You are on page 1of 23

OWNER: 

UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY101L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)

Control Cable in Switchyard

101‐CVT CABLING
1 132 kV 101 within swyd  1‐101‐1‐001 1 Cu./Amr. PVC 101‐RCVT Core.‐1 101‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB1‐1 101‐CVT JB‐TB1‐1 / R‐1a 101‐RCVT Core.‐1‐R‐1a/TB1‐1 Core‐1
ASPL/UPPCL/20415U
132 kV 101‐RCVT Core.‐1 101‐CVT JB Core 2 100 R‐1n TB1‐3 Distance Main‐1 Protection Relay
101 101‐CVT JB‐TB1‐3 / R‐1n 101‐RCVT Core.‐1‐R‐1n/TB1‐3
132 kV 101 101‐RCVT Core.‐1 101‐CVT JB Core 3 SPARE TB1‐5 101‐CVT JB‐TB1‐5 / SPARE 101‐RCVT Core.‐1‐SPARE/TB1‐5 67/67N : O/c & E/f Relay

2 132 kV 101 within swyd  1‐101‐1‐002 1 Cu./Amr. PVC 101‐YCVT Core.‐1 101‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB1‐8 101‐CVT JB‐TB1‐8 / Y‐1a 101‐YCVT Core.‐1‐Y‐1a/TB1‐8 Core‐1
ASPL/UPPCL/20415U
132 kV 101‐YCVT Core.‐1 101‐CVT JB Core 2 100 Y‐1n TB1‐10 Distance Main‐1 Protection Relay
101 101‐CVT JB‐TB1‐10 / Y‐1n 101‐YCVT Core.‐1‐Y‐1n/TB1‐10
132 kV 101 101‐YCVT Core.‐1 101‐CVT JB Core 3 SPARE TB1‐12 101‐CVT JB‐TB1‐12 / SPARE 101‐YCVT Core.‐1‐SPARE/TB1‐12 67/67N : O/c & E/f Relay

3 132 kV 101 within swyd  1‐101‐1‐003 1 Cu./Amr. PVC 101‐BCVT Core.‐1 101‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB1‐15 101‐CVT JB‐TB1‐15 / B‐1a 101‐BCVT Core.‐1‐B‐1a/TB1‐15 Core‐1
ASPL/UPPCL/20415U
132 kV 101‐BCVT Core.‐1 101‐CVT JB Core 2 100 B‐1n TB1‐17 Distance Main‐1 Protection Relay
101 101‐CVT JB‐TB1‐17 / B‐1n 101‐BCVT Core.‐1‐B‐1n/TB1‐17
132 kV 101 101‐BCVT Core.‐1 101‐CVT JB Core 3 SPARE TB1‐19 101‐CVT JB‐TB1‐19 / SPARE 101‐BCVT Core.‐1‐SPARE/TB1‐19 67/67N : O/c & E/f Relay

4 132 kV 101 within swyd  1‐101‐1‐004 1 Cu./Amr. PVC 101‐RCVT Core.‐2 101‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB2‐1 101‐CVT JB‐TB2‐1 / R‐1a 101‐RCVT Core.‐2‐R‐1a/TB2‐1 Core‐2
ASPL/UPPCL/20415U
132 kV 101 101‐RCVT Core.‐2 101‐CVT JB Core 2 100 R‐1n TB2‐3 101‐CVT JB‐TB2‐3 / R‐1n 101‐RCVT Core.‐2‐R‐1n/TB2‐3 Spare
132 kV 101 101‐RCVT Core.‐2 101‐CVT JB Core 3 SPARE TB2‐5 101‐CVT JB‐TB2‐5 / SPARE 101‐RCVT Core.‐2‐SPARE/TB2‐5

5 132 kV 101 within swyd  1‐101‐1‐005 1 Cu./Amr. PVC 101‐YCVT Core.‐2 101‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB2‐8 101‐CVT JB‐TB2‐8 / Y‐1a 101‐YCVT Core.‐2‐Y‐1a/TB2‐8 Core‐2
ASPL/UPPCL/20415U
132 kV 101 101‐YCVT Core.‐2 101‐CVT JB Core 2 100 Y‐1n TB2‐10 101‐CVT JB‐TB2‐10 / Y‐1n 101‐YCVT Core.‐2‐Y‐1n/TB2‐10 Spare
132 kV 101 101‐YCVT Core.‐2 101‐CVT JB Core 3 SPARE TB2‐12 101‐CVT JB‐TB2‐12 / SPARE 101‐YCVT Core.‐2‐SPARE/TB2‐12

6 132 kV 101 within swyd  1‐101‐1‐006 1 Cu./Amr. PVC 101‐BCVT Core.‐2 101‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB2‐15 101‐CVT JB‐TB2‐15 / B‐1a 101‐BCVT Core.‐2‐B‐1a/TB2‐15 Core‐2
ASPL/UPPCL/20415U
132 kV 101 101‐BCVT Core.‐2 101‐CVT JB Core 2 100 B‐1n TB2‐17 101‐CVT JB‐TB2‐17 / B‐1n 101‐BCVT Core.‐2‐B‐1n/TB2‐17 Spare
132 kV 101 101‐BCVT Core.‐2 101‐CVT JB Core 3 SPARE TB2‐19 101‐CVT JB‐TB2‐19 / SPARE 101‐BCVT Core.‐2‐SPARE/TB2‐19

7 132 kV 101 within swyd  1‐101‐1‐007 1 Cu./Amr. PVC 101‐RCVT Core.‐3 101‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB3‐1 101‐CVT JB‐TB3‐1 / R‐1a 101‐RCVT Core.‐3‐R‐1a/TB3‐1 Core‐3
ASPL/UPPCL/20415U
132 kV 101 101‐RCVT Core.‐3 101‐CVT JB Core 2 100 R‐1n TB3‐3 101‐CVT JB‐TB3‐3 / R‐1n 101‐RCVT Core.‐3‐R‐1n/TB3‐3 Metering
132 kV 101 101‐RCVT Core.‐3 101‐CVT JB Core 3 SPARE TB3‐5 101‐CVT JB‐TB3‐5 / SPARE 101‐RCVT Core.‐3‐SPARE/TB3‐5

8 132 kV 101 within swyd  1‐101‐1‐008 1 Cu./Amr. PVC 101‐YCVT Core.‐3 101‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB3‐8 101‐CVT JB‐TB3‐8 / Y‐1a 101‐YCVT Core.‐3‐Y‐1a/TB3‐8 Core‐3
ASPL/UPPCL/20415U
132 kV 101 101‐YCVT Core.‐3 101‐CVT JB Core 2 100 Y‐1n TB3‐10 101‐CVT JB‐TB3‐10 / Y‐1n 101‐YCVT Core.‐3‐Y‐1n/TB3‐10 Metering
132 kV 101 101‐YCVT Core.‐3 101‐CVT JB Core 3 SPARE TB3‐12 101‐CVT JB‐TB3‐12 / SPARE 101‐YCVT Core.‐3‐SPARE/TB3‐12

9 132 kV 101 within swyd  1‐101‐1‐009 1 Cu./Amr. PVC 101‐BCVT Core.‐3 101‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB3‐15 101‐CVT JB‐TB3‐15 / B‐1a 101‐BCVT Core.‐3‐B‐1a/TB3‐15 Core‐3
ASPL/UPPCL/20415U
132 kV 101 101‐BCVT Core.‐3 101‐CVT JB Core 2 100 B‐1n TB3‐17 101‐CVT JB‐TB3‐17 / B‐1n 101‐BCVT Core.‐3‐B‐1n/TB3‐17 Metering
132 kV 101 101‐BCVT Core.‐3 101‐CVT JB Core 3 SPARE TB3‐19 101‐CVT JB‐TB3‐19 / SPARE 101‐BCVT Core.‐3‐SPARE/TB3‐19

101‐CT CABLING
10 132 kV 101 within swyd  1‐101‐1‐010 1 Cu./Amr. PVC 101‐RCT Core.‐5 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 5US1 5US1 101‐CT JB‐5US1 / 5US1 101‐RCT Core.‐5‐5US1/5US1 CORE‐5
ASPL/UPPCL/20415
132 kV 101 101‐RCT Core.‐5 101‐CT JB Core 2 058 5US2 5US2 101‐CT JB‐5US2 / 5US2 101‐RCT Core.‐5‐5US2/5US2 Distance Protection M1
132 kV 101 101‐RCT Core.‐5 101‐CT JB Core 3 5US3 5US3 101‐CT JB‐5US3 / 5US3 101‐RCT Core.‐5‐5US3/5US3
132 kV 101 101‐RCT Core.‐5 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐RCT Core.‐5‐Spare/Spare
132 kV 101 101‐RCT Core.‐5 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐RCT Core.‐5‐Spare/Spare

11 132 kV 101 within swyd  1‐101‐1‐011 1 Cu./Amr. PVC 101‐YCT Core.‐5 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 5VS1 5VS1 101‐CT JB‐5VS1 / 5VS1 101‐YCT Core.‐5‐5VS1/5VS1 CORE‐5
ASPL/UPPCL/20415
132 kV 101 101‐YCT Core.‐5 101‐CT JB Core 2 058 5VS2 5VS2 101‐CT JB‐5VS2 / 5VS2 101‐YCT Core.‐5‐5VS2/5VS2 Distance Protection M1
132 kV 101 101‐YCT Core.‐5 101‐CT JB Core 3 5VS3 5VS3 101‐CT JB‐5VS3 / 5VS3 101‐YCT Core.‐5‐5VS3/5VS3
132 kV 101 101‐YCT Core.‐5 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐YCT Core.‐5‐Spare/Spare
132 kV 101 101‐YCT Core.‐5 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐YCT Core.‐5‐Spare/Spare

12 132 kV 101 within swyd  1‐101‐1‐012 1 Cu./Amr. PVC 101‐BCT Core.‐5 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 5WS1 5WS1 101‐CT JB‐5WS1 / 5WS1 101‐BCT Core.‐5‐5WS1/5WS1 CORE‐5
ASPL/UPPCL/20415
132 kV 101 101‐BCT Core.‐5 101‐CT JB Core 2 058 5WS2 5WS2 101‐CT JB‐5WS2 / 5WS2 101‐BCT Core.‐5‐5WS2/5WS2 Distance Protection M1
132 kV 101 101‐BCT Core.‐5 101‐CT JB Core 3 5WS3 5WS3 101‐CT JB‐5WS3 / 5WS3 101‐BCT Core.‐5‐5WS3/5WS3
132 kV 101 101‐BCT Core.‐5 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐BCT Core.‐5‐Spare/Spare
132 kV 101 101‐BCT Core.‐5 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐BCT Core.‐5‐Spare/Spare

13 132 kV 101 within swyd  1‐101‐1‐013 1 Cu./Amr. PVC 101‐RCT Core.‐2 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 2US1 2US1 101‐CT JB‐2US1 / 2US1 101‐RCT Core.‐2‐2US1/2US1 CORE‐2
ASPL/UPPCL/20415
132 kV 101 101‐RCT Core.‐2 101‐CT JB Core 2 058 2US2 2US2 101‐CT JB‐2US2 / 2US2 101‐RCT Core.‐2‐2US2/2US2 67/67N : O/c & E/f Relay
132 kV 101 101‐RCT Core.‐2 101‐CT JB Core 3 2US3 2US3 101‐CT JB‐2US3 / 2US3 101‐RCT Core.‐2‐2US3/2US3
132 kV 101 101‐RCT Core.‐2 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐RCT Core.‐2‐Spare/Spare
132 kV 101 101‐RCT Core.‐2 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐RCT Core.‐2‐Spare/Spare

14 132 kV 101 within swyd  1‐101‐1‐014 1 Cu./Amr. PVC 101‐YCT Core.‐2 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 2VS1 2VS1 101‐CT JB‐2VS1 / 2VS1 101‐YCT Core.‐2‐2VS1/2VS1 CORE‐2
ASPL/UPPCL/20415
132 kV 101 101‐YCT Core.‐2 101‐CT JB Core 2 058 2VS2 2VS2 101‐CT JB‐2VS2 / 2VS2 101‐YCT Core.‐2‐2VS2/2VS2 67/67N : O/c & E/f Relay
132 kV 101 101‐YCT Core.‐2 101‐CT JB Core 3 2VS3 2VS3 101‐CT JB‐2VS3 / 2VS3 101‐YCT Core.‐2‐2VS3/2VS3
132 kV 101 101‐YCT Core.‐2 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐YCT Core.‐2‐Spare/Spare
132 kV 101 101‐YCT Core.‐2 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐YCT Core.‐2‐Spare/Spare

15 132 kV 101 within swyd  1‐101‐1‐015 1 Cu./Amr. PVC 101‐BCT Core.‐2 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 2WS1 2WS1 101‐CT JB‐2WS1 / 2WS1 101‐BCT Core.‐2‐2WS1/2WS1 CORE‐2
ASPL/UPPCL/20415
132 kV 101 101‐BCT Core.‐2 101‐CT JB Core 2 058 2WS2 2WS2 101‐CT JB‐2WS2 / 2WS2 101‐BCT Core.‐2‐2WS2/2WS2 67/67N : O/c & E/f Relay
132 kV 101 101‐BCT Core.‐2 101‐CT JB Core 3 2WS3 2WS3 101‐CT JB‐2WS3 / 2WS3 101‐BCT Core.‐2‐2WS3/2WS3
132 kV 101 101‐BCT Core.‐2 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐BCT Core.‐2‐Spare/Spare
132 kV 101 101‐BCT Core.‐2 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐BCT Core.‐2‐Spare/Spare

16 132 kV 101 within swyd  1‐101‐1‐016 1 Cu./Amr. PVC 101‐RCT Core.‐1 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 1US1 1US1 101‐CT JB‐1US1 / 1US1 101‐RCT Core.‐1‐1US1/1US1 CORE‐1
ASPL/UPPCL/20415
132 kV 101 101‐RCT Core.‐1 101‐CT JB Core 2 058 1US2 1US2 101‐CT JB‐1US2 / 1US2 101‐RCT Core.‐1‐1US2/1US2 87BB : Busbar Protection
132 kV 101 101‐RCT Core.‐1 101‐CT JB Core 3 1US3 1US3 101‐CT JB‐1US3 / 1US3 101‐RCT Core.‐1‐1US3/1US3
132 kV 101 101‐RCT Core.‐1 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐RCT Core.‐1‐Spare/Spare
132 kV 101 101‐RCT Core.‐1 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐RCT Core.‐1‐Spare/Spare

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 1 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY101L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)

17 132 kV 101 within swyd  1‐101‐1‐017 1 Cu./Amr. PVC 101‐YCT Core.‐1 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 1VS1 1VS1 101‐CT JB‐1VS1 / 1VS1 101‐YCT Core.‐1‐1VS1/1VS1 CORE‐1
ASPL/UPPCL/20415
132 kV 101 101‐YCT Core.‐1 101‐CT JB Core 2 058 1VS2 1VS2 101‐CT JB‐1VS2 / 1VS2 101‐YCT Core.‐1‐1VS2/1VS2 87BB : Busbar Protection
132 kV 101 101‐YCT Core.‐1 101‐CT JB Core 3 1VS3 1VS3 101‐CT JB‐1VS3 / 1VS3 101‐YCT Core.‐1‐1VS3/1VS3
132 kV 101 101‐YCT Core.‐1 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐YCT Core.‐1‐Spare/Spare
132 kV 101 101‐YCT Core.‐1 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐YCT Core.‐1‐Spare/Spare

18 132 kV 101 within swyd  1‐101‐1‐018 1 Cu./Amr. PVC 101‐BCT Core.‐1 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 1WS1 1WS1 101‐CT JB‐1WS1 / 1WS1 101‐BCT Core.‐1‐1WS1/1WS1 CORE‐1
ASPL/UPPCL/20415
132 kV 101 101‐BCT Core.‐1 101‐CT JB Core 2 058 1WS2 1WS2 101‐CT JB‐1WS2 / 1WS2 101‐BCT Core.‐1‐1WS2/1WS2 87BB : Busbar Protection
132 kV 101 101‐BCT Core.‐1 101‐CT JB Core 3 1WS3 1WS3 101‐CT JB‐1WS3 / 1WS3 101‐BCT Core.‐1‐1WS3/1WS3
132 kV 101 101‐BCT Core.‐1 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐BCT Core.‐1‐Spare/Spare
132 kV 101 101‐BCT Core.‐1 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐BCT Core.‐1‐Spare/Spare

19 132 kV 101 within swyd  1‐101‐1‐019 1 Cu./Amr. PVC 101‐RCT Core.‐3 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 3US1 3US1 101‐CT JB‐3US1 / 3US1 101‐RCT Core.‐3‐3US1/3US1 CORE‐3
ASPL/UPPCL/20415
132 kV 101 101‐RCT Core.‐3 101‐CT JB Core 2 058 3US2 3US2 101‐CT JB‐3US2 / 3US2 101‐RCT Core.‐3‐3US2/3US2 BCU : Bay Control Unit
132 kV 101 101‐RCT Core.‐3 101‐CT JB Core 3 3US3 3US3 101‐CT JB‐3US3 / 3US3 101‐RCT Core.‐3‐3US3/3US3
132 kV 101 101‐RCT Core.‐3 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐RCT Core.‐3‐Spare/Spare
132 kV 101 101‐RCT Core.‐3 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐RCT Core.‐3‐Spare/Spare

20 132 kV 101 within swyd  1‐101‐1‐020 1 Cu./Amr. PVC 101‐YCT Core.‐3 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 3VS1 3VS1 101‐CT JB‐3VS1 / 3VS1 101‐YCT Core.‐3‐3VS1/3VS1 CORE‐3
ASPL/UPPCL/20415
132 kV 101 101‐YCT Core.‐3 101‐CT JB Core 2 058 3VS2 3VS2 101‐CT JB‐3VS2 / 3VS2 101‐YCT Core.‐3‐3VS2/3VS2 BCU : Bay Control Unit
132 kV 101 101‐YCT Core.‐3 101‐CT JB Core 3 3VS3 3VS3 101‐CT JB‐3VS3 / 3VS3 101‐YCT Core.‐3‐3VS3/3VS3
132 kV 101 101‐YCT Core.‐3 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐YCT Core.‐3‐Spare/Spare
132 kV 101 101‐YCT Core.‐3 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐YCT Core.‐3‐Spare/Spare

21 132 kV 101 within swyd  1‐101‐1‐021 1 Cu./Amr. PVC 101‐BCT Core.‐3 101‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 3WS1 3WS1 101‐CT JB‐3WS1 / 3WS1 101‐BCT Core.‐3‐3WS1/3WS1 CORE‐3
ASPL/UPPCL/20415
132 kV 101 101‐BCT Core.‐3 101‐CT JB Core 2 058 3WS2 3WS2 101‐CT JB‐3WS2 / 3WS2 101‐BCT Core.‐3‐3WS2/3WS2 BCU : Bay Control Unit
132 kV 101 101‐BCT Core.‐3 101‐CT JB Core 3 3WS3 3WS3 101‐CT JB‐3WS3 / 3WS3 101‐BCT Core.‐3‐3WS3/3WS3
132 kV 101 101‐BCT Core.‐3 101‐CT JB Core 4 Spare Spare 101‐CT JB‐Spare / Spare 101‐BCT Core.‐3‐Spare/Spare
132 kV 101 101‐BCT Core.‐3 101‐CT JB Core 5 Spare Spare 101‐CT JB‐Spare / Spare 101‐BCT Core.‐3‐Spare/Spare

101‐BREAKER & E/s INTERLOCKING
22 132 kV 101 within swyd  1‐101‐1‐022 1 Cu./Amr. PVC 101‐89AE  101‐52  3CX2.5 37 Core 1 not included in CRP  TB3‐126 not included in CRP  x 101‐52 ‐x / TB3‐126 101‐89AE ‐TB3‐126/x CB & E/s Interlock
132 kV 101 101‐89AE  101‐52  Core 2 drawing SPARE drawing
132 kV 101 101‐89AE  101‐52  Core 3 SPARE

23 132 kV 101 within swyd  1‐101‐1‐023 1 Cu./Amr. PVC 101‐89LE1  101‐52  3CX2.5 37 Core 1 not included in CRP  TB3‐126 not included in CRP  x 101‐52 ‐x / TB3‐126 101‐89LE1 ‐TB3‐126/x CB & E/s Interlock
132 kV 101 101‐89LE1  101‐52  Core 2 drawing SPARE drawing
132 kV 101 101‐89LE1  101‐52  Core 3 SPARE

24 132 kV 101 within swyd  1‐101‐1‐024 1 Cu./Amr. PVC 101‐89LE2  101‐52  3CX2.5 30 Core 1 not included in CRP  TB3‐126 not included in CRP  x 101‐52 ‐x / TB3‐126 101‐89LE2 ‐TB3‐126/x CB & E/s Interlock
132 kV 101 101‐89LE2  101‐52  Core 2 drawing SPARE drawing
132 kV 101 101‐89LE2  101‐52  Core 3 SPARE

101‐B/w EARTHSWITCH & ISOLATOR
25 132 kV 101 within swyd  1‐101‐1‐025 1 Cu./Amr. PVC 101‐89A  101‐89AE  3CX2.5 5 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ TB1‐1 101‐89AE ‐TB1‐1 / TB1‐1 101‐89A ‐TB1‐1/TB1‐1 (+)ve DC Supply
132 kV 101 101‐89A  101‐89AE  Core 2 W101, Sh‐35 of 49 TB1‐2 W101, Sh‐35 of 49 TB1‐2 101‐89AE ‐TB1‐2 / TB1‐2 101‐89A ‐TB1‐2/TB1‐2 (‐)ve DC Supply
132 kV 101 101‐89A  101‐89AE  Core 3 SPARE

26 132 kV 101 within swyd  1‐101‐1‐026 1 Cu./Amr. PVC 101‐89L  101‐89LE1  3CX2.5 5 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ TB1‐1 101‐89LE1 ‐TB1‐1 / TB1‐1 101‐89L ‐TB1‐1/TB1‐1 (+)ve DC Supply
132 kV 101 101‐89L  101‐89LE1  Core 2 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 TB1‐2 101‐89LE1 ‐TB1‐2 / TB1‐2 101‐89L ‐TB1‐2/TB1‐2 (‐)ve DC Supply
132 kV 101 101‐89L  101‐89LE1  Core 3 SPARE

27 132 kV 101 within swyd  1‐101‐1‐027 1 Cu./Amr. PVC 101‐89L  101‐89LE2  3CX2.5 5 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ TB1‐1 101‐89LE2 ‐TB1‐1 / TB1‐1 101‐89L ‐TB1‐1/TB1‐1 (+)ve DC Supply
132 kV 101 101‐89L  101‐89LE2  Core 2 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 TB1‐2 101‐89LE2 ‐TB1‐2 / TB1‐2 101‐89L ‐TB1‐2/TB1‐2 (‐)ve DC Supply
132 kV 101 101‐89L  101‐89LE2  Core 3 SPARE

Control Cable from Switchyard to Panel
101‐CVT CABLING TO PANEL
28 132 kV 101 within swyd  1‐101‐1‐028 1 Cu./Amr. PVC 101‐CVT JB 101 RA 5CX2.5 75 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:VTL‐1 101 RA‐X:VTL‐1 / TB1‐1 101‐CVT JB‐TB1‐1/X:VTL‐1 Distance Main‐1 Protection Relay
132 kV 101 101‐CVT JB 101 RA Core 2 W101, Sh‐13 of 49 TB1‐8 W101, Sh‐13 of 49 X:VTL‐2 101 RA‐X:VTL‐2 / TB1‐8 101‐CVT JB‐TB1‐8/X:VTL‐2 67/67N : O/c & E/f Relay
132 kV 101 101‐CVT JB 101 RA Core 3 TB1‐15 X:VTL‐3 101 RA‐X:VTL‐3 / TB1‐15 101‐CVT JB‐TB1‐15/X:VTL‐3
132 kV 101 101‐CVT JB 101 RA Core 4 TB1‐19 X:VTL‐4 101 RA‐X:VTL‐4 / TB1‐19 101‐CVT JB‐TB1‐19/X:VTL‐4
132 kV 101 101‐CVT JB 101 RA Core 5 SPARE

29 132 kV 101 within swyd  1‐101‐1‐029 1 Cu./Amr. PVC 101‐CVT JB 101 RB 10CX2.5 75 Core 1 G719EA‐MG9031‐00‐ TB2‐1 G719EA‐MG9031‐00‐ X:VTL‐1 101 RB‐X:VTL‐1 / TB2‐1 101‐CVT JB‐TB2‐1/X:VTL‐1 Spare
132 kV 101 101‐CVT JB 101 RB Core 2 W101, Sh‐13 of 49 TB2‐8 W101, Sh‐13 of 49 X:VTL‐2 101 RB‐X:VTL‐2 / TB2‐8 101‐CVT JB‐TB2‐8/X:VTL‐2
132 kV 101 101‐CVT JB 101 RB Core 3 TB2‐15 X:VTL‐3 101 RB‐X:VTL‐3 / TB2‐15 101‐CVT JB‐TB2‐15/X:VTL‐3
132 kV 101 101‐CVT JB 101 RB Core 4 TB2‐19 X:VTL‐4 101 RB‐X:VTL‐4 / TB2‐19 101‐CVT JB‐TB2‐19/X:VTL‐4
132 kV 101 101‐CVT JB 101 RB Core 5 G719EA‐MG9031‐00‐ TB3‐1 G719EA‐MG9031‐00‐ X:VTL‐5 101 RB‐X:VTL‐5 / TB3‐1 101‐CVT JB‐TB3‐1/X:VTL‐5
132 kV 101 101‐CVT JB 101 RB Core 6 W101, Sh‐13 of 49 TB3‐8 W101, Sh‐13 of 49 X:VTL‐6 101 RB‐X:VTL‐6 / TB3‐8 101‐CVT JB‐TB3‐8/X:VTL‐6 Metering
132 kV 101 101‐CVT JB 101 RB Core 7 TB3‐15 X:VTL‐7 101 RB‐X:VTL‐7 / TB3‐15 101‐CVT JB‐TB3‐15/X:VTL‐7
132 kV 101 101‐CVT JB 101 RB Core 8 TB3‐19 X:VTL‐8 101 RB‐X:VTL‐8 / TB3‐19 101‐CVT JB‐TB3‐19/X:VTL‐8
132 kV 101 101‐CVT JB 101 RB Core 9 SPARE
132 kV 101 101‐CVT JB 101 RB Core 10 SPARE
101‐CT CABLING
30 132 kV 101 within swyd  1‐101‐1‐030 1 Cu./Amr. PVC 101‐CT MB 101 RA 14CX2.5 72 Core 1 5US2 G719EA‐MG9031‐ X:CT‐1 101 RA‐X:CT‐1 / 5US2 101‐CT MB‐5US2/X:CT‐1
ASPL/UPPCL/20415
132 kV 101 101‐CT MB 101 RA Core 2 5VS2 W101, Sh‐16 of 58 X:CT‐3 101 RA‐X:CT‐3 / 5VS2 101‐CT MB‐5VS2/X:CT‐3
CORE 5: Distance Protection M1
132 kV 101 101‐CT MB 101 RA Core 3 5WS2 X:CT‐5 101 RA‐X:CT‐5 / 5WS2 101‐CT MB‐5WS2/X:CT‐5
132 kV 101 101‐CT MB 101 RA Core 4 5VS1 X:CT‐7 101 RA‐X:CT‐7 / 5VS1 101‐CT MB‐5VS1/X:CT‐7
132 kV 101 101‐CT MB 101 RA Core 5 2US2 G719EA‐MG9031‐00‐ X:CT‐21 101 RA‐X:CT‐21 / 2US2 101‐CT MB‐2US2/X:CT‐21
ASPL/UPPCL/20415
132 kV 101 101‐CT MB 101 RA Core 6 2VS2 W101, Sh‐19 of 49 X:CT‐23 101 RA‐X:CT‐23 / 2VS2 101‐CT MB‐2VS2/X:CT‐23 CORE 2: 67/67N : O/c & E/f Relay

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 2 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY101L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts) CORE 2: 67/67N : O/c & E/f Relay
132 kV 101 101‐CT MB 101 RA Core 7 2WS2 X:CT‐25 101 RA‐X:CT‐25 / 2WS2 101‐CT MB‐2WS2/X:CT‐25
132 kV 101 101‐CT MB 101 RA Core 8 2VS1 X:CT‐27 101 RA‐X:CT‐27 / 2VS1 101‐CT MB‐2VS1/X:CT‐27
132 kV 101 101‐CT MB 101 RA Core 9 1US2 G719EA‐MG9031‐00‐ X:CT‐29 101 RA‐X:CT‐29 / 1US2 101‐CT MB‐1US2/X:CT‐29
ASPL/UPPCL/20415
132 kV 101 101‐CT MB 101 RA Core 10 1VS2 W101, Sh‐21 of 49 X:CT‐31 101 RA‐X:CT‐31 / 1VS2 101‐CT MB‐1VS2/X:CT‐31 CORE1: 87BB : Busbar Protection
132 kV 101 101‐CT MB 101 RA Core 11 1WS2 X:CT‐33 101 RA‐X:CT‐33 / 1WS2 101‐CT MB‐1WS2/X:CT‐33
132 kV 101 101‐CT MB 101 RA Core 12 1VS1 X:CT‐35 101 RA‐X:CT‐35 / 1VS1 101‐CT MB‐1VS1/X:CT‐35
132 kV 101 101‐CT MB 101 RA Core 13 SPARE SPARE
132 kV 101 101‐CT MB 101 RA Core 14 SPARE SPARE

31 132 kV 101 within swyd  1‐101‐1‐031 1 Cu./Amr. PVC 101‐CT MB 101 RB 5CX2.5 72 Core 1 3US2 G719EA‐MG9031‐ X:CT‐23 101 RB‐X:CT‐23 / 3US2 101‐CT MB‐3US2/X:CT‐23
ASPL/UPPCL/20415
132 kV 101 101‐CT MB 101 RB Core 2 3VS2 W101, Sh‐33 of 58 X:CT‐25 101 RB‐X:CT‐25 / 3VS2 101‐CT MB‐3VS2/X:CT‐25
CORE 3: BCU : Bay Control Unit
132 kV 101 101‐CT MB 101 RB Core 3 3WS2 X:CT‐27 101 RB‐X:CT‐27 / 3WS2 101‐CT MB‐3WS2/X:CT‐27
132 kV 101 101‐CT MB 101 RB Core 4 3VS1 X:CT‐29 101 RB‐X:CT‐29 / 3VS1 101‐CT MB‐3VS1/X:CT‐29
132 kV 101 101‐CT MB 101 RB Core 5 SPARE

101‐CIRCUIT BREAKER CABLING TO PANEL
32 132 kV 101 within swyd  1‐101‐1‐032 1 Cu./Amr. PVC 101‐52  101 RA 19CX2.5 50 Core 1 G719EA‐MG9031‐00‐ X1LA‐5 G719EA‐MG9031‐ X:CB‐1 101 RA‐X:CB‐1 / X1LA‐5 101‐52 ‐X1LA‐5/X:CB‐1 Common
132 kV 101 101‐52  101 RA Core 2 W101, Sh‐17 of 49 X1LC‐6 W201, Sh‐17 of 58 X:CB‐2 101 RA‐X:CB‐2 / X1LC‐6 101‐52 ‐X1LC‐6/X:CB‐2 Main CB Open
132 kV 101 101‐52  101 RA Core 3 G719EA‐MG9031‐00‐ X1LA‐6 G719EA‐MG9031‐00‐ X:BB‐3 101 RA‐X:BB‐3 / X1LA‐6 101‐52 ‐X1LA‐6/X:BB‐3 CB Open
132 kV 101 101‐52  101 RA Core 4 W101, Sh‐22 of 49 X1LC‐6 W101, Sh‐22 of 49 X:BB‐4 101 RA‐X:BB‐4 / X1LC‐6 101‐52 ‐X1LC‐6/X:BB‐4 Main/TBC CB Open, B‐Ph
132 kV 101 101‐52  101 RA Core 5 G719EA‐MG9031‐00‐ X1 G719EA‐MG9031‐00‐ X:TC1‐3 101 RA‐X:TC1‐3 / X1 101‐52 ‐X1/X:TC1‐3 Common
132 kV 101 101‐52  101 RA Core 6 W101, Sh‐26 of 49 X1:7 W101, Sh‐26 of 49 X:TC1‐4 101 RA‐X:TC1‐4 / X1:7 101‐52 ‐X1:7/X:TC1‐4 Protection Trip‐1
132 kV 101 101‐52  101 RA Core 7 X1:10 X:TC1‐5 101 RA‐X:TC1‐5 / X1:10 101‐52 ‐X1:10/X:TC1‐5 Post Close TC‐1 Supervision
132 kV 101 101‐52  101 RA Core 8 X1:9 X:TC1‐6 101 RA‐X:TC1‐6 / X1:9 101‐52 ‐X1:9/X:TC1‐6 Pre Close TC‐1 Supervision 
132 kV 101 101‐52  101 RA Core 9 X1:1 X:TC1‐1 101 RA‐X:TC1‐1 / X1:1 101‐52 ‐X1:1/X:TC1‐1 DC Supply (+)Ve
132 kV 101 101‐52  101 RA Core 10 X1:2 X:TC1‐2 101 RA‐X:TC1‐2 / X1:2 101‐52 ‐X1:2/X:TC1‐2 DC Supply (‐)Ve
132 kV 101 101‐52  101 RA Core 11 G719EA‐MG9031‐00‐ X1 G719EA‐MG9031‐00‐ X:TC2‐9 101 RA‐X:TC2‐9 / X1 101‐52 ‐X1/X:TC2‐9 Common
132 kV 101 101‐52  101 RA Core 12 W101, Sh‐27 of 49 X1:16 W101, Sh‐27 of 49 X:TC2‐10 101 RA‐X:TC2‐10 / X1:16 101‐52 ‐X1:16/X:TC2‐10 Protection Trip‐2
132 kV 101 101‐52  101 RA Core 13 X1:19 X:TC2‐11 101 RA‐X:TC2‐11 / X1:19 101‐52 ‐X1:19/X:TC2‐11 Post Close TC‐2 Supervision
132 kV 101 101‐52  101 RA Core 14 X1:18 X:TC2‐12 101 RA‐X:TC2‐12 / X1:18 101‐52 ‐X1:18/X:TC2‐12 Pre Close TC‐2 Supervision 
132 kV 101 101‐52  101 RA Core 15 X1:1A X:TC2‐1 101 RA‐X:TC2‐1 / X1:1A 101‐52 ‐X1:1A/X:TC2‐1 DC Supply (+)Ve
132 kV 101 101‐52  101 RA Core 16 X1:2A X:TC2‐2 101 RA‐X:TC2‐2 / X1:2A 101‐52 ‐X1:2A/X:TC2‐2 DC Supply (‐)Ve
132 kV 101 101‐52  101 RA Core 17 SPARE
132 kV 101 101‐52  101 RA Core 18 SPARE
132 kV 101 101‐52  101 RA Core 19 SPARE

33 132 kV 101 within swyd  1‐101‐1‐033 1 Cu./Amr. PVC 101‐52  101 RB 19CX2.5 50 Core 1 G719EA‐MG9031‐00‐ X1 G719EA‐MG9031‐00‐ X:CB‐1 101 RB‐X:CB‐1 / X1 101‐52 ‐X1/X:CB‐1 Common
132 kV 101 101‐52  101 RB Core 2 W101, Sh‐29 of 49 X1 W101, Sh‐29 of 49 X:CB‐2 101 RB‐X:CB‐2 / X1 101‐52 ‐X1/X:CB‐2 CB Open
132 kV 101 101‐52  101 RB Core 3 X1 X:CB‐3 101 RB‐X:CB‐3 / X1 101‐52 ‐X1/X:CB‐3 CB Close
132 kV 101 101‐52  101 RB Core 4 X1 X:CB‐4 101 RB‐X:CB‐4 / X1 101‐52 ‐X1/X:CB‐4 General SF6 Lockout
132 kV 101 101‐52  101 RB Core 5 X1 X:CB‐5 101 RB‐X:CB‐5 / X1 101‐52 ‐X1/X:CB‐5 Loss of SF6 Alarm
132 kV 101 101‐52  101 RB Core 6 X1 X:CB‐6 101 RB‐X:CB‐6 / X1 101‐52 ‐X1/X:CB‐6 Spring Status protection
132 kV 101 101‐52  101 RB Core 7 X1 X:CB‐7 101 RB‐X:CB‐7 / X1 101‐52 ‐X1/X:CB‐7 Spring Status supervision
132 kV 101 101‐52  101 RB Core 8 X1 X:CB‐8 101 RB‐X:CB‐8 / X1 101‐52 ‐X1/X:CB‐8 DC‐1 & 2 Monitor
132 kV 101 101‐52  101 RB Core 9 G719EA‐MG9031‐00‐ X1:26 G719EA‐MG9031‐00‐ X:CB‐18 101 RB‐X:CB‐18 / X1:26 101‐52 ‐X1:26/X:CB‐18
CB Closing I/L permissible
132 kV 101 101‐52  101 RB Core 10 W101, Sh‐34 of 49 X1:27 W101, Sh‐34 of 49 X:CB‐19 101 RB‐X:CB‐19 / X1:27 101‐52 ‐X1:27/X:CB‐19
132 kV 101 101‐52  101 RB Core 11 X1:23 X:CB‐33 101 RB‐X:CB‐33 / X1:23 101‐52 ‐X1:23/X:CB‐33 Common
132 kV 101 101‐52  101 RB Core 12 X1:24 X:CB‐34 101 RB‐X:CB‐34 / X1:24 101‐52 ‐X1:24/X:CB‐34 Remote Close
132 kV 101 101‐52  101 RB Core 13 X1:25 X:CB‐35 101 RB‐X:CB‐35 / X1:25 101‐52 ‐X1:25/X:CB‐35 Auto Reclose
132 kV 101 101‐52  101 RB Core 14 X1:5 X:CB‐21 101 RB‐X:CB‐21 / X1:5 101‐52 ‐X1:5/X:CB‐21 Common
132 kV 101 101‐52  101 RB Core 15 X1:6 X:CB‐22 101 RB‐X:CB‐22 / X1:6 101‐52 ‐X1:6/X:CB‐22 Remote Trip‐1
132 kV 101 101‐52  101 RB Core 16 X1:14 X:CB‐25 101 RB‐X:CB‐25 / X1:14 101‐52 ‐X1:14/X:CB‐25 Common
132 kV 101 101‐52  101 RB Core 17 X1:15 X:CB‐26 101 RB‐X:CB‐26 / X1:15 101‐52 ‐X1:15/X:CB‐26 Remote Trip‐2
132 kV 101 101‐52  101 RB Core 18 SPARE
132 kV 101 101‐52  101 RB Core 19 SPARE

