You are on page 1of 17

CARPENA, Alexis Jay

TMEC 3-1

Practice Problems

(2-1) A simple saturated refrigeration cycle for R-12 system operates at an evaporating temperature of-5°C and a
condensing temperature of 40°C. Determine the refrigerating effect per kg. (b) the work per kg, (c) the heat rejected at
the condenser per kg, (d) the COP. For a refrigerating capacity of 1 kW, determine (e) the total heat rejected at the
condenser, (f) the work, and (g) the volume flow rate.

Tevap = -5°C Tcond= 40°C

hf = 195.395 kj/kg hf = 238.535 kj/Kg

hg= 349.321 kj/kg hg= 367.146 kj/Kg

Psat= 260.96 kpa Psat= 960.65 kpa

h2 = Pressure @ 40°C (961 kpa) and S1 (1.557) = 372 kj/kg

v4 = vg @ -5°C = 0.06496 m3/kg

h1 = hg @ Tevap = 349.321 kj/kg

h3=h4= hf @ Tcond = 238.535 kj/kg

a) Refrigerating Effect
RE= h1-h4=(349.321 kj/kg-238.535 kj/kg) = 110.8 kj/kg

b) Work per kg
h2=h1 =372-349.3 = 22.7 kj/kg

c) Heat rejected at the condenser per kg


h2 -h3 = 372-238.5 = 133.5 kj/kg

d) COP
h1-h3/h2-h1 = 110.8-22.7 = 4.88

e) Total heat rejected at the condenser


𝑄𝑄𝑄𝑄 1𝑘𝑘𝑘𝑘/𝑠𝑠
m= = = 0.00903𝑘𝑘𝑘𝑘/𝑠𝑠
ℎ1−ℎ3 110.8𝑘𝑘𝑘𝑘.𝑘𝑘𝑘𝑘
Qc= m(h1-h3) = (0.00903 kg/s) (372-238.5)kj/kg
=1.206 kj/s

f) Work
(m)(h2-h1) = (0.00903 kg/s) (372-349.3)kj/kg
=0.205 kJ/s
g) Volume Flow rate
V1=(m)(v4)= (0.00903 kg/s) (0.06496 m3/kg)
=0.0005866 m3/kg
(2-2) An air conditioning system of a high-rise building has a capacity of 350 kW of refrigeration, uses R-12. The
evaporating and condensing temperatures are O°C and 35°C, respectively. Determine the following: (a) Mass of flash
gas per kg of refrigerant circulated, (b) Mass of R-12 circulated per second, (c)Volumetric rate of flow under suction (d)
Work of compression in kW, and (e) COP

h3 = hf at 35ºC = 233.5 kJ/kg


h1 = hg @ 0ºC = 351.48 kJ/kg
v1 = vg @ 0ºC = 0.05539 m3/kg
s1 = sg @ 0ºC = 1.55452kJ/kg·K
h2 = h @ 847.7 kPa and s2 = S1 = 368 kJ/kg
hf4 = hf @ 0°C = 200 kJ/kg
hg4 = h1 = 351.48 kJ/kg

a.) Mass of flash gas per kg of refrigerant circulated


X4 = h4 – hf4/ hfg4 = h4 – hf4/ hg4 – hf4
233.5−200 𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
=
351.48−200𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
= 0.2212kJ/kg
b.) Mass of flash gas per kg of refrigerant circulated
𝑅𝑅𝑅𝑅 𝑅𝑅𝑅𝑅 350 𝑘𝑘𝑘𝑘/𝑠𝑠
ref = = = = 2.97kg/s
𝑅𝑅𝑅𝑅 (ℎ1−ℎ4) (351.48 −233.5 )𝑘𝑘𝑘𝑘/𝑠𝑠
c.) Volumetric rate of flow under suction
V1 = mref(v1) = 2.97kg/s (0.05539 m3/kg) = 0.1645 m3/s
d.) Work of compression in kW
W = m(Wc) = m(h2 – h1) = (2.97kg/s) (368 ­ 351.48) kJ/kg
= 49.06 kW
ℎ1−ℎ4 (351.48 - 233.5)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
e.) COP = = = 7.14
ℎ2−ℎ1 (368 - 351.48)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘

(2-3) A refrigeration system using R-22 is to have a refrigerating capacity of 60kW. The evaporating temperature is -
10ºC and the condensing temperature is 42ºC. Determine (a) the volume flow rate of refrigerant at inlet to the
compressor (b) the power required by the compressor, and (c) the fraction of vapor in the mixture at entrance to the
evaporator expressed both on a mass a basis and a volume basis.

h3 = hf @ 42ºC = 252.4 kJ/kg

h3 = h4

h1 = hg @ -10ºC = 401.6kJ/kg

v1 = vg @ -10ºC = 65.34 L/kg

S1 = 1.76713kJ/kg·K

h2 = h @ Pcond = 1610Kpa and s2 = s1 = 440kj/kg

hf4 =hf@ -10ºC = 188.4 kJ/kg


hg4 = h1 = 401.6kJ/kg

(a) the volume flow rate of refrigerant at inlet to the compressor


𝑅𝑅𝑅𝑅 𝑅𝑅𝑅𝑅 60𝑘𝑘𝑘𝑘/𝑠𝑠
Mref = = =
𝑅𝑅𝑅𝑅 (ℎ1−ℎ4) (401.6− 252.4)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
V1 = (mref) (v1) = (0.4021 kg/s) (65.34 L/Kg) =26.27 L/s
(b) the power required by the compressor
Pc = (mref) (h2 ­ h1) = (0.4021 kg/s) (440 ­ 401.6) kJ/kg =15.44 kW
(c) the fraction of vapor in the mixture
ℎ4−ℎ𝑓𝑓4 (252.4 - 188.4)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
X4 = = = 0.3002
ℎ𝑓𝑓𝑓𝑓4 (401.6 - 188.4)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
So: v4 = vf4 + (x4)(vfg4) = vf4 + x4 (vg4 – vf4)

