MAINTENANCE CHECKLIST – WATER PUMP
LOCATION: MONTH:
Reading/
Item Interval Status Action
N/A Normal Abnormal
A) Pump
1 Visually inspect the pump and check for
abnormal running noise and excessive M
vibration
2 Check and record on log sheet where
M
appropriate on system performance.
3 Check condition of gland packing / seal for
M
excessive wear
4 Check that the drain pipe are not choked, if
M
any
5 Check the pump bearing temperature M
6 Operate the vent valves once. M
7 Check for proper operation of flow switch
M
control system, if any.
8 Check for proper function of make up system
M
to chilled water, rectify if necessary.
9 Check for correct alignment of the motor and
M
pump, rectify if necessary.
10 Grease the bearing (if required) M
11 Check the corrosion of metal surface,
HY
framework and supporting/ mounting brackets
12 Check the performance of controls and safety
cut-outs and control panel indication lamp, HY
rectify as required.
13 Clean electrical panels including wiring
HY
terminals and connection point
14 Clean the suction strainer A
15 Refit the isolating valves, change the valve
gland and gasket, and recondition the globe A
valves, etc. if necessary.
B. Motor
1 Clean motor casing, grease and lubricate M
2 Check and report any abnormal running noise
M
and vibration.
3 Check, adjust and rectify/ repair defect on
M
circuit protective devices.
4 Perform magger test A
* Symbol M: Monthly HY: Half Year A: Annually AP: As Req’d By Performance
Pump_Rev 1
MAINTENANCE CHECKLIST – WATER PUMP
Action List:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Performed By: Date: