mmx150mmx15mm) (2 nos.)
Copper plate will be fixed with the electrode (copper rod or copper strip) by
necessary fixing materials made of copper.
(iv) Copper electrode (12.7mm Dia. copper rod or copper strip (30mmx2mm)
Length of the copper rod or strip : minimum 3000mm
(10+10) = 20 meter.
(v) Ground enhancing materials (40 + 40) = 80 kg.
(2 Nos. of earthing is considered 1 set) job Tk. 130,404.00
4.21.8 Surge protection device (SPD) for protection of over-head line connected to
LT line.
Capacity: 50ka 4-pole with wiring and SPD box.
Brand: ABB / ARICO / LPI or equivalent Product. set Tk. 48,539.00
SUB-HEAD-4 PWD SoR 2018 FOR E/M WORKS 11
4.21.9 Supply and installation of Aviation light fittings wit LED Lamp, day light
sensor, wiring by 1C-2x1.5 sq.mm cable (NYY) with ECC as per instruction
and sample approved by the engineer.
The Aviation Light fitting shall be fixed on GI pipe (GI Bracket) with
necessary fixing materials shown in the fig - 4.21, below the Air Terminal. each Tk. 9,056.00
CABLE KITS
4.22 Supply & fixing of heat shrink joint kit complete with DIN ferrules, cable
preparation kits at the point of jointing of cables for 11 KV 3-core PVC
insulated & PVC sheathed armored / non-armored cables of the following
sizes:- (Made in GERMANY / JAPAN / USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN / SWITZERLAND)
4.23 Supply & fixing of heat shrink termination kit out-door / in-door use complete
with DIN lugs earth connection hardware & cable preparation kit (In-door &
outdoor) at the point of cable termination for 11 KV 3-core PVC insulated &
PVC sheathed & armored / non-armored cable of the following sizes (Made
in GERMANY / USA / UK / FRANCE / JAPAN / ITALY / SWEDEN /
SWITZERLAND or equivalent accepted / approved by the engineer.
4.23.3 Supplying and fitting of heat shr.ink joint kit complete with DIN ferrules & G.I
armored case at the point of jointing of cables for 4-core / 1000 V grade
PVC insulated & sheathed armored / non-armored cable of the following
sizes Made in GERMANY / JAPAN / USA / UK / FRANCE / JAPAN /
ITALY / SWEDEN / SWITZERLAND or equivalent country accepted /
approved by the engineer.
4.24 Supplying and fixing of heat shrink self-amalgamating tape of the following
sizes for bus-bar of both HT switch-gear (11 KV) & LT switch-gear / PFI,
transformer terminals as protection against flash-over.
VOLTMETER
4.25.1 Providing and fixing voltmeter of range 0-500 volt as per sample approved
by the engineer-in-charge (Origin: JAPAN / TAIWAN / CHINA or equivalent
country accepted / approved by the engineer.) each Tk. 700.00
4.25.2 Providing and fixing 500 volt grade 4-way selector switch for voltmeter as
per sample approved by the engineer-in-charge (Origin: JAPAN / TAIWAN /
CHINA or equivalent country accepted / approved by the engineer.)
each Tk. 459.00
AMMETER
4.26 Providing and fixing 500 volt grade Ammeter of following range and as per
sample approved by the engineer-in-charge (Origin: JAPAN / TAIWAN /
CHINA or equivalent country accepted / approved by the engineer.)