Vf4 = 0.75876 L/kg


Vg4 = 65.3399 L/kg
= 0.7588 L/kg + (0.3002) (65.34 ­ 0.7588) L/kg = 20.146 L/kg

For 1 kg of refrigerant entering the evaporator at point 4, the volume of vapor is therefore
(0.3002) (65.3399 L/kg) = 19.615L/kg
19.615
Thus fraction of vapor, volume basis = = .9736 x 100% = 97.36%
20.146

4.) A simple vapor-compression cycle develops 13tons of refrigeration. Using ammonia as refrigerant and operating at a
condensing temperature of 24ºC and evaporating temperature of -18ºC and assuming that the compression are isentropic
and that the gas leaving the condenser is saturated, find the ff: (a) Draw the ph diagram, (b) refrigerating effect in kJ/kg,
(c) circulation rate of refrigerant in kg/min, (d) power requirement, (e) volume flow in cubic meter/(min) (ton), (f) COP,
and (G) power per ton

(a) Draw the ph diagram

h3 = hf @ 24°c == 312.87 kJ/kg

h3 = h4

h1 = hg @ ­18°C = 1439.94 kJ/kg

v1 = v @ ­18°C= 0.5729 m3/kg

s1 = sg @ -18ºC 5.8720kJ/kg·K

h2 = h@ Pcond = 974kPa and s2 = s1 = 1657kJ/kg

b.) Ref Effect = (h1 – h4) = (1439.94 ­ 312.87)kJ/kg = 1127.1 k,J/kg

c.) Ref Capacity = (13tons) (211 kJ/min. ton) = 2743 kJ/min


𝑅𝑅𝑅𝑅 𝑅𝑅𝑅𝑅 2743𝑘𝑘𝑘𝑘/𝑚𝑚𝑚𝑚𝑚𝑚
Mref = = = = 2.43kg/min
𝑅𝑅𝑅𝑅 (ℎ1−ℎ4) 1127.1 𝑘𝑘,𝐽𝐽/𝑘𝑘𝑘𝑘

d.) Power requirement = (mref)(h2 - h1)

= (2.43 kg/min) (1657 1439.94) kJ/kg = 527.5 kJ/min

= (527.5kJ/min)(0.016666667)kW = 8.79 kW

e.) volume flow in cubic meter/(min) (ton)


(2.43𝑘𝑘𝑘𝑘/𝑚𝑚𝑚𝑚𝑚𝑚)( 0.5729 𝑚𝑚3/𝑘𝑘𝑘𝑘)
V1 = (mref)(v1)/(13tons) = = = 0.1071m3/(min) (ton)
13𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡

𝑅𝑅𝑅𝑅 (ℎ1−ℎ4) 1127.1 𝑘𝑘,𝐽𝐽/𝑘𝑘𝑘𝑘


f.) COP = = = = 5.19
𝑊𝑊𝑊𝑊 (ℎ2−ℎ1) (1657 1439.94) 𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘

𝑃𝑃𝑃𝑃
g.) Power per ton = = 0.676kW/ton
13𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡
5.) A refrigeration system is to be used to cool 45,000 kg of water from 29°C to 18°C in 5 hours. The
refrigerant is ammonia and the operation conditions are 616 kPa evaporating pressure and 1737 kPa
liquefaction pressure. Determine (a) the coefficient of performance, (b) the quantity of cooling water in
the condenser for an increase in temperature of 7°C, (c) the compressor power, and (d) the volume of
flow rate entering the compressor. The specific heat of water is 4.187 kJ/kg·Cº

h3 = hf @ 1737 kPa = 410.4 kJ/kg

Solve for h1 using interpolation

595.28 kPa 1470.64


616 kPa X = h1
616.25 kPa 1471.57

h1 = hg @ 616 kPa = 1471.6 kJ/kg

v1 = vg @ 616 kPa = 205.2 L/kg

s1 = 5.4924 kJ/kg·K

h2 = h @Pcond = 1737 kPa and s2 = s1 = 1620kJ/kg


𝑅𝑅𝑅𝑅 ℎ1−ℎ4 (1471.6 - 410.4)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
a.) COP = = = = 7.15
𝑊𝑊𝑊𝑊 ℎ2−ℎ1 (1620 - 1471.6)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘

b.) Quantity of cooling water in the condenser for an increase in temperature of 7°C
𝑘𝑘𝑘𝑘
(𝑀𝑀𝑀𝑀)(𝐶𝐶𝐶𝐶𝐶𝐶)(𝛥𝛥𝛥𝛥) (45,000 𝑘𝑘𝑘𝑘)�4.187 ·º𝐶𝐶�(29 - 18)º𝐶𝐶
𝑘𝑘𝑘𝑘
RC = = 𝑠𝑠 = 115.1kJ/s
𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡 5ℎ ( 3600ℎ)

Let mrefw = mass flow rate of cooling water circulated in the condenser

Heat to water = Heat from refrigerant

(mrefw )(Cpw)(Δtw) = (mref)(h2 – h3)


(𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚)(ℎ2 – ℎ3)
So: mrefw =
(𝐶𝐶𝐶𝐶𝐶𝐶)(𝛥𝛥𝛥𝛥𝛥𝛥)

(0.1085 𝑘𝑘𝑘𝑘/𝑠𝑠) (1620 - 410.4) 𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘


= (4.187)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘°C (7°𝐶𝐶)

Mrefw = 4.48 kg/s

c.) Power Requirement = (mref) (Wc) = (mref)(h2 - h1)

= (0.1085 kg/s) (1620 ­ 1471.6) kJ/kg = 16.10kW

d.) Volume flow rate

V1 = (mref) (v1) = (0.1085 kg/s) (205.2 L/kg) = 22.3 L/s

6.) An ammonia simple saturation cycle operates between evaporator and condenser temperatures of ­20°C and 35°C,
respectively. The system is to be used in producing 5000 kg of ice at ­12°C from water at 29°C in 20 hours. Assuming losses
to be 20 per cent of the heat to be absorbed from the water, determine (a) the mass flow rate, (b) the heat rejected at
the condenser, and (c) the power required by the compressor. The specific heat of ice is 2.094 kJ/kg·ºC and the heat of
fusion is 335 kJ/kg.