107‐CIRCUIT BREAKER CABLING TO PANEL
34 132 kV 107 within swyd  1‐107‐1‐034 1 Cu./Amr. PVC 107‐52  101 RA 3CX2.5 55 Core 1 G719EA‐MG9031‐00‐ X1LA‐5 G719EA‐MG9031‐ X:TCB‐1 101 RA‐X:TCB‐1 / X1LA‐5 107‐52 ‐X1LA‐5/X:TCB‐1 Common
132 kV 107 107‐52  101 RA Core 2 W101, Sh‐17 of 49 X1LA‐6 W101, Sh‐17 of 58 X:TCB‐2 101 RA‐X:TCB‐2 / X1LA‐6 107‐52 ‐X1LA‐6/X:TCB‐2 TBC CB Open
132 kV 107 107‐52  101 RA Core 3 SPARE
101‐ISOLATOR CABLING TO PANEL
35 132 kV 101 within swyd  1‐101‐1‐035 1 Cu./Amr. PVC 101‐89A  101 RA 5CX2.5 30 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐5 101 RA‐X:BB‐5 / TB3‐103 101‐89A ‐TB3‐103/X:BB‐5 Common
132 kV 101 101‐89A  101 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐6 101 RA‐X:BB‐6 / TB3‐104 101‐89A ‐TB3‐104/X:BB‐6 Isolator 89A Open
132 kV 101 101‐89A  101 RA Core 3 G719EA‐MG9031‐00‐ TB3‐101 G719EA‐MG9031‐00‐ X:ISA‐1 101 RA‐X:ISA‐1 / TB3‐101 101‐89A ‐TB3‐101/X:ISA‐1 Isolator 89A Close
132 kV 101 101‐89A  101 RA Core 4 W101, Sh‐25a of 49 TB3‐102 W101, Sh‐25a of 49 X:ISA‐2 101 RA‐X:ISA‐2 / TB3‐102 101‐89A ‐TB3‐102/X:ISA‐2 Common
132 kV 101 101‐89A  101 RA Core 5 SPARE

36 132 kV 101 within swyd  1‐101‐1‐036 1 Cu./Amr. PVC 101‐89A  101 RB 10CX2.5 30 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:ISA‐1 101 RB‐X:ISA‐1 / TB3‐103 101‐89A ‐TB3‐103/X:ISA‐1 Common
132 kV 101 101‐89A  101 RB Core 2 W101, Sh‐29 of 49 TB3‐104 W101, Sh‐29 of 49 X:ISA‐2 101 RB‐X:ISA‐2 / TB3‐104 101‐89A ‐TB3‐104/X:ISA‐2 Isolator 89A Open
132 kV 101 101‐89A  101 RB Core 3 TB3‐102 X:ISA‐3 101 RB‐X:ISA‐3 / TB3‐102 101‐89A ‐TB3‐102/X:ISA‐3 Isolator 89A Close
132 kV 101 101‐89A  101 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISA‐7 101 RB‐X:ISA‐7 / TB1‐1 101‐89A ‐TB1‐1/X:ISA‐7 DC Supply (+)Ve
132 kV 101 101‐89A  101 RB Core 5 W101, Sh‐35 of 49 TB1‐2 W101, Sh‐35 of 49 X:ISA‐8 101 RB‐X:ISA‐8 / TB1‐2 101‐89A ‐TB1‐2/X:ISA‐8 DC Supply (‐)Ve
132 kV 101 101‐89A  101 RB Core 6 TB1‐3 X:ISA‐9 101 RB‐X:ISA‐9 / TB1‐3 101‐89A ‐TB1‐3/X:ISA‐9 Common
132 kV 101 101‐89A  101 RB Core 7 TB1‐5 X:ISA‐10 101 RB‐X:ISA‐10 / TB1‐5 101‐89A ‐TB1‐5/X:ISA‐10 Open 
132 kV 101 101‐89A  101 RB Core 8 TB1‐4 X:ISA‐11 101 RB‐X:ISA‐11 / TB1‐4 101‐89A ‐TB1‐4/X:ISA‐11 Close
132 kV 101 101‐89A  101 RB Core 9 SPARE
132 kV 101 101‐89A  101 RB Core 10 SPARE

37 132 kV 101 within swyd  1‐101‐1‐037 1 Cu./Amr. PVC 101‐89B  101 RA 5CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐7 101 RA‐X:BB‐7 / TB3‐103 101‐89B ‐TB3‐103/X:BB‐7 Common
132 kV 101 101‐89B  101 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐8 101 RA‐X:BB‐8 / TB3‐104 101‐89B ‐TB3‐104/X:BB‐8 Isolator 89B Open
132 kV 101 101‐89B  101 RA Core 3 G719EA‐MG9031‐00‐ TB3‐101 G719EA‐MG9031‐00‐ X:ISB‐1 101 RA‐X:ISB‐1 / TB3‐101 101‐89B ‐TB3‐101/X:ISB‐1 Isolator 89A Close
132 kV 101 101‐89B  101 RA Core 4 W101, Sh‐25a of 49 TB3‐102 W101, Sh‐25a of 49 X:ISB‐2 101 RA‐X:ISB‐2 / TB3‐102 101‐89B ‐TB3‐102/X:ISB‐2 Common
132 kV 101 101‐89B  101 RA Core 5 SPARE

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 3 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY101L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)

38 132 kV 101 within swyd  1‐101‐1‐038 1 Cu./Amr. PVC 101‐89B  101 RB 10CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐ X:ISB‐1 101 RB‐X:ISB‐1 / TB3‐107 101‐89B ‐TB3‐107/X:ISB‐1 Common
132 kV 101 101‐89B  101 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐35 of 58 X:ISB‐2 101 RB‐X:ISB‐2 / TB3‐108 101‐89B ‐TB3‐108/X:ISB‐2 Isolator 89B Open
132 kV 101 101‐89B  101 RB Core 3 TB3‐102 X:ISB‐3 101 RB‐X:ISB‐3 / TB3‐102 101‐89B ‐TB3‐102/X:ISB‐3 Isolator 89B Close
132 kV 101 101‐89B  101 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISB‐4 101 RB‐X:ISB‐4 / TB1‐1 101‐89B ‐TB1‐1/X:ISB‐4 DC Supply (+)Ve
132 kV 101 101‐89B  101 RB Core 5 W101, Sh‐35 of 49 TB1‐2 W101, Sh‐35 of 49 X:ISB‐5 101 RB‐X:ISB‐5 / TB1‐2 101‐89B ‐TB1‐2/X:ISB‐5 DC Supply (‐)Ve
132 kV 101 101‐89B  101 RB Core 6 TB1‐5 X:ISB‐7 101 RB‐X:ISB‐7 / TB1‐5 101‐89B ‐TB1‐5/X:ISB‐7 Open 
132 kV 101 101‐89B  101 RB Core 7 TB1‐4 X:ISB‐8 101 RB‐X:ISB‐8 / TB1‐4 101‐89B ‐TB1‐4/X:ISB‐8 Close
132 kV 101 101‐89B  101 RB Core 8 TB1‐3 X:ISB‐6 101 RB‐X:ISB‐6 / TB1‐3 101‐89B ‐TB1‐3/X:ISB‐6 Common
132 kV 101 101‐89B  101 RB Core 9 SPARE
132 kV 101 101‐89B  101 RB Core 10 SPARE

39 132 kV 101 within swyd  1‐101‐1‐039 1 Cu./Amr. PVC 101‐89T  101 RA 5CX2.5 60 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐9 101 RA‐X:BB‐9 / TB3‐103 101‐89T ‐TB3‐103/X:BB‐9 Common
132 kV 101 101‐89T  101 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐10 101 RA‐X:BB‐10 / TB3‐104 101‐89T ‐TB3‐104/X:BB‐10 Isolator 89T Open
132 kV 101 101‐89T  101 RA Core 3 G719EA‐MG9031‐00‐ TBX‐X G719EA‐MG9031‐00‐ X:IST‐1 101 RA‐X:IST‐1 / TBX‐X 101‐89T ‐TBX‐X/X:IST‐1 Trip Bus‐3 (Transfer Bus)
132 kV 101 101‐89T  101 RA Core 4 W101, Sh‐25a of 49 TBX‐X W101, Sh‐25a of 49 X:IST‐2 101 RA‐X:IST‐2 / TBX‐X 101‐89T ‐TBX‐X/X:IST‐2 Common
132 kV 101 101‐89T  101 RA Core 5 SPARE

40 132 kV 101 within swyd  1‐101‐1‐040 1 Cu./Amr. PVC 101‐89T  101 RB 10CX2.5 60 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:IST‐1 101 RB‐X:IST‐1 / TB3‐107 101‐89T ‐TB3‐107/X:IST‐1 Common
132 kV 101 101‐89T  101 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:IST‐2 101 RB‐X:IST‐2 / TB3‐108 101‐89T ‐TB3‐108/X:IST‐2 Isolator 89T Open
132 kV 101 101‐89T  101 RB Core 3 TB3‐102 X:IST‐3 101 RB‐X:IST‐3 / TB3‐102 101‐89T ‐TB3‐102/X:IST‐3 Isolator 89T Close
132 kV 101 101‐89T  101 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:IST‐4 101 RB‐X:IST‐4 / TB1‐1 101‐89T ‐TB1‐1/X:IST‐4 DC Supply (+)Ve
132 kV 101 101‐89T  101 RB Core 5 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 X:IST‐5 101 RB‐X:IST‐5 / TB1‐2 101‐89T ‐TB1‐2/X:IST‐5 DC Supply (‐)Ve
132 kV 101 101‐89T  101 RB Core 6 TB1‐3 X:IST‐6 101 RB‐X:IST‐6 / TB1‐3 101‐89T ‐TB1‐3/X:IST‐6 Common
132 kV 101 101‐89T  101 RB Core 7 TB1‐5 X:IST‐7 101 RB‐X:IST‐7 / TB1‐5 101‐89T ‐TB1‐5/X:IST‐7 Open 
132 kV 101 101‐89T  101 RB Core 8 TB1‐4 X:IST‐8 101 RB‐X:IST‐8 / TB1‐4 101‐89T ‐TB1‐4/X:IST‐8 Close
132 kV 101 101‐89T  101 RB Core 9 SPARE
132 kV 101 101‐89T  101 RB Core 10 SPARE

41 132 kV 101 within swyd  1‐101‐1‐041 1 Cu./Amr. PVC 101‐89L  101 RA 3CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐11 101 RA‐X:BB‐11 / TB3‐103 101‐89L ‐TB3‐103/X:BB‐11 Common
132 kV 101 101‐89L  101 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐12 101 RA‐X:BB‐12 / TB3‐104 101‐89L ‐TB3‐104/X:BB‐12 Isolator 89L Open
132 kV 101 101‐89L  101 RA Core 3 SPARE

42 132 kV 101 within swyd  1‐101‐1‐042 1 Cu./Amr. PVC 101‐89LE  101 RB 10CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISL‐1 101 RB‐X:ISL‐1 / TB3‐107 101‐89LE ‐TB3‐107/X:ISL‐1 Common
132 kV 101 101‐89LE  101 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:ISL‐2 101 RB‐X:ISL‐2 / TB3‐108 101‐89LE ‐TB3‐108/X:ISL‐2 Isolator 89L Open
132 kV 101 101‐89LE  101 RB Core 3 TB3‐102 X:ISL‐3 101 RB‐X:ISL‐3 / TB3‐102 101‐89LE ‐TB3‐102/X:ISL‐3 Isolator 89L Close
132 kV 101 101‐89LE  101 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISL‐10 101 RB‐X:ISL‐10 / TB1‐1 101‐89LE ‐TB1‐1/X:ISL‐10 DC Supply (+)Ve
132 kV 101 101‐89LE  101 RB Core 5 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 X:ISL‐11 101 RB‐X:ISL‐11 / TB1‐2 101‐89LE ‐TB1‐2/X:ISL‐11 DC Supply (‐)Ve
132 kV 101 101‐89LE  101 RB Core 6 TB1‐3 X:ISL‐12 101 RB‐X:ISL‐12 / TB1‐3 101‐89LE ‐TB1‐3/X:ISL‐12 Common
132 kV 101 101‐89LE  101 RB Core 7 TB1‐5 X:ISL‐13 101 RB‐X:ISL‐13 / TB1‐5 101‐89LE ‐TB1‐5/X:ISL‐13 Open 
132 kV 101 101‐89LE  101 RB Core 8 TB1‐4 X:ISL‐14 101 RB‐X:ISL‐14 / TB1‐4 101‐89LE ‐TB1‐4/X:ISL‐14 Close
132 kV 101 101‐89LE  101 RB Core 9 SPARE
132 kV 101 101‐89LE  101 RB Core 10 SPARE

101‐EARTH SWITCH CABLING TO PANEL
43 132 kV 101 within swyd  1‐101‐1‐043 1 Cu./Amr. PVC 101‐89AE  101 RB 5CX2.5 30 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISA‐4 101 RB‐X:ISA‐4 / TB3‐107 101‐89AE ‐TB3‐107/X:ISA‐4 Common
132 kV 101 101‐89AE  101 RB Core 2 W101, Sh‐29 of 49 TB3‐108 W101, Sh‐29 of 49 X:ISA‐5 101 RB‐X:ISA‐5 / TB3‐108 101‐89AE ‐TB3‐108/X:ISA‐5 E/s 89AE Open
132 kV 101 101‐89AE  101 RB Core 3 TB3‐102 X:ISA‐6 101 RB‐X:ISA‐6 / TB3‐102 101‐89AE ‐TB3‐102/X:ISA‐6 E/s 89AE Close
132 kV 101 101‐89AE  101 RB Core 4 SPARE
Core 5 SPARE

44 132 kV 101 within swyd  1‐101‐1‐044 1 Cu./Amr. PVC 101‐89LE1  101 RB 5CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISL‐4 101 RB‐X:ISL‐4 / TB3‐107 101‐89LE1 ‐TB3‐107/X:ISL‐4 Common
132 kV 101 101‐89LE1  101 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:ISL‐5 101 RB‐X:ISL‐5 / TB3‐108 101‐89LE1 ‐TB3‐108/X:ISL‐5 E/s 89LE1 Open
132 kV 101 101‐89LE1  101 RB Core 3 TB3‐102 X:ISL‐6 101 RB‐X:ISL‐6 / TB3‐102 101‐89LE1 ‐TB3‐102/X:ISL‐6 E/s 89LE1 Close
132 kV 101 101‐89LE1  101 RB Core 4 SPARE
132 kV 101 101‐89LE1  101 RB Core 5 SPARE

45 132 kV 101 within swyd  1‐101‐1‐045 1 Cu./Amr. PVC 101‐89LE2  101 RB 5CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISL‐7 101 RB‐X:ISL‐7 / TB3‐107 101‐89LE2 ‐TB3‐107/X:ISL‐7 Common
132 kV 101 101‐89LE2  101 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:ISL‐8 101 RB‐X:ISL‐8 / TB3‐108 101‐89LE2 ‐TB3‐108/X:ISL‐8 E/s 89LE2 Open
132 kV 101 101‐89LE2  101 RB Core 3 TB3‐102 X:ISL‐9 101 RB‐X:ISL‐9 / TB3‐102 101‐89LE2 ‐TB3‐102/X:ISL‐9 E/s 89LE2 Close
132 kV 101 101‐89LE2  101 RB Core 4 SPARE
132 kV 101 101‐89LE2  101 RB Core 5 SPARE

101‐PLCC CHANNEL TO PANEL
46 132 kV 101 within swyd  1‐101‐1‐046 1 Cu./Amr. PVC 101‐PLCC  CH‐1 101 RA 10CX2.5 10 Core 1 G719EA‐MG9031‐00‐ X12‐1‐P11‐09 G719EA‐MG9031‐00‐ X:PLCC‐1 101 RA‐X:PLCC‐1 / X12‐1‐P11‐09 101‐PLCC  CH‐1‐X12‐1‐P11‐09/X:PLCC‐1 Common
132 kV 101 101‐PLCC  CH‐1 101 RA Core 2 W101, Sh‐18 of 49 X12‐1‐P11‐10 W101, Sh‐18 of 49 X:PLCC‐2 101 RA‐X:PLCC‐2 / X12‐1‐P11‐10 101‐PLCC  CH‐1‐X12‐1‐P11‐10/X:PLCC‐2 Carrier Fail CH‐1
132 kV 101 101‐PLCC  CH‐1 101 RA Core 3 X12‐1‐P10‐2 X:PLCC‐3 101 RA‐X:PLCC‐3 / X12‐1‐P10‐2 101‐PLCC  CH‐1‐X12‐1‐P10‐2/X:PLCC‐3 Common
132 kV 101 101‐PLCC  CH‐1 101 RA Core 4 X12‐1‐P16‐36 X:PLCC‐4 101 RA‐X:PLCC‐4 / X12‐1‐P16‐36 101‐PLCC  CH‐1‐X12‐1‐P16‐36/X:PLCC‐4 Common
132 kV 101 101‐PLCC  CH‐1 101 RA Core 5 X12‐1‐P16‐37 X:PLCC‐5 101 RA‐X:PLCC‐5 / X12‐1‐P16‐37 101‐PLCC  CH‐1‐X12‐1‐P16‐37/X:PLCC‐5 Carrier Received CH‐1
132 kV 101 101‐PLCC  CH‐1 101 RA Core 6 X12‐1‐P11‐13 X:PLCC‐6 101 RA‐X:PLCC‐6 / X12‐1‐P11‐13 101‐PLCC  CH‐1‐X12‐1‐P11‐13/X:PLCC‐6 Direct Trip Received CH‐1
132 kV 101 101‐PLCC  CH‐1 101 RA Core 7 X12‐1‐P11‐14 X:PLCC‐7 101 RA‐X:PLCC‐7 / X12‐1‐P11‐14 101‐PLCC  CH‐1‐X12‐1‐P11‐14/X:PLCC‐7 Carrier Send CH‐1
132 kV 101 101‐PLCC  CH‐1 101 RA Core 8 X12‐1‐P10‐5 X:PLCC‐8 101 RA‐X:PLCC‐8 / X12‐1‐P10‐5 101‐PLCC  CH‐1‐X12‐1‐P10‐5/X:PLCC‐8 Direct Trip Send (Code‐4)
132 kV 101 101‐PLCC  CH‐1 101 RA Core 9 SPARE
132 kV 101 101‐PLCC  CH‐1 101 RA Core 10 SPARE

47 132 kV 101 within swyd  1‐101‐1‐047 1 Cu./Amr. PVC 101‐PLCC  CH‐2 101 RA 10CX2.5 10 Core 1 G719EA‐MG9031‐ X11‐1‐P11‐09 G719EA‐MG9031‐ X:PLCC‐9 101 RA‐X:PLCC‐9 / X11‐1‐P11‐09 101‐PLCC  CH‐2‐X11‐1‐P11‐09/X:PLCC‐9 Direct Trip Received CH‐2
132 kV 101 101‐PLCC  CH‐2 101 RA Core 2 W101, Sh‐18 of 49 X11‐1‐P11‐10 W101, Sh‐18 of 49 X:PLCC‐10 101 RA‐X:PLCC‐10 / X11‐1‐P11‐10 101‐PLCC  CH‐2‐X11‐1‐P11‐10/X:PLCC‐10 Common
132 kV 101 101‐PLCC  CH‐2 101 RA Core 3 X11‐1‐P10‐2 X:PLCC‐11 101 RA‐X:PLCC‐11 / X11‐1‐P10‐2 101‐PLCC  CH‐2‐X11‐1‐P10‐2/X:PLCC‐11 Carrier Fail CH‐2
132 kV 101 101‐PLCC  CH‐2 101 RA Core 4 X11‐1‐P16‐36 X:PLCC‐12 101 RA‐X:PLCC‐12 / X11‐1‐P16‐36 101‐PLCC  CH‐2‐X11‐1‐P16‐36/X:PLCC‐12 Common
132 kV 101 101‐PLCC  CH‐2 101 RA Core 5 X11‐1‐P16‐37 X:PLCC‐13 101 RA‐X:PLCC‐13 / X11‐1‐P16‐37 101‐PLCC  CH‐2‐X11‐1‐P16‐37/X:PLCC‐13 Carrier Received CH‐2
132 kV 101 101‐PLCC  CH‐2 101 RA Core 6 X11‐1‐P11‐13 X:PLCC‐14 101 RA‐X:PLCC‐14 / X11‐1‐P11‐13 101‐PLCC  CH‐2‐X11‐1‐P11‐13/X:PLCC‐14 Carrier Send CH‐2
132 kV 101 101‐PLCC  CH‐2 101 RA Core 7 X11‐1‐P11‐14 X:PLCC‐15 101 RA‐X:PLCC‐15 / X11‐1‐P11‐14 101‐PLCC  CH‐2‐X11‐1‐P11‐14/X:PLCC‐15 Direct Trip Send (Code‐4)
132 kV 101 101‐PLCC  CH‐2 101 RA Core 8 SPARE
132 kV 101 101‐PLCC  CH‐2 101 RA Core 9 SPARE

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 4 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY101L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)
132 kV 101 101‐PLCC  CH‐2 101 RA Core 10 SPARE

101‐Inter Panel Cabling
48 132 kV 101 within swyd  1‐101‐1‐048 1 Cu./Amr. PVC 101 RA 101 RB 27CX2.5 10 Core 1 G719EA‐MG9031‐ XCRA‐31 G719EA‐MG9031‐ XCRB‐31 101 RB‐XCRB‐31 / XCRA‐31 101 RA‐XCRA‐31/XCRB‐31 Common
101 RA 101 RB Core 2 W101, Sh‐25 of 49 XCRA‐32 W101, Sh‐25 of 49 XCRB‐32 101 RB‐XCRB‐32 / XCRA‐32 101 RA‐XCRA‐32/XCRB‐32
101 RA 101 RB Core 3 G719EA‐MG9031‐ XCRA‐15 G719EA‐MG9031‐ XCRB‐15 101 RB‐XCRB‐15 / XCRA‐15 101 RA‐XCRA‐15/XCRB‐15
101 RA 101 RB Core 4 W101, Sh‐26 of 49 XCRA‐16 W101, Sh‐26 of 49 XCRB‐16 101 RB‐XCRB‐16 / XCRA‐16 101 RA‐XCRA‐16/XCRB‐16
101 RA 101 RB Core 5 XCRA‐17 XCRB‐17 101 RB‐XCRB‐17 / XCRA‐17 101 RA‐XCRA‐17/XCRB‐17
101 RA 101 RB Core 6 XCRA‐18 XCRB‐18 101 RB‐XCRB‐18 / XCRA‐18 101 RA‐XCRA‐18/XCRB‐18
101 RA 101 RB Core 7 G719EA‐MG9031‐ XCRA‐10 G719EA‐MG9031‐ XCRB‐10 101 RB‐XCRB‐10 / XCRA‐10 101 RA‐XCRA‐10/XCRB‐10
101 RA 101 RB Core 8 W101, Sh‐27 of 49 XCRA‐11 W101, Sh‐27 of 49 XCRB‐11 101 RB‐XCRB‐11 / XCRA‐11 101 RA‐XCRA‐11/XCRB‐11
101 RA 101 RB Core 9 XCRA‐12 XCRB‐12 101 RB‐XCRB‐12 / XCRA‐12 101 RA‐XCRA‐12/XCRB‐12
101 RA 101 RB Core 10 XCRA‐13 XCRB‐13 101 RB‐XCRB‐13 / XCRA‐13 101 RA‐XCRA‐13/XCRB‐13
101 RA 101 RB Core 11 G719EA‐MG9031‐ XCRA‐45 G719EA‐MG9031‐ XCRB‐45 101 RB‐XCRB‐45 / XCRA‐45 101 RA‐XCRA‐45/XCRB‐45
101 RA 101 RB Core 12 W101, Sh‐33 of 49 XCRA‐46 W101, Sh‐33 of 49 XCRB‐46 101 RB‐XCRB‐46 / XCRA‐46 101 RA‐XCRA‐46/XCRB‐46
101 RA 101 RB Core 13 XCRA‐47 XCRB‐47 101 RB‐XCRB‐47 / XCRA‐47 101 RA‐XCRA‐47/XCRB‐47
101 RA 101 RB Core 14 G719EA‐MG9031‐ XCRA‐48 G719EA‐MG9031‐ XCRB‐48 101 RB‐XCRB‐48 / XCRA‐48 101 RA‐XCRA‐48/XCRB‐48
101 RA 101 RB Core 15 W101, Sh‐34 of 49 XCRA‐49 W101, Sh‐34 of 49 XCRB‐49 101 RB‐XCRB‐49 / XCRA‐49 101 RA‐XCRA‐49/XCRB‐49
101 RA 101 RB Core 16 XCRA‐75 XCRB‐75 101 RB‐XCRB‐75 / XCRA‐75 101 RA‐XCRA‐75/XCRB‐75
101 RA 101 RB Core 17 XCRA‐76 XCRB‐76 101 RB‐XCRB‐76 / XCRA‐76 101 RA‐XCRA‐76/XCRB‐76
101 RA 101 RB Core 18 G719EA‐MG9031‐ XCRA‐66 G719EA‐MG9031‐ XCRB‐66 101 RB‐XCRB‐66 / XCRA‐66 101 RA‐XCRA‐66/XCRB‐66
101 RA 101 RB Core 19 W101, Sh‐34 of 49 XCRA‐67 W101, Sh‐34 of 49 XCRB‐67 101 RB‐XCRB‐67 / XCRA‐67 101 RA‐XCRA‐67/XCRB‐67
101 RA 101 RB Core 20 XCRA‐71 XCRB‐71 101 RB‐XCRB‐71 / XCRA‐71 101 RA‐XCRA‐71/XCRB‐71
101 RA 101 RB Core 21 XCRA‐72 XCRB‐72 101 RB‐XCRB‐72 / XCRA‐72 101 RA‐XCRA‐72/XCRB‐72
101 RA 101 RB Core 22 Spare Spare
101 RA 101 RB Core 23 Spare Spare
101 RA 101 RB Core 24 Spare Spare
101 RA 101 RB Core 25 Spare Spare
101 RA 101 RB Core 26 Spare Spare
101 RA 101 RB Core 27 Spare Spare

49 132 kV 101 within swyd  1‐101‐1‐049 1 Cu./Amr. PVC 101 RA 101 RB 19CX2.5 10 Core 1 G719EA‐MG9031‐ XCRA‐50 G719EA‐MG9031‐ XCRB‐50 101 RB‐XCRB‐50 / XCRA‐50 101 RA‐XCRA‐50/XCRB‐50
101 RA 101 RB Core 2 W101, Sh‐37 of 49 XCRA‐51 W101, Sh‐37 of 49 XCRB‐51 101 RB‐XCRB‐51 / XCRA‐51 101 RA‐XCRA‐51/XCRB‐51
101 RA 101 RB Core 3 XCRA‐54 XCRB‐54 101 RB‐XCRB‐54 / XCRA‐54 101 RA‐XCRA‐54/XCRB‐54
101 RA 101 RB Core 4 XCRA‐55 XCRB‐55 101 RB‐XCRB‐55 / XCRA‐55 101 RA‐XCRA‐55/XCRB‐55
101 RA 101 RB Core 5 XCRA‐58 XCRB‐58 101 RB‐XCRB‐58 / XCRA‐58 101 RA‐XCRA‐58/XCRB‐58
101 RA 101 RB Core 6 XCRA‐59 XCRB‐59 101 RB‐XCRB‐59 / XCRA‐59 101 RA‐XCRA‐59/XCRB‐59
101 RA 101 RB Core 7 XCRA‐63 XCRB‐63 101 RB‐XCRB‐63 / XCRA‐63 101 RA‐XCRA‐63/XCRB‐63
101 RA 101 RB Core 8 Spare
101 RA 101 RB Core 9 Spare
101 RA 101 RB Core 10 Spare
101 RA 101 RB Core 11 Spare
101 RA 101 RB Core 12 Spare
101 RA 101 RB Core 13 Spare
101 RA 101 RB Core 14 Spare
101 RA 101 RB Core 15 Spare
101 RA 101 RB Core 16 Spare
101 RA 101 RB Core 17 Spare
101 RA 101 RB Core 18 Spare
101 RA 101 RB Core 19 Spare

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 5 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY103L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)

Control Cable in Switchyard

103‐CVT CABLING
1 132 kV 103 within swyd  1‐103‐1‐001 1 Cu./Amr. PVC 103‐RCVT Core.‐1 103‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB1‐1 103‐CVT JB‐TB1‐1 / R‐1a 103‐RCVT Core.‐1‐R‐1a/TB1‐1 Core‐1
ASPL/UPPCL/20415U
132 kV 103‐RCVT Core.‐1 103‐CVT JB Core 2 100 R‐1n TB1‐3 Distance Main‐1 Protection Relay
103 103‐CVT JB‐TB1‐3 / R‐1n 103‐RCVT Core.‐1‐R‐1n/TB1‐3
132 kV 103 103‐RCVT Core.‐1 103‐CVT JB Core 3 SPARE TB1‐5 103‐CVT JB‐TB1‐5 / SPARE 103‐RCVT Core.‐1‐SPARE/TB1‐5 67/67N : O/c & E/f Relay

2 132 kV 103 within swyd  1‐103‐1‐002 1 Cu./Amr. PVC 103‐YCVT Core.‐1 103‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB1‐8 103‐CVT JB‐TB1‐8 / Y‐1a 103‐YCVT Core.‐1‐Y‐1a/TB1‐8 Core‐1
ASPL/UPPCL/20415U
132 kV 103‐YCVT Core.‐1 103‐CVT JB Core 2 100 Y‐1n TB1‐10 Distance Main‐1 Protection Relay
103 103‐CVT JB‐TB1‐10 / Y‐1n 103‐YCVT Core.‐1‐Y‐1n/TB1‐10
132 kV 103 103‐YCVT Core.‐1 103‐CVT JB Core 3 SPARE TB1‐12 103‐CVT JB‐TB1‐12 / SPARE 103‐YCVT Core.‐1‐SPARE/TB1‐12 67/67N : O/c & E/f Relay

3 132 kV 103 within swyd  1‐103‐1‐003 1 Cu./Amr. PVC 103‐BCVT Core.‐1 103‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB1‐15 103‐CVT JB‐TB1‐15 / B‐1a 103‐BCVT Core.‐1‐B‐1a/TB1‐15 Core‐1
ASPL/UPPCL/20415U
132 kV 103‐BCVT Core.‐1 103‐CVT JB Core 2 100 B‐1n TB1‐17 Distance Main‐1 Protection Relay
103 103‐CVT JB‐TB1‐17 / B‐1n 103‐BCVT Core.‐1‐B‐1n/TB1‐17
132 kV 103 103‐BCVT Core.‐1 103‐CVT JB Core 3 SPARE TB1‐19 103‐CVT JB‐TB1‐19 / SPARE 103‐BCVT Core.‐1‐SPARE/TB1‐19 67/67N : O/c & E/f Relay

4 132 kV 103 within swyd  1‐103‐1‐004 1 Cu./Amr. PVC 103‐RCVT Core.‐2 103‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB2‐1 103‐CVT JB‐TB2‐1 / R‐1a 103‐RCVT Core.‐2‐R‐1a/TB2‐1 Core‐2
ASPL/UPPCL/20415U
132 kV 103 103‐RCVT Core.‐2 103‐CVT JB Core 2 100 R‐1n TB2‐3 103‐CVT JB‐TB2‐3 / R‐1n 103‐RCVT Core.‐2‐R‐1n/TB2‐3 Spare
132 kV 103 103‐RCVT Core.‐2 103‐CVT JB Core 3 SPARE TB2‐5 103‐CVT JB‐TB2‐5 / SPARE 103‐RCVT Core.‐2‐SPARE/TB2‐5

5 132 kV 103 within swyd  1‐103‐1‐005 1 Cu./Amr. PVC 103‐YCVT Core.‐2 103‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB2‐8 103‐CVT JB‐TB2‐8 / Y‐1a 103‐YCVT Core.‐2‐Y‐1a/TB2‐8 Core‐2
ASPL/UPPCL/20415U
132 kV 103 103‐YCVT Core.‐2 103‐CVT JB Core 2 100 Y‐1n TB2‐10 103‐CVT JB‐TB2‐10 / Y‐1n 103‐YCVT Core.‐2‐Y‐1n/TB2‐10 Spare
132 kV 103 103‐YCVT Core.‐2 103‐CVT JB Core 3 SPARE TB2‐12 103‐CVT JB‐TB2‐12 / SPARE 103‐YCVT Core.‐2‐SPARE/TB2‐12

6 132 kV 103 within swyd  1‐103‐1‐006 1 Cu./Amr. PVC 103‐BCVT Core.‐2 103‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB2‐15 103‐CVT JB‐TB2‐15 / B‐1a 103‐BCVT Core.‐2‐B‐1a/TB2‐15 Core‐2
ASPL/UPPCL/20415U
132 kV 103 103‐BCVT Core.‐2 103‐CVT JB Core 2 100 B‐1n TB2‐17 103‐CVT JB‐TB2‐17 / B‐1n 103‐BCVT Core.‐2‐B‐1n/TB2‐17 Spare
132 kV 103 103‐BCVT Core.‐2 103‐CVT JB Core 3 SPARE TB2‐19 103‐CVT JB‐TB2‐19 / SPARE 103‐BCVT Core.‐2‐SPARE/TB2‐19

7 132 kV 103 within swyd  1‐103‐1‐007 1 Cu./Amr. PVC 103‐RCVT Core.‐3 103‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB3‐1 103‐CVT JB‐TB3‐1 / R‐1a 103‐RCVT Core.‐3‐R‐1a/TB3‐1 Core‐3
ASPL/UPPCL/20415U
132 kV 103 103‐RCVT Core.‐3 103‐CVT JB Core 2 100 R‐1n TB3‐3 103‐CVT JB‐TB3‐3 / R‐1n 103‐RCVT Core.‐3‐R‐1n/TB3‐3 Metering
132 kV 103 103‐RCVT Core.‐3 103‐CVT JB Core 3 SPARE TB3‐5 103‐CVT JB‐TB3‐5 / SPARE 103‐RCVT Core.‐3‐SPARE/TB3‐5

8 132 kV 103 within swyd  1‐103‐1‐008 1 Cu./Amr. PVC 103‐YCVT Core.‐3 103‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB3‐8 103‐CVT JB‐TB3‐8 / Y‐1a 103‐YCVT Core.‐3‐Y‐1a/TB3‐8 Core‐3
ASPL/UPPCL/20415U
132 kV 103 103‐YCVT Core.‐3 103‐CVT JB Core 2 100 Y‐1n TB3‐10 103‐CVT JB‐TB3‐10 / Y‐1n 103‐YCVT Core.‐3‐Y‐1n/TB3‐10 Metering
132 kV 103 103‐YCVT Core.‐3 103‐CVT JB Core 3 SPARE TB3‐12 103‐CVT JB‐TB3‐12 / SPARE 103‐YCVT Core.‐3‐SPARE/TB3‐12

9 132 kV 103 within swyd  1‐103‐1‐009 1 Cu./Amr. PVC 103‐BCVT Core.‐3 103‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB3‐15 103‐CVT JB‐TB3‐15 / B‐1a 103‐BCVT Core.‐3‐B‐1a/TB3‐15 Core‐3
ASPL/UPPCL/20415U
132 kV 103 103‐BCVT Core.‐3 103‐CVT JB Core 2 100 B‐1n TB3‐17 103‐CVT JB‐TB3‐17 / B‐1n 103‐BCVT Core.‐3‐B‐1n/TB3‐17 Metering
132 kV 103 103‐BCVT Core.‐3 103‐CVT JB Core 3 SPARE TB3‐19 103‐CVT JB‐TB3‐19 / SPARE 103‐BCVT Core.‐3‐SPARE/TB3‐19

103‐CT CABLING
10 132 kV 103 within swyd  1‐103‐1‐010 1 Cu./Amr. PVC 103‐RCT Core.‐5 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 5US1 5US1 103‐CT JB‐5US1 / 5US1 103‐RCT Core.‐5‐5US1/5US1 CORE‐5
ASPL/UPPCL/20415
132 kV 103 103‐RCT Core.‐5 103‐CT JB Core 2 058 5US2 5US2 103‐CT JB‐5US2 / 5US2 103‐RCT Core.‐5‐5US2/5US2 Distance Protection M1
132 kV 103 103‐RCT Core.‐5 103‐CT JB Core 3 5US3 5US3 103‐CT JB‐5US3 / 5US3 103‐RCT Core.‐5‐5US3/5US3
132 kV 103 103‐RCT Core.‐5 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐RCT Core.‐5‐Spare/Spare
132 kV 103 103‐RCT Core.‐5 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐RCT Core.‐5‐Spare/Spare

11 132 kV 103 within swyd  1‐103‐1‐011 1 Cu./Amr. PVC 103‐YCT Core.‐5 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 5VS1 5VS1 103‐CT JB‐5VS1 / 5VS1 103‐YCT Core.‐5‐5VS1/5VS1 CORE‐5
ASPL/UPPCL/20415
132 kV 103 103‐YCT Core.‐5 103‐CT JB Core 2 058 5VS2 5VS2 103‐CT JB‐5VS2 / 5VS2 103‐YCT Core.‐5‐5VS2/5VS2 Distance Protection M1
132 kV 103 103‐YCT Core.‐5 103‐CT JB Core 3 5VS3 5VS3 103‐CT JB‐5VS3 / 5VS3 103‐YCT Core.‐5‐5VS3/5VS3
132 kV 103 103‐YCT Core.‐5 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐YCT Core.‐5‐Spare/Spare
132 kV 103 103‐YCT Core.‐5 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐YCT Core.‐5‐Spare/Spare

12 132 kV 103 within swyd  1‐103‐1‐012 1 Cu./Amr. PVC 103‐BCT Core.‐5 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 5WS1 5WS1 103‐CT JB‐5WS1 / 5WS1 103‐BCT Core.‐5‐5WS1/5WS1 CORE‐5
ASPL/UPPCL/20415
132 kV 103 103‐BCT Core.‐5 103‐CT JB Core 2 058 5WS2 5WS2 103‐CT JB‐5WS2 / 5WS2 103‐BCT Core.‐5‐5WS2/5WS2 Distance Protection M1
132 kV 103 103‐BCT Core.‐5 103‐CT JB Core 3 5WS3 5WS3 103‐CT JB‐5WS3 / 5WS3 103‐BCT Core.‐5‐5WS3/5WS3
132 kV 103 103‐BCT Core.‐5 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐BCT Core.‐5‐Spare/Spare
132 kV 103 103‐BCT Core.‐5 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐BCT Core.‐5‐Spare/Spare

13 132 kV 103 within swyd  1‐103‐1‐013 1 Cu./Amr. PVC 103‐RCT Core.‐2 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 2US1 2US1 103‐CT JB‐2US1 / 2US1 103‐RCT Core.‐2‐2US1/2US1 CORE‐2
ASPL/UPPCL/20415
132 kV 103 103‐RCT Core.‐2 103‐CT JB Core 2 058 2US2 2US2 103‐CT JB‐2US2 / 2US2 103‐RCT Core.‐2‐2US2/2US2 67/67N : O/c & E/f Relay
132 kV 103 103‐RCT Core.‐2 103‐CT JB Core 3 2US3 2US3 103‐CT JB‐2US3 / 2US3 103‐RCT Core.‐2‐2US3/2US3
132 kV 103 103‐RCT Core.‐2 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐RCT Core.‐2‐Spare/Spare
132 kV 103 103‐RCT Core.‐2 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐RCT Core.‐2‐Spare/Spare

