CONSTRUCTION OF PT.

VIJAYATEX
JLN. AHMAD YANI III

DESIGN PROPOSAL
CLIENT: MJ CONTRACTOR
DATE : 15-10-2018
NOTES
STANDARD DRAWING NOTES:
9. FOR CONCRETE BEAM THAT RESIST SECONDARY BEAM, THE FOLLOWING
1. ALL DIMENSIONS SHOWN ARE IN METER UNLESS NOTED OTHERWISE
DETAILING SHALL BE USED:
2. ALL WORKS TO BE COMPLETED IN ACCORDANCE TO CLIENT REQUIREMENT
3. DURING CONSTRUCTION, THE CONTRACTOR SHALL BE RESPONSIBLE FOR COLUMN SECONDARY
BEAM
MAINTAINING EXCAVATIONS IN A STABLE CONDITION

12d
SUPPORT SUPPORT
4. THE CONCRETE COVER SHALL SATISFY THE FOLLOWING REQUIREMENTS: Ln/4 12d
12d 12d
12d Ln/4

(SNI 2847-2013 CLAUSE 7.7)

HB
SLAB ≥ 20 MM 12d 12d
SPAN
BEAM AND COLUMN ≥ 40 MM Ln/2

FOOTING ≥ 75 MM SUPPORT STIRRUPS ADDITIONAL SHEAR


STARTING 50 MM FROM COLUMN FACE REINFORCEMENT
5. MAXIMUM STIRRUP SPACING FOR GENERAL CONDITIONS SHALL BE TAKEN THE
MINIMUM BETWEEN D/4 AND 300 MM (WHERE D IS THE EFFECTIVE DEPTH OF Ln = CLEAR SPAN

CONCRETE SECTION, CAN TAKEN AS THE GROSS DEPTH - CONCRETE COVER)


L
6. THE INSTALLATION OF BEAM STIRRUPS SHALL COMPLY WITH THE FOLLOWING
REQUIREMENTS: 10. THE REINFORCED CONCRETE BEAM SECTION SHALL COMPLY WITH THE
≥7 d FOLLOWING REQUIREMENTS:
5m 6
m or - Ln ≥ 4 x HB
or m COVER

6 5 m - WB ≥ 0.3HB
PROJECT
d ≥7 - B1 ≥d
BAR DIAMETER (d)
- B2 ≥d

HB
A B CONSTRUCTION OF CV. VIJAYATEX

B2
B1 TENSION REINFORCEMENT BAR AREA
SHALL NOT EXCEED 2.5% OF BEAM
≥7 WB CROSS SECTIONAL AREA ADDRESS
THE HOOP STIRRUPS SHALL BE INSTALLED 5m
VARYING ONE TO ANOTHER BETWEEN A AND B
75 m

m or 11. FOR PAD FOOTING FOUNDATION, THE REINFORCEMENT DETAILING SHALL JLN. AHMAD YANI III
m 6 d
or COMPLY WITH THE FOLLOWING REQUIREMENTS:
6d
SUPPORT SPACING OF STIRRUP TITLE
(SPECIFIED IN THE NEXT CLAUSE)

LAP LENGTH MAX. OF: COMPACTED SOIL


- 61 x COLUMN HEIGHT
STANDARD DRAWING NOTES
- 450 MM
135o
x x x FINISHED GROUND SURFACE
TIE 4 LEGS STIRRUP 3 LEGS STIRRUP
ISSUE NO. DESCRIPTION
1 - DATE: 24/09/18 INITIAL DESIGN
7. THE LONGITUDINAL REINFORCEMENT OF CONCRETE BEAM SHALL COMPLY WITH THE MIN.
300 MM 2 - DATE: 15/10/18 FOUNDATION REV.
FOLLOWING DETAILING REQUIREMENTS: UNLESS SPECIFIED SIDE COVER MIN. 75 MM

COLUMN CONCRETE COVER MIN.