Time = 20h

M = 5000kg

H3 = hf @ 35°C = 366.1 kJ/kg

H1 = hg @ -20ºC = 1437.2 kJ/kg

H2 = h@Pcond =1352 kPa and s2 = s1 = 1735 kJ/kg

(a) Theoretical heat to be absorbed per kg of water

= (1 kg) (4.187 kJ/kg •ºC (29— 0) C° ( 1 kg) (335 kJ/kg)

+ 1 kg) (2.094 kJ/kg•ºC) [0 - (-12)] ºC = 481.6 kJ


Actual heat to be absorbed

Actual Qa= (1.20) (481.6) = 577.9 kJ/kg


(𝑚𝑚)(𝑄𝑄𝑄𝑄) 5000 𝑘𝑘𝑘𝑘 (577.9 𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘)
RC = = 40.13kJ/s
𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡 (20ℎ)(3600)𝑠𝑠/ℎ

𝑅𝑅𝑅𝑅 𝑅𝑅𝑅𝑅 40.13𝑘𝑘𝑘𝑘/𝑠𝑠


Mref = = = = 0.03747 kg/s
𝑅𝑅𝑅𝑅 (ℎ1−ℎ4) (1437.2 −366.1) 𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘

b.) Q R = (mref)(h2 – h3) = (0.03747 kg/s) (1735 - 366.1) kJ/kg = 51.29 kJ/s

c.) Pc = (mref) (h2 — h1) = (0.03747 kg/s) (1735 — 1437.2) kJ/kg

Pc = 11.16kW

An ammonia refrigerating cycle operates at 247 kPa suction pressure and 1200 kPa condenser pressure.
Other data are the following:

refrigerating capacity 28 kW

compressor clearance 5%

compression efficiency 80%

mechanical efficiency 75%

actual volumetric efficiency 74%

Determine (a) the clearance volumetric efficiency, (b) the ideal and actual COP, (c) the mass flow rate of
ammonia, and (d) the brake work.

h3 = hf @ 1200 kPa =­ 346.1 kJ/kg

h3 = h4

h1 = hg @ 247 kPa = 1445.2 kJ/kg

h2 = h @1200 kPa and s2 = s1 = 1675 kJ/kg

a.) Ƞvc = 1 +c – c[p2/p1]1/k 1 + 0.05 – (0.005) [ 1200/247]1/1.304


.882 x 100%
88.2%

b.) Actual work = isentropic work/ Ƞc


ℎ2−ℎ1 (1675 - 1445.2)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
= = = 287.3kJ/kg
0.80 0.80

𝑅𝑅𝑅𝑅 ℎ1−ℎ4 (1445.2 - 346.1)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘


Ideal COP = = = = 4.78
𝑊𝑊𝑊𝑊 ℎ2−ℎ1 (1675 - 1445.2)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘

𝑅𝑅𝑅𝑅 ℎ1−ℎ4 (1445.2 - 346.1)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘


Actual COP = = = 3.83
𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴𝐴 𝑊𝑊𝑊𝑊𝑊𝑊𝑊𝑊 287.3 (287.3)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘

𝑅𝑅𝑅𝑅 𝑅𝑅𝑅𝑅 28𝑘𝑘𝑘𝑘/𝑠𝑠


c.) Mref = = = = 0.02547 kg/s
𝑅𝑅𝑅𝑅 (ℎ1−ℎ4) (1445.2−346.1) 𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
d.) WI = (mref)(Actual work) = (0.02547 kg/s)( 287.3kJ/kg) = 7.318kW
𝑊𝑊𝑊𝑊 7.318𝑘𝑘𝑘𝑘
e.) WB = = = 9.76kW
Ƞm 0.75

8.) An ammonia simple saturation cycle operates at 247.1 kPa suction pressure and 1169 kPa condenser pressure. For a
load of 1688 kJ/min, determine (a) the m3/h of cooling water in the condenser if the water temperature is increased by
6ºC, (b) the compressor work, and (c) the piston displacement if clearance is 5%

H3 = h @ 30ºC = 341.77 kJ/kg


H1 = h @ ­14ºC = 1445.2 kJlkg

V1 = vg @ -14ºC = 0.4878m3/kg

H2 = h @ 1169 kPa and s2 = s1 = 1677 kJ/kg

V2 = v @ 1169 kPa and s2 = s1 = 0.15m3/kg

a.) cs
𝑘𝑘𝑘𝑘
(𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚)(ℎ2−ℎ1) �1.53𝑚𝑚𝑚𝑚𝑚𝑚�(1677 - 341.77)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
Mref w = = 𝑘𝑘𝑘𝑘
(𝐶𝐶𝐶𝐶𝐶𝐶)(𝛥𝛥𝛥𝛥𝛥𝛥) (4.187) ·º𝐶𝐶 (6º𝐶𝐶)
𝑘𝑘𝑘𝑘
= 81.32kg/min
𝑚𝑚𝑚𝑚 (81.32 𝑘𝑘𝑘𝑘/𝑚𝑚𝑚𝑚𝑚𝑚) (60 𝑚𝑚𝑚𝑚𝑚𝑚/ℎ)
Vw = = 𝑘𝑘𝑘𝑘 = 4.879m3/h
𝑃𝑃𝑃𝑃 (1000𝑚𝑚3)
b.) Wc = (mref)(h2 – h1) = (1.52 kg/min) (1677 ­ 1445.2) kJ/kg
= 352.3kJ/min x 0.0166666667
= 5.87kW
c.) Ƞvc = 1 + c – c [p2/p1]1/k
= 1 + 0.05 – ( 0.05) [1169/247.1]1/1.304
= 0.8854