14 132 kV 103 within swyd  1‐103‐1‐014 1 Cu./Amr. PVC 103‐YCT Core.‐2 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 2VS1 2VS1 103‐CT JB‐2VS1 / 2VS1 103‐YCT Core.‐2‐2VS1/2VS1 CORE‐2
ASPL/UPPCL/20415
132 kV 103 103‐YCT Core.‐2 103‐CT JB Core 2 058 2VS2 2VS2 103‐CT JB‐2VS2 / 2VS2 103‐YCT Core.‐2‐2VS2/2VS2 67/67N : O/c & E/f Relay
132 kV 103 103‐YCT Core.‐2 103‐CT JB Core 3 2VS3 2VS3 103‐CT JB‐2VS3 / 2VS3 103‐YCT Core.‐2‐2VS3/2VS3
132 kV 103 103‐YCT Core.‐2 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐YCT Core.‐2‐Spare/Spare
132 kV 103 103‐YCT Core.‐2 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐YCT Core.‐2‐Spare/Spare

15 132 kV 103 within swyd  1‐103‐1‐015 1 Cu./Amr. PVC 103‐BCT Core.‐2 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 2WS1 2WS1 103‐CT JB‐2WS1 / 2WS1 103‐BCT Core.‐2‐2WS1/2WS1 CORE‐2
ASPL/UPPCL/20415
132 kV 103 103‐BCT Core.‐2 103‐CT JB Core 2 058 2WS2 2WS2 103‐CT JB‐2WS2 / 2WS2 103‐BCT Core.‐2‐2WS2/2WS2 67/67N : O/c & E/f Relay
132 kV 103 103‐BCT Core.‐2 103‐CT JB Core 3 2WS3 2WS3 103‐CT JB‐2WS3 / 2WS3 103‐BCT Core.‐2‐2WS3/2WS3
132 kV 103 103‐BCT Core.‐2 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐BCT Core.‐2‐Spare/Spare
132 kV 103 103‐BCT Core.‐2 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐BCT Core.‐2‐Spare/Spare

16 132 kV 103 within swyd  1‐103‐1‐016 1 Cu./Amr. PVC 103‐RCT Core.‐1 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 1US1 1US1 103‐CT JB‐1US1 / 1US1 103‐RCT Core.‐1‐1US1/1US1 CORE‐1
ASPL/UPPCL/20415
132 kV 103 103‐RCT Core.‐1 103‐CT JB Core 2 058 1US2 1US2 103‐CT JB‐1US2 / 1US2 103‐RCT Core.‐1‐1US2/1US2 87BB : Busbar Protection
132 kV 103 103‐RCT Core.‐1 103‐CT JB Core 3 1US3 1US3 103‐CT JB‐1US3 / 1US3 103‐RCT Core.‐1‐1US3/1US3
132 kV 103 103‐RCT Core.‐1 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐RCT Core.‐1‐Spare/Spare
132 kV 103 103‐RCT Core.‐1 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐RCT Core.‐1‐Spare/Spare

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 1 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY103L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)

17 132 kV 103 within swyd  1‐103‐1‐017 1 Cu./Amr. PVC 103‐YCT Core.‐1 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 1VS1 1VS1 103‐CT JB‐1VS1 / 1VS1 103‐YCT Core.‐1‐1VS1/1VS1 CORE‐1
ASPL/UPPCL/20415
132 kV 103 103‐YCT Core.‐1 103‐CT JB Core 2 058 1VS2 1VS2 103‐CT JB‐1VS2 / 1VS2 103‐YCT Core.‐1‐1VS2/1VS2 87BB : Busbar Protection
132 kV 103 103‐YCT Core.‐1 103‐CT JB Core 3 1VS3 1VS3 103‐CT JB‐1VS3 / 1VS3 103‐YCT Core.‐1‐1VS3/1VS3
132 kV 103 103‐YCT Core.‐1 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐YCT Core.‐1‐Spare/Spare
132 kV 103 103‐YCT Core.‐1 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐YCT Core.‐1‐Spare/Spare

18 132 kV 103 within swyd  1‐103‐1‐018 1 Cu./Amr. PVC 103‐BCT Core.‐1 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 1WS1 1WS1 103‐CT JB‐1WS1 / 1WS1 103‐BCT Core.‐1‐1WS1/1WS1 CORE‐1
ASPL/UPPCL/20415
132 kV 103 103‐BCT Core.‐1 103‐CT JB Core 2 058 1WS2 1WS2 103‐CT JB‐1WS2 / 1WS2 103‐BCT Core.‐1‐1WS2/1WS2 87BB : Busbar Protection
132 kV 103 103‐BCT Core.‐1 103‐CT JB Core 3 1WS3 1WS3 103‐CT JB‐1WS3 / 1WS3 103‐BCT Core.‐1‐1WS3/1WS3
132 kV 103 103‐BCT Core.‐1 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐BCT Core.‐1‐Spare/Spare
132 kV 103 103‐BCT Core.‐1 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐BCT Core.‐1‐Spare/Spare

19 132 kV 103 within swyd  1‐103‐1‐019 1 Cu./Amr. PVC 103‐RCT Core.‐3 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 3US1 3US1 103‐CT JB‐3US1 / 3US1 103‐RCT Core.‐3‐3US1/3US1 CORE‐3
ASPL/UPPCL/20415
132 kV 103 103‐RCT Core.‐3 103‐CT JB Core 2 058 3US2 3US2 103‐CT JB‐3US2 / 3US2 103‐RCT Core.‐3‐3US2/3US2 BCU : Bay Control Unit
132 kV 103 103‐RCT Core.‐3 103‐CT JB Core 3 3US3 3US3 103‐CT JB‐3US3 / 3US3 103‐RCT Core.‐3‐3US3/3US3
132 kV 103 103‐RCT Core.‐3 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐RCT Core.‐3‐Spare/Spare
132 kV 103 103‐RCT Core.‐3 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐RCT Core.‐3‐Spare/Spare

20 132 kV 103 within swyd  #N/A 1 Cu./Amr. PVC 103‐YCT Core.‐3 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 3VS1 3VS1 103‐CT JB‐3VS1 / 3VS1 103‐YCT Core.‐3‐3VS1/3VS1 CORE‐3
ASPL/UPPCL/20415
132 kV 103 103‐YCT Core.‐3 103‐CT JB Core 2 058 3VS2 3VS2 103‐CT JB‐3VS2 / 3VS2 103‐YCT Core.‐3‐3VS2/3VS2 BCU : Bay Control Unit
132 kV 103 103‐YCT Core.‐3 103‐CT JB Core 3 3VS3 3VS3 103‐CT JB‐3VS3 / 3VS3 103‐YCT Core.‐3‐3VS3/3VS3
132 kV 103 103‐YCT Core.‐3 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐YCT Core.‐3‐Spare/Spare
132 kV 103 103‐YCT Core.‐3 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐YCT Core.‐3‐Spare/Spare

21 132 kV 101 within swyd  1‐101‐1‐021 1 Cu./Amr. PVC 103‐BCT Core.‐3 103‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 3WS1 3WS1 103‐CT JB‐3WS1 / 3WS1 103‐BCT Core.‐3‐3WS1/3WS1 CORE‐3
ASPL/UPPCL/20415
132 kV 101 103‐BCT Core.‐3 103‐CT JB Core 2 058 3WS2 3WS2 103‐CT JB‐3WS2 / 3WS2 103‐BCT Core.‐3‐3WS2/3WS2 BCU : Bay Control Unit
132 kV 101 103‐BCT Core.‐3 103‐CT JB Core 3 3WS3 3WS3 103‐CT JB‐3WS3 / 3WS3 103‐BCT Core.‐3‐3WS3/3WS3
132 kV 101 103‐BCT Core.‐3 103‐CT JB Core 4 Spare Spare 103‐CT JB‐Spare / Spare 103‐BCT Core.‐3‐Spare/Spare
132 kV 101 103‐BCT Core.‐3 103‐CT JB Core 5 Spare Spare 103‐CT JB‐Spare / Spare 103‐BCT Core.‐3‐Spare/Spare

103‐BREAKER & E/s INTERLOCKING
22 132 kV 103 within swyd  1‐103‐1‐022 1 Cu./Amr. PVC 103‐89AE  103‐52  3CX2.5 37 Core 1 not included in CRP  TB3‐126 not included in CRP  TB‐XX 103‐52 ‐TB‐XX / TB3‐126 103‐89AE ‐TB3‐126/TB‐XX CB & E/s Interlock
132 kV 103 103‐89AE  103‐52  Core 2 drawing SPARE drawing
132 kV 103 103‐89AE  103‐52  Core 3 SPARE

23 132 kV 103 within swyd  1‐103‐1‐023 1 Cu./Amr. PVC 103‐89LE1  103‐52  3CX2.5 37 Core 1 not included in CRP  TB3‐126 not included in CRP  TB‐XX 103‐52 ‐TB‐XX / TB3‐126 103‐89LE1 ‐TB3‐126/TB‐XX CB & E/s Interlock
132 kV 103 103‐89LE1  103‐52  Core 2 drawing SPARE drawing
132 kV 103 103‐89LE1  103‐52  Core 3 SPARE

24 132 kV 103 within swyd  1‐103‐1‐024 1 Cu./Amr. PVC 103‐89LE2  103‐52  3CX2.5 30 Core 1 not included in CRP  TB3‐126 not included in CRP  TB‐XX 103‐52 ‐TB‐XX / TB3‐126 103‐89LE2 ‐TB3‐126/TB‐XX CB & E/s Interlock
132 kV 103 103‐89LE2  103‐52  Core 2 drawing SPARE drawing
132 kV 103 103‐89LE2  103‐52  Core 3 SPARE

103‐B/w EARTHSWITCH & ISOLATOR
25 132 kV 103 within swyd  1‐103‐1‐025 1 Cu./Amr. PVC 103‐89A  103‐89AE  3CX2.5 5 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ TB1‐1 103‐89AE ‐TB1‐1 / TB1‐1 103‐89A ‐TB1‐1/TB1‐1 (+)ve DC Supply
132 kV 103 103‐89A  103‐89AE  Core 2 W101, Sh‐35 of 49 TB1‐2 W101, Sh‐35 of 49 TB1‐2 103‐89AE ‐TB1‐2 / TB1‐2 103‐89A ‐TB1‐2/TB1‐2 (‐)ve DC Supply
132 kV 103 103‐89A  103‐89AE  Core 3 SPARE

26 132 kV 103 within swyd  1‐103‐1‐026 1 Cu./Amr. PVC 103‐89L  103‐89LE1  3CX2.5 5 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ TB1‐1 103‐89LE1 ‐TB1‐1 / TB1‐1 103‐89L ‐TB1‐1/TB1‐1 (+)ve DC Supply
132 kV 103 103‐89L  103‐89LE1  Core 2 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 TB1‐2 103‐89LE1 ‐TB1‐2 / TB1‐2 103‐89L ‐TB1‐2/TB1‐2 (‐)ve DC Supply
132 kV 103 103‐89L  103‐89LE1  Core 3 SPARE

27 132 kV 103 within swyd  1‐103‐1‐027 1 Cu./Amr. PVC 103‐89L  103‐89LE2  3CX2.5 5 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ TB1‐1 103‐89LE2 ‐TB1‐1 / TB1‐1 103‐89L ‐TB1‐1/TB1‐1 (+)ve DC Supply
132 kV 103 103‐89L  103‐89LE2  Core 2 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 TB1‐2 103‐89LE2 ‐TB1‐2 / TB1‐2 103‐89L ‐TB1‐2/TB1‐2 (‐)ve DC Supply
132 kV 103 103‐89L  103‐89LE2  Core 3 SPARE

Control Cable from Switchyard to Panel
103‐CVT CABLING TO PANEL
28 132 kV 103 within swyd  1‐103‐1‐028 1 Cu./Amr. PVC 103‐CVT JB 103 RA 5CX2.5 75 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:VTL‐1 103 RA‐X:VTL‐1 / TB1‐1 103‐CVT JB‐TB1‐1/X:VTL‐1 Distance Main‐1 Protection Relay
132 kV 103 103‐CVT JB 103 RA Core 2 W101, Sh‐13 of 49 TB1‐8 W101, Sh‐13 of 49 X:VTL‐2 103 RA‐X:VTL‐2 / TB1‐8 103‐CVT JB‐TB1‐8/X:VTL‐2 67/67N : O/c & E/f Relay
132 kV 103 103‐CVT JB 103 RA Core 3 TB1‐15 X:VTL‐3 103 RA‐X:VTL‐3 / TB1‐15 103‐CVT JB‐TB1‐15/X:VTL‐3
132 kV 103 103‐CVT JB 103 RA Core 4 TB1‐19 X:VTL‐4 103 RA‐X:VTL‐4 / TB1‐19 103‐CVT JB‐TB1‐19/X:VTL‐4
132 kV 103 103‐CVT JB 103 RA Core 5 SPARE

29 132 kV 103 within swyd  1‐103‐1‐029 1 Cu./Amr. PVC 103‐CVT JB 103 RB 10CX2.5 75 Core 1 G719EA‐MG9031‐00‐ TB2‐1 G719EA‐MG9031‐00‐ X:VTL‐1 103 RB‐X:VTL‐1 / TB2‐1 103‐CVT JB‐TB2‐1/X:VTL‐1 Spare
132 kV 103 103‐CVT JB 103 RB Core 2 W101, Sh‐13 of 49 TB2‐8 W101, Sh‐13 of 49 X:VTL‐2 103 RB‐X:VTL‐2 / TB2‐8 103‐CVT JB‐TB2‐8/X:VTL‐2
132 kV 103 103‐CVT JB 103 RB Core 3 TB2‐15 X:VTL‐3 103 RB‐X:VTL‐3 / TB2‐15 103‐CVT JB‐TB2‐15/X:VTL‐3
132 kV 103 103‐CVT JB 103 RB Core 4 TB2‐19 X:VTL‐4 103 RB‐X:VTL‐4 / TB2‐19 103‐CVT JB‐TB2‐19/X:VTL‐4
132 kV 103 103‐CVT JB 103 RB Core 5 G719EA‐MG9031‐00‐ TB3‐1 G719EA‐MG9031‐00‐ X:VTL‐5 103 RB‐X:VTL‐5 / TB3‐1 103‐CVT JB‐TB3‐1/X:VTL‐5
132 kV 103 103‐CVT JB 103 RB Core 6 W101, Sh‐13 of 49 TB3‐8 W101, Sh‐13 of 49 X:VTL‐6 103 RB‐X:VTL‐6 / TB3‐8 103‐CVT JB‐TB3‐8/X:VTL‐6 Metering
132 kV 103 103‐CVT JB 103 RB Core 7 TB3‐15 X:VTL‐7 103 RB‐X:VTL‐7 / TB3‐15 103‐CVT JB‐TB3‐15/X:VTL‐7
132 kV 103 103‐CVT JB 103 RB Core 8 TB3‐19 X:VTL‐8 103 RB‐X:VTL‐8 / TB3‐19 103‐CVT JB‐TB3‐19/X:VTL‐8
132 kV 103 103‐CVT JB 103 RB Core 9 SPARE
132 kV 103 103‐CVT JB 103 RB Core 10 SPARE
103‐CT CABLING
30 132 kV 103 within swyd  1‐103‐1‐030 1 Cu./Amr. PVC 103‐CT MB 103 RA 14CX2.5 72 Core 1 5US2 G719EA‐MG9031‐ X:CT‐1 103 RA‐X:CT‐1 / 5US2 103‐CT MB‐5US2/X:CT‐1
ASPL/UPPCL/20415
132 kV 103 103‐CT MB 103 RA Core 2 5VS2 W101, Sh‐16 of 58 X:CT‐3 103 RA‐X:CT‐3 / 5VS2 103‐CT MB‐5VS2/X:CT‐3
CORE 5: Distance Protection M1
132 kV 103 103‐CT MB 103 RA Core 3 5WS2 X:CT‐5 103 RA‐X:CT‐5 / 5WS2 103‐CT MB‐5WS2/X:CT‐5
132 kV 103 103‐CT MB 103 RA Core 4 5VS1 X:CT‐7 103 RA‐X:CT‐7 / 5VS1 103‐CT MB‐5VS1/X:CT‐7
132 kV 103 103‐CT MB 103 RA Core 5 2US2 G719EA‐MG9031‐00‐ X:CT‐21 103 RA‐X:CT‐21 / 2US2 103‐CT MB‐2US2/X:CT‐21
ASPL/UPPCL/20415
132 kV 103 103‐CT MB 103 RA Core 6 2VS2 W101, Sh‐19 of 49 X:CT‐23 103 RA‐X:CT‐23 / 2VS2 103‐CT MB‐2VS2/X:CT‐23 CORE 2: 67/67N : O/c & E/f Relay

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 2 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY103L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts) CORE 2: 67/67N : O/c & E/f Relay
132 kV 103 103‐CT MB 103 RA Core 7 2WS2 X:CT‐25 103 RA‐X:CT‐25 / 2WS2 103‐CT MB‐2WS2/X:CT‐25
132 kV 103 103‐CT MB 103 RA Core 8 2VS1 X:CT‐27 103 RA‐X:CT‐27 / 2VS1 103‐CT MB‐2VS1/X:CT‐27
132 kV 103 103‐CT MB 103 RA Core 9 1US2 G719EA‐MG9031‐00‐ X:CT‐29 103 RA‐X:CT‐29 / 1US2 103‐CT MB‐1US2/X:CT‐29
ASPL/UPPCL/20415
132 kV 103 103‐CT MB 103 RA Core 10 1VS2 W101, Sh‐21 of 49 X:CT‐31 103 RA‐X:CT‐31 / 1VS2 103‐CT MB‐1VS2/X:CT‐31 CORE1: 87BB : Busbar Protection
132 kV 103 103‐CT MB 103 RA Core 11 1WS2 X:CT‐33 103 RA‐X:CT‐33 / 1WS2 103‐CT MB‐1WS2/X:CT‐33
132 kV 103 103‐CT MB 103 RA Core 12 1VS1 X:CT‐35 103 RA‐X:CT‐35 / 1VS1 103‐CT MB‐1VS1/X:CT‐35
132 kV 103 103‐CT MB 103 RA Core 13 SPARE SPARE
132 kV 103 103‐CT MB 103 RA Core 14 SPARE SPARE

31 132 kV 103 within swyd  1‐103‐1‐031 1 Cu./Amr. PVC 103‐CT MB 103 RB 5CX2.5 50 Core 1 3US2 G719EA‐MG9031‐ X:CT‐23 103 RB‐X:CT‐23 / 3US2 103‐CT MB‐3US2/X:CT‐23
ASPL/UPPCL/20415
132 kV 103 103‐CT MB 103 RB Core 2 3VS2 W101, Sh‐33 of 58 X:CT‐25 103 RB‐X:CT‐25 / 3VS2 103‐CT MB‐3VS2/X:CT‐25
CORE 3: BCU : Bay Control Unit
132 kV 103 103‐CT MB 103 RB Core 3 3WS2 X:CT‐27 103 RB‐X:CT‐27 / 3WS2 103‐CT MB‐3WS2/X:CT‐27
132 kV 103 103‐CT MB 103 RB Core 4 3VS1 X:CT‐29 103 RB‐X:CT‐29 / 3VS1 103‐CT MB‐3VS1/X:CT‐29
132 kV 103 103‐CT MB 103 RB Core 5 SPARE

103‐CIRCUIT BREAKER CABLING TO PANEL
32 132 kV 103 within swyd  1‐103‐1‐032 1 Cu./Amr. PVC 103‐52  103 RA 19CX2.5 50 Core 1 G719EA‐MG9031‐00‐ X1LA‐5 G719EA‐MG9031‐ X:CB‐1 103 RA‐X:CB‐1 / X1LA‐5 103‐52 ‐X1LA‐5/X:CB‐1 Common
132 kV 103 103‐52  103 RA Core 2 W101, Sh‐17 of 49 X1LC‐6 W201, Sh‐17 of 58 X:CB‐2 103 RA‐X:CB‐2 / X1LC‐6 103‐52 ‐X1LC‐6/X:CB‐2 Main CB Open
132 kV 103 103‐52  103 RA Core 3 G719EA‐MG9031‐00‐ X1LA‐6 G719EA‐MG9031‐00‐ X:BB‐3 103 RA‐X:BB‐3 / X1LA‐6 103‐52 ‐X1LA‐6/X:BB‐3 CB Open
132 kV 103 103‐52  103 RA Core 4 W101, Sh‐22 of 49 X1LC‐6 W101, Sh‐22 of 49 X:BB‐4 103 RA‐X:BB‐4 / X1LC‐6 103‐52 ‐X1LC‐6/X:BB‐4 Main/TBC CB Open, B‐Ph
132 kV 103 103‐52  103 RA Core 5 G719EA‐MG9031‐00‐ X1 G719EA‐MG9031‐00‐ X:TC1‐3 103 RA‐X:TC1‐3 / X1 103‐52 ‐X1/X:TC1‐3 Common
132 kV 103 103‐52  103 RA Core 6 W101, Sh‐26 of 49 X1:7 W101, Sh‐26 of 49 X:TC1‐4 103 RA‐X:TC1‐4 / X1:7 103‐52 ‐X1:7/X:TC1‐4 Protection Trip‐1
132 kV 103 103‐52  103 RA Core 7 X1:10 X:TC1‐5 103 RA‐X:TC1‐5 / X1:10 103‐52 ‐X1:10/X:TC1‐5 Post Close TC‐1 Supervision
132 kV 103 103‐52  103 RA Core 8 X1:9 X:TC1‐6 103 RA‐X:TC1‐6 / X1:9 103‐52 ‐X1:9/X:TC1‐6 Pre Close TC‐1 Supervision 
132 kV 103 103‐52  103 RA Core 9 X1:1 X:TC1‐1 103 RA‐X:TC1‐1 / X1:1 103‐52 ‐X1:1/X:TC1‐1 DC Supply (+)Ve
132 kV 103 103‐52  103 RA Core 10 X1:2 X:TC1‐2 103 RA‐X:TC1‐2 / X1:2 103‐52 ‐X1:2/X:TC1‐2 DC Supply (‐)Ve
132 kV 103 103‐52  103 RA Core 11 G719EA‐MG9031‐00‐ X1 G719EA‐MG9031‐00‐ X:TC2‐9 103 RA‐X:TC2‐9 / X1 103‐52 ‐X1/X:TC2‐9 Common
132 kV 103 103‐52  103 RA Core 12 W101, Sh‐27 of 49 X1:16 W101, Sh‐27 of 49 X:TC2‐10 103 RA‐X:TC2‐10 / X1:16 103‐52 ‐X1:16/X:TC2‐10 Protection Trip‐2
132 kV 103 103‐52  103 RA Core 13 X1:19 X:TC2‐11 103 RA‐X:TC2‐11 / X1:19 103‐52 ‐X1:19/X:TC2‐11 Post Close TC‐2 Supervision
132 kV 103 103‐52  103 RA Core 14 X1:18 X:TC2‐12 103 RA‐X:TC2‐12 / X1:18 103‐52 ‐X1:18/X:TC2‐12 Pre Close TC‐2 Supervision 
132 kV 103 103‐52  103 RA Core 15 X1:1A X:TC2‐1 103 RA‐X:TC2‐1 / X1:1A 103‐52 ‐X1:1A/X:TC2‐1 DC Supply (+)Ve
132 kV 103 103‐52  103 RA Core 16 X1:2A X:TC2‐2 103 RA‐X:TC2‐2 / X1:2A 103‐52 ‐X1:2A/X:TC2‐2 DC Supply (‐)Ve
132 kV 103 103‐52  103 RA Core 17 SPARE
132 kV 103 103‐52  103 RA Core 18 SPARE
132 kV 103 103‐52  103 RA Core 19 SPARE

33 132 kV 103 within swyd  1‐103‐1‐033 1 Cu./Amr. PVC 103‐52  103 RB 19CX2.5 50 Core 1 G719EA‐MG9031‐00‐ X1 G719EA‐MG9031‐00‐ X:CB‐1 103 RB‐X:CB‐1 / X1 103‐52 ‐X1/X:CB‐1 Common
132 kV 103 103‐52  103 RB Core 2 W101, Sh‐29 of 49 X1 W101, Sh‐29 of 49 X:CB‐2 103 RB‐X:CB‐2 / X1 103‐52 ‐X1/X:CB‐2 CB Open
132 kV 103 103‐52  103 RB Core 3 X1 X:CB‐3 103 RB‐X:CB‐3 / X1 103‐52 ‐X1/X:CB‐3 CB Close
132 kV 103 103‐52  103 RB Core 4 X1 X:CB‐4 103 RB‐X:CB‐4 / X1 103‐52 ‐X1/X:CB‐4 General SF6 Lockout
132 kV 103 103‐52  103 RB Core 5 X1 X:CB‐5 103 RB‐X:CB‐5 / X1 103‐52 ‐X1/X:CB‐5 Loss of SF6 Alarm
132 kV 103 103‐52  103 RB Core 6 X1 X:CB‐6 103 RB‐X:CB‐6 / X1 103‐52 ‐X1/X:CB‐6 Spring Status protection
132 kV 103 103‐52  103 RB Core 7 X1 X:CB‐7 103 RB‐X:CB‐7 / X1 103‐52 ‐X1/X:CB‐7 Spring Status supervision
132 kV 103 103‐52  103 RB Core 8 X1 X:CB‐8 103 RB‐X:CB‐8 / X1 103‐52 ‐X1/X:CB‐8 DC‐1 & 2 Monitor
132 kV 103 103‐52  103 RB Core 9 G719EA‐MG9031‐00‐ X1:26 G719EA‐MG9031‐00‐ X:CB‐18 103 RB‐X:CB‐18 / X1:26 103‐52 ‐X1:26/X:CB‐18
CB Closing I/L permissible
132 kV 103 103‐52  103 RB Core 10 W101, Sh‐34 of 49 X1:27 W101, Sh‐34 of 49 X:CB‐19 103 RB‐X:CB‐19 / X1:27 103‐52 ‐X1:27/X:CB‐19
132 kV 103 103‐52  103 RB Core 11 X1:23 X:CB‐33 103 RB‐X:CB‐33 / X1:23 103‐52 ‐X1:23/X:CB‐33 Common
132 kV 103 103‐52  103 RB Core 12 X1:24 X:CB‐34 103 RB‐X:CB‐34 / X1:24 103‐52 ‐X1:24/X:CB‐34 Remote Close
132 kV 103 103‐52  103 RB Core 13 X1:25 X:CB‐35 103 RB‐X:CB‐35 / X1:25 103‐52 ‐X1:25/X:CB‐35 Auto Reclose
132 kV 103 103‐52  103 RB Core 14 X1:5 X:CB‐21 103 RB‐X:CB‐21 / X1:5 103‐52 ‐X1:5/X:CB‐21 Common
132 kV 103 103‐52  103 RB Core 15 X1:6 X:CB‐22 103 RB‐X:CB‐22 / X1:6 103‐52 ‐X1:6/X:CB‐22 Remote Trip‐1
132 kV 103 103‐52  103 RB Core 16 X1:14 X:CB‐25 103 RB‐X:CB‐25 / X1:14 103‐52 ‐X1:14/X:CB‐25 Common
132 kV 103 103‐52  103 RB Core 17 X1:15 X:CB‐26 103 RB‐X:CB‐26 / X1:15 103‐52 ‐X1:15/X:CB‐26 Remote Trip‐2
132 kV 103 103‐52  103 RB Core 18 SPARE
132 kV 103 103‐52  103 RB Core 19 SPARE

107‐CIRCUIT BREAKER CABLING TO PANEL
34 132 kV 107 within swyd  1‐107‐1‐034 1 Cu./Amr. PVC 107‐52  103 RA 3CX2.5 55 Core 1 G719EA‐MG9031‐00‐ X1LA‐5 G719EA‐MG9031‐ X:TCB‐1 103 RA‐X:TCB‐1 / X1LA‐5 107‐52 ‐X1LA‐5/X:TCB‐1 Common
132 kV 107 107‐52  103 RA Core 2 W101, Sh‐17 of 49 X1LA‐6 W101, Sh‐17 of 58 X:TCB‐2 103 RA‐X:TCB‐2 / X1LA‐6 107‐52 ‐X1LA‐6/X:TCB‐2 TBC CB Open
132 kV 107 107‐52  103 RA Core 3 SPARE
103‐ISOLATOR CABLING TO PANEL
35 132 kV 103 within swyd  1‐103‐1‐035 1 Cu./Amr. PVC 103‐89A  103 RA 5CX2.5 30 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐5 103 RA‐X:BB‐5 / TB3‐103 103‐89A ‐TB3‐103/X:BB‐5 Common
132 kV 103 103‐89A  103 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐6 103 RA‐X:BB‐6 / TB3‐104 103‐89A ‐TB3‐104/X:BB‐6 Isolator 89A Open
132 kV 103 103‐89A  103 RA Core 3 G719EA‐MG9031‐00‐ TB3‐101 G719EA‐MG9031‐00‐ X:ISA‐1 103 RA‐X:ISA‐1 / TB3‐101 103‐89A ‐TB3‐101/X:ISA‐1 Trip Bus‐1 (Main‐1)
132 kV 103 103‐89A  103 RA Core 4 W101, Sh‐25a of 49 TB3‐102 W101, Sh‐25a of 49 X:ISA‐2 103 RA‐X:ISA‐2 / TB3‐102 103‐89A ‐TB3‐102/X:ISA‐2 Common
132 kV 103 103‐89A  103 RA Core 5 SPARE

36 132 kV 103 within swyd  1‐103‐1‐036 1 Cu./Amr. PVC 103‐89A  103 RB 10CX2.5 30 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:ISA‐1 103 RB‐X:ISA‐1 / TB3‐103 103‐89A ‐TB3‐103/X:ISA‐1 Common
132 kV 103 103‐89A  103 RB Core 2 W101, Sh‐29 of 49 TB3‐104 W101, Sh‐29 of 49 X:ISA‐2 103 RB‐X:ISA‐2 / TB3‐104 103‐89A ‐TB3‐104/X:ISA‐2 Isolator 89A Open
132 kV 103 103‐89A  103 RB Core 3 TB3‐102 X:ISA‐3 103 RB‐X:ISA‐3 / TB3‐102 103‐89A ‐TB3‐102/X:ISA‐3 Isolator 89A Close
132 kV 103 103‐89A  103 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISA‐7 103 RB‐X:ISA‐7 / TB1‐1 103‐89A ‐TB1‐1/X:ISA‐7 DC Supply (+)Ve
132 kV 103 103‐89A  103 RB Core 5 W101, Sh‐35 of 49 TB1‐2 W101, Sh‐35 of 49 X:ISA‐8 103 RB‐X:ISA‐8 / TB1‐2 103‐89A ‐TB1‐2/X:ISA‐8 DC Supply (‐)Ve
132 kV 103 103‐89A  103 RB Core 6 TB1‐3 X:ISA‐9 103 RB‐X:ISA‐9 / TB1‐3 103‐89A ‐TB1‐3/X:ISA‐9 Common
132 kV 103 103‐89A  103 RB Core 7 TB1‐5 X:ISA‐10 103 RB‐X:ISA‐10 / TB1‐5 103‐89A ‐TB1‐5/X:ISA‐10 Open 
132 kV 103 103‐89A  103 RB Core 8 TB1‐4 X:ISA‐11 103 RB‐X:ISA‐11 / TB1‐4 103‐89A ‐TB1‐4/X:ISA‐11 Close
132 kV 103 103‐89A  103 RB Core 9 SPARE
132 kV 103 103‐89A  103 RB Core 10 SPARE

37 132 kV 103 within swyd  1‐103‐1‐037 1 Cu./Amr. PVC 103‐89B  103 RA 5CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐7 103 RA‐X:BB‐7 / TB3‐103 103‐89B ‐TB3‐103/X:BB‐7 Common
132 kV 103 103‐89B  103 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐8 103 RA‐X:BB‐8 / TB3‐104 103‐89B ‐TB3‐104/X:BB‐8 Isolator 89B Open
132 kV 103 103‐89B  103 RA Core 3 G719EA‐MG9031‐00‐ TB3‐101 G719EA‐MG9031‐00‐ X:ISB‐1 103 RA‐X:ISB‐1 / TB3‐101 103‐89B ‐TB3‐101/X:ISB‐1 Trip Bus‐2 (Main‐2)
132 kV 103 103‐89B  103 RA Core 4 W101, Sh‐25a of 49 TB3‐102 W101, Sh‐25a of 49 X:ISB‐2 103 RA‐X:ISB‐2 / TB3‐102 103‐89B ‐TB3‐102/X:ISB‐2 Common
132 kV 103 103‐89B  103 RA Core 5 SPARE

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 3 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY103L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)

38 132 kV 103 within swyd  1‐103‐1‐038 1 Cu./Amr. PVC 103‐89B  103 RB 10CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐ X:ISB‐1 103 RB‐X:ISB‐1 / TB3‐107 103‐89B ‐TB3‐107/X:ISB‐1 Common
132 kV 103 103‐89B  103 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W201, Sh‐35 of 58 X:ISB‐2 103 RB‐X:ISB‐2 / TB3‐108 103‐89B ‐TB3‐108/X:ISB‐2 Isolator 89B Open
132 kV 103 103‐89B  103 RB Core 3 TB3‐102 X:ISB‐3 103 RB‐X:ISB‐3 / TB3‐102 103‐89B ‐TB3‐102/X:ISB‐3 Isolator 89B Close
132 kV 103 103‐89B  103 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISB‐4 103 RB‐X:ISB‐4 / TB1‐1 103‐89B ‐TB1‐1/X:ISB‐4 DC Supply (+)Ve
132 kV 103 103‐89B  103 RB Core 5 W101, Sh‐35 of 49 TB1‐2 W101, Sh‐35 of 49 X:ISB‐5 103 RB‐X:ISB‐5 / TB1‐2 103‐89B ‐TB1‐2/X:ISB‐5 DC Supply (‐)Ve
132 kV 103 103‐89B  103 RB Core 6 TB1‐5 X:ISB‐7 103 RB‐X:ISB‐7 / TB1‐5 103‐89B ‐TB1‐5/X:ISB‐7 Open 
132 kV 103 103‐89B  103 RB Core 7 TB1‐4 X:ISB‐8 103 RB‐X:ISB‐8 / TB1‐4 103‐89B ‐TB1‐4/X:ISB‐8 Close
132 kV 103 103‐89B  103 RB Core 8 TB1‐3 X:ISB‐6 103 RB‐X:ISB‐6 / TB1‐3 103‐89B ‐TB1‐3/X:ISB‐6 Common
132 kV 103 103‐89B  103 RB Core 9 SPARE
132 kV 103 103‐89B  103 RB Core 10 SPARE

39 132 kV 103 within swyd  1‐103‐1‐039 1 Cu./Amr. PVC 103‐89T  103 RA 5CX2.5 60 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐9 103 RA‐X:BB‐9 / TB3‐103 103‐89T ‐TB3‐103/X:BB‐9 Common
132 kV 103 103‐89T  103 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐10 103 RA‐X:BB‐10 / TB3‐104 103‐89T ‐TB3‐104/X:BB‐10 Isolator 89T Open
132 kV 103 103‐89T  103 RA Core 3 G719EA‐MG9031‐00‐ TBX‐X G719EA‐MG9031‐00‐ X:IST‐1 103 RA‐X:IST‐1 / TBX‐X 103‐89T ‐TBX‐X/X:IST‐1 Trip Bus‐3 (Transfer Bus)
132 kV 103 103‐89T  103 RA Core 4 W101, Sh‐25a of 49 TBX‐X W101, Sh‐25a of 49 X:IST‐2 103 RA‐X:IST‐2 / TBX‐X 103‐89T ‐TBX‐X/X:IST‐2 Common
132 kV 103 103‐89T  103 RA Core 5 SPARE

40 132 kV 103 within swyd  1‐103‐1‐040 1 Cu./Amr. PVC 103‐89T  103 RB 10CX2.5 60 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:IST‐1 103 RB‐X:IST‐1 / TB3‐107 103‐89T ‐TB3‐107/X:IST‐1 Common
132 kV 103 103‐89T  103 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:IST‐2 103 RB‐X:IST‐2 / TB3‐108 103‐89T ‐TB3‐108/X:IST‐2 Isolator 89T Open
132 kV 103 103‐89T  103 RB Core 3 TB3‐102 X:IST‐3 103 RB‐X:IST‐3 / TB3‐102 103‐89T ‐TB3‐102/X:IST‐3 Isolator 89T Close
132 kV 103 103‐89T  103 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:IST‐4 103 RB‐X:IST‐4 / TB1‐1 103‐89T ‐TB1‐1/X:IST‐4 DC Supply (+)Ve
132 kV 103 103‐89T  103 RB Core 5 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 X:IST‐5 103 RB‐X:IST‐5 / TB1‐2 103‐89T ‐TB1‐2/X:IST‐5 DC Supply (‐)Ve
132 kV 103 103‐89T  103 RB Core 6 TB1‐3 X:IST‐6 103 RB‐X:IST‐6 / TB1‐3 103‐89T ‐TB1‐3/X:IST‐6 Common
132 kV 103 103‐89T  103 RB Core 7 TB1‐5 X:IST‐7 103 RB‐X:IST‐7 / TB1‐5 103‐89T ‐TB1‐5/X:IST‐7 Open 
132 kV 103 103‐89T  103 RB Core 8 TB1‐4 X:IST‐8 103 RB‐X:IST‐8 / TB1‐4 103‐89T ‐TB1‐4/X:IST‐8 Close
132 kV 103 103‐89T  103 RB Core 9 SPARE
132 kV 103 103‐89T  103 RB Core 10 SPARE

41 132 kV 103 within swyd  1‐103‐1‐041 1 Cu./Amr. PVC 103‐89L  103 RA 3CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐11 103 RA‐X:BB‐11 / TB3‐103 103‐89L ‐TB3‐103/X:BB‐11 Common
132 kV 103 103‐89L  103 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐12 103 RA‐X:BB‐12 / TB3‐104 103‐89L ‐TB3‐104/X:BB‐12 Isolator 89L Open
132 kV 103 103‐89L  103 RA Core 3 SPARE

42 132 kV 103 within swyd  1‐103‐1‐042 1 Cu./Amr. PVC 103‐89LE  103 RB 10CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISL‐1 103 RB‐X:ISL‐1 / TB3‐107 103‐89LE ‐TB3‐107/X:ISL‐1 Common
132 kV 103 103‐89LE  103 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:ISL‐2 103 RB‐X:ISL‐2 / TB3‐108 103‐89LE ‐TB3‐108/X:ISL‐2 Isolator 89L Open
132 kV 103 103‐89LE  103 RB Core 3 TB3‐102 X:ISL‐3 103 RB‐X:ISL‐3 / TB3‐102 103‐89LE ‐TB3‐102/X:ISL‐3 Isolator 89L Close
132 kV 103 103‐89LE  103 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISL‐10 103 RB‐X:ISL‐10 / TB1‐1 103‐89LE ‐TB1‐1/X:ISL‐10 DC Supply (+)Ve
132 kV 103 103‐89LE  103 RB Core 5 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 X:ISL‐11 103 RB‐X:ISL‐11 / TB1‐2 103‐89LE ‐TB1‐2/X:ISL‐11 DC Supply (‐)Ve
132 kV 103 103‐89LE  103 RB Core 6 TB1‐3 X:ISL‐12 103 RB‐X:ISL‐12 / TB1‐3 103‐89LE ‐TB1‐3/X:ISL‐12 Common
132 kV 103 103‐89LE  103 RB Core 7 TB1‐5 X:ISL‐13 103 RB‐X:ISL‐13 / TB1‐5 103‐89LE ‐TB1‐5/X:ISL‐13 Open 
132 kV 103 103‐89LE  103 RB Core 8 TB1‐4 X:ISL‐14 103 RB‐X:ISL‐14 / TB1‐4 103‐89LE ‐TB1‐4/X:ISL‐14 Close
132 kV 103 103‐89LE  103 RB Core 9 SPARE
132 kV 103 103‐89LE  103 RB Core 10 SPARE