AS SPECIFIED IN CLAUSE 5 300 MM
12d

SUPPORT SUPPORT
MIN. 150 MM

Ln/4 12d 12d Ln/4


BOTTOM COVER MIN. 75 MM
12d

HB

MAXIMUM SPACING 300 MM 50 MM LEVELING COURSE ABOVE SOIL DRAWN BY : HW, ST, MEngSc
12d 12d
SPAN
Ln/2
DESIGNED BY : HW, ST, MEngSc
SUPPORT STIRRUPS THE DEPTH OF FOUNDATION SHALL BE DETERMINED BASED ON THE SOIL
STARTING 50 MM FROM COLUMN FACE BEARING CAPACITY OBTAINED FROM SITE SOIL INVESTIGATION.
CHECKED BY :
Ln = CLEAR SPAN THE MINIMUM FACTOR OF SAFETY OF 3.0 SHALL BE USED BY USING THE
SERVICEABILITY LOADING CONDITION
L
APPROVED BY :

PAGE : 1
NOTES
STANDARD DRAWING NOTES: (CONTINUED)
12d
12. THE STIRRUPS DETAILING OF COLUMN SHALL SATISFY THE FOLLOWING
REQUIREMENTS:
≥75mm or 6d
ANGLE 90O

SUPPORT SPACING SHALL BE THE MINIMUM OF:


- D/4
- 8 x DIAMETER OF LONGITUDINAL BAR
- 300 MM

H
LAP LENGTH MAX. OF:
SUPPORT STIRRUP
- 61 x COLUMN HEIGHT
LENGTH MAX. OF:
- 450 MM
- 61 x COLUMN HEIGHT
- 450 MM
≥75mm or 6d MAX. 150 MM
ANGLE 135O

FOR LONGITUDINAL BAR WITH DIAMETER < 32 MM, THE STIRRUP'S


LAP SPLICE CAN BE PLACED
SLOPE 1:6
DIAMETER SHALL BE NO LESS THAN 10 MM ANYWHERE IN THE COLUMN

FOR LONGITUDINAL BAR WITH DIAMETER > 32 MM, THE STIRRUP'S SPACING AT THE SPAN SHALL BE THE MINIMUM OF:
- D/2
DIAMETER SHALL BE NO LESS THAN 13 MM - 48 x DIAMETER OF STIRRUP

H
- 16 x DIAMETER OF LONGITUDINAL BAR
PROJECT
THE LONGITUDINAL BAR AREA SHALL NOT EXCEED 8% OF COLUMN
CROSS-SECTIONAL AREA AND SHALL BE MINIMUM OF 1% OF COLUMN CONSTRUCTION OF CV. VIJAYATEX
CROSS-SECTIONAL AREA
+0.00

ADDRESS

JLN. AHMAD YANI III

13. THE STRUCTURAL DETAILING IS PROVIDED FOR THE STRUCTURE TO 21. THE REINFORCEMENT BAR FOR BOTH LONGITUDINAL AND STIRRUP SHALL
TITLE
BEHAVE AS MODERATE MOMENT RESISTING FRAME IN ACCORDANCE TO USE THREAD BAR WITH MINIMUM YIELD STRENGTH OF 420 MPA IN
SNI 1726-2012 FOR SEISMIC DESIGN OF BUILDING ACCORDANCE TO SNI 2847-2013 CLAUSE 3.5.3.7 (ASTM A1064M)
STANDARD DRAWING NOTES
15. THE LOADING REQUIREMENTS IN THE DESIGNING STAGE IS IN 22. THE BENDING RADIUS FOR REINFORCEMENT BAR SHALL COMPLY WITH THE
ACCORDANCE TO 1727-2013 TAKEN AS 0.96 kN/m2 IMPOSED DEADLOAD, 0.96 FOLLOWING REQUIREMENTS: (SNI 2847-2013 CLAUSE 7.2)
2 2
kN/m ROOF LIVE LOAD AND 4.96 kN/m FLOOR LIVELOAD D10 - D25 : 6d ISSUE NO. DESCRIPTION
16. THE MINIMUM ALLOWED CONCRETE COMPRESSIVE STRENGTH SHALL BE D29 - D36 : 8d 1 - DATE: 24/09/18 INITIAL DESIGN

NO LESS THAN 17 MPA (SNI 2847-2013 CLAUSE 5.1.1), THIS DESIGN ADOPTS D44 - D56 : 10d 2 - DATE: 15/10/18 FOUNDATION REV.