9) A six­cylinder, 6.70 x 5.70­cm, refrigerant 22 compreasor operating at 30 r/s indicate a refrigerating capacity of 96.4 kW
and a power requirement of 19.4 kW at an evaporating temperature of 5°C and a condensing temperature of 35°C.
compute (a) the clearance volumetric efficiency if the clearance volume is 5 per cent, (b) the actual volumetric efficiency,
and (c) the compression efficiency.

h3 = hf @ 35ºC =243.1 kJ/kg

h1 = hg @ 5ºC = 407.1 kJ/kg

v1 = vg @ 5ºC =40.36 L/kg

h2 = h @ Pcond =1355 kPa and s2 = s1 = 428 kJ/kg

v2 = v at 1355 kPa and s2 = s1 = 20 L/kg

𝑣𝑣1 40.36
a.) Ƞvc = 1 - c [ − 1] = 1 – (0.05) −1
𝑣𝑣2 20
= 0.9491 x 100%
= 94.91%
𝑅𝑅𝑅𝑅 𝑅𝑅𝑅𝑅 96.4𝑘𝑘𝑘𝑘/𝑠𝑠
b.) Mref = = = = 0.5878 kg/s
𝑅𝑅𝑅𝑅 (ℎ1−ℎ4) (407.1−243.1) 𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
V1 = (mref)(v 1 ) = (0.5878 kg/s)( 40.36 L/kg) = 23.72L/s
𝜋𝜋 (𝜋𝜋)(6.60𝑐𝑐𝑐𝑐)2 (5.70𝑐𝑐𝑐𝑐)(30𝑥𝑥6)𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐/𝑠𝑠
VD = D 2 LN = 1000𝑐𝑐𝑚𝑚3
= 36.17L/s
4 4( )
𝐿𝐿
𝑉𝑉1 23.72𝐿𝐿/𝑠𝑠
Ƞva = = = 0.6558 x 100% =65.58%
𝑉𝑉𝑉𝑉 36.17𝐿𝐿/𝑠𝑠
𝑅𝑅𝑅𝑅 19.4kJ/s
c.) W ca = = = 33kJ/kg
𝑚𝑚𝑚𝑚𝑚𝑚𝑚𝑚 0.5878
Wc = (h2 – h1) = (428 ­ 407.1) kJ/kg = 20.9kJ/kg
𝑊𝑊𝑊𝑊 20.9
Ƞc = = = 0.6333 x 100% = 63.33%
𝑊𝑊𝑊𝑊𝑊𝑊 33

10.) A 100 x 200­mm ammonia compressor with a compression efficiency of 80 per cent operates with a suction
pressure of 291.6 kPa and a condenser pressure of 1204 kPa at 23 r/s. The refrigerant cools 102 kg/min of brine
by 8 degrees in the brine cooler. The specific heat of the brine is 3.14 kJ/kg·ºC. Electric input to the motor driving
the compressor is 14.33 kW. Motor efficiency at this load is 92 per cent. Assuming 5 per cent of the useful
refrigerating effect is lost by brine cooler from the room, determine the mechanical and volumetric efficiencies
of the compressor

Given:
Cpb = 3.14 kJ/kg·ºC
Compression efficiency = 80%
Motor efficiency = 92%
Lost of useful RE = 5% = 0.05

M b =102kg/min
Electric input to the motor = 14.33kW
Properties
h3 = hf @1204 kPa = 346.6 kJ/kg
h3 = h4
h1 = hg @ 291.6 kPa = 1450.2 kJ/kg
v 1 = vg @ 291.6 kPa = 417.5 L/s
h2 = hat 1204 kPa and s2 = s1 = 1653 kJ/kg

Solve for RC – refrigerating capacity

RC = (1.05) (m b) (C pb) (Δtb) = (1.05) (102) (3.14) (8) = 2690 kJ/min

= 2690kJ/min x 0.016666667

= 44.83kW
𝑅𝑅𝑅𝑅 𝑅𝑅𝑅𝑅 44.83𝑘𝑘𝑘𝑘/𝑠𝑠
Mref = = = = 0.0.0406 kg/s
𝑅𝑅𝑅𝑅 (ℎ1−ℎ4) (1450.2 −346.6) 𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘

Pc = (mref)(h2 - h1) = (0.0406)kg/s (1653 ­ 1450.2)kJ/kg = 8.23 kW


8.23 8.23
WI = = = 10.29kW
Ƞc 0.80

Brake work = (work input)(motor efficiency)

= (14.33) (0.92) = 13.18 kW

Solving for Mechanical Efficiency


𝑊𝑊𝑊𝑊 10.29𝑘𝑘𝑘𝑘
Ƞm = = 0.781 x 100% = 78.1%
𝑊𝑊𝑊𝑊 13.18𝑘𝑘𝑘𝑘

V 1 = (mref)(v 1 ) = (0.0406 kg/s)( 417.5 L/kg) = 16.96L/s


𝜋𝜋 (𝜋𝜋)(10𝑐𝑐𝑐𝑐)2 (20𝑐𝑐𝑐𝑐)(23)𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐/𝑠𝑠
VD = D 2 LN = 1000𝑐𝑐𝑚𝑚3
= 21.68L/s
4 4( )
𝐿𝐿
𝑉𝑉1 16.96𝐿𝐿/𝑠𝑠
Ƞva = = = 0.7818x 100% = 78.18%
𝑉𝑉𝑉𝑉 21.68𝐿𝐿/𝑠𝑠
(2-11) A four-cylinder refrigerant 12 compressor operates between evaporator and condenser temperatures of 4°C and
43°C. It is to carry a load of 20 tons of refrigeration at 1200 rpm. If the average piston speed is 213 m/min and the actual
volumetric efficiency is 80 per cent, what should be the bore and stroke of the compressor.