103‐EARTH SWITCH CABLING TO PANEL
43 132 kV 103 within swyd  1‐103‐1‐043 1 Cu./Amr. PVC 103‐89AE  103 RB 5CX2.5 30 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISA‐4 103 RB‐X:ISA‐4 / TB3‐107 103‐89AE ‐TB3‐107/X:ISA‐4 Common
132 kV 103 103‐89AE  103 RB Core 2 W101, Sh‐29 of 49 TB3‐108 W101, Sh‐29 of 49 X:ISA‐5 103 RB‐X:ISA‐5 / TB3‐108 103‐89AE ‐TB3‐108/X:ISA‐5 E/s 89AE Open
132 kV 103 103‐89AE  103 RB Core 3 TB3‐102 X:ISA‐6 103 RB‐X:ISA‐6 / TB3‐102 103‐89AE ‐TB3‐102/X:ISA‐6 E/s 89AE Close
132 kV 103 103‐89AE  103 RB Core 4 SPARE
Core 5 SPARE

44 132 kV 103 within swyd  1‐103‐1‐044 1 Cu./Amr. PVC 103‐89LE1  103 RB 5CX2.5 30 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISL‐4 103 RB‐X:ISL‐4 / TB3‐107 103‐89LE1 ‐TB3‐107/X:ISL‐4 Common
132 kV 103 103‐89LE1  103 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:ISL‐5 103 RB‐X:ISL‐5 / TB3‐108 103‐89LE1 ‐TB3‐108/X:ISL‐5 E/s 89LE1 Open
132 kV 103 103‐89LE1  103 RB Core 3 TB3‐102 X:ISL‐6 103 RB‐X:ISL‐6 / TB3‐102 103‐89LE1 ‐TB3‐102/X:ISL‐6 E/s 89LE1 Close
132 kV 103 103‐89LE1  103 RB Core 4 SPARE
132 kV 103 103‐89LE1  103 RB Core 5 SPARE

45 132 kV 103 within swyd  1‐103‐1‐045 1 Cu./Amr. PVC 103‐89LE2  103 RB 5CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISL‐7 103 RB‐X:ISL‐7 / TB3‐107 103‐89LE2 ‐TB3‐107/X:ISL‐7 Common
132 kV 103 103‐89LE2  103 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:ISL‐8 103 RB‐X:ISL‐8 / TB3‐108 103‐89LE2 ‐TB3‐108/X:ISL‐8 E/s 89LE2 Open
132 kV 103 103‐89LE2  103 RB Core 3 TB3‐102 X:ISL‐9 103 RB‐X:ISL‐9 / TB3‐102 103‐89LE2 ‐TB3‐102/X:ISL‐9 E/s 89LE2 Close
132 kV 103 103‐89LE2  103 RB Core 4 SPARE
132 kV 103 103‐89LE2  103 RB Core 5 SPARE

103‐PLCC CHANNEL TO PANEL
46 132 kV 103 within swyd  1‐103‐1‐046 1 Cu./Amr. PVC 103‐PLCC  CH‐1 103 RA 10CX2.5 10 Core 1 G719EA‐MG9031‐00‐ X12‐1‐P11‐09 G719EA‐MG9031‐00‐ X:PLCC‐1 103 RA‐X:PLCC‐1 / X12‐1‐P11‐09 103‐PLCC  CH‐1‐X12‐1‐P11‐09/X:PLCC‐1Common
132 kV 103 103‐PLCC  CH‐1 103 RA Core 2 W101, Sh‐18 of 49 X12‐1‐P11‐10 W101, Sh‐18 of 49 X:PLCC‐2 103 RA‐X:PLCC‐2 / X12‐1‐P11‐10 103‐PLCC  CH‐1‐X12‐1‐P11‐10/X:PLCC‐2Carrier Fail CH‐1
132 kV 103 103‐PLCC  CH‐1 103 RA Core 3 X12‐1‐P10‐2 X:PLCC‐3 103 RA‐X:PLCC‐3 / X12‐1‐P10‐2 103‐PLCC  CH‐1‐X12‐1‐P10‐2/X:PLCC‐3 Common
132 kV 103 103‐PLCC  CH‐1 103 RA Core 4 X12‐1‐P16‐36 X:PLCC‐4 103 RA‐X:PLCC‐4 / X12‐1‐P16‐36 103‐PLCC  CH‐1‐X12‐1‐P16‐36/X:PLCC‐4Common
132 kV 103 103‐PLCC  CH‐1 103 RA Core 5 X12‐1‐P16‐37 X:PLCC‐5 103 RA‐X:PLCC‐5 / X12‐1‐P16‐37 103‐PLCC  CH‐1‐X12‐1‐P16‐37/X:PLCC‐5Carrier Received CH‐1
132 kV 103 103‐PLCC  CH‐1 103 RA Core 6 X12‐1‐P11‐13 X:PLCC‐6 103 RA‐X:PLCC‐6 / X12‐1‐P11‐13 103‐PLCC  CH‐1‐X12‐1‐P11‐13/X:PLCC‐6Direct Trip Received CH‐1
132 kV 103 103‐PLCC  CH‐1 103 RA Core 7 X12‐1‐P11‐14 X:PLCC‐7 103 RA‐X:PLCC‐7 / X12‐1‐P11‐14 103‐PLCC  CH‐1‐X12‐1‐P11‐14/X:PLCC‐7Carrier Send CH‐1
132 kV 103 103‐PLCC  CH‐1 103 RA Core 8 X12‐1‐P10‐5 X:PLCC‐8 103 RA‐X:PLCC‐8 / X12‐1‐P10‐5 103‐PLCC  CH‐1‐X12‐1‐P10‐5/X:PLCC‐8 Direct Trip Send (Code‐4)
132 kV 103 103‐PLCC  CH‐1 103 RA Core 9 SPARE
132 kV 103 103‐PLCC  CH‐1 103 RA Core 10 SPARE

47 132 kV 103 within swyd  1‐103‐1‐047 1 Cu./Amr. PVC 103‐PLCC  CH‐2 103 RA 10CX2.5 10 Core 1 G719EA‐MG9031‐00‐ X11‐1‐P11‐09 G719EA‐MG9031‐00‐ X:PLCC‐9 103 RA‐X:PLCC‐9 / X11‐1‐P11‐09 103‐PLCC  CH‐2‐X11‐1‐P11‐09/X:PLCC‐9Direct Trip Received CH‐2
132 kV 103 103‐PLCC  CH‐2 103 RA Core 2 W101, Sh‐18 of 49 X11‐1‐P11‐10 W101, Sh‐18 of 49 X:PLCC‐10 103 RA‐X:PLCC‐10 / X11‐1‐P11‐10 03‐PLCC  CH‐2‐X11‐1‐P11‐10/X:PLCC‐1 Common
132 kV 103 103‐PLCC  CH‐2 103 RA Core 3 X11‐1‐P10‐2 X:PLCC‐11 103 RA‐X:PLCC‐11 / X11‐1‐P10‐2 103‐PLCC  CH‐2‐X11‐1‐P10‐2/X:PLCC‐11Carrier Fail CH‐2
132 kV 103 103‐PLCC  CH‐2 103 RA Core 4 X11‐1‐P16‐36 X:PLCC‐12 103 RA‐X:PLCC‐12 / X11‐1‐P16‐36 03‐PLCC  CH‐2‐X11‐1‐P16‐36/X:PLCC‐1 Common
132 kV 103 103‐PLCC  CH‐2 103 RA Core 5 X11‐1‐P16‐37 X:PLCC‐13 103 RA‐X:PLCC‐13 / X11‐1‐P16‐37 03‐PLCC  CH‐2‐X11‐1‐P16‐37/X:PLCC‐1 Carrier Received CH‐2
132 kV 103 103‐PLCC  CH‐2 103 RA Core 6 X11‐1‐P11‐13 X:PLCC‐14 103 RA‐X:PLCC‐14 / X11‐1‐P11‐13 03‐PLCC  CH‐2‐X11‐1‐P11‐13/X:PLCC‐1 Carrier Send CH‐2
132 kV 103 103‐PLCC  CH‐2 103 RA Core 7 X11‐1‐P11‐14 X:PLCC‐15 103 RA‐X:PLCC‐15 / X11‐1‐P11‐14 03‐PLCC  CH‐2‐X11‐1‐P11‐14/X:PLCC‐1 Direct Trip Send (Code‐4)
132 kV 103 103‐PLCC  CH‐2 103 RA Core 8 SPARE
132 kV 103 103‐PLCC  CH‐2 103 RA Core 9 SPARE

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 4 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY103L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)
132 kV 103 103‐PLCC  CH‐2 103 RA Core 10 SPARE

103‐Inter Panel Cabling
48 132 kV 103 within swyd  1‐103‐1‐048 1 Cu./Amr. PVC 103 RA 103 RB 27CX2.5 10 Core 1 G719EA‐MG9031‐ XCRA‐31 G719EA‐MG9031‐ XCRB‐31 103 RB‐XCRB‐31 / XCRA‐31 103 RA‐XCRA‐31/XCRB‐31 Common
132 kV 103 103 RA 103 RB Core 2 W101, Sh‐25 of 49 XCRA‐32 W101, Sh‐25 of 49 XCRB‐32 103 RB‐XCRB‐32 / XCRA‐32 103 RA‐XCRA‐32/XCRB‐32
132 kV 103 103 RA 103 RB Core 3 G719EA‐MG9031‐ XCRA‐15 G719EA‐MG9031‐ XCRB‐15 103 RB‐XCRB‐15 / XCRA‐15 103 RA‐XCRA‐15/XCRB‐15
132 kV 103 103 RA 103 RB Core 4 W101, Sh‐26 of 49 XCRA‐16 W101, Sh‐26 of 49 XCRB‐16 103 RB‐XCRB‐16 / XCRA‐16 103 RA‐XCRA‐16/XCRB‐16
132 kV 103 103 RA 103 RB Core 5 XCRA‐17 XCRB‐17 103 RB‐XCRB‐17 / XCRA‐17 103 RA‐XCRA‐17/XCRB‐17
132 kV 103 103 RA 103 RB Core 6 XCRA‐18 XCRB‐18 103 RB‐XCRB‐18 / XCRA‐18 103 RA‐XCRA‐18/XCRB‐18
132 kV 103 103 RA 103 RB Core 7 G719EA‐MG9031‐ XCRA‐10 G719EA‐MG9031‐ XCRB‐10 103 RB‐XCRB‐10 / XCRA‐10 103 RA‐XCRA‐10/XCRB‐10
132 kV 103 103 RA 103 RB Core 8 W101, Sh‐27 of 49 XCRA‐11 W101, Sh‐27 of 49 XCRB‐11 103 RB‐XCRB‐11 / XCRA‐11 103 RA‐XCRA‐11/XCRB‐11
132 kV 103 103 RA 103 RB Core 9 XCRA‐12 XCRB‐12 103 RB‐XCRB‐12 / XCRA‐12 103 RA‐XCRA‐12/XCRB‐12
132 kV 103 103 RA 103 RB Core 10 XCRA‐13 XCRB‐13 103 RB‐XCRB‐13 / XCRA‐13 103 RA‐XCRA‐13/XCRB‐13
132 kV 103 103 RA 103 RB Core 11 G719EA‐MG9031‐ XCRA‐45 G719EA‐MG9031‐ XCRB‐45 103 RB‐XCRB‐45 / XCRA‐45 103 RA‐XCRA‐45/XCRB‐45
132 kV 103 103 RA 103 RB Core 12 W101, Sh‐33 of 49 XCRA‐46 W101, Sh‐33 of 49 XCRB‐46 103 RB‐XCRB‐46 / XCRA‐46 103 RA‐XCRA‐46/XCRB‐46
132 kV 103 103 RA 103 RB Core 13 XCRA‐47 XCRB‐47 103 RB‐XCRB‐47 / XCRA‐47 103 RA‐XCRA‐47/XCRB‐47
132 kV 103 103 RA 103 RB Core 14 G719EA‐MG9031‐ XCRA‐48 G719EA‐MG9031‐ XCRB‐48 103 RB‐XCRB‐48 / XCRA‐48 103 RA‐XCRA‐48/XCRB‐48
132 kV 103 103 RA 103 RB Core 15 W101, Sh‐34 of 49 XCRA‐49 W101, Sh‐34 of 49 XCRB‐49 103 RB‐XCRB‐49 / XCRA‐49 103 RA‐XCRA‐49/XCRB‐49
132 kV 103 103 RA 103 RB Core 16 XCRA‐75 XCRB‐75 103 RB‐XCRB‐75 / XCRA‐75 103 RA‐XCRA‐75/XCRB‐75
132 kV 103 103 RA 103 RB Core 17 XCRA‐76 XCRB‐76 103 RB‐XCRB‐76 / XCRA‐76 103 RA‐XCRA‐76/XCRB‐76
132 kV 103 103 RA 103 RB Core 18 G719EA‐MG9031‐ XCRA‐66 G719EA‐MG9031‐ XCRB‐66 103 RB‐XCRB‐66 / XCRA‐66 103 RA‐XCRA‐66/XCRB‐66
132 kV 103 103 RA 103 RB Core 19 W101, Sh‐34 of 49 XCRA‐67 W101, Sh‐34 of 49 XCRB‐67 103 RB‐XCRB‐67 / XCRA‐67 103 RA‐XCRA‐67/XCRB‐67
132 kV 103 103 RA 103 RB Core 20 XCRA‐71 XCRB‐71 103 RB‐XCRB‐71 / XCRA‐71 103 RA‐XCRA‐71/XCRB‐71
132 kV 103 103 RA 103 RB Core 21 XCRA‐72 XCRB‐72 103 RB‐XCRB‐72 / XCRA‐72 103 RA‐XCRA‐72/XCRB‐72
132 kV 103 103 RA 103 RB Core 22 Spare Spare
132 kV 103 103 RA 103 RB Core 23 Spare Spare
132 kV 103 103 RA 103 RB Core 24 Spare Spare
132 kV 103 103 RA 103 RB Core 25 Spare Spare
132 kV 103 103 RA 103 RB Core 26 Spare Spare
132 kV 103 103 RA 103 RB Core 27 Spare Spare

49 132 kV 103 within swyd  1‐103‐1‐049 1 Cu./Amr. PVC 103 RA 103 RB 19CX2.5 10 Core 1 G719EA‐MG9031‐ XCRA‐50 G719EA‐MG9031‐ XCRB‐50 103 RB‐XCRB‐50 / XCRA‐50 103 RA‐XCRA‐50/XCRB‐50
132 kV 103 103 RA 103 RB Core 2 W101, Sh‐37 of 49 XCRA‐51 W101, Sh‐37 of 49 XCRB‐51 103 RB‐XCRB‐51 / XCRA‐51 103 RA‐XCRA‐51/XCRB‐51
132 kV 103 103 RA 103 RB Core 3 XCRA‐54 XCRB‐54 103 RB‐XCRB‐54 / XCRA‐54 103 RA‐XCRA‐54/XCRB‐54
132 kV 103 103 RA 103 RB Core 4 XCRA‐55 XCRB‐55 103 RB‐XCRB‐55 / XCRA‐55 103 RA‐XCRA‐55/XCRB‐55
132 kV 103 103 RA 103 RB Core 5 XCRA‐58 XCRB‐58 103 RB‐XCRB‐58 / XCRA‐58 103 RA‐XCRA‐58/XCRB‐58
132 kV 103 103 RA 103 RB Core 6 XCRA‐59 XCRB‐59 103 RB‐XCRB‐59 / XCRA‐59 103 RA‐XCRA‐59/XCRB‐59
132 kV 103 103 RA 103 RB Core 7 XCRA‐63 XCRB‐63 103 RB‐XCRB‐63 / XCRA‐63 103 RA‐XCRA‐63/XCRB‐63
132 kV 103 103 RA 103 RB Core 8 Spare
132 kV 103 103 RA 103 RB Core 9 Spare
132 kV 103 103 RA 103 RB Core 10 Spare
132 kV 103 103 RA 103 RB Core 11 Spare
132 kV 103 103 RA 103 RB Core 12 Spare
132 kV 103 103 RA 103 RB Core 13 Spare
132 kV 103 103 RA 103 RB Core 14 Spare
132 kV 103 103 RA 103 RB Core 15 Spare
132 kV 103 103 RA 103 RB Core 16 Spare
132 kV 103 103 RA 103 RB Core 17 Spare
132 kV 103 103 RA 103 RB Core 18 Spare
132 kV 103 103 RA 103 RB Core 19 Spare

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 5 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY104L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)

Control Cable in Switchyard

104‐CVT CABLING
1 132 kV 104 within swyd  1‐104‐1‐001 1 Cu./Amr. PVC 104‐RCVT Core.‐1 104‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB1‐1 104‐CVT JB‐TB1‐1 / R‐1a 104‐RCVT Core.‐1‐R‐1a/TB1‐1 Core‐1
ASPL/UPPCL/20415U
132 kV 104‐RCVT Core.‐1 104‐CVT JB Core 2 100 R‐1n TB1‐3 Distance Main‐1 Protection Relay
104 104‐CVT JB‐TB1‐3 / R‐1n 104‐RCVT Core.‐1‐R‐1n/TB1‐3
132 kV 104 104‐RCVT Core.‐1 104‐CVT JB Core 3 SPARE TB1‐5 104‐CVT JB‐TB1‐5 / SPARE 104‐RCVT Core.‐1‐SPARE/TB1‐5 67/67N : O/c & E/f Relay

2 132 kV 104 within swyd  1‐104‐1‐002 1 Cu./Amr. PVC 104‐YCVT Core.‐1 104‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB1‐8 104‐CVT JB‐TB1‐8 / Y‐1a 104‐YCVT Core.‐1‐Y‐1a/TB1‐8 Core‐1
ASPL/UPPCL/20415U
132 kV 104‐YCVT Core.‐1 104‐CVT JB Core 2 100 Y‐1n TB1‐10 Distance Main‐1 Protection Relay
104 104‐CVT JB‐TB1‐10 / Y‐1n 104‐YCVT Core.‐1‐Y‐1n/TB1‐10
132 kV 104 104‐YCVT Core.‐1 104‐CVT JB Core 3 SPARE TB1‐12 104‐CVT JB‐TB1‐12 / SPARE 104‐YCVT Core.‐1‐SPARE/TB1‐12 67/67N : O/c & E/f Relay

3 132 kV 104 within swyd  1‐104‐1‐003 1 Cu./Amr. PVC 104‐BCVT Core.‐1 104‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB1‐15 104‐CVT JB‐TB1‐15 / B‐1a 104‐BCVT Core.‐1‐B‐1a/TB1‐15 Core‐1
ASPL/UPPCL/20415U
132 kV 104‐BCVT Core.‐1 104‐CVT JB Core 2 100 B‐1n TB1‐17 Distance Main‐1 Protection Relay
104 104‐CVT JB‐TB1‐17 / B‐1n 104‐BCVT Core.‐1‐B‐1n/TB1‐17
132 kV 104 104‐BCVT Core.‐1 104‐CVT JB Core 3 SPARE TB1‐19 104‐CVT JB‐TB1‐19 / SPARE 104‐BCVT Core.‐1‐SPARE/TB1‐19 67/67N : O/c & E/f Relay

4 132 kV 104 within swyd  1‐104‐1‐004 1 Cu./Amr. PVC 104‐RCVT Core.‐2 104‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB2‐1 104‐CVT JB‐TB2‐1 / R‐1a 104‐RCVT Core.‐2‐R‐1a/TB2‐1 Core‐2
ASPL/UPPCL/20415U
132 kV 104 104‐RCVT Core.‐2 104‐CVT JB Core 2 100 R‐1n TB2‐3 104‐CVT JB‐TB2‐3 / R‐1n 104‐RCVT Core.‐2‐R‐1n/TB2‐3 Spare
132 kV 104 104‐RCVT Core.‐2 104‐CVT JB Core 3 SPARE TB2‐5 104‐CVT JB‐TB2‐5 / SPARE 104‐RCVT Core.‐2‐SPARE/TB2‐5

5 132 kV 104 within swyd  1‐104‐1‐005 1 Cu./Amr. PVC 104‐YCVT Core.‐2 104‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB2‐8 104‐CVT JB‐TB2‐8 / Y‐1a 104‐YCVT Core.‐2‐Y‐1a/TB2‐8 Core‐2
ASPL/UPPCL/20415U
132 kV 104 104‐YCVT Core.‐2 104‐CVT JB Core 2 100 Y‐1n TB2‐10 104‐CVT JB‐TB2‐10 / Y‐1n 104‐YCVT Core.‐2‐Y‐1n/TB2‐10 Spare
132 kV 104 104‐YCVT Core.‐2 104‐CVT JB Core 3 SPARE TB2‐12 104‐CVT JB‐TB2‐12 / SPARE 104‐YCVT Core.‐2‐SPARE/TB2‐12

6 132 kV 104 within swyd  1‐104‐1‐006 1 Cu./Amr. PVC 104‐BCVT Core.‐2 104‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB2‐15 104‐CVT JB‐TB2‐15 / B‐1a 104‐BCVT Core.‐2‐B‐1a/TB2‐15 Core‐2
ASPL/UPPCL/20415U
132 kV 104 104‐BCVT Core.‐2 104‐CVT JB Core 2 100 B‐1n TB2‐17 104‐CVT JB‐TB2‐17 / B‐1n 104‐BCVT Core.‐2‐B‐1n/TB2‐17 Spare
132 kV 104 104‐BCVT Core.‐2 104‐CVT JB Core 3 SPARE TB2‐19 104‐CVT JB‐TB2‐19 / SPARE 104‐BCVT Core.‐2‐SPARE/TB2‐19

7 132 kV 104 within swyd  1‐104‐1‐007 1 Cu./Amr. PVC 104‐RCVT Core.‐3 104‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB3‐1 104‐CVT JB‐TB3‐1 / R‐1a 104‐RCVT Core.‐3‐R‐1a/TB3‐1 Core‐3
ASPL/UPPCL/20415U
132 kV 104 104‐RCVT Core.‐3 104‐CVT JB Core 2 100 R‐1n TB3‐3 104‐CVT JB‐TB3‐3 / R‐1n 104‐RCVT Core.‐3‐R‐1n/TB3‐3 Metering
132 kV 104 104‐RCVT Core.‐3 104‐CVT JB Core 3 SPARE TB3‐5 104‐CVT JB‐TB3‐5 / SPARE 104‐RCVT Core.‐3‐SPARE/TB3‐5

8 132 kV 104 within swyd  1‐104‐1‐008 1 Cu./Amr. PVC 104‐YCVT Core.‐3 104‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB3‐8 104‐CVT JB‐TB3‐8 / Y‐1a 104‐YCVT Core.‐3‐Y‐1a/TB3‐8 Core‐3
ASPL/UPPCL/20415U
132 kV 104 104‐YCVT Core.‐3 104‐CVT JB Core 2 100 Y‐1n TB3‐10 104‐CVT JB‐TB3‐10 / Y‐1n 104‐YCVT Core.‐3‐Y‐1n/TB3‐10 Metering
132 kV 104 104‐YCVT Core.‐3 104‐CVT JB Core 3 SPARE TB3‐12 104‐CVT JB‐TB3‐12 / SPARE 104‐YCVT Core.‐3‐SPARE/TB3‐12

9 132 kV 104 within swyd  1‐104‐1‐009 1 Cu./Amr. PVC 104‐BCVT Core.‐3 104‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB3‐15 104‐CVT JB‐TB3‐15 / B‐1a 104‐BCVT Core.‐3‐B‐1a/TB3‐15 Core‐3
ASPL/UPPCL/20415U
132 kV 104 104‐BCVT Core.‐3 104‐CVT JB Core 2 100 B‐1n TB3‐17 104‐CVT JB‐TB3‐17 / B‐1n 104‐BCVT Core.‐3‐B‐1n/TB3‐17 Metering
132 kV 104 104‐BCVT Core.‐3 104‐CVT JB Core 3 SPARE TB3‐19 104‐CVT JB‐TB3‐19 / SPARE 104‐BCVT Core.‐3‐SPARE/TB3‐19

104‐CT CABLING
10 132 kV 104 within swyd  1‐104‐1‐010 1 Cu./Amr. PVC 104‐RCT Core.‐5 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 5US1 5US1 104‐CT JB‐5US1 / 5US1 104‐RCT Core.‐5‐5US1/5US1 CORE‐5
ASPL/UPPCL/20415
132 kV 104 104‐RCT Core.‐5 104‐CT JB Core 2 058 5US2 5US2 104‐CT JB‐5US2 / 5US2 104‐RCT Core.‐5‐5US2/5US2 Distance Protection M1
132 kV 104 104‐RCT Core.‐5 104‐CT JB Core 3 5US3 5US3 104‐CT JB‐5US3 / 5US3 104‐RCT Core.‐5‐5US3/5US3
132 kV 104 104‐RCT Core.‐5 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐RCT Core.‐5‐Spare/Spare
132 kV 104 104‐RCT Core.‐5 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐RCT Core.‐5‐Spare/Spare

11 132 kV 104 within swyd  1‐104‐1‐011 1 Cu./Amr. PVC 104‐YCT Core.‐5 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 5VS1 5VS1 104‐CT JB‐5VS1 / 5VS1 104‐YCT Core.‐5‐5VS1/5VS1 CORE‐5
ASPL/UPPCL/20415
132 kV 104 104‐YCT Core.‐5 104‐CT JB Core 2 058 5VS2 5VS2 104‐CT JB‐5VS2 / 5VS2 104‐YCT Core.‐5‐5VS2/5VS2 Distance Protection M1
132 kV 104 104‐YCT Core.‐5 104‐CT JB Core 3 5VS3 5VS3 104‐CT JB‐5VS3 / 5VS3 104‐YCT Core.‐5‐5VS3/5VS3
132 kV 104 104‐YCT Core.‐5 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐YCT Core.‐5‐Spare/Spare
132 kV 104 104‐YCT Core.‐5 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐YCT Core.‐5‐Spare/Spare

12 132 kV 104 within swyd  1‐104‐1‐012 1 Cu./Amr. PVC 104‐BCT Core.‐5 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 5WS1 5WS1 104‐CT JB‐5WS1 / 5WS1 104‐BCT Core.‐5‐5WS1/5WS1 CORE‐5
ASPL/UPPCL/20415
132 kV 104 104‐BCT Core.‐5 104‐CT JB Core 2 058 5WS2 5WS2 104‐CT JB‐5WS2 / 5WS2 104‐BCT Core.‐5‐5WS2/5WS2 Distance Protection M1
132 kV 104 104‐BCT Core.‐5 104‐CT JB Core 3 5WS3 5WS3 104‐CT JB‐5WS3 / 5WS3 104‐BCT Core.‐5‐5WS3/5WS3
132 kV 104 104‐BCT Core.‐5 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐BCT Core.‐5‐Spare/Spare
132 kV 104 104‐BCT Core.‐5 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐BCT Core.‐5‐Spare/Spare

13 132 kV 104 within swyd  1‐104‐1‐013 1 Cu./Amr. PVC 104‐RCT Core.‐2 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 2US1 2US1 104‐CT JB‐2US1 / 2US1 104‐RCT Core.‐2‐2US1/2US1 CORE‐2
ASPL/UPPCL/20415
132 kV 104 104‐RCT Core.‐2 104‐CT JB Core 2 058 2US2 2US2 104‐CT JB‐2US2 / 2US2 104‐RCT Core.‐2‐2US2/2US2 67/67N : O/c & E/f Relay
132 kV 104 104‐RCT Core.‐2 104‐CT JB Core 3 2US3 2US3 104‐CT JB‐2US3 / 2US3 104‐RCT Core.‐2‐2US3/2US3
132 kV 104 104‐RCT Core.‐2 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐RCT Core.‐2‐Spare/Spare
132 kV 104 104‐RCT Core.‐2 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐RCT Core.‐2‐Spare/Spare

14 132 kV 104 within swyd  1‐104‐1‐014 1 Cu./Amr. PVC 104‐YCT Core.‐2 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 2VS1 2VS1 104‐CT JB‐2VS1 / 2VS1 104‐YCT Core.‐2‐2VS1/2VS1 CORE‐2
ASPL/UPPCL/20415
132 kV 104 104‐YCT Core.‐2 104‐CT JB Core 2 058 2VS2 2VS2 104‐CT JB‐2VS2 / 2VS2 104‐YCT Core.‐2‐2VS2/2VS2 67/67N : O/c & E/f Relay
132 kV 104 104‐YCT Core.‐2 104‐CT JB Core 3 2VS3 2VS3 104‐CT JB‐2VS3 / 2VS3 104‐YCT Core.‐2‐2VS3/2VS3
132 kV 104 104‐YCT Core.‐2 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐YCT Core.‐2‐Spare/Spare
132 kV 104 104‐YCT Core.‐2 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐YCT Core.‐2‐Spare/Spare

15 132 kV 104 within swyd  1‐104‐1‐015 1 Cu./Amr. PVC 104‐BCT Core.‐2 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 2WS1 2WS1 104‐CT JB‐2WS1 / 2WS1 104‐BCT Core.‐2‐2WS1/2WS1 CORE‐2
ASPL/UPPCL/20415
132 kV 104 104‐BCT Core.‐2 104‐CT JB Core 2 058 2WS2 2WS2 104‐CT JB‐2WS2 / 2WS2 104‐BCT Core.‐2‐2WS2/2WS2 67/67N : O/c & E/f Relay
132 kV 104 104‐BCT Core.‐2 104‐CT JB Core 3 2WS3 2WS3 104‐CT JB‐2WS3 / 2WS3 104‐BCT Core.‐2‐2WS3/2WS3
132 kV 104 104‐BCT Core.‐2 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐BCT Core.‐2‐Spare/Spare
132 kV 104 104‐BCT Core.‐2 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐BCT Core.‐2‐Spare/Spare

16 132 kV 104 within swyd  1‐104‐1‐016 1 Cu./Amr. PVC 104‐RCT Core.‐1 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 1US1 1US1 104‐CT JB‐1US1 / 1US1 104‐RCT Core.‐1‐1US1/1US1 CORE‐1
ASPL/UPPCL/20415
132 kV 104 104‐RCT Core.‐1 104‐CT JB Core 2 058 1US2 1US2 104‐CT JB‐1US2 / 1US2 104‐RCT Core.‐1‐1US2/1US2 87BB : Busbar Protection
132 kV 104 104‐RCT Core.‐1 104‐CT JB Core 3 1US3 1US3 104‐CT JB‐1US3 / 1US3 104‐RCT Core.‐1‐1US3/1US3
132 kV 104 104‐RCT Core.‐1 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐RCT Core.‐1‐Spare/Spare
132 kV 104 104‐RCT Core.‐1 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐RCT Core.‐1‐Spare/Spare

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 1 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY104L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)

17 132 kV 104 within swyd  1‐104‐1‐017 1 Cu./Amr. PVC 104‐YCT Core.‐1 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 1VS1 1VS1 104‐CT JB‐1VS1 / 1VS1 104‐YCT Core.‐1‐1VS1/1VS1 CORE‐1
ASPL/UPPCL/20415
132 kV 104 104‐YCT Core.‐1 104‐CT JB Core 2 058 1VS2 1VS2 104‐CT JB‐1VS2 / 1VS2 104‐YCT Core.‐1‐1VS2/1VS2 87BB : Busbar Protection
132 kV 104 104‐YCT Core.‐1 104‐CT JB Core 3 1VS3 1VS3 104‐CT JB‐1VS3 / 1VS3 104‐YCT Core.‐1‐1VS3/1VS3
132 kV 104 104‐YCT Core.‐1 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐YCT Core.‐1‐Spare/Spare
132 kV 104 104‐YCT Core.‐1 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐YCT Core.‐1‐Spare/Spare

18 132 kV 104 within swyd  1‐104‐1‐018 1 Cu./Amr. PVC 104‐BCT Core.‐1 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 1WS1 1WS1 104‐CT JB‐1WS1 / 1WS1 104‐BCT Core.‐1‐1WS1/1WS1 CORE‐1
ASPL/UPPCL/20415
132 kV 104 104‐BCT Core.‐1 104‐CT JB Core 2 058 1WS2 1WS2 104‐CT JB‐1WS2 / 1WS2 104‐BCT Core.‐1‐1WS2/1WS2 87BB : Busbar Protection
132 kV 104 104‐BCT Core.‐1 104‐CT JB Core 3 1WS3 1WS3 104‐CT JB‐1WS3 / 1WS3 104‐BCT Core.‐1‐1WS3/1WS3
132 kV 104 104‐BCT Core.‐1 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐BCT Core.‐1‐Spare/Spare
132 kV 104 104‐BCT Core.‐1 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐BCT Core.‐1‐Spare/Spare

19 132 kV 104 within swyd  1‐104‐1‐019 1 Cu./Amr. PVC 104‐RCT Core.‐3 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 3US1 3US1 104‐CT JB‐3US1 / 3US1 104‐RCT Core.‐3‐3US1/3US1 CORE‐3
ASPL/UPPCL/20415
132 kV 104 104‐RCT Core.‐3 104‐CT JB Core 2 058 3US2 3US2 104‐CT JB‐3US2 / 3US2 104‐RCT Core.‐3‐3US2/3US2 BCU : Bay Control Unit
132 kV 104 104‐RCT Core.‐3 104‐CT JB Core 3 3US3 3US3 104‐CT JB‐3US3 / 3US3 104‐RCT Core.‐3‐3US3/3US3
132 kV 104 104‐RCT Core.‐3 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐RCT Core.‐3‐Spare/Spare
132 kV 104 104‐RCT Core.‐3 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐RCT Core.‐3‐Spare/Spare

20 132 kV 104 within swyd  #N/A 1 Cu./Amr. PVC 104‐YCT Core.‐3 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 3VS1 3VS1 104‐CT JB‐3VS1 / 3VS1 104‐YCT Core.‐3‐3VS1/3VS1 CORE‐3
ASPL/UPPCL/20415
132 kV 104 104‐YCT Core.‐3 104‐CT JB Core 2 058 3VS2 3VS2 104‐CT JB‐3VS2 / 3VS2 104‐YCT Core.‐3‐3VS2/3VS2 BCU : Bay Control Unit
132 kV 104 104‐YCT Core.‐3 104‐CT JB Core 3 3VS3 3VS3 104‐CT JB‐3VS3 / 3VS3 104‐YCT Core.‐3‐3VS3/3VS3
132 kV 104 104‐YCT Core.‐3 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐YCT Core.‐3‐Spare/Spare
132 kV 104 104‐YCT Core.‐3 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐YCT Core.‐3‐Spare/Spare

21 132 kV 104 within swyd  1‐104‐1‐021 1 Cu./Amr. PVC 104‐BCT Core.‐3 104‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/0 3WS1 3WS1 104‐CT JB‐3WS1 / 3WS1 104‐BCT Core.‐3‐3WS1/3WS1 CORE‐3
ASPL/UPPCL/20415
132 kV 104 104‐BCT Core.‐3 104‐CT JB Core 2 058 3WS2 3WS2 104‐CT JB‐3WS2 / 3WS2 104‐BCT Core.‐3‐3WS2/3WS2 BCU : Bay Control Unit
132 kV 104 104‐BCT Core.‐3 104‐CT JB Core 3 3WS3 3WS3 104‐CT JB‐3WS3 / 3WS3 104‐BCT Core.‐3‐3WS3/3WS3
132 kV 104 104‐BCT Core.‐3 104‐CT JB Core 4 Spare Spare 104‐CT JB‐Spare / Spare 104‐BCT Core.‐3‐Spare/Spare
132 kV 104 104‐BCT Core.‐3 104‐CT JB Core 5 Spare Spare 104‐CT JB‐Spare / Spare 104‐BCT Core.‐3‐Spare/Spare

104‐BREAKER & E/s INTERLOCKING
22 132 kV 104 within swyd  1‐104‐1‐022 1 Cu./Amr. PVC 104‐89AE  104‐52  3CX2.5 37 Core 1 not included in CRP  TB3‐126 not included in CRP  x 104‐52 ‐x / TB3‐126 104‐89AE ‐TB3‐126/x CB & E/s Interlock
132 kV 104 104‐89AE  104‐52  Core 2 drawing SPARE drawing
132 kV 104 104‐89AE  104‐52  Core 3 SPARE

23 132 kV 104 within swyd  1‐104‐1‐023 1 Cu./Amr. PVC 104‐89LE1  104‐52  3CX2.5 37 Core 1 not included in CRP  TB3‐126 not included in CRP  x 104‐52 ‐x / TB3‐126 104‐89LE1 ‐TB3‐126/x CB & E/s Interlock
132 kV 104 104‐89LE1  104‐52  Core 2 drawing SPARE drawing
132 kV 104 104‐89LE1  104‐52  Core 3 SPARE

24 132 kV 104 within swyd  1‐104‐1‐024 1 Cu./Amr. PVC 104‐89LE2  104‐52  3CX2.5 30 Core 1 not included in CRP  TB3‐126 not included in CRP  x 104‐52 ‐x / TB3‐126 104‐89LE2 ‐TB3‐126/x CB & E/s Interlock
132 kV 104 104‐89LE2  104‐52  Core 2 drawing SPARE drawing
132 kV 104 104‐89LE2  104‐52  Core 3 SPARE

104‐B/w EARTHSWITCH & ISOLATOR
25 132 kV 104 within swyd  1‐104‐1‐025 1 Cu./Amr. PVC 104‐89A  104‐89AE  3CX2.5 5 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ TB1‐1 104‐89AE ‐TB1‐1 / TB1‐1 104‐89A ‐TB1‐1/TB1‐1 (+)ve DC Supply
132 kV 104 104‐89A  104‐89AE  Core 2 W101, Sh‐35 of 49 TB1‐2 W101, Sh‐35 of 49 TB1‐2 104‐89AE ‐TB1‐2 / TB1‐2 104‐89A ‐TB1‐2/TB1‐2 (‐)ve DC Supply
132 kV 104 104‐89A  104‐89AE  Core 3 SPARE

26 132 kV 104 within swyd  1‐104‐1‐026 1 Cu./Amr. PVC 104‐89L  104‐89LE1  3CX2.5 5 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ TB1‐1 104‐89LE1 ‐TB1‐1 / TB1‐1 104‐89L ‐TB1‐1/TB1‐1 (+)ve DC Supply
132 kV 104 104‐89L  104‐89LE1  Core 2 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 TB1‐2 104‐89LE1 ‐TB1‐2 / TB1‐2 104‐89L ‐TB1‐2/TB1‐2 (‐)ve DC Supply
132 kV 104 104‐89L  104‐89LE1  Core 3 SPARE

27 132 kV 104 within swyd  1‐104‐1‐027 1 Cu./Amr. PVC 104‐89L  104‐89LE2  3CX2.5 5 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ TB1‐1 104‐89LE2 ‐TB1‐1 / TB1‐1 104‐89L ‐TB1‐1/TB1‐1 (+)ve DC Supply
132 kV 104 104‐89L  104‐89LE2  Core 2 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 TB1‐2 104‐89LE2 ‐TB1‐2 / TB1‐2 104‐89L ‐TB1‐2/TB1‐2 (‐)ve DC Supply
132 kV 104 104‐89L  104‐89LE2  Core 3 SPARE