25 MPA 23. THE TOLERANCE OF 10 MM FROM THE REQUIRED THICKNESS FOR THE
17. LABORATORY TEST SHALL BE CONDUCTED TO TEST THE COMPRESSIVE CONCRETE COVER CAN BE APPLIED (SNI 2847-2013 CLAUSE 7.5.2)
STRENGTH OF THE CONCRETE MIX WITH CYLINDER SAMPLES FOR THE 24. THE DESIGN OF CONCRETE STAIR IS NOT INCLUDED AND SHALL BE
SAME MIX POURED ON SITE (SNI 2847-2013 CLAUSE 5.6.4.3) CONDUCTED AFTER THE PLAN HAS BEEN APPROVED WITH CLIENT
18. THE CONCRETE MIX THAT HAS BEEN ADDED WITH WATER SHALL NOT BE 25. ALL THE WORK SHALL COMPLY WITH THE HEALTH AND SAFETY
DRAWN BY : HW, ST, MEngSc
USED UNLESS APPROVED BY QUALIFIED ENGINEER (SNI 2847-2013 CLAUSE REQUIREMENTS (K3)
5.10.4) 26. BUILDERS MUST ENSURE THE STRUCTURAL WORKS ARE ADEQUATELY DESIGNED BY : HW, ST, MEngSc
19. THE BUILDERS MUST ENSURE THE CONCRETE TO BE IN HUMID AND WARM SUPERVISED BY QUALIFIED ENGINEER ESPECIALLY DURING CONCRETE
ENVIRONMENT AT LEAST 7 DAYS AFTER THE CASTING CASTING, CURING AND UNINSTALLING THE FORM WORK CHECKED BY :
20. THE CONCRETE COMPRESSIVE STRENGTH SHALL BE TESTED AT THE AGE 27. GROUND BEAM SHALL BE PLACED WHEREVER THERE IS WALLS FOR THE
APPROVED BY :
OF 28 DAYS UNLESS NOTED OTHERWISE GROUND LEVEL

PAGE : 2
NOTES

CONCRETE COMPRESSIVE STRENGTH


430 430 70
SHALL BE MINIMUM OF 25 MPA
P1 P1 GROUND BEAM

A
6D13 GROUND BEAM

BEAM AND COLUMN DETAILING SHALL


P2 REFER TO THE PROVIDED GENERAL

200
NOTES

90
110
290

GB 50CM
BOREPILE
P3
6D13 5D13 THE FOUNDATION IS DESIGNED BASED ON
P1 P1
THE PROVIDED SOIL INVESTIGATION

90
GB 5CM LEVELING COURSE
7D13 7D13 FROM PT. MATRA BANGUN
TECHNOCONSULT

A
50CM BOREPILE TO BE
DRILLED TO HARD
SOIL LAYER
THE BORE PILE SHALL BE EMBEDDED TO
FOOTING PILE P1
110
REACH THE HARD SOIL LAYER AT 12.5M
GB SCALE - 1:50 FROM THE SURFACE
GB
480

GB GB 130
SECTION A-A THE GROUND FLOOR IS RECOMMENDED
+0.00
2D13
SCALE - 1:50 TO USE CONCRETE SLAB ON COMPACTED
SOIL WITH THICKNESS OF 8-10 CM WITH

8
P1 P1 ONE LAYER OF MK8 OR MK9 TO PROVIDE

30
GB
D8@200 RESISTANCE FOR CRACKING
2D13
20
COMPACTED GROUND BEAM
SOIL

GROUND BEAM SECTION


SCALE - 1:25 PROJECT
380

GB GB GB

100
B
CONSTRUCTION OF CV. VIJAYATEX
2150

P1 P1 COMPACTED
30 SOIL 20CM

125
GB HOOK

D13@150

20
ADDRESS

D13@150
COLUMN 20X30

20
70

30
20
JLN. AHMAD YANI III

50
75MM
400

D13@150
GB COVER
GB GB
5CM LEVELING COURSE
ABOVE GROUND
120
P1 P1 70 TITLE
D13@150
GB SECTION B-B

B
FOOTING P2 FOUNDATION PLAN
SCALE - 1:25
SCALE - 1:25 (UNIT IN CM ; BAR DIAMETER AND
SPACING UNIT IN MM)
300

GB GB GB
ISSUE NO. DESCRIPTION
P1 P1 70 1 - DATE: 24/09/18 INITIAL DESIGN
GB GROUND BEAM
2 - DATE: 15/10/18 FOUNDATION REV.
D13@200
45
300