Effects of Operating Conditions


Effects of Increasing the vaporizing Temperature
(2-12) A R-12 simple saturated refrigerating cycle operates at an evaporating temperature of -10°C and a condensing
temperature of 40°C. Show the effects of increasing the vaporizing temperature to 5°C.

(2-13) A simple saturated refrigerating cycle using R-12 as the refrigerant, operates at a condensing temperature of 40°C
and an evaporating temperature of -10°C. Show the effects of increasing the condensing temperature to 50°C.
H1=hg @-10°C = 347.1 kj/kg
V1=Vg @-10°C = 0.07665 m3/kg

For the 40°C condensing cycle (cycle 1-2-3-4-1)

h3=h4=hf @40°C = 238.5 kj/kg

h2=h @ 961 kPa and s2 equal to s1 = 373 kj/kg

For the 50°C condensing cycle (1-2’-3’-4’-1)

h3=h4=hf @ 50°C = 248.9 kJ/kg

h2=h @ 1219 kPa and s2 equal to s1 = 378 kj/kg

a) Refrigerating effect
For the 40°C condensing cycle, the refrigerating effect
= h1=h4= 347.1-238.5 = 108.6 kj/kg
For the 50°C condensing cycle, the refrigerating effect
=h1-h4= 347.1-248.9=98.2 kj/kg
b) Effect on mass flow rate per ton
For the 40°C condensing cycle, the mass flow rate,
211 211
m= = =1.943 kg/(min)(ton)
ℎ1−ℎ4 347.1−238.5

For the 50°C condensing cycle, the mass flow rate,


211 211
m’= = =2.149kg/(min)(ton)
ℎ1−ℎ4′ 347.1−248.9

c) Effect on compressor volume capacity


For the 40°C condensing cycle, the volume flow rate,

V1=(m)(v1)=(1.943)(0.07665)=0.1489m3/(min)(ton)

For the 50°C condensing cycle, the volume flow rate,

V1’=(m’)(v1)=2.149(0.07665)

=0.1647 m3/(min)(ton)

d) Effect on COP
For the 40°C condensing cycle
ℎ1−ℎ4 347.1−238.5
COP= = = 4.19
ℎ2−ℎ1 373−347.1
For the 50°C condensing cycle
ℎ1−ℎ4 347.1−248.9
COP= = =3.18
ℎ2′−ℎ1 378−347.1

e) Effect on work per ton of refrigeration


For the 40°C condensing cycle, the work
W=(m)(h2=h1) = (1.943)(373-347.1)
=50.32kJ/(min)(ton) or 0.839 kW/ton
For the 50°C condensing cycle, the work
W=(m’)(h2’=h1) = (2.149)(378-347.1)
=66.40kJ/(min)(ton) or 1.1067 kW/ton

f) Effect on condenser Performance


For the 40°C condensing cycle, the heat rejected at the condenser
Qc=(m)(h2-h3) = 1.943(373.238.5)
=261.3kJ/(min)(ton) or 4.355 kW/ton
For the 50°C condensing cycle, the heat rejected at the condenser
Q’c=(m’)(h2’-h3’) = 1.943(373.238.5)
=277.4 kJ/min(ton) or 4.623 kW/ ton

Effects of increasing the condenser temperature


1 The refrigerating effect per unit mass decreases
2) The mass flow rate per ton increases.
3) The volume flow rate per ton increases.
4) The COP decreases.
5) The work per ton increases.
6) The heat rejected at the condenser per ton increases

(2-14) A 150 x 150mm, twin-cylinder, single acting refrigerant 12 compressor running at 25 r/s carries a refrigerating
load of 39.4 kW while operating at 340 kPa suction and 1277 kPa discharge pressures. If the discharge pressure were
raised to 1397 kPa, at what speed should the compressor must run to carry the same load assuming the volumetric
efficiency remain the same.

h1=hg at 340 kPa = 352.8 kJ/kg

h3 =hf at 1277 kPa = 251 kJ/kg

h3’=hf at 1397 kPa = 255.3 kJ/kg

Let m = old mass flow rate


m = new mass flow rate

n = old compressor speed D2

n' = new compressor speed


𝑄𝑄𝑄𝑄 39.4𝑘𝑘𝑘𝑘/𝑠𝑠
m= = = −.3870 𝑘𝑘𝑘𝑘/𝑠𝑠
ℎ2−ℎ3 (352.8−251)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘

𝑄𝑄𝑄𝑄 39.4𝑘𝑘𝑘𝑘/𝑠𝑠
m’= = = −.4041𝑘𝑘𝑘𝑘/𝑠𝑠
ℎ2−ℎ3′ (352.8−255.3)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘

𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣 𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟 𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒𝑒 𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐


Volumetric efficiency=
𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟 𝑜𝑜𝑜𝑜 𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐

(𝑚𝑚′ )(𝑛𝑛) (0.4041)(25)


n’= =
𝑚𝑚 0.3870

Effects of superheating the Suction Vapor

(2-15) A simple saturated refrigerating cycle for R-12 system operates at an evaporating temperature of -5°C and a
condensing temperature of 40°C. Show the effects of superheating the suction vapor from -5°C to 15 C.