Control Cable from Switchyard to Panel
104‐CVT CABLING TO PANEL
28 132 kV 104 within swyd  1‐104‐1‐028 1 Cu./Amr. PVC 104‐CVT JB 104 RA 5CX2.5 90 Core 1 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:VTL‐1 104 RA‐X:VTL‐1 / TB1‐1 104‐CVT JB‐TB1‐1/X:VTL‐1 Distance Main‐1 Protection Relay
132 kV 104 104‐CVT JB 104 RA Core 2 W101, Sh‐13 of 49 TB1‐8 W101, Sh‐13 of 49 X:VTL‐2 104 RA‐X:VTL‐2 / TB1‐8 104‐CVT JB‐TB1‐8/X:VTL‐2 67/67N : O/c & E/f Relay
132 kV 104 104‐CVT JB 104 RA Core 3 TB1‐15 X:VTL‐3 104 RA‐X:VTL‐3 / TB1‐15 104‐CVT JB‐TB1‐15/X:VTL‐3
132 kV 104 104‐CVT JB 104 RA Core 4 TB1‐19 X:VTL‐4 104 RA‐X:VTL‐4 / TB1‐19 104‐CVT JB‐TB1‐19/X:VTL‐4
132 kV 104 104‐CVT JB 104 RA Core 5 SPARE

29 132 kV 104 within swyd  1‐104‐1‐029 1 Cu./Amr. PVC 104‐CVT JB 104 RB 10CX2.5 90 Core 1 G719EA‐MG9031‐00‐ TB2‐1 G719EA‐MG9031‐00‐ X:VTL‐1 104 RB‐X:VTL‐1 / TB2‐1 104‐CVT JB‐TB2‐1/X:VTL‐1 Spare
132 kV 104 104‐CVT JB 104 RB Core 2 W101, Sh‐13 of 49 TB2‐8 W101, Sh‐13 of 49 X:VTL‐2 104 RB‐X:VTL‐2 / TB2‐8 104‐CVT JB‐TB2‐8/X:VTL‐2
132 kV 104 104‐CVT JB 104 RB Core 3 TB2‐15 X:VTL‐3 104 RB‐X:VTL‐3 / TB2‐15 104‐CVT JB‐TB2‐15/X:VTL‐3
132 kV 104 104‐CVT JB 104 RB Core 4 TB2‐19 X:VTL‐4 104 RB‐X:VTL‐4 / TB2‐19 104‐CVT JB‐TB2‐19/X:VTL‐4
132 kV 104 104‐CVT JB 104 RB Core 5 G719EA‐MG9031‐00‐ TB3‐1 G719EA‐MG9031‐00‐ X:VTL‐5 104 RB‐X:VTL‐5 / TB3‐1 104‐CVT JB‐TB3‐1/X:VTL‐5
132 kV 104 104‐CVT JB 104 RB Core 6 W101, Sh‐13 of 49 TB3‐8 W101, Sh‐13 of 49 X:VTL‐6 104 RB‐X:VTL‐6 / TB3‐8 104‐CVT JB‐TB3‐8/X:VTL‐6 Metering
132 kV 104 104‐CVT JB 104 RB Core 7 TB3‐15 X:VTL‐7 104 RB‐X:VTL‐7 / TB3‐15 104‐CVT JB‐TB3‐15/X:VTL‐7
132 kV 104 104‐CVT JB 104 RB Core 8 TB3‐19 X:VTL‐8 104 RB‐X:VTL‐8 / TB3‐19 104‐CVT JB‐TB3‐19/X:VTL‐8
132 kV 104 104‐CVT JB 104 RB Core 9 SPARE
132 kV 104 104‐CVT JB 104 RB Core 10 SPARE
104‐CT CABLING
30 132 kV 104 within swyd  1‐104‐1‐030 1 Cu./Amr. PVC 104‐CT MB 104 RA 14CX2.5 85 Core 1 5US2 G719EA‐MG9031‐ X:CT‐1 104 RA‐X:CT‐1 / 5US2 104‐CT MB‐5US2/X:CT‐1
ASPL/UPPCL/20415
132 kV 104 104‐CT MB 104 RA Core 2 5VS2 W101, Sh‐16 of 58 X:CT‐3 104 RA‐X:CT‐3 / 5VS2 104‐CT MB‐5VS2/X:CT‐3
CORE 5: Distance Protection M1
132 kV 104 104‐CT MB 104 RA Core 3 5WS2 X:CT‐5 104 RA‐X:CT‐5 / 5WS2 104‐CT MB‐5WS2/X:CT‐5
132 kV 104 104‐CT MB 104 RA Core 4 5VS1 X:CT‐7 104 RA‐X:CT‐7 / 5VS1 104‐CT MB‐5VS1/X:CT‐7
132 kV 104 104‐CT MB 104 RA Core 5 2US2 G719EA‐MG9031‐00‐ X:CT‐21 104 RA‐X:CT‐21 / 2US2 104‐CT MB‐2US2/X:CT‐21
ASPL/UPPCL/20415
132 kV 104 104‐CT MB 104 RA Core 6 2VS2 W101, Sh‐19 of 49 X:CT‐23 104 RA‐X:CT‐23 / 2VS2 104‐CT MB‐2VS2/X:CT‐23 CORE 2: 67/67N : O/c & E/f Relay

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 2 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY104L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts) CORE 2: 67/67N : O/c & E/f Relay
132 kV 104 104‐CT MB 104 RA Core 7 2WS2 X:CT‐25 104 RA‐X:CT‐25 / 2WS2 104‐CT MB‐2WS2/X:CT‐25
132 kV 104 104‐CT MB 104 RA Core 8 2VS1 X:CT‐27 104 RA‐X:CT‐27 / 2VS1 104‐CT MB‐2VS1/X:CT‐27
132 kV 104 104‐CT MB 104 RA Core 9 1US2 G719EA‐MG9031‐00‐ X:CT‐29 104 RA‐X:CT‐29 / 1US2 104‐CT MB‐1US2/X:CT‐29
ASPL/UPPCL/20415
132 kV 104 104‐CT MB 104 RA Core 10 1VS2 W101, Sh‐21 of 49 X:CT‐31 104 RA‐X:CT‐31 / 1VS2 104‐CT MB‐1VS2/X:CT‐31 CORE1: 87BB : Busbar Protection
132 kV 104 104‐CT MB 104 RA Core 11 1WS2 X:CT‐33 104 RA‐X:CT‐33 / 1WS2 104‐CT MB‐1WS2/X:CT‐33
132 kV 104 104‐CT MB 104 RA Core 12 1VS1 X:CT‐35 104 RA‐X:CT‐35 / 1VS1 104‐CT MB‐1VS1/X:CT‐35
132 kV 104 104‐CT MB 104 RA Core 13 SPARE SPARE
132 kV 104 104‐CT MB 104 RA Core 14 SPARE SPARE

31 132 kV 104 within swyd  1‐104‐1‐031 1 Cu./Amr. PVC 104‐CT MB 104 RB 5CX2.5 85 Core 1 3US2 G719EA‐MG9031‐ X:CT‐23 104 RB‐X:CT‐23 / 3US2 104‐CT MB‐3US2/X:CT‐23
ASPL/UPPCL/20415
132 kV 104 104‐CT MB 104 RB Core 2 3VS2 W101, Sh‐33 of 58 X:CT‐25 104 RB‐X:CT‐25 / 3VS2 104‐CT MB‐3VS2/X:CT‐25
CORE 3: BCU : Bay Control Unit
132 kV 104 104‐CT MB 104 RB Core 3 3WS2 X:CT‐27 104 RB‐X:CT‐27 / 3WS2 104‐CT MB‐3WS2/X:CT‐27
132 kV 104 104‐CT MB 104 RB Core 4 3VS1 X:CT‐29 104 RB‐X:CT‐29 / 3VS1 104‐CT MB‐3VS1/X:CT‐29
132 kV 104 104‐CT MB 104 RB Core 5 SPARE

104‐CIRCUIT BREAKER CABLING TO PANEL
32 132 kV 104 within swyd  1‐104‐1‐032 1 Cu./Amr. PVC 104‐52  104 RA 19CX2.5 50 Core 1 G719EA‐MG9031‐00‐ X1LA‐5 G719EA‐MG9031‐ X:CB‐1 104 RA‐X:CB‐1 / X1LA‐5 104‐52 ‐X1LA‐5/X:CB‐1 Common
132 kV 104 104‐52  104 RA Core 2 W101, Sh‐17 of 49 X1LA‐6 W201, Sh‐17 of 58 X:CB‐2 104 RA‐X:CB‐2 / X1LA‐6 104‐52 ‐X1LA‐6/X:CB‐2 Main CB Open
132 kV 104 104‐52  104 RA Core 3 G719EA‐MG9031‐00‐ X1LC‐6 G719EA‐MG9031‐00‐ X:BB‐3 104 RA‐X:BB‐3 / X1LC‐6 104‐52 ‐X1LC‐6/X:BB‐3 CB Open
132 kV 104 104‐52  104 RA Core 4 W101, Sh‐22 of 49 X1LC‐6 W101, Sh‐22 of 49 X:BB‐4 104 RA‐X:BB‐4 / X1LC‐6 104‐52 ‐X1LC‐6/X:BB‐4 Main/TBC CB Open, B‐Ph
132 kV 104 104‐52  104 RA Core 5 G719EA‐MG9031‐00‐ X1 G719EA‐MG9031‐00‐ X:TC1‐3 104 RA‐X:TC1‐3 / X1 104‐52 ‐X1/X:TC1‐3 Common
132 kV 104 104‐52  104 RA Core 6 W101, Sh‐26 of 49 X1:7 W101, Sh‐26 of 49 X:TC1‐4 104 RA‐X:TC1‐4 / X1:7 104‐52 ‐X1:7/X:TC1‐4 Protection Trip‐1
132 kV 104 104‐52  104 RA Core 7 X1:10 X:TC1‐5 104 RA‐X:TC1‐5 / X1:10 104‐52 ‐X1:10/X:TC1‐5 Post Close TC‐1 Supervision
132 kV 104 104‐52  104 RA Core 8 X1:9 X:TC1‐6 104 RA‐X:TC1‐6 / X1:9 104‐52 ‐X1:9/X:TC1‐6 Pre Close TC‐1 Supervision 
132 kV 104 104‐52  104 RA Core 9 X1:1 X:TC1‐1 104 RA‐X:TC1‐1 / X1:1 104‐52 ‐X1:1/X:TC1‐1 DC Supply (+)Ve
132 kV 104 104‐52  104 RA Core 10 X1:2 X:TC1‐2 104 RA‐X:TC1‐2 / X1:2 104‐52 ‐X1:2/X:TC1‐2 DC Supply (‐)Ve
132 kV 104 104‐52  104 RA Core 11 G719EA‐MG9031‐00‐ X1 G719EA‐MG9031‐00‐ X:TC2‐9 104 RA‐X:TC2‐9 / X1 104‐52 ‐X1/X:TC2‐9 Common
132 kV 104 104‐52  104 RA Core 12 W101, Sh‐27 of 49 X1:16 W101, Sh‐27 of 49 X:TC2‐10 104 RA‐X:TC2‐10 / X1:16 104‐52 ‐X1:16/X:TC2‐10 Protection Trip‐2
132 kV 104 104‐52  104 RA Core 13 X1:19 X:TC2‐11 104 RA‐X:TC2‐11 / X1:19 104‐52 ‐X1:19/X:TC2‐11 Post Close TC‐2 Supervision
132 kV 104 104‐52  104 RA Core 14 X1:18 X:TC2‐12 104 RA‐X:TC2‐12 / X1:18 104‐52 ‐X1:18/X:TC2‐12 Pre Close TC‐2 Supervision 
132 kV 104 104‐52  104 RA Core 15 X1:1A X:TC2‐1 104 RA‐X:TC2‐1 / X1:1A 104‐52 ‐X1:1A/X:TC2‐1 DC Supply (+)Ve
132 kV 104 104‐52  104 RA Core 16 X1:2A X:TC2‐2 104 RA‐X:TC2‐2 / X1:2A 104‐52 ‐X1:2A/X:TC2‐2 DC Supply (‐)Ve
132 kV 104 104‐52  104 RA Core 17 SPARE
132 kV 104 104‐52  104 RA Core 18 SPARE
132 kV 104 104‐52  104 RA Core 19 SPARE

33 132 kV 104 within swyd  1‐104‐1‐033 1 Cu./Amr. PVC 104‐52  104 RB 19CX2.5 50 Core 1 G719EA‐MG9031‐00‐ X1 G719EA‐MG9031‐00‐ X:CB‐1 104 RB‐X:CB‐1 / X1 104‐52 ‐X1/X:CB‐1 Common
132 kV 104 104‐52  104 RB Core 2 W101, Sh‐29 of 49 X1 W101, Sh‐29 of 49 X:CB‐2 104 RB‐X:CB‐2 / X1 104‐52 ‐X1/X:CB‐2 CB Open
132 kV 104 104‐52  104 RB Core 3 X1 X:CB‐3 104 RB‐X:CB‐3 / X1 104‐52 ‐X1/X:CB‐3 CB Close
132 kV 104 104‐52  104 RB Core 4 X1 X:CB‐4 104 RB‐X:CB‐4 / X1 104‐52 ‐X1/X:CB‐4 General SF6 Lockout
132 kV 104 104‐52  104 RB Core 5 X1 X:CB‐5 104 RB‐X:CB‐5 / X1 104‐52 ‐X1/X:CB‐5 Loss of SF6 Alarm
132 kV 104 104‐52  104 RB Core 6 X1 X:CB‐6 104 RB‐X:CB‐6 / X1 104‐52 ‐X1/X:CB‐6 Spring Status protection
132 kV 104 104‐52  104 RB Core 7 X1 X:CB‐7 104 RB‐X:CB‐7 / X1 104‐52 ‐X1/X:CB‐7 Spring Status supervision
132 kV 104 104‐52  104 RB Core 8 X1 X:CB‐8 104 RB‐X:CB‐8 / X1 104‐52 ‐X1/X:CB‐8 DC‐1 & 2 Monitor
132 kV 104 104‐52  104 RB Core 9 G719EA‐MG9031‐00‐ X1:26 G719EA‐MG9031‐00‐ X:CB‐18 104 RB‐X:CB‐18 / X1:26 104‐52 ‐X1:26/X:CB‐18
CB Closing I/L permissible
132 kV 104 104‐52  104 RB Core 10 W101, Sh‐34 of 49 X1:27 W101, Sh‐34 of 49 X:CB‐19 104 RB‐X:CB‐19 / X1:27 104‐52 ‐X1:27/X:CB‐19
132 kV 104 104‐52  104 RB Core 11 X1:23 X:CB‐33 104 RB‐X:CB‐33 / X1:23 104‐52 ‐X1:23/X:CB‐33 Common
132 kV 104 104‐52  104 RB Core 12 X1:24 X:CB‐34 104 RB‐X:CB‐34 / X1:24 104‐52 ‐X1:24/X:CB‐34 Remote Close
132 kV 104 104‐52  104 RB Core 13 X1:25 X:CB‐35 104 RB‐X:CB‐35 / X1:25 104‐52 ‐X1:25/X:CB‐35 Auto Reclose
132 kV 104 104‐52  104 RB Core 14 X1:5 X:CB‐21 104 RB‐X:CB‐21 / X1:5 104‐52 ‐X1:5/X:CB‐21 Common
132 kV 104 104‐52  104 RB Core 15 X1:6 X:CB‐22 104 RB‐X:CB‐22 / X1:6 104‐52 ‐X1:6/X:CB‐22 Remote Trip‐1
132 kV 104 104‐52  104 RB Core 16 X1:14 X:CB‐25 104 RB‐X:CB‐25 / X1:14 104‐52 ‐X1:14/X:CB‐25 Common
132 kV 104 104‐52  104 RB Core 17 X1:15 X:CB‐26 104 RB‐X:CB‐26 / X1:15 104‐52 ‐X1:15/X:CB‐26 Remote Trip‐2
132 kV 104 104‐52  104 RB Core 18 SPARE
132 kV 104 104‐52  104 RB Core 19 SPARE

107‐CIRCUIT BREAKER CABLING TO PANEL
34 132 kV 107 within swyd  1‐107‐1‐034 1 Cu./Amr. PVC 107‐52  104 RA 3CX2.5 120 Core 1 G719EA‐MG9031‐00‐ X1LA‐5 G719EA‐MG9031‐ X:TCB‐1 104 RA‐X:TCB‐1 / X1LA‐5 107‐52 ‐X1LA‐5/X:TCB‐1 Common
132 kV 107 107‐52  104 RA Core 2 W101, Sh‐17 of 49 X1LA‐6 W101, Sh‐17 of 58 X:TCB‐2 104 RA‐X:TCB‐2 / X1LA‐6 107‐52 ‐X1LA‐6/X:TCB‐2 TBC CB Open
132 kV 107 107‐52  104 RA Core 3 SPARE
104‐ISOLATOR CABLING TO PANEL
35 132 kV 104 within swyd  1‐104‐1‐035 1 Cu./Amr. PVC 104‐89A  104 RA 5CX2.5 35 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐5 104 RA‐X:BB‐5 / TB3‐103 104‐89A ‐TB3‐103/X:BB‐5 Common
132 kV 104 104‐89A  104 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐6 104 RA‐X:BB‐6 / TB3‐104 104‐89A ‐TB3‐104/X:BB‐6 Isolator 89A Open
132 kV 104 104‐89A  104 RA Core 3 G719EA‐MG9031‐00‐ TB3‐101 G719EA‐MG9031‐00‐ X:ISA‐1 104 RA‐X:ISA‐1 / TB3‐101 104‐89A ‐TB3‐101/X:ISA‐1 Trip Bus‐1 (Main‐1)
132 kV 104 104‐89A  104 RA Core 4 W101, Sh‐25a of 49 TB3‐102 W101, Sh‐25a of 49 X:ISA‐2 104 RA‐X:ISA‐2 / TB3‐102 104‐89A ‐TB3‐102/X:ISA‐2 Common
132 kV 104 104‐89A  104 RA Core 5 SPARE

36 132 kV 104 within swyd  1‐104‐1‐036 1 Cu./Amr. PVC 104‐89A  104 RB 10CX2.5 35 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:ISA‐1 104 RB‐X:ISA‐1 / TB3‐103 104‐89A ‐TB3‐103/X:ISA‐1 Common
132 kV 104 104‐89A  104 RB Core 2 W101, Sh‐29 of 49 TB3‐104 W101, Sh‐29 of 49 X:ISA‐2 104 RB‐X:ISA‐2 / TB3‐104 104‐89A ‐TB3‐104/X:ISA‐2 Isolator 89A Open
132 kV 104 104‐89A  104 RB Core 3 TB3‐102 X:ISA‐3 104 RB‐X:ISA‐3 / TB3‐102 104‐89A ‐TB3‐102/X:ISA‐3 Isolator 89A Close
132 kV 104 104‐89A  104 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISA‐7 104 RB‐X:ISA‐7 / TB1‐1 104‐89A ‐TB1‐1/X:ISA‐7 DC Supply (+)Ve
132 kV 104 104‐89A  104 RB Core 5 W101, Sh‐35 of 49 TB1‐2 W101, Sh‐35 of 49 X:ISA‐8 104 RB‐X:ISA‐8 / TB1‐2 104‐89A ‐TB1‐2/X:ISA‐8 DC Supply (‐)Ve
132 kV 104 104‐89A  104 RB Core 6 TB1‐3 X:ISA‐9 104 RB‐X:ISA‐9 / TB1‐3 104‐89A ‐TB1‐3/X:ISA‐9 Common
132 kV 104 104‐89A  104 RB Core 7 TB1‐5 X:ISA‐10 104 RB‐X:ISA‐10 / TB1‐5 104‐89A ‐TB1‐5/X:ISA‐10 Open 
132 kV 104 104‐89A  104 RB Core 8 TB1‐4 X:ISA‐11 104 RB‐X:ISA‐11 / TB1‐4 104‐89A ‐TB1‐4/X:ISA‐11 Close
132 kV 104 104‐89A  104 RB Core 9 SPARE
132 kV 104 104‐89A  104 RB Core 10 SPARE

37 132 kV 104 within swyd  1‐104‐1‐037 1 Cu./Amr. PVC 104‐89B  104 RA 5CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐7 104 RA‐X:BB‐7 / TB3‐103 104‐89B ‐TB3‐103/X:BB‐7 Common
132 kV 104 104‐89B  104 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐8 104 RA‐X:BB‐8 / TB3‐104 104‐89B ‐TB3‐104/X:BB‐8 Isolator 89B Open
132 kV 104 104‐89B  104 RA Core 3 G719EA‐MG9031‐00‐ TB3‐101 G719EA‐MG9031‐00‐ X:ISB‐1 104 RA‐X:ISB‐1 / TB3‐101 104‐89B ‐TB3‐101/X:ISB‐1 Trip Bus‐2 (Main‐2)
132 kV 104 104‐89B  104 RA Core 4 W101, Sh‐25a of 49 TB3‐102 W101, Sh‐25a of 49 X:ISB‐2 104 RA‐X:ISB‐2 / TB3‐102 104‐89B ‐TB3‐102/X:ISB‐2 Common
132 kV 104 104‐89B  104 RA Core 5 SPARE

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 3 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY104L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)

38 132 kV 104 within swyd  1‐104‐1‐038 1 Cu./Amr. PVC 104‐89B  104 RB 10CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐ X:ISB‐1 104 RB‐X:ISB‐1 / TB3‐107 104‐89B ‐TB3‐107/X:ISB‐1 Common
132 kV 104 104‐89B  104 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W201, Sh‐35 of 58 X:ISB‐2 104 RB‐X:ISB‐2 / TB3‐108 104‐89B ‐TB3‐108/X:ISB‐2 Isolator 89B Open
132 kV 104 104‐89B  104 RB Core 3 TB3‐102 X:ISB‐3 104 RB‐X:ISB‐3 / TB3‐102 104‐89B ‐TB3‐102/X:ISB‐3 Isolator 89B Close
132 kV 104 104‐89B  104 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISB‐4 104 RB‐X:ISB‐4 / TB1‐1 104‐89B ‐TB1‐1/X:ISB‐4 DC Supply (+)Ve
132 kV 104 104‐89B  104 RB Core 5 W101, Sh‐35 of 49 TB1‐2 W101, Sh‐35 of 49 X:ISB‐5 104 RB‐X:ISB‐5 / TB1‐2 104‐89B ‐TB1‐2/X:ISB‐5 DC Supply (‐)Ve
132 kV 104 104‐89B  104 RB Core 6 TB1‐5 X:ISB‐7 104 RB‐X:ISB‐7 / TB1‐5 104‐89B ‐TB1‐5/X:ISB‐7 Open 
132 kV 104 104‐89B  104 RB Core 7 TB1‐4 X:ISB‐8 104 RB‐X:ISB‐8 / TB1‐4 104‐89B ‐TB1‐4/X:ISB‐8 Close
132 kV 104 104‐89B  104 RB Core 8 TB1‐3 X:ISB‐6 104 RB‐X:ISB‐6 / TB1‐3 104‐89B ‐TB1‐3/X:ISB‐6 Common
132 kV 104 104‐89B  104 RB Core 9 SPARE
132 kV 104 104‐89B  104 RB Core 10 SPARE

39 132 kV 104 within swyd  1‐104‐1‐039 1 Cu./Amr. PVC 104‐89T  104 RA 5CX2.5 75 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐9 104 RA‐X:BB‐9 / TB3‐103 104‐89T ‐TB3‐103/X:BB‐9 Common
132 kV 104 104‐89T  104 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐10 104 RA‐X:BB‐10 / TB3‐104 104‐89T ‐TB3‐104/X:BB‐10 Isolator 89T Open
132 kV 104 104‐89T  104 RA Core 3 G719EA‐MG9031‐00‐ TBX‐X G719EA‐MG9031‐00‐ X:IST‐1 104 RA‐X:IST‐1 / TBX‐X 104‐89T ‐TBX‐X/X:IST‐1 Trip Bus‐3 (Transfer Bus)
132 kV 104 104‐89T  104 RA Core 4 W101, Sh‐25a of 49 TBX‐X W101, Sh‐25a of 49 X:IST‐2 104 RA‐X:IST‐2 / TBX‐X 104‐89T ‐TBX‐X/X:IST‐2 Common
132 kV 104 104‐89T  104 RA Core 5 SPARE

40 132 kV 104 within swyd  1‐104‐1‐040 1 Cu./Amr. PVC 104‐89T  104 RB 10CX2.5 75 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:IST‐1 104 RB‐X:IST‐1 / TB3‐107 104‐89T ‐TB3‐107/X:IST‐1 Common
132 kV 104 104‐89T  104 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:IST‐2 104 RB‐X:IST‐2 / TB3‐108 104‐89T ‐TB3‐108/X:IST‐2 Isolator 89T Open
132 kV 104 104‐89T  104 RB Core 3 TB3‐102 X:IST‐3 104 RB‐X:IST‐3 / TB3‐102 104‐89T ‐TB3‐102/X:IST‐3 Isolator 89T Close
132 kV 104 104‐89T  104 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:IST‐4 104 RB‐X:IST‐4 / TB1‐1 104‐89T ‐TB1‐1/X:IST‐4 DC Supply (+)Ve
132 kV 104 104‐89T  104 RB Core 5 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 X:IST‐5 104 RB‐X:IST‐5 / TB1‐2 104‐89T ‐TB1‐2/X:IST‐5 DC Supply (‐)Ve
132 kV 104 104‐89T  104 RB Core 6 TB1‐3 X:IST‐6 104 RB‐X:IST‐6 / TB1‐3 104‐89T ‐TB1‐3/X:IST‐6 Common
132 kV 104 104‐89T  104 RB Core 7 TB1‐5 X:IST‐7 104 RB‐X:IST‐7 / TB1‐5 104‐89T ‐TB1‐5/X:IST‐7 Open 
132 kV 104 104‐89T  104 RB Core 8 TB1‐4 X:IST‐8 104 RB‐X:IST‐8 / TB1‐4 104‐89T ‐TB1‐4/X:IST‐8 Close
132 kV 104 104‐89T  104 RB Core 9 SPARE
132 kV 104 104‐89T  104 RB Core 10 SPARE

41 132 kV 104 within swyd  1‐104‐1‐041 1 Cu./Amr. PVC 104‐89L  104 RA 3CX2.5 65 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:BB‐11 104 RA‐X:BB‐11 / TB3‐103 104‐89L ‐TB3‐103/X:BB‐11 Common
132 kV 104 104‐89L  104 RA Core 2 W101, Sh‐22 of 49 TB3‐104 W101, Sh‐22 of 49 X:BB‐12 104 RA‐X:BB‐12 / TB3‐104 104‐89L ‐TB3‐104/X:BB‐12 Isolator 89L Open
132 kV 104 104‐89L  104 RA Core 3 SPARE

42 132 kV 104 within swyd  1‐104‐1‐042 1 Cu./Amr. PVC 104‐89LE  104 RB 10CX2.5 65 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISL‐1 104 RB‐X:ISL‐1 / TB3‐107 104‐89LE ‐TB3‐107/X:ISL‐1 Common
132 kV 104 104‐89LE  104 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:ISL‐2 104 RB‐X:ISL‐2 / TB3‐108 104‐89LE ‐TB3‐108/X:ISL‐2 Isolator 89L Open
132 kV 104 104‐89LE  104 RB Core 3 TB3‐102 X:ISL‐3 104 RB‐X:ISL‐3 / TB3‐102 104‐89LE ‐TB3‐102/X:ISL‐3 Isolator 89L Close
132 kV 104 104‐89LE  104 RB Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISL‐10 104 RB‐X:ISL‐10 / TB1‐1 104‐89LE ‐TB1‐1/X:ISL‐10 DC Supply (+)Ve
132 kV 104 104‐89LE  104 RB Core 5 W101, Sh‐36 of 49 TB1‐2 W101, Sh‐36 of 49 X:ISL‐11 104 RB‐X:ISL‐11 / TB1‐2 104‐89LE ‐TB1‐2/X:ISL‐11 DC Supply (‐)Ve
132 kV 104 104‐89LE  104 RB Core 6 TB1‐3 X:ISL‐12 104 RB‐X:ISL‐12 / TB1‐3 104‐89LE ‐TB1‐3/X:ISL‐12 Common
132 kV 104 104‐89LE  104 RB Core 7 TB1‐5 X:ISL‐13 104 RB‐X:ISL‐13 / TB1‐5 104‐89LE ‐TB1‐5/X:ISL‐13 Open 
132 kV 104 104‐89LE  104 RB Core 8 TB1‐4 X:ISL‐14 104 RB‐X:ISL‐14 / TB1‐4 104‐89LE ‐TB1‐4/X:ISL‐14 Close
132 kV 104 104‐89LE  104 RB Core 9 SPARE
132 kV 104 104‐89LE  104 RB Core 10 SPARE

104‐EARTH SWITCH CABLING TO PANEL
43 132 kV 104 within swyd  1‐104‐1‐043 1 Cu./Amr. PVC 104‐89AE  104 RB 5CX2.5 35 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISA‐4 104 RB‐X:ISA‐4 / TB3‐107 104‐89AE ‐TB3‐107/X:ISA‐4 Common
132 kV 104 104‐89AE  104 RB Core 2 W101, Sh‐29 of 49 TB3‐108 W101, Sh‐29 of 49 X:ISA‐5 104 RB‐X:ISA‐5 / TB3‐108 104‐89AE ‐TB3‐108/X:ISA‐5 E/s 89AE Open
132 kV 104 104‐89AE  104 RB Core 3 TB3‐102 X:ISA‐6 104 RB‐X:ISA‐6 / TB3‐102 104‐89AE ‐TB3‐102/X:ISA‐6 E/s 89AE Close
132 kV 104 104‐89AE  104 RB Core 4 SPARE
Core 5 SPARE

44 132 kV 104 within swyd  1‐104‐1‐044 1 Cu./Amr. PVC 104‐89LE1  104 RB 5CX2.5 65 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISL‐4 104 RB‐X:ISL‐4 / TB3‐107 104‐89LE1 ‐TB3‐107/X:ISL‐4 Common
132 kV 104 104‐89LE1  104 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:ISL‐5 104 RB‐X:ISL‐5 / TB3‐108 104‐89LE1 ‐TB3‐108/X:ISL‐5 E/s 89LE1 Open
132 kV 104 104‐89LE1  104 RB Core 3 TB3‐102 X:ISL‐6 104 RB‐X:ISL‐6 / TB3‐102 104‐89LE1 ‐TB3‐102/X:ISL‐6 E/s 89LE1 Close
132 kV 104 104‐89LE1  104 RB Core 4 SPARE
132 kV 104 104‐89LE1  104 RB Core 5 SPARE

45 132 kV 104 within swyd  1‐104‐1‐045 1 Cu./Amr. PVC 104‐89LE2  104 RB 5CX2.5 65 Core 1 G719EA‐MG9031‐00‐ TB3‐107 G719EA‐MG9031‐00‐ X:ISL‐7 104 RB‐X:ISL‐7 / TB3‐107 104‐89LE2 ‐TB3‐107/X:ISL‐7 Common
132 kV 104 104‐89LE2  104 RB Core 2 W101, Sh‐30 of 49 TB3‐108 W101, Sh‐30 of 49 X:ISL‐8 104 RB‐X:ISL‐8 / TB3‐108 104‐89LE2 ‐TB3‐108/X:ISL‐8 E/s 89LE2 Open
132 kV 104 104‐89LE2  104 RB Core 3 TB3‐102 X:ISL‐9 104 RB‐X:ISL‐9 / TB3‐102 104‐89LE2 ‐TB3‐102/X:ISL‐9 E/s 89LE2 Close
132 kV 104 104‐89LE2  104 RB Core 4 SPARE
132 kV 104 104‐89LE2  104 RB Core 5 SPARE

104‐PLCC CHANNEL TO PANEL
46 132 kV 104 within swyd  1‐104‐1‐046 1 Cu./Amr. PVC 104‐PLCC  CH‐1 104 RA 10CX2.5 10 Core 1 G719EA‐MG9031‐00‐ X12‐1‐P11‐09 G719EA‐MG9031‐00‐ X:PLCC‐1 104 RA‐X:PLCC‐1 / X12‐1‐P11‐09 104‐PLCC  CH‐1‐X12‐1‐P11‐09/X:PLCC‐1Common
132 kV 104 104‐PLCC  CH‐1 104 RA Core 2 W101, Sh‐18 of 49 X12‐1‐P11‐10 W101, Sh‐18 of 49 X:PLCC‐2 104 RA‐X:PLCC‐2 / X12‐1‐P11‐10 104‐PLCC  CH‐1‐X12‐1‐P11‐10/X:PLCC‐2Carrier Fail CH‐1
132 kV 104 104‐PLCC  CH‐1 104 RA Core 3 X12‐1‐P10‐2 X:PLCC‐3 104 RA‐X:PLCC‐3 / X12‐1‐P10‐2 104‐PLCC  CH‐1‐X12‐1‐P10‐2/X:PLCC‐3 Common
132 kV 104 104‐PLCC  CH‐1 104 RA Core 4 X12‐1‐P16‐36 X:PLCC‐4 104 RA‐X:PLCC‐4 / X12‐1‐P16‐36 104‐PLCC  CH‐1‐X12‐1‐P16‐36/X:PLCC‐4Common
132 kV 104 104‐PLCC  CH‐1 104 RA Core 5 X12‐1‐P16‐37 X:PLCC‐5 104 RA‐X:PLCC‐5 / X12‐1‐P16‐37 104‐PLCC  CH‐1‐X12‐1‐P16‐37/X:PLCC‐5Carrier Received CH‐1
132 kV 104 104‐PLCC  CH‐1 104 RA Core 6 X12‐1‐P11‐13 X:PLCC‐6 104 RA‐X:PLCC‐6 / X12‐1‐P11‐13 104‐PLCC  CH‐1‐X12‐1‐P11‐13/X:PLCC‐6Direct Trip Received CH‐1
132 kV 104 104‐PLCC  CH‐1 104 RA Core 7 X12‐1‐P11‐14 X:PLCC‐7 104 RA‐X:PLCC‐7 / X12‐1‐P11‐14 104‐PLCC  CH‐1‐X12‐1‐P11‐14/X:PLCC‐7Carrier Send CH‐1
132 kV 104 104‐PLCC  CH‐1 104 RA Core 8 X12‐1‐P10‐5 X:PLCC‐8 104 RA‐X:PLCC‐8 / X12‐1‐P10‐5 104‐PLCC  CH‐1‐X12‐1‐P10‐5/X:PLCC‐8 Direct Trip Send (Code‐4)
132 kV 104 104‐PLCC  CH‐1 104 RA Core 9 SPARE
132 kV 104 104‐PLCC  CH‐1 104 RA Core 10 SPARE

47 132 kV 104 within swyd  1‐104‐1‐047 1 Cu./Amr. PVC 104‐PLCC  CH‐2 104 RA 10CX2.5 10 Core 1 G719EA‐MG9031‐ X11‐1‐P11‐09 G719EA‐MG9031‐ X:PLCC‐9 104 RA‐X:PLCC‐9 / X11‐1‐P11‐09 104‐PLCC  CH‐2‐X11‐1‐P11‐09/X:PLCC‐9Direct Trip Received CH‐2
132 kV 104 104‐PLCC  CH‐2 104 RA Core 2 W201, Sh‐28 of 58 X11‐1‐P11‐10 W201, Sh‐28 of 58 X:PLCC‐10 104 RA‐X:PLCC‐10 / X11‐1‐P11‐10 04‐PLCC  CH‐2‐X11‐1‐P11‐10/X:PLCC‐1 Common
132 kV 104 104‐PLCC  CH‐2 104 RA Core 3 X11‐1‐P10‐2 X:PLCC‐11 104 RA‐X:PLCC‐11 / X11‐1‐P10‐2 104‐PLCC  CH‐2‐X11‐1‐P10‐2/X:PLCC‐11Carrier Fail CH‐2
132 kV 104 104‐PLCC  CH‐2 104 RA Core 4 X11‐1‐P16‐36 X:PLCC‐12 104 RA‐X:PLCC‐12 / X11‐1‐P16‐36 04‐PLCC  CH‐2‐X11‐1‐P16‐36/X:PLCC‐1 Common
132 kV 104 104‐PLCC  CH‐2 104 RA Core 5 X11‐1‐P16‐37 X:PLCC‐13 104 RA‐X:PLCC‐13 / X11‐1‐P16‐37 04‐PLCC  CH‐2‐X11‐1‐P16‐37/X:PLCC‐1 Carrier Received CH‐2
132 kV 104 104‐PLCC  CH‐2 104 RA Core 6 X11‐1‐P11‐13 X:PLCC‐14 104 RA‐X:PLCC‐14 / X11‐1‐P11‐13 04‐PLCC  CH‐2‐X11‐1‐P11‐13/X:PLCC‐1 Carrier Send CH‐2
132 kV 104 104‐PLCC  CH‐2 104 RA Core 7 X11‐1‐P11‐14 X:PLCC‐15 104 RA‐X:PLCC‐15 / X11‐1‐P11‐14 04‐PLCC  CH‐2‐X11‐1‐P11‐14/X:PLCC‐1 Direct Trip Send (Code‐4)
132 kV 104 104‐PLCC  CH‐2 104 RA Core 8 SPARE
132 kV 104 104‐PLCC  CH‐2 104 RA Core 9 SPARE

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 4 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY104L

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM (TERM.  TO ‐ EQUIP. REF.  TO (TERM. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. NO.) DWG. NO.)
(in mts) (in mts)
132 kV 104 104‐PLCC  CH‐2 104 RA Core 10 SPARE