GB GB GB 20
D13@150

P1 P1
120

D8@150
30

GB COMPACTED
1250

SOIL
15CM HOOK
DRAWN BY : HW, ST, MEngSc
430 430 COLUMN 20X30
D13@200
860 C C
DESIGNED BY : HW, ST, MEngSc
30

D13@150
20

COVER 75MM
25 25
FOUNDATION AND GROUND BEAM PLAN CHECKED BY :
70 5CM LEVELING COURSE
SCALE - 1:100 ABOVE GROUND
FOOTING P3 SECTION C-C APPROVED BY :
SCALE - 1:25 SCALE - 1:25

PAGE : 3
NOTES

300 110 215 235 CONCRETE COMPRESSIVE STRENGTH


COLUMN 300 240 320
35X50 SHALL BE MINIMUM OF 25 MPA
B4 (20X40)

COLUMN BEAM AND COLUMN DETAILING SHALL


B1 COLUMN B5
20X30
20X30
(20X40) (20X50) REFER TO THE PROVIDED GENERAL
B2 B2 B2 B2 NOTES

290

290
(20X30) B4 B4 B4
(20X30) (20X30) (20X30) B4
(20X40) (20X40) (20X40)
(20X40) COLUMN
COLUMN B5
120 B1 20X30
(20X50)
35X50 COLUMN (20X40) FLOOR SLAB HAS THICKNESS OF 120MM
20X30
WITH REINFORCEMENT BAR OF D10@200
B2 B4 FOR TOP AND BOTTOM
(20X30) (20X40)
120

B5 B5 DETAIL 2
THE HEIGHT OF 2ND FLOOR ABOVE SHALL
(20X50) (20X50) BE NO MORE THAN 3.75M
B2 150
(20X30)
THE HEIGHT OF FIRST FLOOR SHALL NOT

480
VOID
EXCEED 5.5M
B2
B5
(20X30)
(20X50)

COLUMN COLUMN
35X50 35X50

B3
(30X60)

PROJECT

380
B4 B4 B4 B4
(20X40) (20X40) (20X40) (20X40)

COLUMN
CONSTRUCTION OF CV. VIJAYATEX
COLUMN
35X50 35X50

B3
(30X60)
DETAIL 1
ADDRESS

JLN. AHMAD YANI III

400
B4 B4 B4 B4
(20X40) (20X40) (20X40) (20X40)

COLUMN COLUMN TITLE


35X50 35X50

B3
(30X60) FLOOR BEAM PLAN
(UNIT IN CM)
300 B4 B4 B4 B4
(20X40) (20X40) (20X40) (20X40)
ISSUE NO. DESCRIPTION
COLUMN COLUMN
35X50 35X50
1 - DATE: 24/09/18 INITIAL DESIGN
2 - DATE: 15/10/18 FOUNDATION REV.
B3
(30X60)
300

B4 B4 B4 B4
(20X40) (20X40) (20X40) (20X40)

COLUMN COLUMN
35X50 35X50

B3
(30X60) DRAWN BY : HW, ST, MEngSc
150

B4 B4 B4
B4
(20X40) (20X40) (20X40)
(20X40)

DESIGNED BY : HW, ST, MEngSc


B6 B6 B6
(15X30) (15X30) (15X30)

CHECKED BY :
MEZZANIE FLOOR BEAM PLAN 2ND FLOOR BEAM PLAN
SCALE - 1:100 SCALE - 1:100 APPROVED BY :

PAGE : 4
NOTES

CONCRETE COMPRESSIVE STRENGTH


300 240
B3
320 300 240 320 SHALL BE MINIMUM OF 25 MPA
(30X60)

BEAM AND COLUMN DETAILING SHALL


B7 REFER TO THE PROVIDED GENERAL
(20X60) B4 B4
B4 B4 B4 B4 B4
(20X40) (20X40)
NOTES
290

290
(20X40) (20X40) (20X40) (20X40) (20X40)