For the saturated cycle (cycle 1-2-3-4-1)

V1=Vg at -5°C= 0.06496 m3/kg

h1= hg at -5°C = 349.3 kJ/kg

h2=h at 961 kPa and s2 equal to s1= 372 kJ/kg

For the superheated cycle (cycle 1’-2’-3-4-1’)

V1’=V at 261 kPa and 15°C = 0.071 m3/kg

h1’= h at 261 kPa and 15°C = 362 kJ/kg

h2’=h at 961 kPa and s2 equal to s1= 372 kJ/kg

a) Refrigerating effect
For the saturated cycle, the refrigerating effect is
= h1-h4= 349.3-238.5 = 110.8 kJ/kg

For the superheated cycle


1) When superheating of suction vapor occurs inside the refrigerated space, useful cooling results and the
refrigerating effect is
=h1’-h4=362-238.5=123.5 kJ/kg
2) When superheating of suction vapor occurs in the suction line, no useful cooling results and the refrigerating
effect is
=h1-h4=349.3-238.5=110.8 kJ/kg
b) Effect on mass flow rate per ton
For the saturated cycle, the mass flow rate,
211 211
𝑚𝑚 = = = 1.904𝑘𝑘𝑘𝑘/(𝑚𝑚𝑚𝑚𝑚𝑚)(ton)
ℎ1 − ℎ4 349.3 − 238.5

For the superheated cycle,

1) With useful cooling, the mass flow rate,


211 211
𝑚𝑚′ = = =1.709kg/(min)(ton)
ℎ1′−ℎ4 362−238.5
2) Without useful cooling, the mass flow rate,
211 211
𝑚𝑚′′ = = =1.904kg/(min)(ton)
ℎ1′−ℎ4 349−238.5

c) Effect on compressor volume capacity


For the saturated cycle, the volume flow rate,
Vr=(m)(v1) = (1.904)(0.06496)=0.1237m3/(min)(ton)

For the superheated cycle,


1) With useful cooling, the volume flow rate,
Vr=(m’)(v1) = (1.709)(0.091)
= 0.1213 m3/(min)(ton)
2) Without useful cooling, the volume flow rate
Vr=(m’)(v’1) = (1.904)(0.071)
= 0.1352 m3/(min)(ton)

d) Effect on COP
ℎ1−ℎ4 349.3−238.5
For the saturated cycle, COP = = = 4.88
ℎ2−ℎ1 372−349.3
For the saturated cycle
ℎ1′ −ℎ4 362−238.5
1) With useful cooling, COP = = = 4.94
ℎ2′ −ℎ1′ 387−362
ℎ1−ℎ4 349.3−238.5
2) Without useful cooling, COP = = 4.43
ℎ2′−ℎ1′ 387−362

e) Effect on work per ton of refrigeration


For the saturated cycle, the work,
W= (m)(h2-h1) = (1.904) (372-349.3)
=43.22 kJ/(min)(ton) or 0.720 kW/ton

For the superheated cycle


1) With useful cooling, the work,
W’ = (m) (h2’-h1’) = (1.709) (387-362)
=42.73 kJ/(min) (ton) or 0.712 kW/ton
2) Without useful cooling, the work.
W’’ = (m’) (h2’-h1’) = (1.904) (387-362)
=47.6 kJ/(min) (ton) or 0.793 kW/ton

f) Effect on condenser performance


For the saturated cycle, the heat rejected at the condenser
Qc = (m) (h2-h3) = (1.904) (372-238.5)
= 254.2 kJ/ (min) (ton) or 4.24 kW/ton
For the superheated cycle.
1) With useful cooling, the heat rejected at the condenser,
Q’c = (m’) (h2’-h3) = (1.709) (387-238.5)
= 253.8 kJ/ (min) (ton) or 4.23 kW/ton
2) Without useful cooling, the heat rejected at the condenser,
Q’c’ = (m) (h2’-h3) = (1.904) (387-238.5)
= 282.7 kJ/ (min) (ton) or 4.71 kW/ton

Effects of superheating the suction vapor


When superheating produces useful cooling
(1) The refrigerating effect per unit mass increases
(2) The mass flow rate per ton decreases.
(3) The volume flow rate per ton decreases.
(4) The COP increases.
(5) The work per tun decreases.
When superheating occurs without useful cooling:
(6) The refrigerating effect per unit mass remains the same
(7) The mass flow rate per ton remains the same.
(8) The volume flow rate per ton increases.
(9) The COP decreases.
(10) The work per ton increases.
(1) The heat rejected at the condenser per ton increases.

(2-16) A simple saturated refrigerating cycle using R-12 as the refrigerant operates at an evaporating temperature of -
5°C and a condensing temperature of 40°C. Show the effects of subcooling the liquid from 40°C to 30°C before
reaching the expansion valve.

V1 = Vg at -5°C = 0.06496 m3/kg


H1 = hg at -5C = 349.3 Kj/kg
H2 = at 961 kPa and s2 equal

For the saturated cycle (cycle 1-2-3-4-1)

h3=h4=hf @40°C = 238.5 kj/kg

For the subcooled cycle (cycle 1-2-3’-4’-1)


h3=h4’=hf @30°C = 228.5 kj/kg

a) Refrigerating effect
For the saturated cycle, the refrigerating effect = h1 – h4
=349.3 – 238.5 = 110.8 kJ/kg
For the subcooled cycle, the refrigerating effect = h1 – h4’

b) Effect on mass flow rate per ton


For the saturated cycle, the mass flow rate
211 211
m= = =1.918 kg/(min)(ton)
ℎ1−ℎ4 349.3−238.5

For the subcooled cycle, the mass flow rate,


211 211
m’= = =1.747 kg/(min)(ton)
ℎ1−ℎ4′ 349.3−228.5

c) Effect on compressor volume capacity

For the saturated cycle, the volume flow rate

V1= (m) (v1) = (1.918) (0.06496) = 0.1246 m3/ (min) (ton)

For the subcooled cycle, the volume flow rate

V1= (m’) (v1) = (1.747) (0.06496) = 0.1135 m3/ (min) (ton)

d) Effect on COP
ℎ1−ℎ4 349.3−238.5
For the saturated cycle, COP = = = 4.88
ℎ2−ℎ1 372−349.3
ℎ1−ℎ4′ 349.3−228.5
For the subcooled cycle, COP = = = 5.32
ℎ2−ℎ1 372−349.3

e) Effect on work per ton of refrigeration


For the saturated cycle, the work,
W= (m) (h2-h1) = (1.918) (372-349.3)
=43.53 kJ/ (min) (ton) or 0.726 kW/ ton
For the subcooled cycle, the work,
W’= (m’) (h2-h1) = (1.747) (372-349.3)
=39.66 kJ (min) (ton) or 0.661 kW/ ton

f) Effect on condenser performance


For the saturated cycle, the heat rejected at the condenser
Qc = (m) (h2-h3) = (1.918) (372-238.5)
= 256.1 kJ/ (min) (ton) or 4.268 kW/ton
For the subcooled cycle, the heat rejected at the condenser,
Q’c = (m) (h2-h3) = (1.747) (372-228.5)
= 250.7 kJ/ (min) (ton) or 4.178 kW/ton

Effects of subcooling the liquid


(1) The refrigerating effect per unit mass increases.
(2) The mass flow rate per ton decreases.
(3) The volume flow rate per ton decreases.
(4) The COP increases.
(5) The work per ton decreases.
(6) The heat rejected at the condenser per ton decreases.