104‐Inter Panel Cabling
48 132 kV 104 within swyd  1‐104‐1‐048 1 Cu./Amr. PVC 104 RA 104 RB 27CX2.5 10 Core 1 G719EA‐MG9031‐ XCRA‐31 G719EA‐MG9031‐ XCRB‐31 104 RB‐XCRB‐31 / XCRA‐31 104 RA‐XCRA‐31/XCRB‐31 Common
132 kV 104 104 RA 104 RB Core 2 W101, Sh‐25 of 49 XCRA‐32 W101, Sh‐25 of 49 XCRB‐32 104 RB‐XCRB‐32 / XCRA‐32 104 RA‐XCRA‐32/XCRB‐32
132 kV 104 104 RA 104 RB Core 3 G719EA‐MG9031‐ XCRA‐15 G719EA‐MG9031‐ XCRB‐15 104 RB‐XCRB‐15 / XCRA‐15 104 RA‐XCRA‐15/XCRB‐15
132 kV 104 104 RA 104 RB Core 4 W101, Sh‐26 of 49 XCRA‐16 W101, Sh‐26 of 49 XCRB‐16 104 RB‐XCRB‐16 / XCRA‐16 104 RA‐XCRA‐16/XCRB‐16
132 kV 104 104 RA 104 RB Core 5 XCRA‐17 XCRB‐17 104 RB‐XCRB‐17 / XCRA‐17 104 RA‐XCRA‐17/XCRB‐17
132 kV 104 104 RA 104 RB Core 6 XCRA‐18 XCRB‐18 104 RB‐XCRB‐18 / XCRA‐18 104 RA‐XCRA‐18/XCRB‐18
132 kV 104 104 RA 104 RB Core 7 G719EA‐MG9031‐ XCRA‐10 G719EA‐MG9031‐ XCRB‐10 104 RB‐XCRB‐10 / XCRA‐10 104 RA‐XCRA‐10/XCRB‐10
132 kV 104 104 RA 104 RB Core 8 W101, Sh‐27 of 49 XCRA‐11 W101, Sh‐27 of 49 XCRB‐11 104 RB‐XCRB‐11 / XCRA‐11 104 RA‐XCRA‐11/XCRB‐11
132 kV 104 104 RA 104 RB Core 9 XCRA‐12 XCRB‐12 104 RB‐XCRB‐12 / XCRA‐12 104 RA‐XCRA‐12/XCRB‐12
132 kV 104 104 RA 104 RB Core 10 XCRA‐13 XCRB‐13 104 RB‐XCRB‐13 / XCRA‐13 104 RA‐XCRA‐13/XCRB‐13
132 kV 104 104 RA 104 RB Core 11 G719EA‐MG9031‐ XCRA‐45 G719EA‐MG9031‐ XCRB‐45 104 RB‐XCRB‐45 / XCRA‐45 104 RA‐XCRA‐45/XCRB‐45
132 kV 104 104 RA 104 RB Core 12 W101, Sh‐33 of 49 XCRA‐46 W101, Sh‐33 of 49 XCRB‐46 104 RB‐XCRB‐46 / XCRA‐46 104 RA‐XCRA‐46/XCRB‐46
132 kV 104 104 RA 104 RB Core 13 XCRA‐47 XCRB‐47 104 RB‐XCRB‐47 / XCRA‐47 104 RA‐XCRA‐47/XCRB‐47
132 kV 104 104 RA 104 RB Core 14 G719EA‐MG9031‐ XCRA‐48 G719EA‐MG9031‐ XCRB‐48 104 RB‐XCRB‐48 / XCRA‐48 104 RA‐XCRA‐48/XCRB‐48
132 kV 104 104 RA 104 RB Core 15 W101, Sh‐34 of 49 XCRA‐49 W101, Sh‐34 of 49 XCRB‐49 104 RB‐XCRB‐49 / XCRA‐49 104 RA‐XCRA‐49/XCRB‐49
132 kV 104 104 RA 104 RB Core 16 XCRA‐75 XCRB‐75 104 RB‐XCRB‐75 / XCRA‐75 104 RA‐XCRA‐75/XCRB‐75
132 kV 104 104 RA 104 RB Core 17 XCRA‐76 XCRB‐76 104 RB‐XCRB‐76 / XCRA‐76 104 RA‐XCRA‐76/XCRB‐76
132 kV 104 104 RA 104 RB Core 18 G719EA‐MG9031‐ XCRA‐66 G719EA‐MG9031‐ XCRB‐66 104 RB‐XCRB‐66 / XCRA‐66 104 RA‐XCRA‐66/XCRB‐66
132 kV 104 104 RA 104 RB Core 19 W101, Sh‐34 of 49 XCRA‐67 W101, Sh‐34 of 49 XCRB‐67 104 RB‐XCRB‐67 / XCRA‐67 104 RA‐XCRA‐67/XCRB‐67
132 kV 104 104 RA 104 RB Core 20 XCRA‐71 XCRB‐71 104 RB‐XCRB‐71 / XCRA‐71 104 RA‐XCRA‐71/XCRB‐71
132 kV 104 104 RA 104 RB Core 21 XCRA‐72 XCRB‐72 104 RB‐XCRB‐72 / XCRA‐72 104 RA‐XCRA‐72/XCRB‐72
132 kV 104 104 RA 104 RB Core 22 Spare Spare
132 kV 104 104 RA 104 RB Core 23 Spare Spare
132 kV 104 104 RA 104 RB Core 24 Spare Spare
132 kV 104 104 RA 104 RB Core 25 Spare Spare
132 kV 104 104 RA 104 RB Core 26 Spare Spare
132 kV 104 104 RA 104 RB Core 27 Spare Spare

49 132 kV 104 within swyd  1‐104‐1‐049 1 Cu./Amr. PVC 101 RA 101 RB 19CX2.5 10 Core 1 G719EA‐MG9031‐ XCRA‐50 G719EA‐MG9031‐ XCRB‐50 101 RB‐XCRB‐50 / XCRA‐50 101 RA‐XCRA‐50/XCRB‐50
132 kV 104 101 RA 101 RB Core 2 W101, Sh‐37 of 49 XCRA‐51 W101, Sh‐37 of 49 XCRB‐51 101 RB‐XCRB‐51 / XCRA‐51 101 RA‐XCRA‐51/XCRB‐51
132 kV 104 101 RA 101 RB Core 3 XCRA‐54 XCRB‐54 101 RB‐XCRB‐54 / XCRA‐54 101 RA‐XCRA‐54/XCRB‐54
132 kV 104 101 RA 101 RB Core 4 XCRA‐55 XCRB‐55 101 RB‐XCRB‐55 / XCRA‐55 101 RA‐XCRA‐55/XCRB‐55
132 kV 104 101 RA 101 RB Core 5 XCRA‐58 XCRB‐58 101 RB‐XCRB‐58 / XCRA‐58 101 RA‐XCRA‐58/XCRB‐58
132 kV 104 101 RA 101 RB Core 6 XCRA‐59 XCRB‐59 101 RB‐XCRB‐59 / XCRA‐59 101 RA‐XCRA‐59/XCRB‐59
132 kV 104 101 RA 101 RB Core 7 XCRA‐63 XCRB‐63 101 RB‐XCRB‐63 / XCRA‐63 101 RA‐XCRA‐63/XCRB‐63
132 kV 104 101 RA 101 RB Core 8 Spare
132 kV 104 101 RA 101 RB Core 9 Spare
132 kV 104 101 RA 101 RB Core 10 Spare
132 kV 104 101 RA 101 RB Core 11 Spare
132 kV 104 101 RA 101 RB Core 12 Spare
132 kV 104 101 RA 101 RB Core 13 Spare
132 kV 104 101 RA 101 RB Core 14 Spare
132 kV 104 101 RA 101 RB Core 15 Spare
132 kV 104 101 RA 101 RB Core 16 Spare
132 kV 104 101 RA 101 RB Core 17 Spare
132 kV 104 101 RA 101 RB Core 18 Spare
132 kV 104 101 RA 101 RB Core 19 Spare

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 5 of 5
OWNER: UPPTCL
CLIENT: GEPDEC
CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY105BC

ESTIMATED  ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. LENGTH (in  LENGTH   CORE TO ‐ EQUIP. REF. DWG. TO (TERM. NO.) FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. (TERM. NO.)
mts) (in mts)

Control Cable in Switchyard

105‐CT INTERPOLE CABLING
1 132 kV 105 within swyd  1‐105‐1‐001 1 Cu./Amr. PVC 105‐RCT Core.‐5 105‐CT JB 5CX2.5 10 Core 1 5US1 5US1 105‐CT JB‐5US1 / 5US1 105‐RCT Core.‐5‐5US1/5US1 CORE‐5
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐RCT Core.‐5 105‐CT JB Core 2 5US2 5US2 105‐CT JB‐5US2 / 5US2 105‐RCT Core.‐5‐5US2/5US2 87BB : Busbar Protection
132 kV 105 105‐RCT Core.‐5 105‐CT JB Core 3 5US3 5US3 105‐CT JB‐5US3 / 5US3 105‐RCT Core.‐5‐5US3/5US3
132 kV 105 105‐RCT Core.‐5 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐RCT Core.‐5‐Spare/Spare
132 kV 105 105‐RCT Core.‐5 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐RCT Core.‐5‐Spare/Spare

2 132 kV 105 within swyd  1‐105‐1‐002 1 Cu./Amr. PVC 105‐YCT Core.‐5 105‐CT JB 5CX2.5 10 Core 1 5VS1 5VS1 105‐CT JB‐5VS1 / 5VS1 105‐YCT Core.‐5‐5VS1/5VS1 CORE‐5
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐YCT Core.‐5 105‐CT JB Core 2 5VS2 5VS2 105‐CT JB‐5VS2 / 5VS2 105‐YCT Core.‐5‐5VS2/5VS2 87BB : Busbar Protection
132 kV 105 105‐YCT Core.‐5 105‐CT JB Core 3 5VS3 5VS3 105‐CT JB‐5VS3 / 5VS3 105‐YCT Core.‐5‐5VS3/5VS3
132 kV 105 105‐YCT Core.‐5 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐YCT Core.‐5‐Spare/Spare
132 kV 105 105‐YCT Core.‐5 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐YCT Core.‐5‐Spare/Spare

3 132 kV 105 within swyd  1‐105‐1‐003 1 Cu./Amr. PVC 105‐BCT Core.‐5 105‐CT JB 5CX2.5 10 Core 1 5WS1 5WS1 105‐CT JB‐5WS1 / 5WS1 105‐BCT Core.‐5‐5WS1/5WS1 CORE‐5
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐BCT Core.‐5 105‐CT JB Core 2 5WS2 5WS2 105‐CT JB‐5WS2 / 5WS2 105‐BCT Core.‐5‐5WS2/5WS2 87BB : Busbar Protection
132 kV 105 105‐BCT Core.‐5 105‐CT JB Core 3 5WS3 5WS3 105‐CT JB‐5WS3 / 5WS3 105‐BCT Core.‐5‐5WS3/5WS3
132 kV 105 105‐BCT Core.‐5 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐BCT Core.‐5‐Spare/Spare
132 kV 105 105‐BCT Core.‐5 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐BCT Core.‐5‐Spare/Spare

4 132 kV 105 within swyd  1‐105‐1‐004 1 Cu./Amr. PVC 105‐RCT Core.‐2 105‐CT JB 5CX2.5 10 Core 1 2US1 2US1 105‐CT JB‐2US1 / 2US1 105‐RCT Core.‐2‐2US1/2US1 CORE‐2
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐RCT Core.‐2 105‐CT JB Core 2 2US2 2US2 105‐CT JB‐2US2 / 2US2 105‐RCT Core.‐2‐2US2/2US2 67 : Direc. O/c, E/f  & LBB Relay
132 kV 105 105‐RCT Core.‐2 105‐CT JB Core 3 2US3 2US3 105‐CT JB‐2US3 / 2US3 105‐RCT Core.‐2‐2US3/2US3
132 kV 105 105‐RCT Core.‐2 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐RCT Core.‐2‐Spare/Spare
132 kV 105 105‐RCT Core.‐2 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐RCT Core.‐2‐Spare/Spare

5 132 kV 105 within swyd  1‐105‐1‐005 1 Cu./Amr. PVC 105‐YCT Core.‐2 105‐CT JB 5CX2.5 10 Core 1 2VS1 2VS1 105‐CT JB‐2VS1 / 2VS1 105‐YCT Core.‐2‐2VS1/2VS1 CORE‐2
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐YCT Core.‐2 105‐CT JB Core 2 2VS2 2VS2 105‐CT JB‐2VS2 / 2VS2 105‐YCT Core.‐2‐2VS2/2VS2 67 : Direc. O/c, E/f  & LBB Relay
132 kV 105 105‐YCT Core.‐2 105‐CT JB Core 3 2VS3 2VS3 105‐CT JB‐2VS3 / 2VS3 105‐YCT Core.‐2‐2VS3/2VS3
132 kV 105 105‐YCT Core.‐2 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐YCT Core.‐2‐Spare/Spare
132 kV 105 105‐YCT Core.‐2 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐YCT Core.‐2‐Spare/Spare

6 132 kV 105 within swyd  1‐105‐1‐006 1 Cu./Amr. PVC 105‐BCT Core.‐2 105‐CT JB 5CX2.5 10 Core 1 2WS1 2WS1 105‐CT JB‐2WS1 / 2WS1 105‐BCT Core.‐2‐2WS1/2WS1 CORE‐2
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐BCT Core.‐2 105‐CT JB Core 2 2WS2 2WS2 105‐CT JB‐2WS2 / 2WS2 105‐BCT Core.‐2‐2WS2/2WS2 67 : Direc. O/c, E/f  & LBB Relay
132 kV 105 105‐BCT Core.‐2 105‐CT JB Core 3 2WS3 2WS3 105‐CT JB‐2WS3 / 2WS3 105‐BCT Core.‐2‐2WS3/2WS3
132 kV 105 105‐BCT Core.‐2 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐BCT Core.‐2‐Spare/Spare
132 kV 105 105‐BCT Core.‐2 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐BCT Core.‐2‐Spare/Spare

7 132 kV 105 within swyd  1‐105‐1‐007 1 Cu./Amr. PVC 105‐RCT Core.‐1 105‐CT JB 5CX2.5 10 Core 1 1US1 1US1 105‐CT JB‐1US1 / 1US1 105‐RCT Core.‐1‐1US1/1US1 CORE‐1
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐RCT Core.‐1 105‐CT JB Core 2 1US2 1US2 105‐CT JB‐1US2 / 1US2 105‐RCT Core.‐1‐1US2/1US2 SPARE
132 kV 105 105‐RCT Core.‐1 105‐CT JB Core 3 1US3 1US3 105‐CT JB‐1US3 / 1US3 105‐RCT Core.‐1‐1US3/1US3
132 kV 105 105‐RCT Core.‐1 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐RCT Core.‐1‐Spare/Spare
132 kV 105 105‐RCT Core.‐1 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐RCT Core.‐1‐Spare/Spare

8 132 kV 105 within swyd  1‐105‐1‐008 1 Cu./Amr. PVC 105‐YCT Core.‐1 105‐CT JB 5CX2.5 10 Core 1 1VS1 1VS1 105‐CT JB‐1VS1 / 1VS1 105‐YCT Core.‐1‐1VS1/1VS1 CORE‐1
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐YCT Core.‐1 105‐CT JB Core 2 1VS2 1VS2 105‐CT JB‐1VS2 / 1VS2 105‐YCT Core.‐1‐1VS2/1VS2 SPARE
132 kV 105 105‐YCT Core.‐1 105‐CT JB Core 3 1VS3 1VS3 105‐CT JB‐1VS3 / 1VS3 105‐YCT Core.‐1‐1VS3/1VS3
132 kV 105 105‐YCT Core.‐1 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐YCT Core.‐1‐Spare/Spare
132 kV 105 105‐YCT Core.‐1 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐YCT Core.‐1‐Spare/Spare

9 132 kV 105 within swyd  1‐105‐1‐009 1 Cu./Amr. PVC 105‐BCT Core.‐1 105‐CT JB 5CX2.5 10 Core 1 1WS1 1WS1 105‐CT JB‐1WS1 / 1WS1 105‐BCT Core.‐1‐1WS1/1WS1 CORE‐1
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐BCT Core.‐1 105‐CT JB Core 2 1WS2 1WS2 105‐CT JB‐1WS2 / 1WS2 105‐BCT Core.‐1‐1WS2/1WS2 SPARE
132 kV 105 105‐BCT Core.‐1 105‐CT JB Core 3 1WS3 1WS3 105‐CT JB‐1WS3 / 1WS3 105‐BCT Core.‐1‐1WS3/1WS3
132 kV 105 105‐BCT Core.‐1 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐BCT Core.‐1‐Spare/Spare
132 kV 105 105‐BCT Core.‐1 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐BCT Core.‐1‐Spare/Spare

10 132 kV 105 within swyd  1‐105‐1‐010 1 Cu./Amr. PVC 105‐RCT Core.‐3 105‐CT JB 5CX2.5 10 Core 1 3US1 3US1 105‐CT JB‐3US1 / 3US1 105‐RCT Core.‐3‐3US1/3US1 CORE‐3
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐RCT Core.‐3 105‐CT JB Core 2 3US2 3US2 105‐CT JB‐3US2 / 3US2 105‐RCT Core.‐3‐3US2/3US2 BCU: Bay Control& Protection Unit
132 kV 105 105‐RCT Core.‐3 105‐CT JB Core 3 3US3 3US3 105‐CT JB‐3US3 / 3US3 105‐RCT Core.‐3‐3US3/3US3
132 kV 105 105‐RCT Core.‐3 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐RCT Core.‐3‐Spare/Spare
132 kV 105 105‐RCT Core.‐3 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐RCT Core.‐3‐Spare/Spare

11 132 kV 105 within swyd  1‐105‐1‐011 1 Cu./Amr. PVC 105‐YCT Core.‐3 105‐CT JB 5CX2.5 10 Core 1 3VS1 3VS1 105‐CT JB‐3VS1 / 3VS1 105‐YCT Core.‐3‐3VS1/3VS1 CORE‐3
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐YCT Core.‐3 105‐CT JB Core 2 3VS2 3VS2 105‐CT JB‐3VS2 / 3VS2 105‐YCT Core.‐3‐3VS2/3VS2 BCU: Bay Control& Protection Unit
132 kV 105 105‐YCT Core.‐3 105‐CT JB Core 3 3VS3 3VS3 105‐CT JB‐3VS3 / 3VS3 105‐YCT Core.‐3‐3VS3/3VS3
132 kV 105 105‐YCT Core.‐3 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐YCT Core.‐3‐Spare/Spare
132 kV 105 105‐YCT Core.‐3 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐YCT Core.‐3‐Spare/Spare

12 132 kV 105 within swyd  1‐105‐1‐012 1 Cu./Amr. PVC 105‐BCT Core.‐3 105‐CT JB 5CX2.5 10 Core 1 3WS1 3WS1 105‐CT JB‐3WS1 / 3WS1 105‐BCT Core.‐3‐3WS1/3WS1 CORE‐3
GD/JAUNPUR/GAL/0058 ASPL/UPPCL/20415
132 kV 105 105‐BCT Core.‐3 105‐CT JB Core 2 3WS2 3WS2 105‐CT JB‐3WS2 / 3WS2 105‐BCT Core.‐3‐3WS2/3WS2 BCU: Bay Control& Protection Unit
132 kV 105 105‐BCT Core.‐3 105‐CT JB Core 3 3WS3 3WS3 105‐CT JB‐3WS3 / 3WS3 105‐BCT Core.‐3‐3WS3/3WS3
132 kV 105 105‐BCT Core.‐3 105‐CT JB Core 4 Spare Spare 105‐CT JB‐Spare / Spare 105‐BCT Core.‐3‐Spare/Spare
132 kV 105 105‐BCT Core.‐3 105‐CT JB Core 5 Spare Spare 105‐CT JB‐Spare / Spare 105‐BCT Core.‐3‐Spare/Spare

105‐BUS‐1 PT CABLING
13 132 kV 105 within swyd  1‐105‐1‐013 1 Cu./Amr. PVC 100BB1‐RCVT Core.‐1 100BB1‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB1‐1 100BB1‐CVT JB‐TB1‐1 / R‐1a 100BB1‐RCVT Core.‐1‐R‐1a/TB1‐1 Core‐1
ASPL/UPPCL/20415U
132 kV 105 100BB1‐RCVT Core.‐1 100BB1‐CVT JB Core 2 100 R‐1n TB1‐3 100BB1‐CVT JB‐TB1‐3 / R‐1n 100BB1‐RCVT Core.‐1‐R‐1n/TB1‐3 Distance Main‐1 Protection Relay
132 kV 105 100BB1‐RCVT Core.‐1 100BB1‐CVT JB Core 3 SPARE TB1‐5 100BB1‐CVT JB‐TB1‐5 / SPARE 100BB1‐RCVT Core.‐1‐SPARE/TB1‐5 67/67N : O/c & E/f Relay

14 132 kV 105 within swyd  1‐105‐1‐014 1 Cu./Amr. PVC 100BB1‐YCVT Core.‐1 100BB1‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB1‐8 100BB1‐CVT JB‐TB1‐8 / Y‐1a 100BB1‐YCVT Core.‐1‐Y‐1a/TB1‐8 Core‐1
ASPL/UPPCL/20415U
132 kV 105 100BB1‐YCVT Core.‐1 100BB1‐CVT JB Core 2 100 Y‐1n TB1‐10 100BB1‐CVT JB‐TB1‐10 / Y‐1n 100BB1‐YCVT Core.‐1‐Y‐1n/TB1‐10 Distance Main‐1 Protection Relay

DOCUMENT NUMBER: PE‐2021‐01‐C‐S001
REV:B 1 of 5
OWNER: UPPTCL
CLIENT: GEPDEC
CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY105BC

ESTIMATED  ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. LENGTH (in  LENGTH   CORE TO ‐ EQUIP. REF. DWG. TO (TERM. NO.) FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. (TERM. NO.)
mts) (in mts)
132 kV 105 100BB1‐YCVT Core.‐1 100BB1‐CVT JB Core 3 SPARE TB1‐12 100BB1‐CVT JB‐TB1‐12 / SPARE 100BB1‐YCVT Core.‐1‐SPARE/TB1‐12 67/67N : O/c & E/f Relay

15 132 kV 105 within swyd  1‐105‐1‐015 1 Cu./Amr. PVC 100BB1‐BCVT Core.‐1 100BB1‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB1‐15 100BB1‐CVT JB‐TB1‐15 / B‐1a 100BB1‐BCVT Core.‐1‐B‐1a/TB1‐15 Core‐1
ASPL/UPPCL/20415U
132 kV 105 100BB1‐BCVT Core.‐1 100BB1‐CVT JB Core 2 100 B‐1n TB1‐17 100BB1‐CVT JB‐TB1‐17 / B‐1n 100BB1‐BCVT Core.‐1‐B‐1n/TB1‐17 Distance Main‐1 Protection Relay
132 kV 105 100BB1‐BCVT Core.‐1 100BB1‐CVT JB Core 3 SPARE TB1‐19 100BB1‐CVT JB‐TB1‐19 / SPARE 100BB1‐BCVT Core.‐1‐SPARE/TB1‐19 67/67N : O/c & E/f Relay

16 132 kV 105 within swyd  1‐105‐1‐016 1 Cu./Amr. PVC 100BB1‐RCVT Core.‐2 100BB1‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB2‐1 100BB1‐CVT JB‐TB2‐1 / R‐1a 100BB1‐RCVT Core.‐2‐R‐1a/TB2‐1 Core‐2
ASPL/UPPCL/20415U
132 kV 105 100BB1‐RCVT Core.‐2 100BB1‐CVT JB Core 2 100 R‐1n TB2‐3 100BB1‐CVT JB‐TB2‐3 / R‐1n 100BB1‐RCVT Core.‐2‐R‐1n/TB2‐3 Spare
132 kV 105 100BB1‐RCVT Core.‐2 100BB1‐CVT JB Core 3 SPARE TB2‐5 100BB1‐CVT JB‐TB2‐5 / SPARE 100BB1‐RCVT Core.‐2‐SPARE/TB2‐5

17 132 kV 105 within swyd  1‐105‐1‐017 1 Cu./Amr. PVC 100BB1‐YCVT Core.‐2 100BB1‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB2‐8 100BB1‐CVT JB‐TB2‐8 / Y‐1a 100BB1‐YCVT Core.‐2‐Y‐1a/TB2‐8 Core‐2
ASPL/UPPCL/20415U
132 kV 105 100BB1‐YCVT Core.‐2 100BB1‐CVT JB Core 2 100 Y‐1n TB2‐10 100BB1‐CVT JB‐TB2‐10 / Y‐1n 100BB1‐YCVT Core.‐2‐Y‐1n/TB2‐10 Spare
132 kV 105 100BB1‐YCVT Core.‐2 100BB1‐CVT JB Core 3 SPARE TB2‐12 100BB1‐CVT JB‐TB2‐12 / SPARE 100BB1‐YCVT Core.‐2‐SPARE/TB2‐12

18 132 kV 105 within swyd  1‐105‐1‐018 1 Cu./Amr. PVC 100BB1‐BCVT Core.‐2 100BB1‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB2‐15 100BB1‐CVT JB‐TB2‐15 / B‐1a 100BB1‐BCVT Core.‐2‐B‐1a/TB2‐15 Core‐2
ASPL/UPPCL/20415U
132 kV 105 100BB1‐BCVT Core.‐2 100BB1‐CVT JB Core 2 100 B‐1n TB2‐17 100BB1‐CVT JB‐TB2‐17 / B‐1n 100BB1‐BCVT Core.‐2‐B‐1n/TB2‐17 Spare
132 kV 105 100BB1‐BCVT Core.‐2 100BB1‐CVT JB Core 3 SPARE TB2‐19 100BB1‐CVT JB‐TB2‐19 / SPARE 100BB1‐BCVT Core.‐2‐SPARE/TB2‐19

19 132 kV 105 within swyd  1‐105‐1‐019 1 Cu./Amr. PVC 100BB1‐RCVT Core.‐3 100BB1‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB3‐1 100BB1‐CVT JB‐TB3‐1 / R‐1a 100BB1‐RCVT Core.‐3‐R‐1a/TB3‐1 Core‐3
ASPL/UPPCL/20415U
132 kV 105 100BB1‐RCVT Core.‐3 100BB1‐CVT JB Core 2 100 R‐1n TB3‐3 100BB1‐CVT JB‐TB3‐3 / R‐1n 100BB1‐RCVT Core.‐3‐R‐1n/TB3‐3 Metering
132 kV 105 100BB1‐RCVT Core.‐3 100BB1‐CVT JB Core 3 SPARE TB3‐5 100BB1‐CVT JB‐TB3‐5 / SPARE 100BB1‐RCVT Core.‐3‐SPARE/TB3‐5

20 132 kV 105 within swyd  1‐105‐1‐020 1 Cu./Amr. PVC 100BB1‐YCVT Core.‐3 100BB1‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB3‐8 100BB1‐CVT JB‐TB3‐8 / Y‐1a 100BB1‐YCVT Core.‐3‐Y‐1a/TB3‐8 Core‐3
ASPL/UPPCL/20415U
132 kV 105 100BB1‐YCVT Core.‐3 100BB1‐CVT JB Core 2 100 Y‐1n TB3‐10 100BB1‐CVT JB‐TB3‐10 / Y‐1n 100BB1‐YCVT Core.‐3‐Y‐1n/TB3‐10 Metering
132 kV 105 100BB1‐YCVT Core.‐3 100BB1‐CVT JB Core 3 SPARE TB3‐12 100BB1‐CVT JB‐TB3‐12 / SPARE 100BB1‐YCVT Core.‐3‐SPARE/TB3‐12

21 132 kV 105 within swyd  1‐105‐1‐021 1 Cu./Amr. PVC 100BB1‐BCVT Core.‐3 100BB1‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB3‐15 100BB1‐CVT JB‐TB3‐15 / B‐1a 100BB1‐BCVT Core.‐3‐B‐1a/TB3‐15 Core‐3
ASPL/UPPCL/20415U
132 kV 105 100BB1‐BCVT Core.‐3 100BB1‐CVT JB Core 2 100 B‐1n TB3‐17 100BB1‐CVT JB‐TB3‐17 / B‐1n 100BB1‐BCVT Core.‐3‐B‐1n/TB3‐17 Metering
132 kV 105 100BB1‐BCVT Core.‐3 100BB1‐CVT JB Core 3 SPARE TB3‐19 100BB1‐CVT JB‐TB3‐19 / SPARE 100BB1‐BCVT Core.‐3‐SPARE/TB3‐19

105‐BUS‐2 PT CABLING
22 132 kV 105 within swyd  1‐105‐1‐022 1 Cu./Amr. PVC 100BB2‐RCVT Core.‐1 100BB2‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB1‐1 100BB2‐CVT JB‐TB1‐1 / R‐1a 100BB2‐RCVT Core.‐1‐R‐1a/TB1‐1 Core‐1
ASPL/UPPCL/20415U
132 kV 105 100BB2‐RCVT Core.‐1 100BB2‐CVT JB Core 2 100 R‐1n TB1‐3 100BB2‐CVT JB‐TB1‐3 / R‐1n 100BB2‐RCVT Core.‐1‐R‐1n/TB1‐3 Distance Main‐1 Protection Relay
132 kV 105 100BB2‐RCVT Core.‐1 100BB2‐CVT JB Core 3 SPARE TB1‐5 100BB2‐CVT JB‐TB1‐5 / SPARE 100BB2‐RCVT Core.‐1‐SPARE/TB1‐5 67/67N : O/c & E/f Relay

23 132 kV 105 within swyd  1‐105‐1‐023 1 Cu./Amr. PVC 100BB2‐YCVT Core.‐1 100BB2‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB1‐8 100BB2‐CVT JB‐TB1‐8 / Y‐1a 100BB2‐YCVT Core.‐1‐Y‐1a/TB1‐8 Core‐1
ASPL/UPPCL/20415U
132 kV 105 100BB2‐YCVT Core.‐1 100BB2‐CVT JB Core 2 100 Y‐1n TB1‐10 100BB2‐CVT JB‐TB1‐10 / Y‐1n 100BB2‐YCVT Core.‐1‐Y‐1n/TB1‐10 Distance Main‐1 Protection Relay
132 kV 105 100BB2‐YCVT Core.‐1 100BB2‐CVT JB Core 3 SPARE TB1‐12 100BB2‐CVT JB‐TB1‐12 / SPARE 100BB2‐YCVT Core.‐1‐SPARE/TB1‐12 67/67N : O/c & E/f Relay

24 132 kV 105 within swyd  1‐105‐1‐024 1 Cu./Amr. PVC 100BB2‐BCVT Core.‐1 100BB2‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB1‐15 100BB2‐CVT JB‐TB1‐15 / B‐1a 100BB2‐BCVT Core.‐1‐B‐1a/TB1‐15 Core‐1
ASPL/UPPCL/20415U
132 kV 105 100BB2‐BCVT Core.‐1 100BB2‐CVT JB Core 2 100 B‐1n TB1‐17 100BB2‐CVT JB‐TB1‐17 / B‐1n 100BB2‐BCVT Core.‐1‐B‐1n/TB1‐17 Distance Main‐1 Protection Relay
132 kV 105 100BB2‐BCVT Core.‐1 100BB2‐CVT JB Core 3 SPARE TB1‐19 100BB2‐CVT JB‐TB1‐19 / SPARE 100BB2‐BCVT Core.‐1‐SPARE/TB1‐19 67/67N : O/c & E/f Relay

25 132 kV 105 within swyd  1‐105‐1‐025 1 Cu./Amr. PVC 100BB2‐RCVT Core.‐2 100BB2‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB2‐1 100BB2‐CVT JB‐TB2‐1 / R‐1a 100BB2‐RCVT Core.‐2‐R‐1a/TB2‐1 Core‐2
ASPL/UPPCL/20415U
132 kV 105 100BB2‐RCVT Core.‐2 100BB2‐CVT JB Core 2 100 R‐1n TB2‐3 100BB2‐CVT JB‐TB2‐3 / R‐1n 100BB2‐RCVT Core.‐2‐R‐1n/TB2‐3 Spare
132 kV 105 100BB2‐RCVT Core.‐2 100BB2‐CVT JB Core 3 SPARE TB2‐5 100BB2‐CVT JB‐TB2‐5 / SPARE 100BB2‐RCVT Core.‐2‐SPARE/TB2‐5

26 132 kV 105 within swyd  1‐105‐1‐026 1 Cu./Amr. PVC 100BB2‐YCVT Core.‐2 100BB2‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB2‐8 100BB2‐CVT JB‐TB2‐8 / Y‐1a 100BB2‐YCVT Core.‐2‐Y‐1a/TB2‐8 Core‐2
ASPL/UPPCL/20415U
132 kV 105 100BB2‐YCVT Core.‐2 100BB2‐CVT JB Core 2 100 Y‐1n TB2‐10 100BB2‐CVT JB‐TB2‐10 / Y‐1n 100BB2‐YCVT Core.‐2‐Y‐1n/TB2‐10 Spare
132 kV 105 100BB2‐YCVT Core.‐2 100BB2‐CVT JB Core 3 SPARE TB2‐12 100BB2‐CVT JB‐TB2‐12 / SPARE 100BB2‐YCVT Core.‐2‐SPARE/TB2‐12

27 132 kV 105 within swyd  1‐105‐1‐027 1 Cu./Amr. PVC 100BB2‐BCVT Core.‐2 100BB2‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB2‐15 100BB2‐CVT JB‐TB2‐15 / B‐1a 100BB2‐BCVT Core.‐2‐B‐1a/TB2‐15 Core‐2
ASPL/UPPCL/20415U
132 kV 105 100BB2‐BCVT Core.‐2 100BB2‐CVT JB Core 2 100 B‐1n TB2‐17 100BB2‐CVT JB‐TB2‐17 / B‐1n 100BB2‐BCVT Core.‐2‐B‐1n/TB2‐17 Spare
132 kV 105 100BB2‐BCVT Core.‐2 100BB2‐CVT JB Core 3 SPARE TB2‐19 100BB2‐CVT JB‐TB2‐19 / SPARE 100BB2‐BCVT Core.‐2‐SPARE/TB2‐19

28 132 kV 105 within swyd  1‐105‐1‐028 1 Cu./Amr. PVC 100BB2‐RCVT Core.‐3 100BB2‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ R‐1a TB3‐1 100BB2‐CVT JB‐TB3‐1 / R‐1a 100BB2‐RCVT Core.‐3‐R‐1a/TB3‐1 Core‐3
ASPL/UPPCL/20415U
132 kV 105 100BB2‐RCVT Core.‐3 100BB2‐CVT JB Core 2 100 R‐1n TB3‐3 100BB2‐CVT JB‐TB3‐3 / R‐1n 100BB2‐RCVT Core.‐3‐R‐1n/TB3‐3 Metering
132 kV 105 100BB2‐RCVT Core.‐3 100BB2‐CVT JB Core 3 SPARE TB3‐5 100BB2‐CVT JB‐TB3‐5 / SPARE 100BB2‐RCVT Core.‐3‐SPARE/TB3‐5

29 132 kV 105 within swyd  1‐105‐1‐029 1 Cu./Amr. PVC 100BB2‐YCVT Core.‐3 100BB2‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ Y‐1a TB3‐8 100BB2‐CVT JB‐TB3‐8 / Y‐1a 100BB2‐YCVT Core.‐3‐Y‐1a/TB3‐8 Core‐3
ASPL/UPPCL/20415U
132 kV 105 100BB2‐YCVT Core.‐3 100BB2‐CVT JB Core 2 100 Y‐1n TB3‐10 100BB2‐CVT JB‐TB3‐10 / Y‐1n 100BB2‐YCVT Core.‐3‐Y‐1n/TB3‐10 Metering
132 kV 105 100BB2‐YCVT Core.‐3 100BB2‐CVT JB Core 3 SPARE TB3‐12 100BB2‐CVT JB‐TB3‐12 / SPARE 100BB2‐YCVT Core.‐3‐SPARE/TB3‐12

30 132 kV 105 within swyd  1‐105‐1‐030 1 Cu./Amr. PVC 100BB2‐BCVT Core.‐3 100BB2‐CVT JB 3Cx2.5 10 Core 1 G71AIN‐IA202‐N1171‐ B‐1a TB3‐15 100BB2‐CVT JB‐TB3‐15 / B‐1a 100BB2‐BCVT Core.‐3‐B‐1a/TB3‐15 Core‐3
ASPL/UPPCL/20415U
132 kV 105 100BB2‐BCVT Core.‐3 100BB2‐CVT JB Core 2 100 B‐1n TB3‐17 100BB2‐CVT JB‐TB3‐17 / B‐1n 100BB2‐BCVT Core.‐3‐B‐1n/TB3‐17 Metering
132 kV 105 100BB2‐BCVT Core.‐3 100BB2‐CVT JB Core 3 SPARE TB3‐19 100BB2‐CVT JB‐TB3‐19 / SPARE 100BB2‐BCVT Core.‐3‐SPARE/TB3‐19

Control Cable from Switchyard to Panel
105‐CIRCUIT BREAKER CABLING TO PANEL
31 132 kV 105 swyd  to control bldg. 1‐105‐2‐031 1 Cu./Amr. PVC 105‐52  105 CRP 27CX2.5 52 Core 1 G719EA‐MG9031‐00‐ X1LA‐9 G719EA‐MG9031‐00‐ X:CB‐18 105 CRP‐X:CB‐18 / X1LA‐9 105‐52 ‐X1LA‐9/X:CB‐18 Common
132 kV 105 105‐52  105 CRP Core 2 W105, Sh‐21 of 40 X1LC‐10 W105, Sh‐21 of 40 X:CB‐19 105 CRP‐X:CB‐19 / X1LC‐10 105‐52 ‐X1LC‐10/X:CB‐19 CB Open
132 kV 105 105‐52  105 CRP Core 3 G719EA‐MG9031‐00‐ X1LA‐5 G719EA‐MG9031‐00‐ X:CB‐1 105 CRP‐X:CB‐1 / X1LA‐5 105‐52 ‐X1LA‐5/X:CB‐1 Common
132 kV 105 105‐52  105 CRP Core 4 W105, Sh‐23 of 40 X1LC‐6 W105, Sh‐23 of 40 X:CB‐2 105 CRP‐X:CB‐2 / X1LC‐6 105‐52 ‐X1LC‐6/X:CB‐2 CB Open
132 kV 105 105‐52  105 CRP Core 5 X1LC‐4 X:CB‐3 105 CRP‐X:CB‐3 / X1LC‐4 105‐52 ‐X1LC‐4/X:CB‐3 CB Close
132 kV 105 105‐52  105 CRP Core 6 G719EA‐MG9031‐00‐ X1‐95 G719EA‐MG9031‐00‐ X:CB‐4 105 CRP‐X:CB‐4 / X1‐95 105‐52 ‐X1‐95/X:CB‐4 POLE DISCREPANCY ALARM
132 kV 105 105‐52  105 CRP Core 7 W105, Sh‐24 of 40 X1‐85 W105, Sh‐24 of 40 X:CB‐5 105 CRP‐X:CB‐5 / X1‐85 105‐52 ‐X1‐85/X:CB‐5 LOSS OF SF6
132 kV 105 105‐52  105 CRP Core 8 X1‐87 X:CB‐6 105 CRP‐X:CB‐6 / X1‐87 105‐52 ‐X1‐87/X:CB‐6 General Lockout SF6
132 kV 105 105‐52  105 CRP Core 9 X1‐52 X:CB‐7 105 CRP‐X:CB‐7 / X1‐52 105‐52 ‐X1‐52/X:CB‐7 DC Supply 1&2 Monitor
132 kV 105 105‐52  105 CRP Core 10 X1‐98 X:CB‐8 105 CRP‐X:CB‐8 / X1‐98 105‐52 ‐X1‐98/X:CB‐8 CB Remote Indication
132 kV 105 105‐52  105 CRP Core 11 X1‐100 X:CB‐9 105 CRP‐X:CB‐9 / X1‐100 105‐52 ‐X1‐100/X:CB‐9 Spring Status
132 kV 105 105‐52  105 CRP Core 12 G719EA‐MG9031‐00‐ X G719EA‐MG9031‐00‐ X:CT1‐3 105 CRP‐X:CT1‐3 / X 105‐52 ‐X/X:CT1‐3 Common
132 kV 105 105‐52  105 CRP Core 13 W105, Sh‐29 of 40 X1‐16 W105, Sh‐29 of 40 X 105 CRP‐X / X1‐16 105‐52 ‐X1‐16/X Common
132 kV 105 105‐52  105 CRP Core 14 TB‐XX XCB‐22 105 CRP‐XCB‐22 / TB‐XX 105‐52 ‐TB‐XX/XCB‐22 DC Supply (+)Ve

DOCUMENT NUMBER: PE‐2021‐01‐C‐S001
REV:B 2 of 5
OWNER: UPPTCL
CLIENT: GEPDEC
CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY105BC