SUB-HEAD-4 PWD SoR 2018 FOR E/M WORKS 13
4.27 Providing and fixing 500 volt grade 3-way ammeter selector switch as per
sample approved by the engineer-in-charge (Origin: JAPAN / TAIWAN /
CHINA or equivalent country accepted / approved by the engineer.) each Tk. 459.00
4.28.(i) 12A (Ith 27A) magnetic contactor ------------------------------------- each Tk. 2,687.00
4.28.(ii) 25A (Ith 45A) magnetic contactor ------------------------------------ each Tk. 3,759.00
4.28.(iii) 32A (Ith 55A) magnetic contactor ------------------------------------ each Tk. 8,015.00
4.28.(iv) 38A (Ith 60A) magnetic contactor ------------------------------------ each Tk. 12,225.00
4.28.(v) 65A (Ith 115A) magnetic contactor ------------------------------------ each Tk. 20,301.00
4.28.(vi) 80A (Ith 125A) magnetic contactor ------------------------------------ each Tk. 24,602.00
4.28.(vii) 95A (Ith 145A) magnetic contactor ------------------------------------ each Tk. 28,753.00
Supply & fixing 415 / 400 / 380 V, 50 Hz thermal overload relay suitable for
use with magnetic contactors SIEMENS / TELEMECANIQUE / ABB /
SCHNEIDER / DORMAN SMITH / VITZRO or equivalent brand
accepted/approved by the engineer of the following ratings .
CUT-OUT
4.31 Supply & fixing 500 volt grade rewire able fuse link porcelain carrier cutout
(foreign made) on prepared board of the following ratings.
4.31.1 15 Amps. Rating ----------------------------------------------------------- each Tk. 36.00
4.31.2 30 Amps. Rating ---------------------------------------------------------- each Tk. 72.00
4.31.3 60 Amps. Rating ----------------------------------------------------------- each Tk. 145.00
4.31.4 100 Amps. Rating --------------------------------------------------------- each Tk. 217.00
4.31.5 200 Amps. Rating --------------------------------------------------------- each Tk. 423.00
SUB-HEAD-4 PWD SoR 2018 FOR E/M WORKS 15
Annexure: 4
The low impedance prefabricated sand witch type main bus bar trunking system shall conform to IEC 439/1-2, tested Seismic
standard shall be suitable for use in installation conforming to IEC 364.
The low impedance prefabricated sand witch type main bus bar trunking system shall conform to IEC 439/1-2, tested seismic
standard shall be suitable for use in installation conforming to IEC 364.
Tap-off units must be designed in such a way so that the tap-off units can be fitted or removed while the system i.e. the main
bus bar trunking is energized.
Circuit breakers in the Tap-off units shall be of quick make, quick break, trip-free indicating type having adjustable thermal
over-current and adjustable instantaneous electro-magnetic short circuit release having the rated interrupting capacity.
All the components of the BBT i.e. main bus bar length, reduction unit, fire barrier, fixing bracket, tap-off boxes with circuit
breakers, elbows, tee, feed unit, end cover, expansion unit, etc. shall be from the same manufacturer. All the joint & contact
surface shall be silver plated.
The components of BBT shall be appropriately as follows but the bidder must inspect the site and supply everything to
complete total system.
BBT-1 :
1600A Distribution Board Connection Unit : 1 No.
1600A Bends : 2 Nos.
1600A Transformer connection unit : 1 No.
1600A Straight length : 5.00 meter(approx.)
Fire Barrier : 1 Lot.
Hanger :
SUB-HEAD-4 PWD SoR 2018 FOR E/M WORKS 16
BBT-2 : :
BBT-3 : :
INSTALLATION:
The BBT system shall be fixed on floor ceiling and walls with all necessary, cutting and breaking, cleaning and mending the
same including cement/sand plastering and painting clamps, nuts, bolts as per the installation drawing of the manufacturer
aft.er getting approval from the owner / consultants. The contractor shall supply all materials required for complete installation
of the BBT system.
1) Earth resistance tests shall be made on the system, separating and reconnecting each earth connection.
2) The electrical resistance of the earth continuity conductor together with the resistance of the earthing lead measured
from the connection with the earth electrode to any other position in the completed installation shall not exceed 1
ohm.
3) Where more than one earthing sets are installed, the earth resistance between two sets shall be measured by
means of resistance bridge instrument. The earth resistance between two sets shall not exceed 1 ohm.
END OF SUB–HEAD-4
SUB-HEAD-4 PWD SoR 2018 FOR E/M WORKS