(2-17) A refrigerant 22, four cylinder, 85 x 70-mm, compressor operating at 28 r/s, a condensing temperature of 38°C,
and an evaporating temperature of -2°C carries a refrigerating load of 112 kW. The motor driving the compressor has
an efficiency of 92 per cent and draws 32.5 kW. There is a 5 C subcooling and 7°C superheating of the suction gas
entering the compressor. Compute (a) the actual volumetric efficiency and (b) the compression efficiency.

H3 = hf at 33°C = 240.5 kJ/kg


H1 = h at 5°C and 466kPa = 410 kJ/kg
V1 = v at 5°C and 466kPa = 53L/kg
H2 = h at 1460 kPa and S2 equal to S1 = 440 kJ/kg
𝑄𝑄𝑄𝑄 112𝑘𝑘𝑘𝑘/𝑠𝑠
a) m = = (410−240.5)𝑘𝑘𝑘𝑘 = 0.6608𝑘𝑘𝑘𝑘/𝑠𝑠
ℎ1−ℎ3
V1 = mv1 = (0.6608) (53) = 35.02L/s
𝜋𝜋 (8.5𝑐𝑐𝑐𝑐)2 (7.0𝑐𝑐𝑐𝑐) (28𝑥𝑥4𝑥𝑥𝑥𝑥𝑥𝑥𝑥𝑥𝑥𝑥𝑥𝑥𝑥𝑥)
Vd = 𝞹𝞹/4 D2LN = 𝑐𝑐𝑐𝑐3 = 44.49L/s
(4)(1000 )
𝐿𝐿
𝑉𝑉1 35.02
nva = = = 0.7871 𝑜𝑜𝑜𝑜 78.71%
𝑉𝑉𝑉𝑉 44.49

b) Isentropic work = (m) (h2-h1) = (0.6608) (440-410) = 19.82 kW


Actual work = (32.5) (0.92) = 29.90kW
Compression efficiency, nc = 19.82/29.90 = 0.6629 or 66.29%

(2-18) (2-18) An ammonia compressor operates at an evaporator pressure of 316 kPa and a condenser pressure of
1514.2 kPa. The refrigerant is subcooled 5 degrees and is superheated 8 degrees. A twin-cylinder compressor with
bore to stroke ratio of 0.85 is to be used at 1200 rpm. The mechanical efficiency is 77h.
For a load of 87.5 kW, determine:
(a) the quantity of cooling water in the condenser if the
increase in temperature 1s degrees,
(b) the bore and stroke,
(c) the size of the driving motor, and
(d) the quality of the refrigerant entering the evaporator.

h3 = hf at 34° = 361.2 kJ/kg


h1 = h at 316 kPa and 0°C = 1472 kJ/kg
v1 = v at 316 kPa and 0°C = 0.41 m3/kg
h2 = h at 1514.2 kPa and s2 equal to s1 = 1715 kJ/kg
𝑄𝑄𝑄𝑄 87.5𝑘𝑘𝑘𝑘/𝑠𝑠
a) m = = (1472−361.2)𝑘𝑘𝑘𝑘 = 0.07877𝑘𝑘𝑘𝑘/𝑠𝑠
ℎ1−ℎ3

𝑚𝑚 (ℎ2−ℎ3) (0.07877𝑘𝑘𝑘𝑘/𝑠𝑠)(1715−361.2)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
mw = (𝐶𝐶𝐶𝐶)(𝛥𝛥𝛥𝛥𝛥𝛥) = 𝑘𝑘𝑘𝑘 = 3.64 kg/s
4.187𝑘𝑘𝑘𝑘𝐶𝐶°(7𝐶𝐶°)
b) V1= (m) (v1) = (0.07877 kg/s) (410 L/kg) = 32.3 L/s
Assume nva = 100%, then Vd = V1 = 32.3 L/s
𝜋𝜋 (0.85𝐿𝐿𝐿𝐿𝐿𝐿)2 (𝐿𝐿𝐿𝐿𝐿𝐿) (20𝑥𝑥2𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐)
Vd = 𝞹𝞹/4 D2LN = 𝑐𝑐𝑐𝑐3 = 0.0227L3L/s
(4)(1000 )
𝐿𝐿

0.0227L3 = 32.3
L = 11.25 cm
D = (0.85) (11.25) = 9.56 cm

c) W = (m) (h2-h1) = (0.07877 kg/s) (1715 – 1472) kJ/kg = 19.14kW


Power input to compressor = power output of motor = 19.14/0.77
=24.86kW

ℎ4−ℎ𝑓𝑓4 361.2−163.2
d) X4 = = = 0.1536 𝑜𝑜𝑜𝑜 15.36%
𝒉𝒉𝒉𝒉𝒉𝒉𝒉𝒉 1289.44

(2-19) A 10-ton vapor compression refrigeration system is


to evaporate R-12 at-20°C and to condense it at 40°C. The twin-
cylinder vertical compressor is to run at 900 rpm; it is single
acting, has the bore equal to the stroke, and has 2% clearance.
Vapor enters the compressor at -10°C and liquid enters the
expansion valve at 30°C.
(a) What refrigeration flow rate is required?
(b) What would be the bore and stroke of the compressor?
(c) What power is required by the compressor?
(d) What is the quantity of the cooling water required in the
condenser for an 8-degree increase in temperature?