ESTIMATED  ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. LENGTH (in  LENGTH   CORE TO ‐ EQUIP. REF. DWG. TO (TERM. NO.) FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. (TERM. NO.)
mts) (in mts)
132 kV 105 105‐52  105 CRP Core 15 TB‐XX XCB‐23 105 CRP‐XCB‐23 / TB‐XX 105‐52 ‐TB‐XX/XCB‐23 DC Supply (‐)Ve
132 kV 105 105‐52  105 CRP Core 16 TB‐XX XCB‐24 105 CRP‐XCB‐24 / TB‐XX 105‐52 ‐TB‐XX/XCB‐24 Common
132 kV 105 105‐52  105 CRP Core 17 TB‐XX XCB‐25 105 CRP‐XCB‐25 / TB‐XX 105‐52 ‐TB‐XX/XCB‐25 Protection Trip‐1
132 kV 105 105‐52  105 CRP Core 18 TB‐XX XCB‐26 105 CRP‐XCB‐26 / TB‐XX 105‐52 ‐TB‐XX/XCB‐26 Post Close TC‐1 Supervision
132 kV 105 105‐52  105 CRP Core 19 TB‐XX XCB‐27 105 CRP‐XCB‐27 / TB‐XX 105‐52 ‐TB‐XX/XCB‐27 Pre Close TC‐1 Supervision 
132 kV 105 105‐52  105 CRP Core 20 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 21 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 22 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 23 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 24 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 25 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 26 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 27 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE

32 132 kV 105 swyd  to control bldg. 1‐105‐2‐032 1 Cu./Amr. PVC 105‐52  105 CRP 27CX2.5 52 Core 1 G719EA‐MG9031‐00‐ TB‐XX G719EA‐MG9031‐00‐ X‐CB‐28 105 CRP‐X‐CB‐28 / TB‐XX 105‐52 ‐TB‐XX/X‐CB‐28 DC Supply (+)Ve
132 kV 105 105‐52  105 CRP Core 2 W105, Sh‐30 of 40 TB‐XX W105, Sh‐30 of 40 X‐CB‐29 105 CRP‐X‐CB‐29 / TB‐XX 105‐52 ‐TB‐XX/X‐CB‐29 DC Supply (‐)Ve
132 kV 105 105‐52  105 CRP Core 3 TB‐XX X‐CB‐30 105 CRP‐X‐CB‐30 / TB‐XX 105‐52 ‐TB‐XX/X‐CB‐30 Common
132 kV 105 105‐52  105 CRP Core 4 TB‐XX X‐CB‐31 105 CRP‐X‐CB‐31 / TB‐XX 105‐52 ‐TB‐XX/X‐CB‐31 Protection Trip‐2 
132 kV 105 105‐52  105 CRP Core 5 TB‐XX X‐CB‐32 105 CRP‐X‐CB‐32 / TB‐XX 105‐52 ‐TB‐XX/X‐CB‐32 Post Close TC‐2 Supervision 
132 kV 105 105‐52  105 CRP Core 6 TB‐XX X‐CB‐33 105 CRP‐X‐CB‐33 / TB‐XX 105‐52 ‐TB‐XX/X‐CB‐33 Pre Close TC‐2 Supervision
132 kV 105 105‐52  105 CRP Core 7 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 8 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 9 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 10 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 11 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 12 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 13 SPARE SPARE 105 CRP‐SPARE / SPARE 105‐52 ‐SPARE/SPARE
132 kV 105 105‐52  105 CRP Core 14 G719EA‐MG9031‐00‐ X1:68 G719EA‐MG9031‐00‐ X:CB‐10 105 CRP‐X:CB‐10 / X1:68 105‐52 ‐X1:68/X:CB‐10 Common
132 kV 105 105‐52  105 CRP Core 15 W105, Sh‐31 of 40 X1:69 W105, Sh‐31 of 40 X:CB‐11 105 CRP‐X:CB‐11 / X1:69 105‐52 ‐X1:69/X:CB‐11 CB Closing I/L permissible
132 kV 105 105‐52  105 CRP Core 16 X1:64 X:CB‐12 105 CRP‐X:CB‐12 / X1:64 105‐52 ‐X1:64/X:CB‐12 Common
132 kV 105 105‐52  105 CRP Core 17 X1:65 X:CB‐13 105 CRP‐X:CB‐13 / X1:65 105‐52 ‐X1:65/X:CB‐13 Remote Close
132 kV 105 105‐52  105 CRP Core 18 X1:9 X:CB‐14 105 CRP‐X:CB‐14 / X1:9 105‐52 ‐X1:9/X:CB‐14 Common
132 kV 105 105‐52  105 CRP Core 19 X1:10 X:CB‐15 105 CRP‐X:CB‐15 / X1:10 105‐52 ‐X1:10/X:CB‐15 Remote Trip‐1
132 kV 105 105‐52  105 CRP Core 20 X1:42 X:CB‐16 105 CRP‐X:CB‐16 / X1:42 105‐52 ‐X1:42/X:CB‐16 Common
132 kV 105 105‐52  105 CRP Core 21 X1:43 X:CB‐17 105 CRP‐X:CB‐17 / X1:43 105‐52 ‐X1:43/X:CB‐17 Remote Trip‐2
132 kV 105 105‐52  105 CRP Core 22 SPARE
132 kV 105 105‐52  105 CRP Core 23 SPARE
132 kV 105 105‐52  105 CRP Core 24 SPARE
132 kV 105 105‐52  105 CRP Core 25 SPARE
132 kV 105 105‐52  105 CRP Core 26 SPARE
132 kV 105 105‐52  105 CRP Core 27 SPARE

105‐ISOLATOR CABLING TO PANEL
33 132 kV 105 swyd  to control bldg. 1‐105‐2‐033 1 Cu./Amr. PVC 105‐89A  105 CRP 14CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB1‐107 G719EA‐MG9031‐00‐ X:ISA‐11 105 CRP‐X:ISA‐11 / TB1‐107 105‐89A ‐TB1‐107/X:ISA‐11 Common
132 kV 105 105‐89A  105 CRP Core 2 W105, Sh‐21 of 40 TB1‐108 W105, Sh‐21 of 40 X:ISA‐12 105 CRP‐X:ISA‐12 / TB1‐108 105‐89A ‐TB1‐108/X:ISA‐12 Isolator 89A Open
132 kV 105 105‐89A  105 CRP Core 3 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:ISA‐6 105 CRP‐X:ISA‐6 / TB1‐103 105‐89A ‐TB1‐103/X:ISA‐6 Common
132 kV 105 105‐89A  105 CRP Core 4 W105, Sh‐23 of 40 TB1‐104 W105, Sh‐23 of 40 X:ISA‐7 105 CRP‐X:ISA‐7 / TB1‐104 105‐89A ‐TB1‐104/X:ISA‐7 89A Isolator Open
132 kV 105 105‐89A  105 CRP Core 5 TB1‐102 X:ISA‐8 105 CRP‐X:ISA‐8 / TB1‐102 105‐89A ‐TB1‐102/X:ISA‐8 89A Isolator Close
132 kV 105 105‐89A  105 CRP Core 6 G719EA‐MG9031‐00‐ TB1‐105 G719EA‐MG9031‐00‐ X:ISA‐9 105 CRP‐X:ISA‐9 / TB1‐105 105‐89A ‐TB1‐105/X:ISA‐9
Isolator 89A Close
132 kV 105 105‐89A  105 CRP Core 7 W105, Sh‐26 of 40 TB1‐106 W105, Sh‐26 of 40 X:ISA‐10 105 CRP‐X:ISA‐10 / TB1‐106 105‐89A ‐TB1‐106/X:ISA‐10
132 kV 105 105‐89A  105 CRP Core 8 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISA‐1 105 CRP‐X:ISA‐1 / TB1‐1 105‐89A ‐TB1‐1/X:ISA‐1 DC Supply (+)Ve
132 kV 105 105‐89A  105 CRP Core 9 W105, Sh‐32 of 40 TB1‐2 W105, Sh‐32 of 40 X:ISA‐2 105 CRP‐X:ISA‐2 / TB1‐2 105‐89A ‐TB1‐2/X:ISA‐2 DC Supply (‐)Ve
132 kV 105 105‐89A  105 CRP Core 10 TB1‐3 X:ISA‐3 105 CRP‐X:ISA‐3 / TB1‐3 105‐89A ‐TB1‐3/X:ISA‐3 Common
132 kV 105 105‐89A  105 CRP Core 11 TB1‐5 X:ISA‐4 105 CRP‐X:ISA‐4 / TB1‐5 105‐89A ‐TB1‐5/X:ISA‐4 Open 
132 kV 105 105‐89A  105 CRP Core 12 TB1‐4 X:ISA‐5 105 CRP‐X:ISA‐5 / TB1‐4 105‐89A ‐TB1‐4/X:ISA‐5 Close
132 kV 105 105‐89A  105 CRP Core 13 SPARE
132 kV 105 105‐89A  105 CRP Core 14 SPARE

34 132 kV 105 swyd  to control bldg. 1‐105‐2‐034 1 Cu./Amr. PVC 105‐89B  105 CRP 14CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB1‐107 G719EA‐MG9031‐00‐ X:ISB‐11 105 CRP‐X:ISB‐11 / TB1‐107 105‐89B ‐TB1‐107/X:ISB‐11 Common
132 kV 105 105‐89B  105 CRP Core 2 W105, Sh‐21 of 40 TB1‐108 W105, Sh‐21 of 40 X:ISB‐12 105 CRP‐X:ISB‐12 / TB1‐108 105‐89B ‐TB1‐108/X:ISB‐12 Isolator 89B Open
132 kV 105 105‐89B  105 CRP Core 3 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:ISB‐6 105 CRP‐X:ISB‐6 / TB1‐103 105‐89B ‐TB1‐103/X:ISB‐6 Common
132 kV 105 105‐89B  105 CRP Core 4 W105, Sh‐23 of 40 TB1‐104 W105, Sh‐23 of 40 X:ISB‐7 105 CRP‐X:ISB‐7 / TB1‐104 105‐89B ‐TB1‐104/X:ISB‐7 89A Isolator Open
132 kV 105 105‐89B  105 CRP Core 5 TB1‐102 X:ISB‐8 105 CRP‐X:ISB‐8 / TB1‐102 105‐89B ‐TB1‐102/X:ISB‐8 89A Isolator Close
132 kV 105 105‐89B  105 CRP Core 6 G719EA‐MG9031‐00‐ TB1‐105 G719EA‐MG9031‐00‐ X:ISB‐9 105 CRP‐X:ISB‐9 / TB1‐105 105‐89B ‐TB1‐105/X:ISB‐9
Isolator 89B Close
132 kV 105 105‐89B  105 CRP Core 7 W105, Sh‐26 of 40 TB1‐106 W105, Sh‐26 of 40 X:ISB‐10 105 CRP‐X:ISB‐10 / TB1‐106 105‐89B ‐TB1‐106/X:ISB‐10
132 kV 105 105‐89B  105 CRP Core 8 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISB‐1 105 CRP‐X:ISB‐1 / TB1‐1 105‐89B ‐TB1‐1/X:ISB‐1 DC Supply (+)Ve
132 kV 105 105‐89B  105 CRP Core 9 W105, Sh‐32 of 40 TB1‐2 W105, Sh‐32 of 40 X:ISB‐2 105 CRP‐X:ISB‐2 / TB1‐2 105‐89B ‐TB1‐2/X:ISB‐2 DC Supply (‐)Ve
132 kV 105 105‐89B  105 CRP Core 10 TB1‐3 X:ISB‐3 105 CRP‐X:ISB‐3 / TB1‐3 105‐89B ‐TB1‐3/X:ISB‐3 Common
132 kV 105 105‐89B  105 CRP Core 11 TB1‐5 X:ISB‐4 105 CRP‐X:ISB‐4 / TB1‐5 105‐89B ‐TB1‐5/X:ISB‐4 Open 
132 kV 105 105‐89B  105 CRP Core 12 TB1‐4 X:ISB‐5 105 CRP‐X:ISB‐5 / TB1‐4 105‐89B ‐TB1‐4/X:ISB‐5 Close
132 kV 105 105‐89B  105 CRP Core 13 SPARE
132 kV 105 105‐89B  105 CRP Core 14 SPARE

105‐E/s CABLING TO PANEL
35 132 kV 105 swyd  to control bldg. 1‐105‐2‐035 1 Cu./Amr. PVC 105‐89AE1  105 CRP 7CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:ESW‐9 105 CRP‐X:ESW‐9 / TB3‐103 105‐89AE1 ‐TB3‐103/X:ESW‐9 Common
132 kV 105 105‐89AE1  105 CRP Core 2 W105, Sh‐23 of 40 TB3‐104 W105, Sh‐23 of 40 X:ESW‐10 105 CRP‐X:ESW‐10 / TB3‐104 105‐89AE1 ‐TB3‐104/X:ESW‐10 Earth Switch 89AE1 Open
132 kV 105 105‐89AE1  105 CRP Core 3 TB3‐102 X:ESW‐11 105 CRP‐X:ESW‐11 / TB3‐102 105‐89AE1 ‐TB3‐102/X:ESW‐11 Earth Switch 89AE1 Close
132 kV 105 105‐89AE1  105 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ESW‐1 105 CRP‐X:ESW‐1 / TB1‐1 105‐89AE1 ‐TB1‐1/X:ESW‐1 DC Supply (+)Ve
132 kV 105 105‐89AE1  105 CRP Core 5 W105, Sh‐32 of 40 TB1‐2 W105, Sh‐32 of 40 X:ESW‐2 105 CRP‐X:ESW‐2 / TB1‐2 105‐89AE1 ‐TB1‐2/X:ESW‐2 DC Supply (‐)Ve
132 kV 105 105‐89AE1  105 CRP Core 6 SPARE
132 kV 105 105‐89AE1  105 CRP Core 7 SPARE

DOCUMENT NUMBER: PE‐2021‐01‐C‐S001
REV:B 3 of 5
OWNER: UPPTCL
CLIENT: GEPDEC
CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY105BC

ESTIMATED  ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. LENGTH (in  LENGTH   CORE TO ‐ EQUIP. REF. DWG. TO (TERM. NO.) FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. (TERM. NO.)
mts) (in mts)

36 132 kV 105 swyd  to control bldg. 1‐105‐2‐036 1 Cu./Amr. PVC 105‐89AE2  105 CRP 7CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:ESW‐12 105 CRP‐X:ESW‐12 / TB3‐103 105‐89AE2 ‐TB3‐103/X:ESW‐12 Common
132 kV 105 105‐89AE2  105 CRP Core 2 W105, Sh‐24 of 40 TB3‐104 W105, Sh‐24 of 40 X:ESW‐13 105 CRP‐X:ESW‐13 / TB3‐104 105‐89AE2 ‐TB3‐104/X:ESW‐13 Earth Switch 89AE2 Open
132 kV 105 105‐89AE2  105 CRP Core 3 TB3‐102 X:ESW‐14 105 CRP‐X:ESW‐14 / TB3‐102 105‐89AE2 ‐TB3‐102/X:ESW‐14 Earth Switch 89AE2 Close
132 kV 105 105‐89AE2  105 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ESW‐3 105 CRP‐X:ESW‐3 / TB1‐1 105‐89AE2 ‐TB1‐1/X:ESW‐3 DC Supply (+)Ve
132 kV 105 105‐89AE2  105 CRP Core 5 W105, Sh‐32 of 40 TB1‐2 W105, Sh‐32 of 40 X:ESW‐4 105 CRP‐X:ESW‐4 / TB1‐2 105‐89AE2 ‐TB1‐2/X:ESW‐4 DC Supply (‐)Ve
132 kV 105 105‐89AE2  105 CRP Core 6 SPARE
132 kV 105 105‐89AE2  105 CRP Core 7 SPARE

37 132 kV 105 swyd  to control bldg. 1‐105‐2‐037 1 Cu./Amr. PVC 105‐89BE1  105 CRP 7CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:ESW‐15 105 CRP‐X:ESW‐15 / TB3‐103 105‐89BE1 ‐TB3‐103/X:ESW‐15 Common
132 kV 105 105‐89BE1  105 CRP Core 2 W105, Sh‐24 of 40 TB3‐104 W105, Sh‐24 of 40 X:ESW‐16 105 CRP‐X:ESW‐16 / TB3‐104 105‐89BE1 ‐TB3‐104/X:ESW‐16 Earth Switch 89BE1 Open
132 kV 105 105‐89BE1  105 CRP Core 3 TB3‐102 X:ESW‐17 105 CRP‐X:ESW‐17 / TB3‐102 105‐89BE1 ‐TB3‐102/X:ESW‐17 Earth Switch 89BE1 Close
132 kV 105 105‐89BE1  105 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ESW‐5 105 CRP‐X:ESW‐5 / TB1‐1 105‐89BE1 ‐TB1‐1/X:ESW‐5 DC Supply (+)Ve
132 kV 105 105‐89BE1  105 CRP Core 5 W105, Sh‐32 of 40 TB1‐2 W105, Sh‐32 of 40 X:ESW‐6 105 CRP‐X:CB‐6 / X1‐87 105‐52 ‐X1‐87/X:CB‐6 DC Supply (‐)Ve
132 kV 105 105‐52  105 CRP Core 6 SPARE
132 kV 105 105‐52  105 CRP Core 7 SPARE

38 132 kV 105 swyd  to control bldg. 1‐105‐2‐038 1 Cu./Amr. PVC 105‐89BE2  105 CRP 7CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB3‐103 G719EA‐MG9031‐00‐ X:ESW‐18 105 CRP‐X:ESW‐18 / TB3‐103 105‐89BE2 ‐TB3‐103/X:ESW‐18 Common
132 kV 105 105‐89BE2  105 CRP Core 2 W105, Sh‐25 of 40 TB3‐104 W105, Sh‐25 of 40 X:ESW‐19 105 CRP‐X:ESW‐19 / TB3‐104 105‐89BE2 ‐TB3‐104/X:ESW‐19 Earth Switch 89BE2 Open
132 kV 105 105‐89BE2  105 CRP Core 3 TB3‐102 X:ESW‐20 105 CRP‐X:ESW‐20 / TB3‐102 105‐89BE2 ‐TB3‐102/X:ESW‐20 Earth Switch 89BE2 Close
132 kV 105 105‐89BE2  105 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ESW‐7 105 CRP‐X:ESW‐7 / TB1‐1 105‐89BE2 ‐TB1‐1/X:ESW‐7 DC Supply (+)Ve
132 kV 105 105‐89BE2  105 CRP Core 5 W105, Sh‐32 of 40 TB1‐2 W105, Sh‐32 of 40 X:ESW‐8 105 CRP‐X:ESW‐8 / TB1‐2 105‐89BE2 ‐TB1‐2/X:ESW‐8 DC Supply (‐)Ve
132 kV 105 105‐89BE2  105 CRP Core 6 SPARE
132 kV 105 105‐89BE2  105 CRP Core 7 SPARE

105‐BB1 PT CABLING TO PANEL
39 132 kV 105 within swyd  1‐105‐1‐039 1 Cu./Amr. PVC 105‐BB1 PT JB 105 CRP 5CX2.5 50 Core 1 TB1‐1 G719EA‐MG9031‐00‐ X:VLT‐1 105 CRP‐X:VLT‐1 / TB1‐1 105‐BB1 PT JB‐TB1‐1/X:VLT‐1 Distance Main‐1 Protection Relay
ASPL/UPPCL/20415U
132 kV 105 105‐BB1 PT JB 105 CRP Core 2 TB1‐8 W105, Sh‐11 of 40 X:VLT‐2 105 CRP‐X:VLT‐2 / TB1‐8 105‐BB1 PT JB‐TB1‐8/X:VLT‐2 67/67N : O/c & E/f Relay
132 kV 105 105‐BB1 PT JB 105 CRP Core 3 TB1‐15 X:VLT‐3 105 CRP‐X:VLT‐3 / TB1‐15 105‐BB1 PT JB‐TB1‐15/X:VLT‐3
132 kV 105 105‐BB1 PT JB 105 CRP Core 4 TB1‐19 X:VLT‐4 105 CRP‐X:VLT‐4 / TB1‐19 105‐BB1 PT JB‐TB1‐19/X:VLT‐4
132 kV 105 105‐BB1 PT JB 105 CRP Core 5 SPARE

40 132 kV 105 within swyd  1‐105‐1‐040 1 Cu./Amr. PVC 105‐BB1 PT JB 105 CRP 10CX2.5 50 Core 1 TB2‐1 G719EA‐MG9031‐00‐ X:VLT‐1 105 CRP‐X:VLT‐1 / TB2‐1 105‐BB1 PT JB‐TB2‐1/X:VLT‐1 Spare
ASPL/UPPCL/20415U
132 kV 105 105‐BB1 PT JB 105 CRP Core 2 TB2‐8 W105, Sh‐11 of 40 X:VLT‐2 105 CRP‐X:VLT‐2 / TB2‐8 105‐BB1 PT JB‐TB2‐8/X:VLT‐2
132 kV 105 105‐BB1 PT JB 105 CRP Core 3 TB2‐15 X:VLT‐3 105 CRP‐X:VLT‐3 / TB2‐15 105‐BB1 PT JB‐TB2‐15/X:VLT‐3
132 kV 105 105‐BB1 PT JB 105 CRP Core 4 TB2‐19 X:VLT‐4 105 CRP‐X:VLT‐4 / TB2‐19 105‐BB1 PT JB‐TB2‐19/X:VLT‐4
132 kV 105 105‐BB1 PT JB 105 CRP Core 5 TB3‐1 G719EA‐MG9031‐00‐ X:VLT‐5 105 CRP‐X:VLT‐5 / TB3‐1 105‐BB1 PT JB‐TB3‐1/X:VLT‐5
ASPL/UPPCL/20415U
132 kV 105 105‐BB1 PT JB 105 CRP Core 6 TB3‐8 W105, Sh‐11 of 40 X:VLT‐6 105 CRP‐X:VLT‐6 / TB3‐8 105‐BB1 PT JB‐TB3‐8/X:VLT‐6 Metering
132 kV 105 105‐BB1 PT JB 105 CRP Core 7 TB3‐15 X:VLT‐7 105 CRP‐X:VLT‐7 / TB3‐15 105‐BB1 PT JB‐TB3‐15/X:VLT‐7
132 kV 105 105‐BB1 PT JB 105 CRP Core 8 TB3‐19 X:VLT‐8 105 CRP‐X:VLT‐8 / TB3‐19 105‐BB1 PT JB‐TB3‐19/X:VLT‐8
132 kV 105 105‐BB1 PT JB 105 CRP Core 9 SPARE
132 kV 105 105‐BB1 PT JB 105 CRP Core 10 SPARE
105‐BB2 PT CABLING TO PANEL
41 132 kV 105 within swyd  1‐105‐1‐041 1 Cu./Amr. PVC 105‐BB2 PT JB 105 CRP 5CX2.5 65 Core 1 TB1‐1 G719EA‐MG9031‐00‐ X:VLT‐1 105 CRP‐X:VLT‐1 / TB1‐1 105‐BB2 PT JB‐TB1‐1/X:VLT‐1 Distance Main‐1 Protection Relay
ASPL/UPPCL/20415U
132 kV 105 105‐BB2 PT JB 105 CRP Core 2 TB1‐8 W105, Sh‐12 of 40 X:VLT‐2 105 CRP‐X:VLT‐2 / TB1‐8 105‐BB2 PT JB‐TB1‐8/X:VLT‐2 67/67N : O/c & E/f Relay
132 kV 105 105‐BB2 PT JB 105 CRP Core 3 TB1‐15 X:VLT‐3 105 CRP‐X:VLT‐3 / TB1‐15 105‐BB2 PT JB‐TB1‐15/X:VLT‐3
132 kV 105 105‐BB2 PT JB 105 CRP Core 4 TB1‐19 X:VLT‐4 105 CRP‐X:VLT‐4 / TB1‐19 105‐BB2 PT JB‐TB1‐19/X:VLT‐4
132 kV 105 105‐BB2 PT JB 105 CRP Core 5 SPARE

42 132 kV 105 within swyd  1‐105‐1‐042 1 Cu./Amr. PVC 105‐BB2 PT JB 105 CRP 10CX2.5 65 Core 1 TB2‐1 G719EA‐MG9031‐00‐ X:VLT‐1 105 CRP‐X:VLT‐1 / TB2‐1 105‐BB2 PT JB‐TB2‐1/X:VLT‐1 Spare
ASPL/UPPCL/20415U
132 kV 105 105‐BB2 PT JB 105 CRP Core 2 TB2‐8 W105, Sh‐12 of 40 X:VLT‐2 105 CRP‐X:VLT‐2 / TB2‐8 105‐BB2 PT JB‐TB2‐8/X:VLT‐2
132 kV 105 105‐BB2 PT JB 105 CRP Core 3 TB2‐15 X:VLT‐3 105 CRP‐X:VLT‐3 / TB2‐15 105‐BB2 PT JB‐TB2‐15/X:VLT‐3
132 kV 105 105‐BB2 PT JB 105 CRP Core 4 TB2‐19 X:VLT‐4 105 CRP‐X:VLT‐4 / TB2‐19 105‐BB2 PT JB‐TB2‐19/X:VLT‐4
132 kV 105 105‐BB2 PT JB 105 CRP Core 5 TB3‐1 G719EA‐MG9031‐00‐ X:VLT‐5 105 CRP‐X:VLT‐5 / TB3‐1 105‐BB2 PT JB‐TB3‐1/X:VLT‐5
ASPL/UPPCL/20415U
132 kV 105 105‐BB2 PT JB 105 CRP Core 6 TB3‐8 W105, Sh‐12 of 40 X:VLT‐6 105 CRP‐X:VLT‐6 / TB3‐8 105‐BB2 PT JB‐TB3‐8/X:VLT‐6 Metering
132 kV 105 105‐BB2 PT JB 105 CRP Core 7 TB3‐15 X:VLT‐7 105 CRP‐X:VLT‐7 / TB3‐15 105‐BB2 PT JB‐TB3‐15/X:VLT‐7
132 kV 105 105‐BB2 PT JB 105 CRP Core 8 TB3‐19 X:VLT‐8 105 CRP‐X:VLT‐8 / TB3‐19 105‐BB2 PT JB‐TB3‐19/X:VLT‐8
132 kV 105 105‐BB2 PT JB 105 CRP Core 9 SPARE
132 kV 105 105‐BB2 PT JB 105 CRP Core 10 SPARE
105‐CT CABLING
43 132 kV 105 within swyd  1‐105‐1‐043 1 Cu./Amr. PVC 105‐CT JB 105 CRP 14CX2.5 73 Core 1 5US2 G719EA‐MG9031‐ X:CT‐1 105 CRP‐X:CT‐1 / 5US2 105‐CT JB‐5US2/X:CT‐1
ASPL/UPPCL/20415
132 kV 105 105‐CT JB 105 CRP Core 2 5VS2 W105, Sh‐09 of 40 X:CT‐3 105 CRP‐X:CT‐3 / 5VS2 105‐CT JB‐5VS2/X:CT‐3
Core 5 87BB : Busbar Protection
132 kV 105 105‐CT JB 105 CRP Core 3 5WS2 X:CT‐5 105 CRP‐X:CT‐5 / 5WS2 105‐CT JB‐5WS2/X:CT‐5
132 kV 105 105‐CT JB 105 CRP Core 4 5VS1 X:CT‐7 105 CRP‐X:CT‐7 / 5VS1 105‐CT JB‐5VS1/X:CT‐7
132 kV 105 105‐CT JB 105 CRP Core 5 2US2 G719EA‐MG9031‐ X:CT‐21 105 CRP‐X:CT‐21 / 2US2 105‐CT JB‐2US2/X:CT‐21
ASPL/UPPCL/20415
132 kV 105 105‐CT JB 105 CRP Core 6 2VS2 W105, Sh‐09 of 40 X:CT‐23 105 CRP‐X:CT‐23 / 2VS2 105‐CT JB‐2VS2/X:CT‐23 Core 2 67/67N : O/c & E/f Relay
132 kV 105 105‐CT JB 105 CRP Core 7 2WS2 X:CT‐25 105 CRP‐X:CT‐25 / 2WS2 105‐CT JB‐2WS2/X:CT‐25
132 kV 105 105‐CT JB 105 CRP Core 8 2VS1 X:CT‐27 105 CRP‐X:CT‐27 / 2VS1 105‐CT JB‐2VS1/X:CT‐27
132 kV 105 105‐CT JB 105 CRP Core 9 1US2 G719EA‐MG9031‐ X:CT‐29 105 CRP‐X:CT‐29 / 1US2 105‐CT JB‐1US2/X:CT‐29
ASPL/UPPCL/20415
132 kV 105 105‐CT JB 105 CRP Core 10 1VS2 W105, Sh‐09 of 40 X:CT‐31 105 CRP‐X:CT‐31 / 1VS2 105‐CT JB‐1VS2/X:CT‐31 Core 1 Spare
132 kV 105 105‐CT JB 105 CRP Core 11 1WS2 X:CT‐33 105 CRP‐X:CT‐33 / 1WS2 105‐CT JB‐1WS2/X:CT‐33
132 kV 105 105‐CT JB 105 CRP Core 12 1VS1 X:CT‐35 105 CRP‐X:CT‐35 / 1VS1 105‐CT JB‐1VS1/X:CT‐35
132 kV 105 105‐CT JB 105 CRP Core 13 SPARE SPARE
132 kV 105 105‐CT JB 105 CRP Core 14 SPARE SPARE

44 132 kV 101 within swyd  1‐101‐1‐044 1 Cu./Amr. PVC 105‐CT JB 105 CRP 10CX2.5 85 Core 1 3US2 G719EA‐MG9031‐ X:CT‐23 105 CRP‐X:CT‐23 / 3US2 105‐CT JB‐3US2/X:CT‐23
ASPL/UPPCL/20415
132 kV 101 105‐CT JB 105 CRP Core 2 3VS2 W105, Sh‐10 of 40 X:CT‐25 105 CRP‐X:CT‐25 / 3VS2 105‐CT JB‐3VS2/X:CT‐25
CORE 3: BCU : Bay Control Unit
132 kV 101 105‐CT JB 105 CRP Core 3 3WS2 X:CT‐27 105 CRP‐X:CT‐27 / 3WS2 105‐CT JB‐3WS2/X:CT‐27
132 kV 101 105‐CT JB 105 CRP Core 4 3VS1 X:CT‐29 105 CRP‐X:CT‐29 / 3VS1 105‐CT JB‐3VS1/X:CT‐29
132 kV 101 105‐CT JB 105 CRP Core 5 SPARE

105‐105 CRP TO 107 CRP

DOCUMENT NUMBER: PE‐2021‐01‐C‐S001
REV:B 4 of 5
OWNER: UPPTCL
CLIENT: GEPDEC
CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY105BC

ESTIMATED  ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. LENGTH (in  LENGTH   CORE TO ‐ EQUIP. REF. DWG. TO (TERM. NO.) FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. (TERM. NO.)
mts) (in mts)
45 132 kV 105 within swyd  1‐105‐1‐045 1 Cu./Amr. PVC 105 CRP 107 CRP 27CX2.5 100 Core 1 G719EA‐MG9031‐00‐00‐ TB5‐X G719EA‐MG9031‐00‐00‐ TB5‐X 107 CRP‐TB5‐X / TB5‐X 105 CRP‐TB5‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 2 W105, Sh 15 & 16 TB5‐X W105, Sh 15 & 16 TB5‐X 107 CRP‐TB5‐X / TB5‐X 105 CRP‐TB5‐X/TB5‐X
Distance Protection M1
132 kV 105 105 CRP 107 CRP Core 3 TB5‐X TB5‐X 107 CRP‐TB5‐X / TB5‐X 105 CRP‐TB5‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 4 TB5‐X TB5‐X 107 CRP‐TB5‐X / TB5‐X 105 CRP‐TB5‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 5 G719EA‐MG9031‐00‐00‐ TB2‐X G719EA‐MG9031‐00‐00‐ TB5‐X 107 CRP‐TB5‐X / TB2‐X 105 CRP‐TB2‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 6 W105, Sh 15 & 16 TB2‐X W105, Sh 15 & 16 TB5‐X 107 CRP‐TB5‐X / TB2‐X 105 CRP‐TB2‐X/TB5‐X 67/67N : O/c & E/f Relay
132 kV 105 105 CRP 107 CRP Core 7 TB2‐X TB5‐X 107 CRP‐TB5‐X / TB2‐X 105 CRP‐TB2‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 8 TB2‐X TB5‐X 107 CRP‐TB5‐X / TB2‐X 105 CRP‐TB2‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 9 G719EA‐MG9031‐00‐00‐ TB1‐X G719EA‐MG9031‐00‐00‐ TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 10 W105, Sh 15 & 16 TB1‐X W105, Sh 15 & 16 TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X 87BB : Busbar Protection
132 kV 105 105 CRP 107 CRP Core 11 TB1‐X TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 12 TB1‐X TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 13 G719EA‐MG9031‐00‐00‐ TB1‐X G719EA‐MG9031‐00‐00‐ TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 14 W105, Sh 15 & 16 TB1‐X W105, Sh 15 & 16 TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
Distance Protection M1
132 kV 105 105 CRP 107 CRP Core 15 TB1‐X TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 16 TB1‐X TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 17 G719EA‐MG9031‐00‐00‐ TB1‐X G719EA‐MG9031‐00‐00‐ TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 18 W105, Sh 15 & 16 TB1‐X W105, Sh 15 & 16 TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
67/67N : O/c & E/f Relay
132 kV 105 105 CRP 107 CRP Core 19 TB1‐X TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 20 TB1‐X TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 21 G719EA‐MG9031‐00‐00‐ TB1‐X G719EA‐MG9031‐00‐00‐ TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 22 W105, Sh 15 & 16 TB1‐X W105, Sh 15 & 16 TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
87BB : Busbar Protection
132 kV 105 105 CRP 107 CRP Core 23 TB1‐X TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 24 TB1‐X TB5‐X 107 CRP‐TB5‐X / TB1‐X 105 CRP‐TB1‐X/TB5‐X
132 kV 105 105 CRP 107 CRP Core 25 SPARE SPARE
132 kV 105 105 CRP 107 CRP Core 26 SPARE SPARE
132 kV 105 105 CRP 107 CRP Core 27 SPARE SPARE

DOCUMENT NUMBER: PE‐2021‐01‐C‐S001
REV:B 5 of 5
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY107TBC

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM  TO ‐ EQUIP. REF. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE TO (TERM. NO.) FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. (TERM. NO.) DWG.
(in mts) (in mts)

Control Cable in Switchyard

107‐CT INTERPOLE CABLING
1 132 kV 107 within swyd  1‐107‐1‐001 1 Cu./Amr. PVC 107‐RCT Core.‐5 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 5US1 5US1 107‐CT JB‐5US1 / 5US1 107‐RCT Core.‐5‐5US1/5US1 CORE‐5
ASPL/UPPCL/20415
132 kV 107 107‐RCT Core.‐5 107‐CT JB Core 2 8 5US2 5US2 107‐CT JB‐5US2 / 5US2 107‐RCT Core.‐5‐5US2/5US2 87BB : Busbar Protection
132 kV 107 107‐RCT Core.‐5 107‐CT JB Core 3 5US3 5US3 107‐CT JB‐5US3 / 5US3 107‐RCT Core.‐5‐5US3/5US3
132 kV 107 107‐RCT Core.‐5 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐5‐Spare/Spare
132 kV 107 107‐RCT Core.‐5 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐5‐Spare/Spare

2 132 kV 107 within swyd  1‐107‐1‐002 1 Cu./Amr. PVC 107‐YCT Core.‐5 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 5VS1 5VS1 107‐CT JB‐5VS1 / 5VS1 107‐YCT Core.‐5‐5VS1/5VS1 CORE‐5
ASPL/UPPCL/20415
132 kV 107 107‐YCT Core.‐5 107‐CT JB Core 2 8 5VS2 5VS2 107‐CT JB‐5VS2 / 5VS2 107‐YCT Core.‐5‐5VS2/5VS2 87BB : Busbar Protection
132 kV 107 107‐YCT Core.‐5 107‐CT JB Core 3 5VS3 5VS3 107‐CT JB‐5VS3 / 5VS3 107‐YCT Core.‐5‐5VS3/5VS3
132 kV 107 107‐YCT Core.‐5 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐5‐Spare/Spare
132 kV 107 107‐YCT Core.‐5 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐5‐Spare/Spare

3 132 kV 107 within swyd  1‐107‐1‐003 1 Cu./Amr. PVC 107‐BCT Core.‐5 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 5WS1 5WS1 107‐CT JB‐5WS1 / 5WS1 107‐BCT Core.‐5‐5WS1/5WS1 CORE‐5
ASPL/UPPCL/20415
132 kV 107 107‐BCT Core.‐5 107‐CT JB Core 2 8 5WS2 5WS2 107‐CT JB‐5WS2 / 5WS2 107‐BCT Core.‐5‐5WS2/5WS2 87BB : Busbar Protection
132 kV 107 107‐BCT Core.‐5 107‐CT JB Core 3 5WS3 5WS3 107‐CT JB‐5WS3 / 5WS3 107‐BCT Core.‐5‐5WS3/5WS3
132 kV 107 107‐BCT Core.‐5 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐5‐Spare/Spare
132 kV 107 107‐BCT Core.‐5 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐5‐Spare/Spare

4 132 kV 107 within swyd  1‐107‐1‐004 1 Cu./Amr. PVC 107‐RCT Core.‐2 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 2US1 2US1 107‐CT JB‐2US1 / 2US1 107‐RCT Core.‐2‐2US1/2US1 CORE‐2
ASPL/UPPCL/20415
132 kV 107 107‐RCT Core.‐2 107‐CT JB Core 2 8 2US2 2US2 107‐CT JB‐2US2 / 2US2 107‐RCT Core.‐2‐2US2/2US2 67 : Direc. O/c, E/f  & LBB Relay
132 kV 107 107‐RCT Core.‐2 107‐CT JB Core 3 2US3 2US3 107‐CT JB‐2US3 / 2US3 107‐RCT Core.‐2‐2US3/2US3
132 kV 107 107‐RCT Core.‐2 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐2‐Spare/Spare
132 kV 107 107‐RCT Core.‐2 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐2‐Spare/Spare

5 132 kV 107 within swyd  1‐107‐1‐005 1 Cu./Amr. PVC 107‐YCT Core.‐2 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 2VS1 2VS1 107‐CT JB‐2VS1 / 2VS1 107‐YCT Core.‐2‐2VS1/2VS1 CORE‐2
ASPL/UPPCL/20415
132 kV 107 107‐YCT Core.‐2 107‐CT JB Core 2 8 2VS2 2VS2 107‐CT JB‐2VS2 / 2VS2 107‐YCT Core.‐2‐2VS2/2VS2 67 : Direc. O/c, E/f  & LBB Relay
132 kV 107 107‐YCT Core.‐2 107‐CT JB Core 3 2VS3 2VS3 107‐CT JB‐2VS3 / 2VS3 107‐YCT Core.‐2‐2VS3/2VS3
132 kV 107 107‐YCT Core.‐2 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐2‐Spare/Spare
132 kV 107 107‐YCT Core.‐2 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐2‐Spare/Spare