B7
B3
(20X60)
FLOOR SLAB HAS THICKNESS OF 120MM
(30X60)
WITH REINFORCEMENT BAR OF D10@200
FOR TOP AND BOTTOM
B5
(20X50)

B5
ROOF SLAB HAS THICKNESS OF 110MM
(20X50) WITH REINFORCEMENT BAR D8@150 FOR
B5 B5 B5 B5
B5
(20X50)
B5
(20X50) (20X50) (20X50) (20X50) (20X50)
TOP AND BOTTOM
480

480
B2 B2
(20X30) (20X30)

B7
(20X60)

DETAIL 3 B3 B4 B4 B4 B4

175
(30X60) (20X40) (20X40) (20X40) (20X40)

B4
B4
(20X40)
(20X40)
B4 B4 PROJECT
380

(20X40) (20X40)

ROOF BEAM PLAN


CONSTRUCTION OF CV. VIJAYATEX
B3 SCALE - 1:100
(30X60)

ADDRESS

16D16
B4 B4 B4 B4 JLN. AHMAD YANI III
400

(20X40) (20X40) (20X40) (20X40)


6D16

D10@100 SUPPORT
TITLE
B3
(30X60) D10@200 SPAN
FLOOR AND ROOF BEAM PLAN
D10@150 SUPPORT COLUMN DETAILING
D10@250 SPAN
(UNIT IN CM ; BAR DIAMETER AND

30
50
B4 B4 B4 B4 PROVIDE D10@100 AT
SPACING UNIT IN MM)
300

(20X40) (20X40) (20X40) (20X40) SUPPORT FOR FIRST LEVEL


COLUMN
ISSUE NO. DESCRIPTION
B3 1 - DATE: 24/09/18 INITIAL DESIGN
(30X60) 20
2 - DATE: 15/10/18 FOUNDATION REV.

COLUMN 20X30 DETAILING


35
B4 B4 B4 B4 SCALE - 1:10
300

(20X40) (20X40) (20X40) (20X40)

COLUMN 35X50 DETAILING


B3 SCALE - 1:10 NOTE:
(30X60) COLUMN 20X30 ONLY SPANS
FROM GROUND LEVEL TO
B4 B4 B4 B4 THE SUPPORT AND SPAN SECOND LEVEL DRAWN BY : HW, ST, MEngSc
150

(20X40) (20X40) (20X40) (20X40) DISTANCE SHALL REFER TO


CLAUSE 12 IN THE STANDARD
DESIGNED BY : HW, ST, MEngSc
B6 B6 B6
DRAWING NOTES
(15X30) (15X30) (15X30) *THE MAXIMUM OF HEIGHT/6
3RD TO 5TH FLOOR BEAM PLAN OR 450MM CHECKED BY :
SCALE - 1:100
APPROVED BY :

PAGE : 5
NOTES

CONCRETE COMPRESSIVE STRENGTH


SHALL BE MINIMUM OF 25 MPA
300 240 320
BEAM AND COLUMN DETAILING SHALL
220 220 7D16 5D16
PROVIDE
D8@200
PROVIDE REFER TO THE PROVIDED GENERAL
2U BAR 2U BAR
7D16 NOTES

12
D8 7D16 5D16 D8

D8@100 D8@200
25

25
FLOOR SLAB HAS THICKNESS OF 120MM

60

60
40 MM
COVER
WITH REINFORCEMENT BAR OF D10@200
5D16 7D16
7D16 2D16 5D16
FOR TOP AND BOTTOM
D8@100 5D16 D8@100
2D16
B4(20X40)
30 30
180 40 350 40 180 THE HEIGHT OF 2ND FLOOR ABOVE SHALL
BE NO MORE THAN 3.75M
B3 SUPPORT B3 SPAN
COLUMN COLUMN
35X50 35X50 SCALE - 1:25 SCALE - 1:25
860

DETAIL 1
SCALE - 1:50 3D13 3D13

12

12
40

40
D8@150 D8@300

3D13 3D13
20 20 20
COLUMN
35X50 515
PROVIDE 255 230 PROVIDE
B4 SUPPORT B4 SPAN PROJECT
2U BAR 2D16
D8 65 150
D8@200
150 2U BAR SCALE - 1:25 SCALE - 1:25
D8
3D13 3D16 3D16