h3 = hf at 30°C = 228.53 kJ/kg

h1 = h at 150.9 kPa and -10°C = 348 kJ/kg

v1 = v at 150.9 kPa and -10°C = 0.12 m3/kg

h2 = h at 960.7 kPa and s2 equal to s1 = 383 kJ/kg

v2 = v at 960.7 kPa and s2 equal to s1 = 0.021 m3/kg


𝑘𝑘𝑘𝑘
(10𝑡𝑡𝑡𝑡𝑡𝑡𝑡𝑡)(3.52 )
a) m = Qe/h1-h3 = (348−228.54)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
𝑡𝑡𝑡𝑡𝑡𝑡
= 𝟎𝟎. 𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒌𝒌𝒌𝒌/𝒔𝒔
0.12
b) nvc = 1 – c [(v1-v2) / -1] = 1-0.02 [ − 1] = 0.9057
0.021
V1 = (m) (v1) = (0.2947 kg/s) (0.12 m3/kg) = 0.03536 m3/s
Assume nva= nvc
𝑉𝑉1 0.03563 𝑚𝑚3 𝑚𝑚3
Vd = = = 0.03904 𝑜𝑜𝑜𝑜 2.3424
𝑁𝑁𝑁𝑁𝑁𝑁 0.09057 𝑠𝑠 𝑚𝑚𝑚𝑚𝑚𝑚
Vd = 𝞹𝞹/4 D2LN = 𝞹𝞹/4(D m)2 (D m) (900x2cycles/min)
=1413.7 D3m3/min
1413.7 D3 = 2.3424
D = 0.1183m or 11.83cm
L = 11.83cm

c) W = (m) (h2 – h1) = (0.2947 kg/s) (383-348) kJ/kg


=10.31kW

𝑚𝑚 (ℎ2−ℎ3) (0.2947𝑘𝑘𝑘𝑘/𝑠𝑠)(383−228.54)𝑘𝑘𝑘𝑘/𝑘𝑘𝑘𝑘
d) mw = (𝐶𝐶𝐶𝐶)(𝛥𝛥𝛥𝛥𝛥𝛥) = 𝑘𝑘𝑘𝑘 = 1.36 kg/s
4.187𝑘𝑘𝑘𝑘𝐶𝐶°(8𝐶𝐶°)
(2-20) A simple saturated refrigerating cycle using R-12 as refrigerant operates at an evaporating temperature of -5°C
and a condensing temperature of 40°C. Show the effects of installing a heat exchanger that would superheat the
suction vapor from -5°C to 15°C in the heat exchanger.
h1 = h at 261 kPa and 15°C = 362 kJ/kg
h2 = h at 961 kPa and s2 equal to s1 = 387 kJ/kg
h3 = hf at 40°C = 238.5 kJ/kg
Heat balance of the heat exchanger
h 3 + h6 = h1 = h4

Refrigerating effect = h6-h4 = h1-h3


ℎ1−ℎ3 362−238.5
COP= = = 4.94
ℎ2−ℎ1 387−362

The coefficient of performance of the heat exchanger cycle differs than of the saturated cycle by only
4.94 − 4.88
= 1.23%
4.88
Depending upon the particular case, the coefficient of performance of a heat exchanger cycle may be either greater
than, less than, or the same as that of a saturated cycle operating between the same pressure limits.

(2-21) A refrigerant 22 vapor compression system includes a liquid-to-suction heat exchanger in thc system. The heat
exchanger cools saturated liquid coming from the condenser from 32°C to 21°C with vapor which comes from the
evaporator at 10°C. (a) Calculate the COP of the system without the heat exchanger but with the condensing
temperature a 32°C and an evaporator temperature at -10°C. (b) Calculate the COP of the system with the heat
exchanger. (c) If the compressor is capable of pumping 20 L/s measured at the compressor suction, what is the
refrigerating capacity of the system without the heat exchanger? (d) With the same compressor capacity as in (c),
what is the refrigerating capacity of the system with the heat exchanger?

a)

h3 = hf at 32°C = 239.2 kJ/kg

h1 = hg at -10°C = 401.6 kJ/kg

V1 = Vg at -10°C = 65.34 L/kg

h2 = h at 1255 kPa and s2 equal to s1 = 433 kJ/kg


ℎ1−ℎ3 401.6−239.2
COP= = = 𝟓𝟓. 𝟏𝟏𝟏𝟏
ℎ2−ℎ1 433−401.6

b)

h3 = hf at 32°C = 239.2 kJ/kg

h4 = h5 = hf at 21°C = 225.3 kJ/kg

h6 = hg at 10°C = 401.6 kJ/kg

H1 + h4 = h3 + h6

h1 = 239.2 + 401.6 -225.3 = 415.5 kJ/kg

V1 = 72 L/kg

h2 = h at 1255 kPa and s2 equal to s1 = 450kJ/kg


ℎ6−ℎ5 401.6−225.3
COP= = = 𝟓𝟓. 𝟏𝟏𝟏𝟏
ℎ2−ℎ1 450−415.5

c) Without the heat exchanger


20𝐿𝐿/𝑠𝑠
m = V1/v1 = = 0.3061 𝑘𝑘𝑘𝑘/𝑠𝑠
65.34𝐿𝐿/𝑘𝑘𝑘𝑘

Qe = (m) (h1-h4) = (0.3061 kg/s) (401.6-239.2)kJ/kg


=49.71 kW

d) With the heat exchanger


20𝐿𝐿/𝑠𝑠
m = V1/v1 = = 0.2777 𝑘𝑘𝑘𝑘/𝑠𝑠
72𝐿𝐿/𝑘𝑘𝑘𝑘
Qe = (m) (h6-h5) = (0.2777 kg/s) (401.6-225.3) kJ/kg
=48.96 kW

You might also like