6 132 kV 107 within swyd  1‐107‐1‐006 1 Cu./Amr. PVC 107‐BCT Core.‐2 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 2WS1 2WS1 107‐CT JB‐2WS1 / 2WS1 107‐BCT Core.‐2‐2WS1/2WS1 CORE‐2
ASPL/UPPCL/20415
132 kV 107 107‐BCT Core.‐2 107‐CT JB Core 2 8 2WS2 2WS2 107‐CT JB‐2WS2 / 2WS2 107‐BCT Core.‐2‐2WS2/2WS2 67 : Direc. O/c, E/f  & LBB Relay
132 kV 107 107‐BCT Core.‐2 107‐CT JB Core 3 2WS3 2WS3 107‐CT JB‐2WS3 / 2WS3 107‐BCT Core.‐2‐2WS3/2WS3
132 kV 107 107‐BCT Core.‐2 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐2‐Spare/Spare
132 kV 107 107‐BCT Core.‐2 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐2‐Spare/Spare

7 132 kV 107 within swyd  1‐107‐1‐007 1 Cu./Amr. PVC 107‐RCT Core.‐1 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 1US1 1US1‐Shorted 107‐CT JB‐1US1‐Shorted / 1US1 107‐RCT Core.‐1‐1US1/1US1‐Shorted CORE‐1
ASPL/UPPCL/20415
132 kV 107 107‐RCT Core.‐1 107‐CT JB Core 2 8 1US2 1US2‐Shorted 107‐CT JB‐1US2‐Shorted / 1US2 107‐RCT Core.‐1‐1US2/1US2‐Shorted SPARE
132 kV 107 107‐RCT Core.‐1 107‐CT JB Core 3 1US3 1US3‐Shorted 107‐CT JB‐1US3‐Shorted / 1US3 107‐RCT Core.‐1‐1US3/1US3‐Shorted
132 kV 107 107‐RCT Core.‐1 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐1‐Spare/Spare
132 kV 107 107‐RCT Core.‐1 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐1‐Spare/Spare

8 132 kV 107 within swyd  1‐107‐1‐008 1 Cu./Amr. PVC 107‐YCT Core.‐1 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 1VS1 1VS1‐Shorted 107‐CT JB‐1VS1‐Shorted / 1VS1 107‐YCT Core.‐1‐1VS1/1VS1‐Shorted CORE‐1
ASPL/UPPCL/20415
132 kV 107 107‐YCT Core.‐1 107‐CT JB Core 2 8 1VS2 1VS2‐Shorted 107‐CT JB‐1VS2‐Shorted / 1VS2 107‐YCT Core.‐1‐1VS2/1VS2‐Shorted SPARE
132 kV 107 107‐YCT Core.‐1 107‐CT JB Core 3 1VS3 1VS3‐Shorted 107‐CT JB‐1VS3‐Shorted / 1VS3 107‐YCT Core.‐1‐1VS3/1VS3‐Shorted
132 kV 107 107‐YCT Core.‐1 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐1‐Spare/Spare
132 kV 107 107‐YCT Core.‐1 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐1‐Spare/Spare

9 132 kV 107 within swyd  1‐107‐1‐009 1 Cu./Amr. PVC 107‐BCT Core.‐1 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 1WS1 1WS1‐Shorted 107‐CT JB‐1WS1‐Shorted / 1WS1 107‐BCT Core.‐1‐1WS1/1WS1‐Shorted CORE‐1
ASPL/UPPCL/20415
132 kV 107 107‐BCT Core.‐1 107‐CT JB Core 2 8 1WS2 1WS2‐Shorted 107‐CT JB‐1WS2‐Shorted / 1WS2 107‐BCT Core.‐1‐1WS2/1WS2‐Shorted SPARE
132 kV 107 107‐BCT Core.‐1 107‐CT JB Core 3 1WS3 1WS3‐Shorted 107‐CT JB‐1WS3‐Shorted / 1WS3 107‐BCT Core.‐1‐1WS3/1WS3‐Shorted
132 kV 107 107‐BCT Core.‐1 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐1‐Spare/Spare
132 kV 107 107‐BCT Core.‐1 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐1‐Spare/Spare

10 132 kV 107 within swyd  1‐107‐1‐010 1 Cu./Amr. PVC 107‐RCT Core.‐3 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 3US1 3US1 107‐CT JB‐3US1 / 3US1 107‐RCT Core.‐3‐3US1/3US1 CORE‐3
ASPL/UPPCL/20415
132 kV 107 107‐RCT Core.‐3 107‐CT JB Core 2 8 3US2 3US2 107‐CT JB‐3US2 / 3US2 107‐RCT Core.‐3‐3US2/3US2 BCU: Bay Control& Protection Unit
132 kV 107 107‐RCT Core.‐3 107‐CT JB Core 3 3US3 3US3 107‐CT JB‐3US3 / 3US3 107‐RCT Core.‐3‐3US3/3US3
132 kV 107 107‐RCT Core.‐3 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐3‐Spare/Spare
132 kV 107 107‐RCT Core.‐3 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐3‐Spare/Spare

11 132 kV 107 within swyd  1‐107‐1‐011 1 Cu./Amr. PVC 107‐YCT Core.‐3 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 3VS1 3VS1 107‐CT JB‐3VS1 / 3VS1 107‐YCT Core.‐3‐3VS1/3VS1 CORE‐3
ASPL/UPPCL/20415
132 kV 107 107‐YCT Core.‐3 107‐CT JB Core 2 8 3VS2 3VS2 107‐CT JB‐3VS2 / 3VS2 107‐YCT Core.‐3‐3VS2/3VS2 BCU: Bay Control& Protection Unit
132 kV 107 107‐YCT Core.‐3 107‐CT JB Core 3 3VS3 3VS3 107‐CT JB‐3VS3 / 3VS3 107‐YCT Core.‐3‐3VS3/3VS3
132 kV 107 107‐YCT Core.‐3 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐3‐Spare/Spare
132 kV 107 107‐YCT Core.‐3 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐3‐Spare/Spare

12 132 kV 107 within swyd  1‐107‐1‐012 1 Cu./Amr. PVC 107‐BCT Core.‐3 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 3WS1 3WS1 107‐CT JB‐3WS1 / 3WS1 107‐BCT Core.‐3‐3WS1/3WS1 CORE‐3
ASPL/UPPCL/20415
132 kV 107 107‐BCT Core.‐3 107‐CT JB Core 2 8 3WS2 3WS2 107‐CT JB‐3WS2 / 3WS2 107‐BCT Core.‐3‐3WS2/3WS2 BCU: Bay Control& Protection Unit
132 kV 107 107‐BCT Core.‐3 107‐CT JB Core 3 3WS3 3WS3 107‐CT JB‐3WS3 / 3WS3 107‐BCT Core.‐3‐3WS3/3WS3
132 kV 107 107‐BCT Core.‐3 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐3‐Spare/Spare
132 kV 107 107‐BCT Core.‐3 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐3‐Spare/Spare

13 132 kV 107 within swyd  1‐107‐1‐013 1 Cu./Amr. PVC 107‐RCT Core.‐4 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 1US1 1US1‐Shorted 107‐CT JB‐1US1‐Shorted / 1US1 107‐RCT Core.‐4‐1US1/1US1‐Shorted CORE‐1
ASPL/UPPCL/20415
132 kV 107 107‐RCT Core.‐4 107‐CT JB Core 2 8 1US2 1US2‐Shorted 107‐CT JB‐1US2‐Shorted / 1US2 107‐RCT Core.‐4‐1US2/1US2‐Shorted SPARE
132 kV 107 107‐RCT Core.‐4 107‐CT JB Core 3 1US3 1US3‐Shorted 107‐CT JB‐1US3‐Shorted / 1US3 107‐RCT Core.‐4‐1US3/1US3‐Shorted
132 kV 107 107‐RCT Core.‐4 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐4‐Spare/Spare
132 kV 107 107‐RCT Core.‐4 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐RCT Core.‐4‐Spare/Spare

14 132 kV 107 within swyd  1‐107‐1‐014 1 Cu./Amr. PVC 107‐YCT Core.‐4 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 1VS1 1VS1‐Shorted 107‐CT JB‐1VS1‐Shorted / 1VS1 107‐YCT Core.‐4‐1VS1/1VS1‐Shorted CORE‐1
ASPL/UPPCL/20415
132 kV 107 107‐YCT Core.‐4 107‐CT JB Core 2 8 1VS2 1VS2‐Shorted 107‐CT JB‐1VS2‐Shorted / 1VS2 107‐YCT Core.‐4‐1VS2/1VS2‐Shorted SPARE

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 1 of 3
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY107TBC

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM  TO ‐ EQUIP. REF. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE TO (TERM. NO.) FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. (TERM. NO.) DWG.
(in mts) (in mts)
132 kV 107 107‐YCT Core.‐4 107‐CT JB Core 3 1VS3 1VS3‐Shorted 107‐CT JB‐1VS3‐Shorted / 1VS3 107‐YCT Core.‐4‐1VS3/1VS3‐Shorted
132 kV 107 107‐YCT Core.‐4 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐4‐Spare/Spare
132 kV 107 107‐YCT Core.‐4 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐YCT Core.‐4‐Spare/Spare

15 132 kV 107 within swyd  1‐107‐1‐015 1 Cu./Amr. PVC 107‐BCT Core.‐4 107‐CT JB 5CX2.5 10 Core 1 GD/JAUNPUR/GAL/005 1WS1 1WS1‐Shorted 107‐CT JB‐1WS1‐Shorted / 1WS1 107‐BCT Core.‐4‐1WS1/1WS1‐Shorted CORE‐1
ASPL/UPPCL/20415
132 kV 107 107‐BCT Core.‐4 107‐CT JB Core 2 8 1WS2 1WS2‐Shorted 107‐CT JB‐1WS2‐Shorted / 1WS2 107‐BCT Core.‐4‐1WS2/1WS2‐Shorted SPARE
132 kV 107 107‐BCT Core.‐4 107‐CT JB Core 3 1WS3 1WS3‐Shorted 107‐CT JB‐1WS3‐Shorted / 1WS3 107‐BCT Core.‐4‐1WS3/1WS3‐Shorted
132 kV 107 107‐BCT Core.‐4 107‐CT JB Core 4 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐4‐Spare/Spare
132 kV 107 107‐BCT Core.‐4 107‐CT JB Core 5 Spare Spare 107‐CT JB‐Spare / Spare 107‐BCT Core.‐4‐Spare/Spare
Control Cable from Switchyard to Panel
107‐CT CABLING TO PANEL
16 132 kV 107 swyd  to control bldg. 1‐107‐2‐016 1 Cu./Amr. PVC 107‐CT MB 107 CRP 14CX2.5 60 Core 1 5US2 G719EA‐MG9031‐00‐ X:CT‐1 107 CRP‐X:CT‐1 / 5US2 107‐CT MB‐5US2/X:CT‐1 87BB : Busbar Protection
ASPL/UPPCL/20415
132 kV 107 107‐CT MB 107 CRP Core 2 5VS2 W107, Sh‐10 of 45 X:CT‐3 107 CRP‐X:CT‐3 / 5VS2 107‐CT MB‐5VS2/X:CT‐3
132 kV 107 107‐CT MB 107 CRP Core 3 5WS2 X:CT‐5 107 CRP‐X:CT‐5 / 5WS2 107‐CT MB‐5WS2/X:CT‐5
132 kV 107 107‐CT MB 107 CRP Core 4 5VS1 X:CT‐7 107 CRP‐X:CT‐7 / 5VS1 107‐CT MB‐5VS1/X:CT‐7
132 kV 107 107‐CT MB 107 CRP Core 5 2US2 X:CT‐9 107 CRP‐X:CT‐9 / 2US2 107‐CT MB‐2US2/X:CT‐9 67 : Direc. O/c, E/f  & LBB Relay
132 kV 107 107‐CT MB 107 CRP Core 6 2VS2 X:CT‐11 107 CRP‐X:CT‐11 / 2VS2 107‐CT MB‐2VS2/X:CT‐11
132 kV 107 107‐CT MB 107 CRP Core 7 2WS2 X:CT‐13 107 CRP‐X:CT‐13 / 2WS2 107‐CT MB‐2WS2/X:CT‐13
132 kV 107 107‐CT MB 107 CRP Core 8 2VS1 X:CT‐15 107 CRP‐X:CT‐15 / 2VS1 107‐CT MB‐2VS1/X:CT‐15
132 kV 107 107‐CT MB 107 CRP Core 9 1US2 G719EA‐MG9031‐00‐ X:CT‐23 107 CRP‐X:CT‐23 / 1US2 107‐CT MB‐1US2/X:CT‐23 Spare
ASPL/UPPCL/20415
132 kV 107 107‐CT MB 107 CRP Core 10 1VS2 W107, Sh‐11 of 45 X:CT‐17 107 CRP‐X:CT‐17 / 1VS2 107‐CT MB‐1VS2/X:CT‐17
132 kV 107 107‐CT MB 107 CRP Core 11 1WS2 X:CT‐19 107 CRP‐X:CT‐19 / 1WS2 107‐CT MB‐1WS2/X:CT‐19
132 kV 107 107‐CT MB 107 CRP Core 12 1VS1 X:CT‐21 107 CRP‐X:CT‐21 / 1VS1 107‐CT MB‐1VS1/X:CT‐21
132 kV 107 107‐CT MB 107 CRP Core 13 SPARE
132 kV 107 107‐CT MB 107 CRP Core 14 SPARE

17 132 kV 107 within swyd  1‐107‐1‐017 1 Cu./Amr. PVC 107‐CT MB 105 CRP 5CX2.5 60 Core 1 3US2 G719EA‐MG9031‐ X:CT‐23 105 CRP‐X:CT‐23 / 3US2 107‐CT MB‐3US2/X:CT‐23
ASPL/UPPCL/20415
132 kV 107 107‐CT MB 105 CRP Core 2 3VS2 W201, Sh‐33 of 58 X:CT‐25 105 CRP‐X:CT‐25 / 3VS2 107‐CT MB‐3VS2/X:CT‐25
CORE 3: BCU : Bay Control Unit
132 kV 107 107‐CT MB 105 CRP Core 3 3WS2 X:CT‐27 105 CRP‐X:CT‐27 / 3WS2 107‐CT MB‐3WS2/X:CT‐27
132 kV 107 107‐CT MB 105 CRP Core 4 3VS1 X:CT‐29 105 CRP‐X:CT‐29 / 3VS1 107‐CT MB‐3VS1/X:CT‐29
132 kV 107 107‐CT MB 105 CRP Core 5 SPARE

107‐CIRCUIT BREAKER CABLING TO PANEL
18 132 kV 107 swyd  to control bldg. 1‐107‐2‐018 1 Cu./Amr. PVC 107‐52  107 CRP 27CX2.5 50 Core 1 G719EA‐MG9031‐00‐ X1LA‐5 G719EA‐MG9031‐00‐ X:CB‐3 107 CRP‐X:CB‐3 / X1LA‐5 107‐52 ‐X1LA‐5/X:CB‐3 Common
132 kV 107 107‐52  107 CRP Core 2 W107, Sh‐23 of 45 X1LC‐6 W107, Sh‐23 of 45 X:CB‐4 107 CRP‐X:CB‐4 / X1LC‐6 107‐52 ‐X1LC‐6/X:CB‐4 CB Open
132 kV 107 107‐52  107 CRP Core 3 X1LC‐4 X:CB‐5 107 CRP‐X:CB‐5 / X1LC‐4 107‐52 ‐X1LC‐4/X:CB‐5 CB Close
132 kV 107 107‐52  107 CRP Core 4 G719EA‐MG9031‐00‐ X1‐95 G719EA‐MG9031‐00‐ X:CB‐6 107 CRP‐X:CB‐6 / X1‐95 107‐52 ‐X1‐95/X:CB‐6 Pole Descrepency Alarm
132 kV 107 107‐52  107 CRP Core 5 W107, Sh‐24 of 45 X1‐85 W107, Sh‐24 of 45 X:CB‐7 107 CRP‐X:CB‐7 / X1‐85 107‐52 ‐X1‐85/X:CB‐7 Loss of SF6
132 kV 107 107‐52  107 CRP Core 6 X1‐87 X:CB‐8 107 CRP‐X:CB‐8 / X1‐87 107‐52 ‐X1‐87/X:CB‐8 General Lockout SF6
132 kV 107 107‐52  107 CRP Core 7 X1‐52 X:CB‐9 107 CRP‐X:CB‐9 / X1‐52 107‐52 ‐X1‐52/X:CB‐9 DC Supply 1&2 Monitor
132 kV 107 107‐52  107 CRP Core 8 X1‐98 X:CB‐10 107 CRP‐X:CB‐10 / X1‐98 107‐52 ‐X1‐98/X:CB‐10 CB Remote Indication
132 kV 107 107‐52  107 CRP Core 9 X1‐100 X:CB‐11 107 CRP‐X:CB‐11 / X1‐100 107‐52 ‐X1‐100/X:CB‐11 Spring Status
132 kV 107 107‐52  107 CRP Core 10 G719EA‐MG9031‐00‐ X1LA‐9 G719EA‐MG9031‐00‐ X:CB‐12 107 CRP‐X:CB‐12 / X1LA‐9 107‐52 ‐X1LA‐9/X:CB‐12 Common
132 kV 107 107‐52  107 CRP Core 11 W107, Sh‐27 of 45 X1LC‐10 W107, Sh‐27 of 45 X:CB‐13 107 CRP‐X:CB‐13 / X1LC‐10 107‐52 ‐X1LC‐10/X:CB‐13 52‐CB open
132 kV 107 107‐52  107 CRP Core 12 G719EA‐MG9031‐00‐ X G719EA‐MG9031‐00‐ X:CT1‐3 107 CRP‐X:CT1‐3 / X 107‐52 ‐X/X:CT1‐3 Common
132 kV 107 107‐52  107 CRP Core 13 W107, Sh‐32 of 45 X1‐16 W107, Sh‐32 of 45 X:CT1‐4 107 CRP‐X:CT1‐4 / X1‐16 107‐52 ‐X1‐16/X:CT1‐4
132 kV 107 107‐52  107 CRP Core 14 TB‐XX XCB‐22 107 CRP‐XCB‐22 / TB‐XX 107‐52 ‐TB‐XX/XCB‐22 DC Supply (+)Ve
132 kV 107 107‐52  107 CRP Core 15 TB‐XX XCB‐23 107 CRP‐XCB‐23 / TB‐XX 107‐52 ‐TB‐XX/XCB‐23 DC Supply (‐)Ve
132 kV 107 107‐52  107 CRP Core 16 TB‐XX XCB‐24 107 CRP‐XCB‐24 / TB‐XX 107‐52 ‐TB‐XX/XCB‐24 Common
132 kV 107 107‐52  107 CRP Core 17 TB‐XX XCB‐25 107 CRP‐XCB‐25 / TB‐XX 107‐52 ‐TB‐XX/XCB‐25 Protection Trip‐1
132 kV 107 107‐52  107 CRP Core 18 TB‐XX XCB‐26 107 CRP‐XCB‐26 / TB‐XX 107‐52 ‐TB‐XX/XCB‐26 Post Close TC‐1 Supervision
132 kV 107 107‐52  107 CRP Core 19 TB‐XX XCB‐27 107 CRP‐XCB‐27 / TB‐XX 107‐52 ‐TB‐XX/XCB‐27 Pre Close TC‐1 Supervision 
132 kV 107 107‐52  107 CRP Core 20 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 21 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 22 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 23 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 24 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 25 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 26 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 27 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE

19 132 kV 107 swyd  to control bldg. 1‐107‐2‐019 1 Cu./Amr. PVC 107‐52  107 CRP 27CX2.5 50 Core 1 G719EA‐MG9031‐00‐ TB‐XX G719EA‐MG9031‐00‐ X‐CB‐28 107 CRP‐X‐CB‐28 / TB‐XX 107‐52 ‐TB‐XX/X‐CB‐28 DC Supply (+)Ve
132 kV 107 107‐52  107 CRP Core 2 W107, Sh‐33 of 45 TB‐XX W107, Sh‐33 of 45 X‐CB‐29 107 CRP‐X‐CB‐29 / TB‐XX 107‐52 ‐TB‐XX/X‐CB‐29 DC Supply (‐)Ve
132 kV 107 107‐52  107 CRP Core 3 TB‐XX X‐CB‐30 107 CRP‐X‐CB‐30 / TB‐XX 107‐52 ‐TB‐XX/X‐CB‐30 Common
132 kV 107 107‐52  107 CRP Core 4 TB‐XX X‐CB‐31 107 CRP‐X‐CB‐31 / TB‐XX 107‐52 ‐TB‐XX/X‐CB‐31 Protection Trip‐2 
132 kV 107 107‐52  107 CRP Core 7 TB‐XX X‐CB‐32 107 CRP‐X‐CB‐32 / TB‐XX 107‐52 ‐TB‐XX/X‐CB‐32 Post Close TC‐2 Supervision 
132 kV 107 107‐52  107 CRP Core 8 TB‐XX X‐CB‐33 107 CRP‐X‐CB‐33 / TB‐XX 107‐52 ‐TB‐XX/X‐CB‐33 Pre Close TC‐2 Supervision
132 kV 107 107‐52  107 CRP Core 9 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 10 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 11 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 12 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 13 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 14 SPARE SPARE 107 CRP‐SPARE / SPARE 107‐52 ‐SPARE/SPARE
132 kV 107 107‐52  107 CRP Core 15 G719EA‐MG9031‐00‐ X1:68 G719EA‐MG9031‐00‐ X:CB‐14 107 CRP‐X:CB‐14 / X1:68 107‐52 ‐X1:68/X:CB‐14 Common
132 kV 107 107‐52  107 CRP Core 16 W107, Sh‐34 of 45 X1:69 W107, Sh‐34 of 45 X:CB‐15 107 CRP‐X:CB‐15 / X1:69 107‐52 ‐X1:69/X:CB‐15 CB Closing I/L permissible
132 kV 107 107‐52  107 CRP Core 17 X1:64 X:CB‐16 107 CRP‐X:CB‐16 / X1:64 107‐52 ‐X1:64/X:CB‐16 Common
132 kV 107 107‐52  107 CRP Core 18 X1:65 X:CB‐17 107 CRP‐X:CB‐17 / X1:65 107‐52 ‐X1:65/X:CB‐17 Remote Close
132 kV 107 107‐52  107 CRP Core 19 X1:9 X:CB‐18 107 CRP‐X:CB‐18 / X1:9 107‐52 ‐X1:9/X:CB‐18 Common
132 kV 107 107‐52  107 CRP Core 20 X1:10 X:CB‐19 107 CRP‐X:CB‐19 / X1:10 107‐52 ‐X1:10/X:CB‐19 Remote Trip‐1
132 kV 107 107‐52  107 CRP Core 21 X1:42 X:CB‐20 107 CRP‐X:CB‐20 / X1:42 107‐52 ‐X1:42/X:CB‐20 Common
132 kV 107 107‐52  107 CRP Core 22 X1:43 X:CB‐21 107 CRP‐X:CB‐21 / X1:43 107‐52 ‐X1:43/X:CB‐21 Remote Trip‐2
132 kV 107 107‐52  107 CRP Core 23 G719EA‐MG9031‐00‐ X1:67 G719EA‐MG9031‐00‐ X:CB‐1 107 CRP‐X:CB‐1 / X1:67 107‐52 ‐X1:67/X:CB‐1 CB Open

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 2 of 3
OWNER: UPPTCL CABLE SCHEDULE FOR JANPUR 400‐220‐132kV SUBSTATION
CLIENT: GEPDEC
CONSULTANT: PITATH ELECTRIC PRIVATE LIMITED
ANNEXURE: BAY107TBC

ESTIMATE ACTUAL 
SL.  SWYD.  LAYOUT  NO. OF  CABLE COND.  CABLE  FROM ‐ EQUIP. REF.  FROM  TO ‐ EQUIP. REF. 
BAY No. CABLE  NO. FROM EQUIP. TO EQUIP. D LENGTH  LENGTH   CORE TO (TERM. NO.) FERRULE No. ‐FROM FERRULE No. ‐TO APPLICATION
NO. AREA IDENTIFICATION RUNs MATERIAL SIZE  DWG. (TERM. NO.) DWG.
(in mts) (in mts) CB Open
132 kV 107 107‐52  107 CRP Core 24 W107, Sh‐37 of 45 X1:68 W107, Sh‐37 of 45 X:CB‐2 107 CRP‐X:CB‐2 / X1:68 107‐52 ‐X1:68/X:CB‐2
132 kV 107 107‐52  107 CRP Core 25 SPARE
132 kV 107 107‐52  107 CRP Core 26 SPARE
132 kV 107 107‐52  107 CRP Core 27 SPARE

107‐ISOLATOR CABLING TO PANEL
20 132 kV 107 swyd  to control bldg. 1‐107‐2‐020 1 Cu./Amr. PVC 107‐89A  107 CRP 14CX2.5 30 Core 1 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:ISA‐3 107 CRP‐X:ISA‐3 / TB1‐103 107‐89A ‐TB1‐103/X:ISA‐3 Common
132 kV 107 107‐89A  107 CRP Core 2 W107, Sh‐23 of 45 TB1‐104 W107, Sh‐23 of 45 X:ISA‐4 107 CRP‐X:ISA‐4 / TB1‐104 107‐89A ‐TB1‐104/X:ISA‐4 Isolator 89A Open
132 kV 107 107‐89A  107 CRP Core 3 TB1‐102 X:ISA‐5 107 CRP‐X:ISA‐5 / TB1‐102 107‐89A ‐TB1‐102/X:ISA‐5 Isolator 89A Close
132 kV 107 107‐89A  107 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐107 G719EA‐MG9031‐00‐ X:ISA‐1 107 CRP‐X:ISA‐1 / TB1‐107 107‐89A ‐TB1‐107/X:ISA‐1 Common
132 kV 107 107‐89A  107 CRP Core 5 W107, Sh‐27 of 45 TB1‐108 W107, Sh‐27 of 45 X:ISA‐2 107 CRP‐X:ISA‐2 / TB1‐108 107‐89A ‐TB1‐108/X:ISA‐2 Isolator 89A Open
132 kV 107 107‐89A  107 CRP Core 6 G719EA‐MG9031‐00‐ TB1‐105 G719EA‐MG9031‐00‐ X:ISA‐11 107 CRP‐X:ISA‐11 / TB1‐105 107‐89A ‐TB1‐105/X:ISA‐11 Trip Bus‐1 (Main‐1)
132 kV 107 107‐89A  107 CRP Core 7 W107, Sh‐28 of 45 TB1‐106 W107, Sh‐28 of 45 X:ISA‐12 107 CRP‐X:ISA‐12 / TB1‐106 107‐89A ‐TB1‐106/X:ISA‐12 Common
132 kV 107 107‐89A  107 CRP Core 8 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISA‐6 107 CRP‐X:ISA‐6 / TB1‐1 107‐89A ‐TB1‐1/X:ISA‐6 DC Supply (+)Ve
132 kV 107 107‐89A  107 CRP Core 9 W107, Sh‐35 of 45 TB1‐2 W107, Sh‐35 of 45 X:ISA‐7 107 CRP‐X:ISA‐7 / TB1‐2 107‐89A ‐TB1‐2/X:ISA‐7 DC Supply (‐)Ve
132 kV 107 107‐89A  107 CRP Core 10 TB1‐3 X:ISA‐8 107 CRP‐X:ISA‐8 / TB1‐3 107‐89A ‐TB1‐3/X:ISA‐8 Common
132 kV 107 107‐89A  107 CRP Core 11 TB1‐5 X:ISA‐9 107 CRP‐X:ISA‐9 / TB1‐5 107‐89A ‐TB1‐5/X:ISA‐9 Open 
132 kV 107 107‐89A  107 CRP Core 12 TB1‐4 X:ISA‐10 107 CRP‐X:ISA‐10 / TB1‐4 107‐89A ‐TB1‐4/X:ISA‐10 Close
132 kV 107 107‐89A  107 CRP Core 13 SPARE
132 kV 107 107‐89A  107 CRP Core 14 SPARE

21 132 kV 107 swyd  to control bldg. 1‐107‐2‐021 1 Cu./Amr. PVC 107‐89B  107 CRP 14CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:ISB‐3 107 CRP‐X:ISB‐3 / TB1‐103 107‐89B ‐TB1‐103/X:ISB‐3 Common
132 kV 107 107‐89B  107 CRP Core 2 W107, Sh‐23 of 45 TB1‐104 W107, Sh‐23 of 45 X:ISB‐4 107 CRP‐X:ISB‐4 / TB1‐104 107‐89B ‐TB1‐104/X:ISB‐4 Isolator 89B Open
132 kV 107 107‐89B  107 CRP Core 3 TB1‐102 X:ISB‐5 107 CRP‐X:ISB‐5 / TB1‐102 107‐89B ‐TB1‐102/X:ISB‐5 Isolator 89B Close
132 kV 107 107‐89B  107 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐107 G719EA‐MG9031‐00‐ X:ISB‐1 107 CRP‐X:ISB‐1 / TB1‐107 107‐89B ‐TB1‐107/X:ISB‐1 Common
132 kV 107 107‐89B  107 CRP Core 5 W107, Sh‐27 of 45 TB1‐108 W107, Sh‐27 of 45 X:ISB‐2 107 CRP‐X:ISB‐2 / TB1‐108 107‐89B ‐TB1‐108/X:ISB‐2 Isolator 89B Open
132 kV 107 107‐89B  107 CRP Core 6 G719EA‐MG9031‐00‐ TB1‐105 G719EA‐MG9031‐00‐ X:ISB‐11 107 CRP‐X:ISB‐11 / TB1‐105 107‐89B ‐TB1‐105/X:ISB‐11 Trip Bus‐2 (Main‐2)
132 kV 107 107‐89B  107 CRP Core 7 W107, Sh‐28 of 45 TB1‐106 W107, Sh‐28 of 45 X:ISB‐12 107 CRP‐X:ISB‐12 / TB1‐106 107‐89B ‐TB1‐106/X:ISB‐12 Common
132 kV 107 107‐89B  107 CRP Core 8 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:ISB‐6 107 CRP‐X:ISB‐6 / TB1‐1 107‐89B ‐TB1‐1/X:ISB‐6 DC Supply (+)Ve
132 kV 107 107‐89B  107 CRP Core 9 W107, Sh‐35 of 45 TB1‐2 W107, Sh‐35 of 45 X:ISB‐7 107 CRP‐X:ISB‐7 / TB1‐2 107‐89B ‐TB1‐2/X:ISB‐7 DC Supply (‐)Ve
132 kV 107 107‐89B  107 CRP Core 10 TB1‐3 X:ISB‐8 107 CRP‐X:ISB‐8 / TB1‐3 107‐89B ‐TB1‐3/X:ISB‐8 Common
132 kV 107 107‐89B  107 CRP Core 11 TB1‐5 X:ISB‐9 107 CRP‐X:ISB‐9 / TB1‐5 107‐89B ‐TB1‐5/X:ISB‐9 Open 
132 kV 107 107‐89B  107 CRP Core 12 TB1‐4 X:ISB‐10 107 CRP‐X:ISB‐10 / TB1‐4 107‐89B ‐TB1‐4/X:ISB‐10 Close
132 kV 107 107‐89B  107 CRP Core 13 SPARE
132 kV 107 107‐89B  107 CRP Core 14 SPARE

22 132 kV 107 swyd  to control bldg. 1‐107‐2‐022 1 Cu./Amr. PVC 107‐89T  107 CRP 14CX2.5 65 Core 1 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:IST‐3 107 CRP‐X:IST‐3 / TB1‐103 107‐89T ‐TB1‐103/X:IST‐3 Common
132 kV 107 107‐89T  107 CRP Core 2 W107, Sh‐23 of 45 TB1‐104 W107, Sh‐23 of 45 X:IST‐4 107 CRP‐X:IST‐4 / TB1‐104 107‐89T ‐TB1‐104/X:IST‐4 Isolator 89T Open
132 kV 107 107‐89T  107 CRP Core 3 TB1‐102 X:IST‐5 107 CRP‐X:IST‐5 / TB1‐102 107‐89T ‐TB1‐102/X:IST‐5 Isolator 89T Close
132 kV 107 107‐89T  107 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐107 G719EA‐MG9031‐00‐ X:IST‐1 107 CRP‐X:IST‐1 / TB1‐107 107‐89T ‐TB1‐107/X:IST‐1 Common
132 kV 107 107‐89T  107 CRP Core 5 W107, Sh‐27 of 45 TB1‐108 W107, Sh‐27 of 45 X:IST‐2 107 CRP‐X:IST‐2 / TB1‐108 107‐89T ‐TB1‐108/X:IST‐2 Isolator 89T Open
132 kV 107 107‐89T  107 CRP Core 6 G719EA‐MG9031‐00‐ TB1‐105 G719EA‐MG9031‐00‐ X:IST‐11 107 CRP‐X:IST‐11 / TB1‐105 107‐89T ‐TB1‐105/X:IST‐11 Trip Bus‐3 (Transfer Bus)
132 kV 107 107‐89T  107 CRP Core 7 W107, Sh‐28 of 45 TB1‐106 W107, Sh‐28 of 45 X:IST‐12 107 CRP‐X:IST‐12 / TB1‐106 107‐89T ‐TB1‐106/X:IST‐12 Common
132 kV 107 107‐89T  107 CRP Core 8 G719EA‐MG9031‐00‐ TB1‐1 G719EA‐MG9031‐00‐ X:IST‐6 107 CRP‐X:IST‐6 / TB1‐1 107‐89T ‐TB1‐1/X:IST‐6 DC Supply (+)Ve
132 kV 107 107‐89T  107 CRP Core 9 W107, Sh‐36 of 45 TB1‐2 W107, Sh‐36 of 45 X:IST‐7 107 CRP‐X:IST‐7 / TB1‐2 107‐89T ‐TB1‐2/X:IST‐7 DC Supply (‐)Ve
132 kV 107 107‐89T  107 CRP Core 10 TB1‐3 X:IST‐8 107 CRP‐X:IST‐8 / TB1‐3 107‐89T ‐TB1‐3/X:IST‐8 Common
132 kV 107 107‐89T  107 CRP Core 11 TB1‐5 X:IST‐9 107 CRP‐X:IST‐9 / TB1‐5 107‐89T ‐TB1‐5/X:IST‐9 Open 
132 kV 107 107‐89T  107 CRP Core 12 TB1‐4 X:IST‐10 107 CRP‐X:IST‐10 / TB1‐4 107‐89T ‐TB1‐4/X:IST‐10 Close
132 kV 107 107‐89T  107 CRP Core 13 SPARE
132 kV 107 107‐89T  107 CRP Core 14 SPARE

107‐E/s CABLING TO PANEL
23 132 kV 107 swyd  to control bldg. 1‐107‐2‐023 1 Cu./Amr. PVC 107‐89BE  107 CRP 7CX2.5 40 Core 1 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:ESW‐7 107 CRP‐X:ESW‐7 / TB1‐103 107‐89BE ‐TB1‐103/X:ESW‐7 Common
132 kV 107 107‐89BE  107 CRP Core 2 W107, Sh‐25 of 45 TB1‐104 W107, Sh‐25 of 45 X:ESW‐8 107 CRP‐X:ESW‐8 / TB1‐104 107‐89BE ‐TB1‐104/X:ESW‐8 Earth Switch 89BE1 Open
132 kV 107 107‐89BE  107 CRP Core 3 TB1‐102 X:ESW‐9 107 CRP‐X:ESW‐9 / TB1‐102 107‐89BE ‐TB1‐102/X:ESW‐9 Earth Switch 89BE1 Close
132 kV 107 107‐89BE  107 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X‐IST:7 107 CRP‐X‐IST:7 / TB1‐103 107‐89BE ‐TB1‐103/X‐IST:7 Earth Switch 89BE Open
132 kV 107 107‐89BE  107 CRP Core 5 W107, Sh‐36 of 45 TB1‐104 W107, Sh‐36 of 45 X‐IST:8 107 CRP‐X‐IST:8 / TB1‐104 107‐89BE ‐TB1‐104/X‐IST:8 Earth Switch 89BE Close
132 kV 107 107‐89BE  107 CRP Core 6 SPARE
132 kV 107 107‐89BE  107 CRP Core 7 SPARE

107‐E/s CABLING TO PANEL
24 132 kV 107 swyd  to control bldg. 1‐107‐2‐024 1 Cu./Amr. PVC 107‐89TE1  107 CRP 7CX2.5 65 Core 1 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:ESW‐1 107 CRP‐X:ESW‐1 / TB1‐103 107‐89TE1 ‐TB1‐103/X:ESW‐1 Common
132 kV 107 107‐89TE1  107 CRP Core 2 W107, Sh‐24 of 45 TB1‐104 W107, Sh‐24 of 45 X:ESW‐2 107 CRP‐X:ESW‐2 / TB1‐104 107‐89TE1 ‐TB1‐104/X:ESW‐2 Earth Switch 89TE1 Open
132 kV 107 107‐89TE1  107 CRP Core 3 TB1‐102 X:ESW‐3 107 CRP‐X:ESW‐3 / TB1‐102 107‐89TE1 ‐TB1‐102/X:ESW‐3 Earth Switch 89TE1 Close
132 kV 107 107‐89TE1  107 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:IST‐9 107 CRP‐X:IST‐9 / TB1‐103 107‐89TE1 ‐TB1‐103/X:IST‐9 Earth Switch 89TE1 Open
132 kV 107 107‐89TE1  107 CRP Core 5 W107, Sh‐36 of 45 TB1‐104 W107, Sh‐36 of 45 X:IST‐10 107 CRP‐X:IST‐10 / TB1‐104 107‐89TE1 ‐TB1‐104/X:IST‐10 Earth Switch 89TE1 Close
132 kV 107 107‐89TE1  107 CRP Core 6 SPARE
132 kV 107 107‐89TE1  107 CRP Core 7 SPARE

25 132 kV 107 swyd  to control bldg. 1‐107‐2‐025 1 Cu./Amr. PVC 107‐89TE2 107 CRP 7CX2.5 65 Core 1 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:ESW‐4 107 CRP‐X:ESW‐4 / TB1‐103 107‐89TE2‐TB1‐103/X:ESW‐4 Common
132 kV 107 107‐89TE2 107 CRP Core 2 W107, Sh‐24 of 45 TB1‐104 W107, Sh‐24 of 45 X:ESW‐5 107 CRP‐X:ESW‐5 / TB1‐104 107‐89TE2‐TB1‐104/X:ESW‐5 Earth Switch 89TE2 Open
132 kV 107 107‐89TE2 107 CRP Core 3 TB1‐102 X:ESW‐6 107 CRP‐X:ESW‐6 / TB1‐102 107‐89TE2‐TB1‐102/X:ESW‐6 Earth Switch 89TE2 Close
132 kV 107 107‐89TE2 107 CRP Core 4 G719EA‐MG9031‐00‐ TB1‐103 G719EA‐MG9031‐00‐ X:IST‐11 107 CRP‐X:IST‐11 / TB1‐103 107‐89TE2‐TB1‐103/X:IST‐11 Earth Switch 89TE2 Open
132 kV 107 107‐89TE2 107 CRP Core 5 W107, Sh‐36 of 45 TB1‐104 W107, Sh‐36 of 45 X:IST‐12 107 CRP‐X:IST‐12 / TB1‐104 107‐89TE2‐TB1‐104/X:IST‐12 Earth Switch 89TE2 Close
132 kV 107 107‐89TE2 107 CRP Core 6 SPARE
132 kV 107 107‐89TE2 107 CRP Core 7 SPARE

DOCUMENT NUMBER: PE‐2021‐01‐CS‐001
REV:B 3 of 3

You might also like