CONSTRUCTION OF CV. VIJAYATEX

20
3D16 2D16
20

D8@200

12

12
20

2D16 2D16 3D16 2D16


3D13 B5
(20X50) D8@100
ADDRESS
D8@100

50

50
20 215 20 D8@100 D8@200

COLUMN
2D16 3D16
JLN. AHMAD YANI III
20X30 COLUMN
35X50 20 20

300 560
B5 SUPPORT B5 SPAN TITLE
860
SCALE - 1:25 SCALE - 1:25
BEAM DETAILING
(UNIT IN CM UNLESS FOR BAR
DETAIL 2
DIAMETER IS MM)
SCALE - 1:50

ISSUE NO. DESCRIPTION


5D16
3D13 2D13 2D13
1 - DATE: 24/09/18 INITIAL DESIGN

12
12

12

12
2 - DATE: 15/10/18 FOUNDATION REV.
30

30
40

D8@150 D8@200

60
D8@100
D8@150
2D13 2D13
3D13 20 15
20
3D16

B1 SUPPORT B2 SUPPORT B6 SUPPORT 20

SCALE - 1:25 SCALE - 1:25 SCALE - 1:25 B7 SUPPORT


SCALE - 1:25
DRAWN BY : HW, ST, MEngSc
2D13 3D16
3D13 2D13
12

12
DESIGNED BY : HW, ST, MEngSc
30

12
12

D8@150
30

D8@200

60
40

2D13 D8@200
D8@300 20 CHECKED BY :
2D13
15
3D13
5D16
20
B2 SPAN B6 SPAN APPROVED BY :
20
B1 SPAN SCALE - 1:25 SCALE - 1:25
B7 SPAN
SCALE - 1:25 PAGE : 6
SCALE - 1:25
NOTES

CONCRETE COMPRESSIVE STRENGTH


SHALL BE MINIMUM OF 25 MPA

15.8
BEAM AND COLUMN DETAILING SHALL
D10@200
+2.50 SECOND FLOOR
+5.50 FLOOR SLAB 120MM THICK REFER TO THE PROVIDED GENERAL
NOTES
20

30
15.6
20
FLOOR SLAB HAS THICKNESS OF 120MM
20 B2
D10@200 WITH REINFORCEMENT BAR OF D10@200
B1 30X60
120 FOR TOP AND BOTTOM
30
D10@150

250
SLAB THICKNESS 120MM
20 THE HEIGHT OF 2ND FLOOR ABOVE SHALL

300
15.8
BE NO MORE THAN 3.75M
SLAB THICKNESS 120MM
D10@200
D10@150
GROUND
BEAM
+0.00 D13@200
FLOOR SLAB

+2.50

30 CAST 5CM THICK CONCRETE


5

FOR ADDITIONAL STAIR SUPPORT

300 360 120


B1
400 480

PROJECT
STAIRS MEZZANIE TO 2ND FLOOR
STAIRS GROUND TO MEZZANIE
SCALE - 1:50
SCALE - 1:50
CONSTRUCTION OF CV. VIJAYATEX

ADDRESS

FLOOR SLAB 120MM THICK


NEXT FLOOR JLN. AHMAD YANI III

SLAB THICKNESS
TITLE
B1 30X60 120MM

30 STAIRS DETAILING
300

(UNIT IN CM ; BAR DIAMETER AND


20
20 SPACING UNIT IN MM)

15
15.8

75
SLAB THICKNESS 120MM
REINFORCEMENT
375

D10@150 D10@200 ISSUE NO. DESCRIPTION


TOP AND BOTTOM
120 1 - DATE: 24/09/18 INITIAL DESIGN
D13@200
2 - DATE: 15/10/18 FOUNDATION REV.
B5
(20X50)
75

360

THE STAIRS CONFIGURATION DRAWN BY : HW, ST, MEngSc


IS TYPICAL UP TO LEVEL 5

STAIRS 2ND LEVEL TO 3RD LEVEL DESIGNED BY : HW, ST, MEngSc


SCALE - 1:50
CHECKED BY :

APPROVED BY :

PAGE : 7